05 Installation J 6HP 15
05 Installation J 6HP 15
SERIES
5 . INSTALLATION
5-1. PIPING DESIGN
5-1-1. PIPING METHOD
SUMMARY OF PIPING SYSTEM
Heat pump type / Cooling only type
Outdoor Separation
unit tube Header
EV kit
INSTALLATION
INSTALLATION
- (05 - 01) -
TYPE OF PIPING SYSTEM
Line Piping System
Outdoor Separation
unit tube
EV kit
Outdoor Header
unit
EV kit
INSTALLATION
Combined (Separation tube/Header) Piping System
Separation
Outdoor tube Header
unit
EV kit
Separation
Outdoor tube Header
unit
EV kit
- (05 - 02) -
5-1-2. LIMITATIONS
EXAMPLE 1 EXAMPLE 2
Branch kit : Header Branch kit : Separation tube
Outdoor Outdoor
unit unit
a a
b c d e
H1
H1 g h i j k
b c d e EV kit f
l EV kit
Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor
unit unit unit unit unit unit unit unit H2
H2
f Indoor
unit
Indoor
unit
EXAMPLE 3
Branch kit : Separation tube + Header
Outdoor
unit
a b
EV kit
H1 g c d e f
i j
h Indoor Indoor Indoor Indoor
Indoor
unit unit unit unit H2
INSTALLATION
INSTALLATION
unit
Indoor
unit
CAUTIONS
Keep the length of straight portion of pipe between two branch kits longer than 0.5m.
Don't use separation tube downstream of header.
Install separation tube and header in the correct direction specified in installation manual.
Outside diameter
(mm) 6.35 9.52 12.70 15.88 19.05
1)
Material ASTM B280; JIS H3300 C1220T-O or equivalent
Wall thickness
(mm) 0.8 0.8 0.8 1.0 1.2
2
1) : Allowable tensile stress 33 N/mm at 125°C.
INSTALLATION
Liquid pipe Gas pipe
Less than 14 6.35 12.70
15 or more to 16 9.52 12.70
17 or more to 30 9.52 15.88
31 or more 9.52 19.05
- (05 - 04) -
5-1-4. SELECTION OF PIPE HEAT INSULATING MATERIAL
1. Always insulate the refrigerant pipe to prevent condensation and water droplets by the refrigerant pipe.
2. Decide the thickness of the heat insulating material by referring to the recommended minimum thickness
in Table 1.
(For installation condition T=30°CDB, humidity 70%, humidity 75%, humidity 80%, humidity 85%)
3. When the outdoor unit is installed at a higher position than the indoor unit, fill the connecting part gap with
putty, etc. to prevent the dew condensation water of the valve of the outdoor unit from flowing to
the indoors from the gap between the pipe and the heat insulating material.
4. Liquid pipe and gas pipe should be completely insulated with same specification and sealed.
5. In case not to insulate and not to seal refrigerant pipe completely, it will become the cause of water leak.
Table 1 Size of refrigerant pipe and recommended minimum thickness of heat insulating material
(In case a heat insulating material which thermal conductivity is equal to or less than 0.040 W/(m·k)
at 20°C is used.
INSTALLATION
9.52 9 11 14 18
12.70 10 12 15 19
15.88 10 12 16 20
19.05 10 13 16 21
When an ambient temperature and relative humidity exceed 30°CDB and 85% respectively,
please strengthen heat insulation of refrigerant pipe. When not strengthening heat insulation of refrigerant
pipe, the surface of the heat insulation may be dewed.
Finishing Tape
Liquid Pipe
Liquid Pipe
Heat Insulation Heat Insulation
1.Make sure that pipe is covered completely by the heat insulation,not expoding to air.
Inadequate heat insulation may cause condensation.
2.Do not covered heat insulation gas and liquid pipes together as above figure.
It may cause condensation and capacity drop by heat loss.
- (05 - 05) -
5-1-5. ADDITIONAL CHARGE CALCULATION
INSTALLATION
Ø6.35mm = 20m
" Additional charge for pipe length " is
35(m) x 0.06(kg/m) + 20(m) x 0.02(kg/m) = 2.50(kg) (1)
- (05 - 06) -
5-1-6. EXAMPLE OF PIPING DESIGN
(1) Refrigerant system
Outdoor
unit
a b
A
c
B C
EV kit
d e f g h i j k
1 2 3 4 5 6 7 8
Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor
unit unit unit unit unit unit unit unit
System configuration
1 2 3 4 5 6 7 8 Total capacity
INSTALLATION
Capacity(kW) 2.8 2.8 2.8 2.8 2.8 3.5 3.5 3.5 24.5
h I j k
Ø9.52 Ø9.52 Ø9.52 Ø9.52
Ø6.35 Ø6.35 Ø6.35 Ø6.35
5 10 10 5
- (05 - 07) -
Pipe length
Maximum allowable length (actual pipe length) Refrigerant system 1
a+b+h 25m
a+b+i 30m
a+b+j 30m
Between outdoor unit and a+b+k 25m
70m
the farthest indoor unit a+c+d 30m
a+c+e 30m
a+c+f 35m
a+c+g 30m
Total pipe length 115m a+b+c+d+e+f+g+h+i+j+k 90m
Between outdoor unit and the 1st branch kit 60m a 10m
b+h 15m
b+i 20m
b+j 20m
Between the 1st branch kit b+k 15m
40m
and the farthest indoor unit c+d 20m
c+e 20m
c+f 25m
c+g 20m
Between EV kit and indoor unit 1.2m - Within limit
INSTALLATION
INSTALLATION
Maximum allowable height difference Refrigerant system 1
Between outdoor unit and indoor unit 30m - Within limit
AJ*A54 15m
Between indoor units - Within limit
AO*54 5m
Additional charge
Liquid pipe diameter (mm) 9.52 6.35
Additional refrigerant
(0.06 x 35) + (0.02 x 55) = 3.20 (kg)
- (05 - 08) -
(2) Refrigerant system
Outdoor
unit
a
A
b c d e
EV kit
1 2 3 4
Indoor Indoor Indoor Indoor
unit unit unit unit
System configuration
1 2 3 4 Total capacity
INSTALLATION
Capacity(kW) 5.3 6.0 6.0 6.0 23.3
- (05 - 09) -
Pipe length
Maximum allowable length (actual pipe length) Refrigerant system 2
a+b 35m
Between outdoor unit and a+c 30m
70m
the farthest indoor unit a+d 30m
a+e 35m
Total pipe length 115m a+b+c+d+e 70m
Between outdoor unit and the 1st branch kit 60m a 20m
b 15m
Between the 1st branch kit c 10m
40m
and the farthest indoor unit d 10m
e 15m
Between EV kit and indoor unit 1.2m - Within limit
Selection of header
A
INSTALLATION
INSTALLATION
Model name UTR-HD546U
Additional charge
Additional refrigerant
(0.06 x 20) + (0.02 x 50) = 2.20 (kg)
- (05 - 10) -
(3) Refrigerant system
Outdoor
unit
a b
A
B
c
C
EV kit
d e
f g h i
1 2 3 4 5 6
Indoor Indoor Indoor Indoor Indoor Indoor
unit unit unit unit unit unit
System configuration
1 2 3 4 5 6 Total capacity
INSTALLATION
Capacity (kW)
h I
Ø9.52 Ø9.52
Ø6.35 Ø6.35
5 10
- (05 - 11) -
Pipe length
Maximum allowable length (actual pipe length) Refrigerant system 3
a+b+f 40m
a+b+g 35m
Between outdoor unit and a+b+h 35m
70m
the farthest indoor unit a+b+i 40m
a+c+d 22m
a+c+e 27m
Total pipe length 115m a+b+c+d+e+f+g+h+i 84m
Between outdoor unit and the 1st branch kit 60m a 10m
b+f 30m
b+g 25m
Between the 1st branch kit b+h 25m
40m
and the farthest indoor unit b+i 30m
c+d 12m
c+e 17m
Between EV kit and indoor unit 1.2m - Within limit
INSTALLATION
Selection of separation tube and header
A B C
UTR-BP054X / UTR-BP054X /
Model name UTR-HD546U
UTR-BP54U UTR-BP54U
Additional charge
Liquid pipe diameter (mm) 9.52 6.35
Additional refrigerant
(0.06 x 35) + (0.02 x 49) = 3.08 (kg)
- (05 - 12) -
5-2. WIRING DESIGN
5-2-1. WIRING SPECIFICATIONS
Wire size
Use 2 Remark
[ cross-section (mm )]
H07RN-F or equivalent,
Power supply cable Outdoor unit 5.0 to 8.0 Single-phase, 50HZ, 220-240V, 1
2Wire + Ground
INSTALLATION
Circuit breaker 30 (A) 7
NOTE: Installation work must be performer as outlined in installation manuals of equipments
and in accordance with national wiring standards and codes.
- (05 - 13) -
5-2-2. POWER SUPPLY & CONNECTION CABLE WIRING
POWER SUPPLY CABLE SPECIFICATION AND LIMITATIONS
Always make the air conditioner power supply a special branch circuit and provide a
special breaker.
The capacity of the circuit breaker for leak current should be 30 mA or more.
The total length of the connection cable (TL) should be shorter than 150m.
If the total length of the connection cable exceeds 100m, keep the length of the connection
cable between the units longer than 5m.
a b c d e f g h i
Breaker
Indoor
220 - 240V 1 50Hz
unit
INSTALLATION
IF TL > 100m
c > 5m, d > 5m, e > 5m, f > 5m, g > 5m, h > 5m, i > 5m
Breaker
Indoor
220 - 240V 1 50Hz
unit
The wiring which branched from the outdoor unit to plurality and was connected to
the indoor unit is prohibition.
Connection cable
Power supply cable
(3wire + ground)
(2wire + ground) Outdoor unit
(Power supply & signal)
Breaker
Indoor
220 - 240V 1 50Hz unit
Terminal board
- (05 - 14) -
5-2-3. WIRING EXAMPLE
OUTDOOR UNIT
Connect to CN13(PCB)
220-240V
1 50Hz
WIRELESS REMOTE
CONTROLLER
INDOOR UNIT 1)
CONVERTOR (Compact wall mounted type)
* INDOOR UNIT INDOOR UNIT
INSTALLATION
INSTALLATION
RC Line AC Line REMOTE CONTROL REMOTE CONTROL REMOTE CONTROL
CONNECTION CABLE CONNECTION CABLE CONNECTION CABLE
CORD E CORD E CORD E
(L)(N) (G)
1 2 3 G 1 2 3 4 1 2 3 1(L)2(N) 3 1 2 3 1(L)2(N) 3 1 2 3 1(L)2(N) 3
* 1) for
Wired and simple remote controllers are not available
compact wall mounted type indoor units.
- (05 - 15) -
5-3. SYSTEM SETTING
5-3-1. SYSTEM TYPE SETTING
Set the DIP switch to the corresponding system type as shown in the table.
Do not use a nonexistent switch combination.
Pipe length
Recommended SW 6-1 SW 6-2
range of L (m)
INSTALLATION
INSTALLATION
Standard 7.5 <
= L < 50 OFF OFF
L 50 <
=L <
= 70 ON ON
Header
EV kit
- (05 - 16) -
5-3-2. ADDRESS SETTING
OPERATION
indicator Pi Pi Pi
(Red)
FAN CONTROL
SET TEMP (+)
INSTALLATION
Pi Pi
CUSTOM CODE
( - - - )
ADDRESS SETTING
(5) Press the “MASTER CONTROL ” button (6) Make sure the bottom number is ‘01’. If the
to access the address setting mode. number is other than ‘01’, press the “+” or the
“-” buttons to alter.
SET "01"
(7) Press the “FAN CONTROL ” button to access (8) Press the “+” or the “-” buttons to adjust the
the address data setting mode. The address data address. The address range is between A:00
will flash once this button is pressed. and A:07 with A:00 always being the first
address to be used.
Range
00 - 07
Address data
+ : UP
- : DOWN
- (05 - 17) -
(9) Press the “START/STOP ” button once to send (10) Indoor unit will display the indoor unit address
the information. A beeping noise will be heard if the data number on "TIMER "(GREEN) light.
command is accepted. OPERATION TIMER
(RED) (GREEN)
Pi Pi
Pi PiPiPi
continuously Flashing times of
address numbers
(Example) ADDRESS : 03
01
OPERATION LAMP ON
(RED) OFF
TIMER LAMP ON
(GREEN) OFF
PiPi
CORRECT : Pi PiPiPiPiPi
INSTALLATION
INSTALLATION
PiPi
WRONG: Pi (3 sec)
MANUAL AUTO
ACL
Timer lamp keep blinks the number of times of address No.
- (05 - 18) -
RESET THE POWER AFTER SETTING UP ADDRESS OF ALL
INDOOR UNITS
Important
If the reset is not performed, address can not be read in normally.
After all the addresses have been set, the circuit breaker needs to be switched off for
at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set address is stored in the PCB and will remain in memory even when the power
is turned off.
However setting address is effective after power reset.
Record the address set in the indoor unit on a label, etc., and affix the label to the unit
so it can be used for after-sales service operations.
INSTALLATION
ADJUSTING THE DIP SWITCH
1 INDOOR UNIT (Except Compact Wall Mounted Type)
( Factory setting)
SW5-1 SW5-2 Custom code
OFF OFF Type A
ON OFF Type B
OFF ON Type C
ON ON Type D
1
3 3. Press the MASTER CONTROL button again
2 to end the code change.
Remote controller
- (05 - 19) -
5-4. FUNCTION SETTING
5-4-1. OUTDOOR UNIT
Outdoor unit Factory setting
1 Test run (Cooling) OFF
2 Test run (Heating) OFF
SW1
3 Pump down operation OFF
4 Forced oil recovery operation OFF
1 Silent operation mode OFF
2 Forbidden OFF
SW2
3 Electric current selector switch 1 OFF
4 Electric current selector switch 2 OFF
1 Forbidden OFF
2 Forbidden OFF
SW3
3 Forbidden OFF
4 Forbidden OFF
1 Forbidden OFF
2 Forbidden OFF
SW4
3 Forbidden OFF
4 Forbidden OFF
1 Cooling capacity shift switch 1 OFF
DIP SW 2 Cooling capacity shift switch 2 OFF
SW5
3 Heating capacity shift switch 1 OFF
4 Heating capacity shift switch 2 OFF
INSTALLATION
INSTALLATION
1 Pipe length switch 1 OFF
2 Pipe length switch 2 OFF
SW6
3 Forbidden OFF
4 Forbidden OFF
1 Forbidden (System type switch) See table in 5-4-2
2 Forbidden OFF
SW7
3 Forbidden OFF
4 Forbidden OFF
1 Forbidden OFF
2 Forbidden OFF
SW8
3 Forbidden OFF
4 Forbidden OFF
1 Forbidden OFF
2 Forbidden OFF
SW201
3 Forbidden OFF
4 Forbidden OFF
- (05 - 20) -
SWITCH POSITION
Outdoor unit control circuit board
Main - PCB
CN49 CN48
(BLACK) (BLUE)
SW6
SW2
ON ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
SW3
SW7
SW5
SW1
ON ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
CN50 CN52
INSTALLATION
INSTALLATION
(YELLOW) (GREEN)
EX.IN-1 EX.IN-2
P (Filter PWB)
ON
1 2 3 4
SW201
- (05 - 21) -
5-4-2 SWITCH FUNCTION (OUTDOOR UNIT)
DIP SWITCH SETTING
(1) SW1 setting
1-1 Test run
All the indoor units connected to the outdoor unit can be test-operated by DIP switch setting.
SELECTOR SWITCH FOR TEST RUN AND NORMAL OPERATION ( . . . Factory setting)
SW1-1 SW1-2 Test Run Remarks
OFF OFF Normal operation
ON OFF Cooling test run SW1-1 / SW1-2 : OFF / OFF or ON / ON ON / OFF
OFF ON Heating test run SW1-1 / SW1-2 : OFF / OFF or ON / ON OFF / ON
ON ON Normal operation
INSTALLATION
1-3 Forced oil recovery operation
FORCED OIL RECOVERY OPERATION ( . . . Factory setting)
SW1-4 Pump down operation Remarks
OFF Release
ON Operate OFF ON and be kept at ON position for more than 10 sec.
- (05 - 22) -
2-3 SW2-3, 2-4 Electric current selector switch 1 and 2
Upper limit of electric current is set by DIP switches 2-3 and 2-4 according to the current limit.
Depending on the local power supply condition, the breaker capacity can be selected in 4 steps.
( . . . Factory setting)
SW2-3 SW2-4 Circuit breaker (A)
OFF OFF 30
OFF ON 25
ON OFF 20
ON ON 15
INSTALLATION
SW5-1 SW5-2 CAPACITY SHIFT
OFF OFF Normal mode
OFF ON Save energy mode
ON OFF High power mode 1
ON ON High power mode 2
- (05 - 23) -
(6) SW6 setting
6-1 SW 6-1, 6-2 Pipe length switch
SW setting can provide the operation to supplement the loss created by the pipe length.
( . . . Factory setting)
SW 6 - 1 SW 6 - 2 Pipe length Recommended rang of L (m)
OFF OFF Standard 7.5 < L < 50
ON ON Pipe length L 50 < L < 70
The pipe lengths shown here are one of the standards. It may differ depending on the system.
INSTALLATION
7-2 SW 7-2, 7-3, 7-4 setting forbidden.
Error Display
CN49 -----
(DC12V)
- (05 - 24) -
5-4-3. INDOOR UNIT
Indoor unit Factory setting
1 Forbidden OFF
2 Forbidden OFF
SW1
3 Room temp correct coefficient of heating 1 OFF
4 Room temp correct coefficient of heating 2 OFF
1 Room temp correct coefficient of cooling OFF
2 Forbidden OFF
SW2
3 Forbidden OFF
4 Auto restart validity / invalidity OFF
1 Forbidden (Indoor unit fan speed switch1) See table in 5-4-4
2 Forbidden (Indoor unit fan speed switch2) See table in 5-4-4
DIP SW SW3
3 Forbidden (Indoor unit fan speed switch3) See table in 5-4-4
4 External input select edge / pulse OFF
1 Forbidden (Indoor unit model code) See table in 5-4-4
2 Forbidden (Indoor unit model code) See table in 5-4-4
SW4
3 Forbidden (Indoor unit model code) See table in 5-4-4
4 Forbidden (Indoor unit model code) See table in 5-4-4
1 Wireless remote controller custom code switch 1 OFF
2 Wireless remote controller custom code switch 2 OFF
SW5
INSTALLATION
INSTALLATION
3 Forbidden OFF
4 Draft prevention setting switch OFF
SWITCH POSITION
Indoor unit control circuit board
CN24
CN23
CN22
SW5
CN24 CN21 SW3
CN27 SW1
CN22 CN23 SW2
SW3 SW4 SW5
SW4
SW1 SW2
- (05 - 25) -
5-4-4 SWITCH FUNCTION (INDOOR UNIT)
DIP SWITCH SETTING
(1) SW1 setting
1-1 SW 1-1, 1-2 setting forbidden
INSTALLATION
COOLING TEMPERATURE CORRECTION ( . . .Factory setting)
SW2-1 Coefficient value
OFF 0 deg
ON + 2 deg
- (05 - 26) -
2-3 Auto restart validity / invalidity.
Control the auto restart function by turning this switch ON/OFF.
AUTO RESTART SETTING ( . . . Factory setting)
SW2-4 Auto restart
OFF Invalidity
ON Validity
INSTALLATION
SW3-2 OFF ON ON
SW3-3 ON ON ON
- (05 - 27) -
(4) SW4 setting (Never change at the site)
This switch for changing the model code information of indoor unit PCB.
INDOOR UNIT MODEL CODE
Capacity
54 45 36 30 25(24) 20(22) 18 14 12 9 7
SW4-1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF
SW4-2 ON OFF OFF ON ON OFF OFF ON ON OFF OFF
SW4-3 OFF OFF OFF ON ON ON ON OFF OFF OFF OFF
SW4-4 ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF
INSTALLATION
OFF ON Type C 2. Press the (+) or (-) button to select the
desired code. A B C D
ON ON Type D
3. Press the MASTER CONTROL button again
to end the code change.
- (05 - 28) -
EXTERNAL INPUT AND OUTPUT
INSTALLATION
- (05 - 29) -
5-4-5. INDOOR UNIT (COMPACT WALL MOUNTED TYPE)
Indoor unit Factory setting
1 Forbidden (Indoor unit fan speed switch1) See table in 5-4-6
2 Forbidden (Indoor unit fan speed switch2) See table in 5-4-6
SW1
3 Forbidden (Indoor unit model code) See table in 5-4-6
4 Forbidden (Indoor unit model code) See table in 5-4-6
DIP SW
1 Forbidden OFF
2 Forbidden OFF
SW2
3 Auto restart validity / invalidity OFF
4 Forbidden OFF
Jumper JM 1 Wireless remote controller custom code Connect
wire JM 2 Wireless remote controller custom code Connect
SWITCH POSITION
Compact wall mounted type indoor unit control circuit board
SW1 SW2
CN10
INSTALLATION
INSTALLATION
CN11
JM2
JM1
- (05 - 30) -
5-4-6 SWITCH FUNCTION (COMPACT WALL MOUNTED TYPE)
DIP SWITCH SETTING
(1) SW1 setting (Never change at the site)
1-1 Fan speed setting switch
The fan speed corresponding to each model is set with the switch.
AS7 AS9 AS12 AS14
SW1-1 OFF ON OFF ON
SW1-2 OFF OFF ON ON
INSTALLATION
2-2 Auto restart validity / invalidity.
Control the auto restart function by turning this switch ON/OFF.
AUTO RESTART SETTING ( . . . Factory setting)
SW2-3 Auto restart
OFF Invalidity
ON Validity
- (05 - 31) -
JUMPER WIRE
Wireless remote controller custom code switch
Limit the type of infrared control signal which the indoor unit is controlled, in order to
prevent misoperation of indoor unit due to signal from other wirless remote controller.
REMOTE CONTROLLER CUSTOM CODE SWITCH
( . . . Factory setting)
JM1 JM2 Custom code
Connect Connect Type A
Disconnect Connect Type B 1. Press the MASTER CONTROL button for more
than five seconds to start the code change.
Connect Disconnect Type C 2. Press the (+) or (-) button to select the desired code.
A B C D
Disconnect Disconnect Type D
3. Press the MASTER CONTROL button again to
end the code change.
CONTROL INPUT
CN10
(OPERATION / STOP) See 5-5-2
OPERATION DISPLAY for details
INSTALLATION
INSTALLATION
CN11
(DC12V)
- (05 - 32) -
5-4-7 WIRED, SIMPLE REMOTE CONTROLLER
SWITCH POSITION
INSTALLATION
INSTALLATION
Wired remote controller
Front case (back side)
OFF ON
1
2
3
4
5
6
ON
DIP Switch
ON
OFF
1
2
3
4
5
6
DIP switches
- (05 - 33) -
5-4-8. SWITCH FUNCTION (WIRED, SIMPLE REMOTE CONTROLLER)
Always set the DIP SW before turning the power on.
DIP SWITCH SETTING
(1) Dual remote controller setting
Two separate remote controllers can be used to operate the same indoor unit.
Set the Dip SW 1,2 according to the following table.
( . . . Factory setting) Indoor unit
Remote controller
Number of remote Master unit Slave unit cable
1 2 3
controllers Dip SW 1 Dip SW 2 Dip SW 1 Dip SW 2 When ground
wire is necessary
1 (Normal) ON OFF
2 (Dual) OFF OFF ON ON
1 2 3 1 2 3
Master unit Slave unit
Remote controller
(2) SW 3 setting forbidden
INSTALLATION
ON Cooling only
- (05 - 34) -
5-4-9. GROUP REMOTE CONTROLLER
SWITCH POSITION
Group remote controller
Front case (back side)
OFF ON
1
2
ON
DIP switch
INSTALLATION
INSTALLATION
5-4-10 SWITCH FUNCTION (GROUP REMOTE CONTROLLER)
DIP SWITCH SETTING
(1) SW1 setting
Set SW1 to ON to enable the memory backup.
If there is a power failure when the memory backup is enabled, the setting stored in the memory will be saved.
( . . . Factory setting)
SW1 Memory backup
OFF Invalidity
ON Validity
- (05 - 35) -
5-5.EXTERNAL INPUT & OUTPUT
5-5-1. INDOOR UNIT
(1) Control input (Operation/Stop)
Indoor unit can be operated or stopped by using indoor unit PCB CN 21 (Wall mounted type )
or CN27 (other types).
INSTALLATION
Ch1 of On
CN21 *1) or Off
CN27 *2)
Remote On
Controller
Operation
Indoor
Stop
Unit
Ch1 Off
CN21 *1)
or On
CN27 *2)
Ch2 Off
Operation
Indoor
Unit Stop
- (05 - 36) -
(2) Output
3)
CONNECTOR OUTPUT STATUS
CN22 >
= 10 V; ( <
= 15 mA) Operation
(WHITE) < Stop
= 2 V; ( 0mA )
>
= 10 V; ( < Error
CN23 = 15 mA)
(WHITE) <
= 2 V; ( 0mA ) Normal
CN24 >
= 10 V; ( <
= 15 mA) Fan run
(WHITE) < Fan stop
= 2 V; ( 0mA )
3) Output of open collector circuit.
1 Operation display
Indoor Operation +
unit 1
Stop Operation CN 22
Indicator 2 (WHITE)
-
CN 22 12V
4)
0V
2 Error display
INSTALLATION
INSTALLATION
Indoor Error +
unit 1
Normal Error CN 23
Indicator 2 (WHITE)
CN 23 12V -
4)
0V
(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Usage Name and shapes Q'ty Parts No.
EXTERNAL
For output port
INPUT WIRE
1 9368778002
- (05 - 37) -
5-5-2. INDOOR UNIT(COMPACT WALL MOUNTED)
(1) Control input (Operation/Stop)
Indoor unit can be operated or stopped by using the connector CN10(RED) on indoor unit PCB.
(2) Output
INSTALLATION
INSTALLATION
5)
CONNECTOR OUTPUT STATUS
CN11 >
= 10 V; ( < = 15 mA) Operation
(WHITE) < Stop
= 2 V; ( 0mA )
+
5) Output of open collector circuit.
Operation 1 CN 11
Indicator 2 (WHITE)
Operation display -
6)
Operation
Indoor
unit 6) If the indicator malfunctions, please insert
Stop a ceramic capacitor (0.1 F ± 20%, > = 25V)
near the input port of the equipment.
12V
CN 11
0V
(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Usage Name and shapes Q'ty Parts No.
EXTERNAL
For output port
INPUT WIRE
1 9368778002
- (05 - 38) -
5-5-3. OUTDOOR UNIT
(1) Input
Heat and Cool switch (Heat pump type only)
"Cooling priority" or "Heating priority" can be selected by this input.
CONNECTOR INPUT STATUS
SIGNAL REMARKS
Cooling 1 CN52
Priority
Indoor Heating
Priority
2 (GREEN)
Unit R.C.
Priority
P.C.B
Open circuit voltage : <= 5.25 (V).
Short circuit current : <
= 0.6 (mA).
Short circuit detection resistance (RON) : <
= 500 (ohm).
Open circuit detection resistance (ROFF) : >
= 100 (kilo-ohm).
(2) Output
+
INSTALLATION
INSTALLATION
1 Operation display 1
Operation CN 48
This output indicates the outdoor unit's "Operation" status. Indicator
2 (BLUE)
-
2 Error display 7) P.C.B
This output indicates the outdoor unit and connected indoor +
unit's "Normal" or "Error" status. Error 1 CN 49
Indicator
2 (BLACK)
8)
STATUS 7) -
CONNECTOR OUTPUT P.C.B
CN48 >
= 10 V; ( <
= 100 mA) Operation Operation
(BLUE) < Stop 7) If the indicator malfunctions,
= 2 V; ( 0mA ) Stop
please insert a ceramic capacitor
> CN48
CN49 = 10 V; ( <
= 100 mA) Error 12V (0.1 F ± 20%, > = 25V) near the
(BLACK) <
= 2 V; ( 0mA ) Normal input port of the equipment.
0V
8) Output of open collector circuit.
Error
Normal
CN49
12V
1 Base heater
CN 9
(Field supply)
(YELLOW)
2 AC240V,25W
(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Usage Name and shapes Q'ty Parts No.
BASE
For base heater
port
HEATER 1 9374796014
WIRE
EXTERNAL
For input & ouput
port
INPUT 1 9368777005
WIRE
- (05 - 39) -
5-5-4. GROUP REMOTE CONTROLLER CONVERTER
Control input
1 Input select
Terminal block
CN1
Brown Open circuit voltage : 12 (V) +
1 - 5%.
CONVERTOR
INSTALLATION
INSTALLATION
CN 2 Short circuit current : <
= 2 (mA).
<
PCB
<Operation>
When it input GND short signal of 200ms or more to terminal 1, it transfer this operation
signal to all indoor unit on the this network. When it input GND open signal of 200ms or more
to terminal 1, it transfer this stop signal to all indoor unit on the this network.
However, it limits it when there is a change in the state.
( The operating signal has been output. GND short signal is 200ms or more
The stopping signal has been output. GND open signal is 200ms or more )
- (05 - 40) -
3 In the case of "pulse" input
<Operation>
When it input GND short signal of 200ms or more to terminal 1, it transfer this operation
signal to all indoor unit on the this network.
Terminal short
When it input GND short signal of 200ms or more to terminal 2, it transfer this operation signal
to all indoor unit on the this network.
INSTALLATION
INSTALLATION
200 ms 200 ms 200 ms
Terminal short
- (05 - 41) -
GROUP REMOTE CONTROLLER CONVERTER how to setting operation
Setting of external input function selection.
It is neccessory to set a initial parameter setting on the group remote convertor Printed
circuit board.
An external input setting is invalid on factory setting. It set up to use the button on the main
Printed circuit board.
At first, connect indoor unit, Group remote convertor and Group remote controller.
And next, the setting begins from the state to sup ply the power supply.
Red LED lights while this conition.
Push the “MODE ” button on the group remote convertor main Printed circuit board.
It displays “ Pr ”on the 7 segment(monitor lamps).(following the fig)
INSTALLATION
Parameter number
It is blinking.
It gathers information of sub print circuit board. Set value of the parameter number.
It is not possible to operate it wi th button . There are numerical values other than 0, too.
- (05 - 42) -
Set value of the parameter number.
It changes into blinking.
Select the input method of an external input with the key of “UP” or “DOWN” setting.
INSTALLATION
to the ordinary mode.
- (05 - 43) -
5-6. INSTALLATION WORK
5-6-1. INSTALLATION THE OUTDOOR UNIT
SELECTING THE MOUNTING POSITION
WARNING
Install the unit where it will not be tilted by more than 5 .
When installing the outdoor unit it may be exposed to strong wind, fasten it securely.
Set the unit on a strong stand, such as one made of concrete blocks to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Do not install the unit where a strong wind blows or where it is very dusty.
Install the unit so that it will not fall down or harm people.
If outdoor unit is not installed to specifications, capacity may drop because of a short-circuit.
As a result, a high pressure error may occur.
Since specified values are minimum permissible measurements, install unit after duly
considering the measurements required for installation location,piping work and maintenance.
FOR INDIVIDUALLY
h
h
H (900mm or less)
H (900mm or less)
L1 (300mm or over)
L2 (300mm or over)
300mm or over
INSTALLATION
INSTALLATION
The height (H) of the side wall should be less than 900mm.
If the height (H) of the side walls exceeds 900mm by h mm, and h mm to the space widths for L1 and L2.
H 900 : L1 300, L2 300
H > 900 : L1 > 300 + h, L2 > 300 + h
600mm or over
600mm or over
300mm or over
FOR CONTINUOUS
300mm or over
300mm or over
800mm or over
: Air discharge
- (05 - 44) -
5-6-2. INSTALLATION SPACE
COMPACT DUCT TYPE
Indoor unit
Inlet
air
2 1
100 mm 300 mm
or more or more Strong and
2 durable floor
1 When drain pump is used, leave the 30 mm 30 mm
100 mm 300 mm or more or more
space required for service and or more or more
maintenance (Refer to 5-6-6. DRAIN
PUMP UNIT)
2 When drain hose is connected, the required
dimension is 150mm or more.
INSTALLATION
300 mm 150 mm
or more or more
1,000 mm
1,000 mm
or more
2,300 mm or more
or more Obstruction
Floor
- (05 - 45) -
CASSETTE TYPE
You can select 2-way setting
Strong and durable ceiling
(A) Standard setting (B) Slender setting
AU20 - 30
200 mm
235 mm
or more
1,000
2,300 1,000 AU36 - 54
or more
or more or more
250 mm
285 mm
or more
Obstruction
Floor
60 mm or over
Left side
50 mm or over Right side
50 mm or over
INSTALLATION
INSTALLATION
1500 mm
or over
2300 mm or over
60 mm or over
Left side Right side
50 mm 200 mm
or over or over
1500 mm
or over
2300 mm or over
- (05 - 46) -
CAUTION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positi-
vely so that the units will not topple or fall.
CAUTION
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they
cannot reach the unit.
Install the indoor unit on a strong wall ,floor,ceiling which is not subject to vibration.
The inlet and outlet ports should not be obstructed. The air should be able to blow all over the room.
Do not install the unit where it will be exposed to direct sunlight.
Install the unit where the connection pipe can be easily installed.
Install the unit where the drain pipe can be easily installed.
INSTALLATION
INSTALLATION
Take servicing, etc. into consideration and leave the spaces. Also install the unit where the filter can be removed.
Install the indoor unit where vibrations and noise are not amplifired.
When Installing the unit on the floor, make sure that there is plently of space a around the inlet port.
- (05 - 47) -
5-6-3. PIPING CONNECTION
CAUTION
Use the designated size (diameter & thickness) of refrigerant pipes.
Those pipes purchased locally may contain dust inside. Please blow out the dust by
dried inert gas when using.
Be careful to avoid the dust or water falling into the pipe when performing piping
process and piping installation.
When processing the pipe, make the number of bending portion as few as possible,
and the bending radius as large as possible.
To process the branch, do not use T-shaped pipe, which causes a uneven refrigerant
flow. Use the optionally available standard branch kit.
Horizontal Vertical
INSTALLATION
INSTALLATION
NG
o or
OK
30
NG
NO GOOD
Separation tube
Header
Gas pipe
Outdoor b1 Vertical
A unit side line
Horizontal line
Horizontal
line
Brazing point
a1 VIEW A b2
H1
VIEW B
Liquid pipe
Outdoor H1, H2 = 0mm to 10mm
B unit side Horizontal line
a1, a2 : 0° to 1°
Brazing
b1, b2 : -10° to 10°
point a2
H2
If the diameter of the required pipe is different from the branch unit, either cut it out or
use reducer.
- (05 - 48) -
CAUTION
Keep the permissible length of every piping limitation to prevent a defect or cooling failure.
When replacing the unit, never use piping which has been used for previous installations.
Only use the new piping.
Welding
While welding the pipe, be sure to blow dry nitrogen gas through the pipes.
If not used, it will be caused to damage for compressor and clog the strainer and
electronic expansion valve.
0.02MPa
Pressure hose
Bello ws v alve
Nitr og en gas
Rubber stopper
INSTALLATION
Nitrogen Gas used Nitrogen Gas used but not sufficient Nitrogen Gas does not used
(Oxygen gas still inside the pipe)
The pipes vibrate, expand, and contract during operation, so if loads are concentrated in one area,
it could cause cracks in the pipes. Provide the pipes with supports every 2 to 3m.
Make sure to insulate the refrigeration pipes separately with ample thickness of
heat-resistant polyethylene form etc. For the connecting portion, apply the enough
insulation to avoid any gap.
- (05 - 49) -
FLARE PROCESSING
(1) Cut the connection pipe with pipe cutter so that the pipe is not deformed.
(2) Holding the pipe downwards so that cutting cannot enter the pipe and remove the burrs.
(3) Remove the flare nut from the indoor unit pipe and assemble as shown in Table 1 and insert
the flare nut onto the pipe, and flare the pipe with a flare tool.
(4) Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ
according to the type of flear tool. Be careful. When using a conventional flare tool, be sure to
secure "Dimension A" by using a gage for size adjustment.
(5) Check if the flared part is spread uniformly and that there are no crack. Finally, check the
"Dimension D" to confirm that the flared part was produced in correct size.
INSTALLATION
0 to 0.5 1.0 to 1.5 19.7 63.0 to 75.0
19.05 36 0 to 0.5 1.0 to 1.5 24.0 90.0 to 110.0
Die d
A
d
Pipe
- (05 - 50) -
Separation tube installation
Horizontal Vertical
or
NG
OK
30
NG
Use the pipe cutter to cut at the location which matches the piping size when the
piping size is different.
INSTALLATION
INSTALLATION
15 mm or more Pipe cutter
stopper
To indoor unit
Caution
Leave the distance 0.5m or more for straight part to separation tube.
(To prevent the outdoor unit mulfunction and generation of refrigerant noise)
- (05 - 51) -
2) Be sure to install the tape (accessory) in each heat insulation to the 4 positions as shown in
the following figure.
3) Use tape (locally procured) to seal the seam so that there will be no gap at the junction between
the aforementioned heat insulation and the heat insulation on the local piping.
Contact each other Contact each other Tape (locally procured) Tape (locally procured)
Insulation (locally procured)
CAUTION
As with the gas pipes, fully insulate the liquid pipes. Unless they are thermally insulated, water condensation can
cause accidents or reduction in performance.
After installing the heat insulation, if you worry about possible condensation, please cover the heat insulation
onto the gas pipe from top at field installation.
INSTALLATION
INSTALLATION
[Add the standard of heat insulating meterial]
When using, the environment temperature shoud be higher than 35 and humidity over 85%.
When using, the environment temperature shoud be higher than 25 and humidity over 90%.
Installation example
- (05 - 52) -
Header installation
Caution
Separation after header is not allowed.
Outdoor Header
unit
Outdoor Header
unit
Indoor Indoor
unit unit
INSTALLATION
Piping connection
(1) When connecting the connection pipes from the indoor units, connect them to the header branch
pipes in the order 1, 2, 3, etc.
1
2 1
3 2
4 3
4
5 Outdoor unit or 5
Outdoor unit or 6
separation tube 6
separation tube
(2) Use a pipe cutter to cut at the location that matches the piping size.
Be sure to cut the piping off at least 15 mm from the piping stopper
If the piping is cut too short, leaks can occur. After cutting the piping off, be sure to deburr it.
Make sure that dirt or water does not enter the piping when connecting the piping.
Pipe cutter 15 mm
or more
(3) Attach a plugging pipe provided if there is no piping connected at the headers.
Plugging pipe
- (05 - 53) -
Installation
Install the header so that it branches horizontally.
Use a level to make sure that the header is positioned as shown in following figure,
and then, secure it in place.
INSTALLATION
Cover the plugging pipe with heat insulation and seal with tape.
- (05 - 54) -
EV KIT INSTALLATION
EV kit selection
Dimension Applicable to indoor unit
Model name of EV kit
(H x W x D) (mm) with following model code
UTR - EV2A L 83 x 288 x 45 <30
UP
View A
A UP
Liquid pipe EV KIT cord
(indoor unit side)
EV KIT cord
NG
Liquid pipe
(indoor unit side) 0° < a < 90° -90° < b < 90°
INSTALLATION
Be sure to connect the EV KIT as shown in the following figure. Otherwise, the EV KIT and indoor unit could be damaged.
Horizontal direction
Install the EV KIT so that the arrow on the label is within the range shown in the figure.
Liquid pipe
(indoor unit side) a
NG
O
K
EV KIT cord
UP
EV kit installation
(1) Connect the flare nut side of the EV KIT to the liquid pipe of the indoor unit.
To Indoor To Outdoor
unit unit
To Indoor To Outdoor
unit unit
Pipe length L
(Refer to NOTES.)
- (05 - 55) -
NOTES (for UTR - EV2A L)
[For wall mounted type indoor units]
The EV KIT cannot be installed to the rear of compact wall mounted type indoor units. Install the EV KIT to the piping from the left or right side
of the indoor unit as shown in the following figure.
Refer to the table for the maximum pipe length of L, L1, L2. EV KIT
Pipe cover
L L1 L2
Compact wall mounted type 1.0 m 0.7 m 1.2 m
Maximum
Wall mounted type 0.8 m 0.2 m 1.0 m Maximum
length L2
length L1
Use a pipe cover with a width of 100 mm or more.
INSTALLATION
(2) Connection pipe
When the flare nut is tightened properly by your hand, Holding spanner Table
hold the body side coupling with a separate spanner , Body side Pipe Tightening torque
then tighten with a torque wrench.
6.35 14.0 to 18.0 N m
(1/4")
Torque 9.52
33.0 to 42.0 N m
wrench (3/8")
UTR - EV2A L
(3) Connect the wire
Wrap the tube (long) around the EV KIT cord from the end of the cord to
the indoor unit control box so that the cord will not be exposed, and then
fasten both ends of the tube with the binders (small). Binder (small)
(Cut the tube (long) if it is too long and will enter the indoor unit control box.)
When the pipe length was extended
Use the supplied wire to extend the length of the EV KIT cord.
Wrap the tube (short) around the connection, and then fasten both ends with
the binders (small) as shown in the figure to the right.
Connect the EV KIT cord to the indoor unit. (Refer to the INSTALLATION When the pipe length was extended
Fasten the EV KIT cord to the piping, etc., with the binders (medium)
to remove any slack in the cord.
Wire (supplied) EV KIT cord
(4) Finishing
Before performing this section, perform a sealing test. (Refer to
the INSTALLATION MANUAL of the outdoor unit.)
Coupler heat insulation
WARNING Coupler heat insulation
Binder (large)
(included with the
Make sure that the pipe is covered completely by the insulation, not EV KIT indoor unit)
exposing to air. Inadequate heat insulation may cause condensation.
Indoor
Put all the six heat insulating seals around the EV KIT. unit
Fix with the binders (large).
No gap No gap
Insulate the EV KIT connecting part.
Heat insulating
seal (6 pieces)
- (05 - 56) -
AIR TIGHT TEST
After the piping has been installed, perform a sealing test.
Charge the piping with nitrogen to within the sealing test pressure (4.2 MPa).
After 24 hours, check that the pressure has not fallen.
Make sure to add the pressure to both Gas pipe and Liquid pipe.
Perform the leak test on all flared and brazed parts.
Note: When the ambient temperature changes 5 deg. ,the test pressure changes 0.07MPa.
VACUUM PROCESS
CAUTION
Do not purge the air with refrigerant but use a vacuum pump to remove air from the indoor unit
and connection pipes!
(1) Remove the cap, and connect the gauge manifold and the vacuum pump to the charging
valves by the service hoses.
(2) Vacuum the indoor units and the connecting pipes until the pressure gauge indicates –76cmHg.
Be sure to vacuum from both 3-way valves.
(3) When –76cmHg is reached, operate the vacuum pump for at least 1 hour.
(4) If necessary, add the refrigerant for the appropriate amount after the vacuum process is completed
(Refer to next page "ADDITIONAL CHARGE").
(5) Disconnect the service hoses and fit the cap to the charging valve.
INSTALLATION
INSTALLATION
(6) Remove the blank caps, and fully open the spindles of the 3-way valves with a hexagon wrench.
(7) Tighten the blank caps of the 3-way valves to the specified torque.
Liquid pipe (3-way valve) 20.0 to 25.0 N·m 12.5 to 16.0 N·m
Gas pipe (3-way valve) 35.0 to 40.0 N·m 12.5 to 16.0 N·m
Check valve
Auxiliary pipe assembly
Operation Check valve
mode pressure Gauge manifold
- (05 - 57) -
ADDITIONAL CHARGE
Always add the refrigerant for the appropriate amount.
Refer the additional refrigent charge amount to item 5-1-4 "ADDITIONAL CHARGE
CALCULATION".
Either larger or smaller refrigerant charge amount leads to the cause of trouble.
For after service purpose , the added refrigerant charge amount and the calculation
shall be memorized.
CAUTION
When moving and installing the air conditioner,do not mix gas other than the specified refri-
gerant inside the refrigerant circuit.
When chaging the refrigerant ,always use an electronic balance for refrigerant chaging
(to measure the refrigerant by weight).
Add refrigerant from the charging valve after the completion of the work.
The maximum length of the piping is 70 m (actual pipe length). If the units are further apart
than this, correct operation can not be guaranteed.
INSTALLATION
INSTALLATION
R410A
Scale
When you use scale, please use electronic scale with few errors.
- (05 - 58) -
5-6-4. ELECTRICAL WIRING
Always perform the installation referring to the installation instruction sheet, based on your local
regions related laws and regurations,and electric company
WARNING
Before starting work, check that power is not being supplied to the outdoor unit.
Connect the connection cable firmly to the terminal board. Imperfect installation
may cause a fire.
Always fasten the outside covering of the connection cable with the cord clamp.
(If the insulator is chafed,electric leakage may occur.)
Match the terminal board numbers of outdoor unit side with those of the indoor side.
Improper connection will lead to malfunction or cause fuse blow.
INSTALLATION
Using a screwdriver, remove the terminal screw(s) on the terminal board.
25 mm
Strip
Loop
Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver. Insulation
Screw with
Screw with special washer
special washer Round
terminal
Round Wire Terminal
terminal board
Wire
Terminal block
- (05 - 59) -
Fix the connection cable and power supply cable at the cord clamp
After passing the connection cable and power supply cable through the
insulation tube, fasten it with the cord clamp.
Use VW-1,0.5 to 1.0mm thick, PVC tube as the insulation tube.
OUTDOOR UNIT
(1) Remove the terminal cover of the outdoor unit, and connect the connection cable and
the power supply cable to the terminal board.
(2) Fasten the connection and power supply cable with the cord clamp, and install the terminal cover.
Terminal board
Terminal cover
INSTALLATION
INSTALLATION
L N 1(L) 2(N) 3
POWER CONNECTION
Insulation tube
(V·W –1, 0.5 to 1.0 mm thick PVC tube)
Power Connection
supply cable
cable
- (05 - 60) -
INDOOR UNIT
EV KIT cord EV KIT cord
3
3
2
Outdoor unit
1
1
Connection cable
1 2 3
L (N)
1 2 3
• L• (N)
Breaker
220 - 240V Connection cable
1 50HZ EV EV EV
Indoor unit
CAUTION
Never bundle the power supply cable or connection cable with remote controller cable together.
Bundling these cables together will cause misoperation.
The power source capacity must be the sum of the air conditioner current and the current of other
electrical appliances.When the current contracted capacity is insufficient,change the contracted
INSTALLATION
INSTALLATION
capacity.
When the voltage is low and the air conditioner is difficult to start, contact the power company
to raise electrical voltage.
WARNING
The rated voltage of this product is 220-240V A.C.50 Hz.
Before turning on verify that the voltage is within the 198 V to 264 V range.
Always use a special branch circuit and install a special receptacle to supply power to the air
conditioner.
Use a circuit breaker and receptacle matched to the capacity of the air conditioner.
Perform wiring work in accordance with standards so that the air conditioner can be operated
safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations and electric
company standards.
stopper
Screw
(standard Cover
Hook metal
part)
ceiling
Insulation
Receiver Connect
unit
Cover
Open the hole
Tapping screw Hang to
Hole profile
Tapping screw (standard part) the hook
(60mm x 120mm)
(large:standard part) Receiver unit
- (05 - 61) -
5-6-5. DRAIN PROCESSING
OUTDOOR UNIT
Please connect the hose when the processing of the drain water of the installation in the room
etc. is necessary by the following method.
Since the drain water flows out of the outdoor unit during heating operation,
install the drain pipe (STANDARD PARTS) and connect it to a commercial 16mm hose.
(Heat pump model)
When installing the drain pipe, plug all the holes (• holes at seven places) other than the drain
pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage.
Make a space between bottom plate and the ground for the drain water.
Create ditch for the drain water around the outdoor unit if necessary.
Make sure that the drain hose is not lifted up, winding, or its end is not in the water.
INSTALLATION
INSTALLATION
Drain pipe mounting hole
Hose
Drain pipe
Drain pipe
CAUTION
- (05 - 62) -
INDOOR UNIT
NOTE : Install the drain pipe.
Install the drain pipe with downward gradient(1/50 to 1/100) and so there are
no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) and connect it with adhesive
(polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perfrom air bleeding.
Always heat insulate the indoor side of the drain pipe.
A. CEILING SETTING
Outlet air Drain hose
flow Trap Rise
OK NO NO
Arrange the drain hose
lower than this portion
Supporter
Air bleeding
INSTALLATION
INSTALLATION
1.5 to 2 m
(5 to 6.5 ft)
OK NO NO
CAUTION
Connect the drain hose so that the control box cover can easily be removed for servicing
when necessary.
In order to prevent water from leaking into the control box, make sure that the piping is
well insulated.
After finishing the piping, the drain hose installation and the wiring, seal the holes in the wall.
- (05 - 63) -
LOW STATIC PRESSURE DUCT TYPE / DUCT TYPE
Outlet Drain port : O.D 38mm
air Drain Trap Rise
flow hose
OK NO NO
Arrange the drain hose
lower than this portion.
Supporter
Air bleeding
1.5 to 2 m
The outside diameter of the drain port is 38 mm. Use a suitable drain hose.
There is a drain port on both the left and right sides. Select the drain port to match
the local conditions
INSTALLATION
Drain hose
CAUTION
Always check that the drain cap is installed to the unused drain port and is fastened with the
nylon fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon
fastener, water may drip during the cooling operation.
Rise
Trap
1.5 to 2 m
Air bleeding 150 mm or less
Max. 400 mm
When desiring a high drain pipe height, raise it up to 400 mm or less from the ceiling
within a range of 150 mm from the body.
A rise dimension over this range will cause leakage.
- (05 - 64) -
CASSETTE TYPE Drain port : O.D 32mm
Supporter
Rise
Trap
1.5 to 2 m
Air bleeding 150 mm or less
Max. 800 mm
When desiring a high drain pipe height, raise it up to 800 mm or less from the ceiling
within a range of 150 mm from the body.
A rise dimension over this range will cause leakage.
INSTALLATION
Insert the drain cap and drain hose
until it butts against the drain port.
Lifted up
Saddle Wave End in water
Drain hose
Right side
Drain cap
Drain hose
Lifted up
Saddle Wave End in water
Drain cap
Insert the drain cap until it
butts against the drain port. Insert the drain hose until it
butts against the drain port.
- (05 - 65) -
DRAIN PIPE INSULATION
Please confirm water is injected into Drain pan of the indoor unit, and drain is done normally
when the connection of Drain hose is completed.
Please check whether there is water leak part in the Drain piping.
Please insulate it from heat by the heat insulator of enough thickness so that there is no be
dewy when the confirmation ends. It causes the water leak like being imperfect.
Drain hose
Drain hose insulation
insulation
Unit
Unit
Drain hose
0 mm
Drain hose
INSTALLATION
Drain cap 0 mm * Please roll the heat insulator also on the
Drain cap side.(some models)
Outside
wall cap
Saddle
Sealer
putty
Wall (Outdoors)
Pipe
* Please cover the space with the putty etc. when
you put out Drain hose from the wall.
When converging multiple drain pipes , install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
- (05 - 66) -
5-6-6. DRAIN PUMP UNIT
MODEL : UTZ-PX1BBA
Specifications
Unit Specifications
Height of drain up mm Maximum 1000
Power source - 220 - 240V, 50 - 60Hz
Power input (230V, 50Hz/60Hz) W 12 / 10.8
Current (230V, 50Hz/60Hz) mA 114 / 92
Dimensions (H x W x D) mm 176 x 178 x 154
Weight kg 2.5
Connection pipe diameter - VP25 (I.D. 25mm, O.D. 32mm)
Direction of pipe connection *1 - 360°
Angle of pipe connection *2 - 0° (Horizontal) - 90°(Vertical)
Control method - Control board of Indoor unit
Safety device - Float switch, Thermal fuse
*1 Direction of pipe connection *2 Angle of pipe connection
INSTALLATION
INSTALLATION
Application indoor units
Type Model
Compact Duct AR07, AR09, AR12, AR14, AR18, AR22
Max.1000
side side
217
176
51
560*3/850*4
*3: AR07,09
*4: AR12,14,18, 22 Leave the space required to service the unit.
127
720
575
AIR
178
Top view
- (05 - 67) -
Installing drain pump unit
Use the tapping screw to install
the drain pump unit to the indoor unit.
20±0.3
Hole Diameter : 3.3
105±3
Hose band
15±3
Joint hose
INSTALLATION
Ceiling Level meter
Air
Level meter
10 mm
or less
10 mm
or less
GOOD BAD
GOOD BAD
Installing hose
Trap
Horizontal BAD
Downward gradient of BAD
1/50 to 1/100
Vertical loop
Part : Hose
- (05 - 68) -
Installing pipe
Supporter
Locally arranged pipe
VP25
Max. 1 m
Trap
[O.D 32mm]
or more
BAD
INSTALLATION
Observe the following procedures to construct centralized drain pipe fittings.
Electrical wiring
Control box
Indoor unit
Float switch wire
Circuit board (Connector:Red)
- (05 - 69) -
5-6-7. TEST RUN
TEST RUN METHOD
The procedures for performing the test run are desribed below.
(Supply power for at least 4 hours before starting operation in the winter.)
(1) Perform a test run (cooling) separately for each indoor unit that is connected to the refrigerant system,
and check the operation in order to confirm there is no problem on the wiring connection and the address.
(2)Perform a test run (cooling) simultaneously for all indoor units are connected to the refrigerant system,
and check the operation in order to confirm all installation is completed.
SW 1 - 1 SW 1 - 2
INSTALLATION
Test operation using remote controller
Short two metallic pieces in the remote controllers test run frame while the indoor unit is running.
To stop the test run, push START/STOP button of the remote controller.
When the air conditioner is being test run, the OPERATION and TIMER indicators flash slowly
at the same time.
CHECK LIST
Check item Checking Method Standard
After operating the indoor unit, Check operation sound and
1 Outdoor unit LED 3 :flushing
the compressor operates? the LED of outdoor unit PCB.
High pressure and low pressure Cooling : Low pressure 0.7 to 0.9MPa (approx.)
2 Confirm with a pressure gauge
are normal? Heating : High pressure 2.2 to 2.7 MPa (approx.)
- (05 - 70) -
5-7. STANDARD ACCESSORIES
The following installation parts are supplied. Use them as required.
INSTALLATION
- (05 - 71) -
5-7-2. INDOOR UNIT
COMPACT CASSETTE TYPE
GRILLE ACCESSORIES
Battery
2
INSTALLATION
INSTALLATION
CASSETTE TYPE
Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty
Installation Remote Battery Remote
template controller controller
1 1 2 holder 1
- (05 - 72) -
COMPACT DUCT TYPE
Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty
Installation Special nut A (M10) Remote Receiver unit Binder 2
template (small)
1 (large flange) 4 controller 1 1
4
(large)
Hanger Special nut B (M10) Remote Hook metal Filter 2
(small flange) controller 1 1 (AR7/9)
4 4
holder 3
(AR12/14
18/22)
Tapping screw Coupler heat Battery Cover
( 4X10) insulation 1 2 1
10
(large)
Name and Shape Q’ ty Name and Shape Q’ ty Name and Shape Q’ ty Name and Shape Q’ ty Name and Shape Q’ ty
INSTALLATION
INSTALLATION
Installation Special nut A (M10) Remote Receiver unit Screw 2
template (large ßange) controller (Ø3×12)
1 4 1 1
2
(Ø4×20)
Hanger Special nut B (M10) Remote Hook metal 1
(small ßange) controller (Ø4×12)
4 4 holder 1 1
1
(Ø4×10)
Binder Coupler heat Battery Cover Adopter
insulation Ø6.35-Ø9.52
5 (large) 1 2 1
1
Drain hose insulation Coupler heat Insulation
insulation AR30 type only
1 (small) 1 1
- (05 - 73) -
COMPACT WALL MOUNTED TYPE
Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty
Wall hook bracket Cloth tape Remote controller Remote controller holder
1 1 1 1
8 1 2 2
Binder
INSTALLATION
Wall hook bracket Wire assembly Remote controller Remote controller holder
1 1 1 1
Tapping screw Big EMI filter (ZCAT 1518-0730) Tapping screw Battery
12 Small
1 3 2
Normal
4
- (05 - 74) -
5-8. REFRIGERANT LEAKAGE CAUTION
The installer and system specialist shall secure safety against leakage according to local
regulations or standards. The following concentration limit may be applicable if local
regulations are not available.
5-8-1. INTRODUCTION
Almost all our VRF(J series) type air conditioners use R410A as refrigerant. Though are
harmless and incombustible in itself, the room in which the air conditioner is installed
should be large enough that the refrigerant gas will not exceed the concentration limit
even if the refrigerant gas leaks.
Concentration limit
Concentration limit is the limit of Freon gas concentration where immediate measures
can be taken without hurting the human body when refrigerant leaks in to the air. The
concentration limit shall be described in units of Kg/m3 (Freon gas weight in /m3 air) to
facilite calculation.
Outdoor unit
Flow of
(No.1 system) refrigerant
INSTALLATION
INSTALLATION
Room where refrigerant leaks
(Refrigerant of the whole No.1
Indoor unit
system flows out.)
- (05 - 75) -
Outdoor unit
(b) With partition and without opening which serve as
passage of air to adjoining room.
smallest
Indoor unit room
Countermeasure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below or provide opening without door.
Countermeasure 2
INSTALLATION
INSTALLATION
Provide gas leak alarm linked with mechanical ventilator.
Indoor unit
Pay special attention to the place, such as a basement, etc. When refrigerant can accummalate,
since refrigerant is heavier than air.
- (05 - 76) -