L7 - L7C - 0016 Manual in English
L7 - L7C - 0016 Manual in English
                         TOEPC71067602A
                   Table of Contents
    Warnings .......................................................................................................VII
    Safety Precautions and Instructions ............................................................ VIII
    EMC Compatibility ......................................................................................... X
    Line Filters ....................................................................................................XII
    Registered Trademarks ............................................................................... XIII
                                                                                                                                                    I
         Wiring Main Circuit Terminals ...................................................................... 2-5
               Applicable Wire Sizes and Crimp Terminals .................................................................. 2-5
               Main Circuit Terminal Functions .................................................................................... 2-9
               Main Circuit Configurations ......................................................................................... 2-10
               Standard Connection Diagrams .................................................................................. 2-11
               Wiring the Main Circuits .............................................................................................. 2-12
II
         Autotuning Mode Selection ............................................................................................ 4-4
         Auto Tuning Precautions ............................................................................................... 4-5
         Autotuning Procedure with Induction Motors ................................................................. 4-6
         Autotuning Procedure with PM Motors .......................................................................... 4-7
         PM Motor Encoder Offset Tuning .................................................................................. 4-8
         Precautions for Induction Motor Autotuning ................................................................... 4-9
         Autotuning Alarms and Faults ...................................................................................... 4-10
                                                                                                                                              III
     Acceleration and Deceleration Characteristics ......................................... 6-20
          Setting Acceleration and Deceleration Times .............................................................. 6-20
          Acceleration and S-curve Settings .............................................................................. 6-22
          Output Speed Hold (Dwell Function) ........................................................................... 6-22
          Stall Prevention During Acceleration ........................................................................... 6-23
IV
    Output Terminal Functions .........................................................................6-56
    Motor and V/f Pattern Setup ......................................................................6-59
       Setting Motor Parameters for Induction Motors (Motor 1 and 2) ................................. 6-59
       Setting Motor Parameters for PM Motors .................................................................... 6-62
       Motor Rotation Direction Change ................................................................................ 6-63
    Digital Operator/LED Monitor Functions ....................................................6-64
          Setting Digital Operator/LED Monitor Functions .......................................................... 6-64
          Copying Parameters (JVOP-160-OY only) .................................................................. 6-66
          Prohibiting Overwriting of Parameters ......................................................................... 6-70
          Setting a Password ...................................................................................................... 6-70
          Displaying User-set Parameters Only .......................................................................... 6-71
    Troubleshooting .........................................................................................7-18
          If A Parameter Cannot Be Set ..................................................................................... 7-18
          If the Motor Does Not Operate Properly ...................................................................... 7-19
          If the Direction of the Motor Rotation is Reversed ....................................................... 7-19
          If the Motor Stalls or Acceleration is Slow .................................................................... 7-19
          If Motor Deceleration is Slow ....................................................................................... 7-20
          Motor torque is insufficient. .......................................................................................... 7-20
          If the Motor Overheats ................................................................................................. 7-20
          If Peripheral Devices are Influenced by the Starting or Running Inverter .................... 7-21
          If the Earth Leakage Breaker Operates When the Inverter is Running ....................... 7-21
          If There is Mechanical Oscillation ................................................................................ 7-21
                                                                                                                                                V
     8    Maintenance and Inspection .................................................8-1
          Maintenance and Inspection ....................................................................... 8-2
                Periodic Inspection ........................................................................................................ 8-2
                Periodic Maintenance of Parts ...................................................................................... 8-3
                Cooling Fan Replacement ............................................................................................. 8-4
                Removing and Mounting the Terminal Card .................................................................. 8-6
     9    Specifications .........................................................................9-1
          Inverter Specifications ................................................................................. 9-2
             Specifications by Model ................................................................................................. 9-2
             Common Specifications ................................................................................................. 9-4
          Derating ....................................................................................................... 9-6
             Ambient Temperature Derating ..................................................................................... 9-6
             Carrier Frequency Derating ........................................................................................... 9-6
             Altitude Derating ............................................................................................................ 9-7
          AC Reactors for EN 12015 Compatibility .................................................... 9-8
          EN 954-1 / EN81-1 Certificates ................................................................... 9-9
     10   Appendix ...............................................................................10-1
          Inverter Application Precautions ............................................................... 10-2
                Selection ...................................................................................................................... 10-2
                Installation ................................................................................................................... 10-2
                Settings ....................................................................................................................... 10-2
                Handling ...................................................................................................................... 10-3
VI
Warnings
CAUTION
     Cables must not be connected or disconnected, nor signal tests carried out, while the power is
     switched on.
     The Varispeed L7 DC bus capacitor remains charged even after the power has been switched off. To
     avoid an electric shock hazard, disconnect the frequency inverter from the mains before carrying out
     maintenance. Then wait for at least 5 minutes after all LEDs have gone out.
     Do not perform a withstand voltage test on any part of the inverter. It contains semiconductors,
     which are not designed for such high voltages.
     Do not remove the digital operator while the mains supply is switched on. The printed circuit board
     must also not be touched while the inverter is connected to the power.
     Never connect general LC/RC interference suppression filters, capacitors or overvoltage protection devices to
     the inverter input or output.
     To avoid unnecessary over current faults, etc., being displayed, the signaling contacts of any contac-
     tor or switch fitted between inverter and motor must be integrated into the inverter control logic
     (e.g. baseblock).
     The inverter must be operated with the appropriate line filters, following the installation instructions
     in this manual and with all covers closed and terminals covered.
     Only then will adequate protection be provided. Please do not connect or operate any equipment
     with visible damage or missing parts. The operating company is responsible for any injuries or
     equipment damage resulting from failure to heed the warnings in this manual.
                                                                                                                     2
    Safety Precautions and Instructions
     1. General
       Please read these safety precautions and instructions for use thoroughly before installing and operating this
       inverter. Also read all of the warning signs on the inverter and ensure they are never damaged or removed.
       Live and hot inverter components may be accessible during operation. Removal of housing components, the
       digital operator or terminal covers runs the risk of serious injuries or damage in the event of incorrect installa-
       tion or operation. The fact that frequency inverters control rotating mechanical machine components can give
       rise to other dangers.
       The instructions in this manual must be followed. Installation, operation and maintenance may only be carried
       out by qualified personnel. For the purposes of the safety precautions, qualified personnel are defined as indi-
       viduals who are familiar with the installation, starting, operation and maintenance of frequency inverters and
       have the proper qualifications for this work. Safe operation of these units is only possible if they are used
       properly for their intended purpose.
       The DC bus capacitors can remain live for about 5 minutes after the inverter is disconnected from the power.
       It is therefore necessary to wait for this time before opening its covers. All of the main circuit terminals may
       still carry dangerous voltages.
       Children and other unauthorized persons must not be allowed access to these inverters.
       Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all persons with
       any form of access to the inverters.
     4. Installation
       Install and cool the inverters as specified in the documentation. The cooling air must flow in the specified
       direction. The inverter may therefore only be operated in the specified position (e.g. upright). Maintain the
       specified clearances. Protect the inverters against impermissible loads. Components must not be bent nor insu-
       lation clearances changed. To avoid damage being caused by static electricity, do not touch any electronic
       components or contacts.
3
  arrangement and laying of cables. This also applies to equipment with the CE mark. It is the responsibility of
  the manufacturer of the system or machine to ensure conformity with EMC limits.
  Contact your supplier or Yaskawa representative when using leakage current circuit breaker in conjunction
  with frequency inverters.
  In certain systems it may be necessary to use additional monitoring and safety devices in compliance with the
  relevant safety and accident prevention regulations. The frequency inverter hardware must not be modified.
CAUTION
   If a PM motor is turned by any external force, high voltage is generated in the windings.
   • During wiring, maintenance or inspection make sure, that the motor is stopped and can not turn.
   • If the inverter is turned off and the motor must be turned, make sure that motor and inverter output are
      electrically disconnected.
  If a motor is exchanged or operated the first time, always set up the motor control relevant parameters using
  the nameplate data or perform autotuning. Do not change the parameters recklessly. To ensure a safe operation
  with PM motors always set the:
   • correct motor data
   • the PG open detection parameters
   • the speed deviation detection parameters
   • the over acceleration detection parameters
  Wrong parameter settings can cause dangerous behavior or motor and inverter damage.
CAUTION
   If a permanent magnet motor is used, the peak current capability of the motor should always be higher than
   the maximum inverter output current in order to prevent a demagnetization of the motor.
Refer to page 4-2, Start Up for details about the correct start up procedure.
7. Notes
  The Varispeed L7 frequency inverters are certified to CE, UL, and c-UL.
                                                                                                                   4
    EMC Compatibility
     1. Introduction
       This manual was compiled to help system manufacturers using Yaskawa frequency inverters to design and
       install electrical switch gear. It also describes the measures necessary to comply with the EMC Directive. The
       manual's installation and wiring instructions must therefore be followed.
       Our products are tested by authorized bodies using the standards listed below.
       EN 61800-3:2004
     2. Measures to Ensure Conformity of Yaskawa Frequency inverters to the EMC Direc-
      tive
       Yaskawa frequency inverters do not necessarily have to be installed in a switch cabinet.
       It is not possible to give detailed instructions for all of the possible types of installation. This manual therefore
       has to be limited to general guidelines.
       All electrical equipment produces radio and line-borne interference at various frequencies. The cables pass
       this on to the environment like an aerial.
       Connecting an item of electrical equipment (e.g. drive) to a supply without a line filter can therefore allow HF
       or LF interference to get into the mains.
       The basic countermeasures are isolation of the wiring of control and power components, proper grounding and
       shielding of cables.
       A large contact area is necessary for low-impedance grounding of HF interference. The use of grounding
       straps instead of cables is therefore definitely advisable.
       Moreover, cable shields must be connected with purpose-made ground clips.
5
                                      Ground clip         Ground plate
  The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and paint.
  –Ground the cable shields at both ends.
  –Ground the motor of the machine.
                                                                        Load                         L2   V
                                                                                               GND L1 L3 U W GND
                                                               Cable Lenght
                                                               as short as possible
                                                          Grounded
                                                          Metal Plate
                                                                                                               Screened
                                                                                                               Motor cable
                                                                               Ground Bonds
                                                                               Remove any paint!
                                                                                                          M
                                                                                                          ~3
                                                                                                                             6
    Line Filters
7
Registered Trademarks
                                                                                                   8
9
                                                                  1
Handling Inverters
    This chapter describes the checks required upon receiving or installing an Inverter.
1-2
Confirmations upon Delivery
 Checks
    Check the following items as soon as the Inverter is delivered.
                                                                                         Table 1.2 Checks
                             Item
    Has the correct model of Inverter been
                                                                                                                                            Method
                                                                                                                                                                                           1
                                                                              Check the model number on the nameplate on the side of the Inverter.
    delivered?
                                                                              Inspect the entire exterior of the Inverter to see if there are any scratches or
    Is the Inverter damaged in any way?
                                                                              other damage resulting from shipping.
    Are any screws or other components
                                                                              Use a screwdriver or other tools to check for tightness.
    loose?
    In case of any irregularities in the above items, contact the agency from which the Inverter was purchased or
    your Yaskawa representative immediately.
 Nameplate Information
    The nameplate attached to the side of each Inverter showing the model number, specifications, lot number,
    serial number and other information about the Inverter.
   Example Nameplate
    The following nameplate is an example for a standard European Inverter: 3-phase, 400 VAC,
    3.7 kW, IEC IP20 standards
In v e r te r m o d e l MO DEL C IM R - L 7X 4 3P 7 S P E C: 4 3P 7 7A In v e r te r s p e c i fi c a ti o n s
                    In p u t s p e c i fi c a ti o n        IN P U T     A C 3P H    3 8 0- 4 8 0V   5 0/6 0 H z 1 0. 2A
                  O u tp u t s p e c i fi c a ti o n        O U T P U T AC 3 PH      0- 4 8 0V   0- 1 2 0H z 8. 5A 3m in. 5 0% ED 8. 5kVA
                               Lot num ber                  O /N                                                   M A S S: 4. 0 kg              M as s
                            S er ial num ber                S /N                                                   P R G:
                           U L fi l e n u m b e r           F IL E N O E1 3 1 4 5 7
                                                                   YASKAW A EL EC T R IC C O R PO R AR IO N           M A DE I N JA P A N   Ms
                                                                   CIMR – L7 X 2 3P7
                       Inverter
                        Varispeed L7
                                                                                                                                                                                           1-3
        Inverter Specifications
          The Inverter specifications (“SPEC”) on the nameplate indicate the voltage class, maximum motor capacity,
          the protective structure, and the revision of the Inverter in alphanumeric codes.
                                                           2 3P7 1 B
                        No.         Voltage Class                      No.    Hardware Revision
1                        2
                         4
                                AC Input, 3-phase, 200 V
                                AC Input, 3-phase 400 V
                                                                        A
                                                                        B
                                                                             Spec A
                                                                             Spec B
                              This manual describes the functionality of the inverter software version VSL702031
                              Older software versions may not support all described functions. Check the software version
            IMPORTANT         before start working with this manual!
1-4
 Component Names
                        Front cover
                                                                               Heatsink
                    Digital Operator
                                                                              Nameplate
Terminal cover
Charge indicator
Ground terminal
                                                                                                                  1-5
       Inverters of 22 kW or More
        The external appearance and component names of the Inverter are shown in Fig 1.6. The Inverter with the ter-
        minal cover removed is shown in Fig 1.7.
                                                                                          Cooling fan
                   Front cover
Terminal cover
                   Control circuit
                       terminals
                                                                                          Charge indicator
                     Main circiut
                      terminals
Ground terminals
1-6
Exterior and Mounting Dimensions
 IP00 Inverters
       Exterior diagrams of the IP00 Inverters are shown below.
          W1              4-d                                                        W1          4-d
                                                                                                 H1
                                                                                                       H0
                                                                                                              H
                         H1
                                                                                                 H2
                                                                                                                                 t1
                                                            t1
                                                                                                       H3
                                                                                                              Max.10
                                                                                                                                D1
                         H2
W D1 Max.10 W Max.10 5 D
3 D Grommet
H0
                                                                                                                H
                                         H
H2
                                                                                                                                t1
                                                                 t1
                                                                                                         H3
                                                                                                               Max.10
                                                                                                                                D1
                        H2
H3
W D1 Max.10 W Max.10 5 D
                                         3             D                                       Grommet
   200/400 V Class Inverters of 3.7 to 18.5 kW                          200V Class inverters of 22kW or 55kW
                                                                        400 V Class Inverters of 22kW or 55 kW
                                                                                                                                      1-7
                                                                                                                                                                                                                    1
1-8
              Max.                                                                                       Dimensions (mm)                                                                                          Caloric Value (W)
              Appli-                         IP00                                                    NEMA1                                                            IP20                                                   Total Cool-
      Voltage cable                                                                                                                                                                                         Mount
                                                                                                                                                                                                                             Heat   ing
       Class Motor                                                      App-                                                           App-                                                            App- ing Exter Inter- Gen-
                             H     D     W1 H1      H2     D1     t1     rox W     H     D     W1 H0   H1    H2     H3    D1     t1    rox. W      H      D   W1 H0   H1     H2    H3     D1     t1    rox. Holes nal  nal         Method
              Output W                                                                                                                                                                                                       era-
              [kW]                                                      Mass                                                           Mass                                                            Mass d*               tion
                  3.7                                                                                                                                                                                              112   74    186
                         140 280 177 126 266         7     59     5      4   140   280   177 126 280 266      7           59     5      4   140   280     177 126 280 266    7            59     5      4    M5
                  5.5                                                                                                0                                                              0                              164   84    248
                  7.5                                                    6         300                                                  6         300                                                   6          219   113   332
                         200 300 197 186 285               65.5              200         197 186 300 285      8           65.5              200           197 186 300 285    8            65.5
                  11                                                     7         310                              10                  7         310                              10                   7          374   170   544
                 15                                                                350                               0                            350                               0            2.3         M6    429   183   612
        200 V            240 350 207 216 335 7.5           78     2.3   11   240         207 216 350 335                  78     2.3   11   240           207 216 350 335                 78            11
                18.5                                                               380                              30                            380                        7.5   30                              501   211   712    Fan
      (3-phase)                                                                                              7.5
                 22      250 400         195 385                        17   254   535         195 400 385          135                20   254   464     258 195 400 385          64 100               19         586   274   860
                                   258                     100                           258                              100
                  30     275 450         220 435                        20   279   615         220 450 435          165                23                                                                          865   352   1217
                  37               298                     100          52               298                              100          57                                                                         1015   411   1426
                         375 600         250 575                             380   809         250 600 575          209
                  45               328              12.5          3.2   57               328                 12.5                3.2   62                                                                         1266   505   1771
                                                           130                                                            130
                  55     450 725 348 325 700                            78   453 1027 350 325 725 700               302                86                                                                         1588   619   2207
                  3.7                                                                                                                                                                                              80    68    148
                  4.0    140 280 177 126 266         7     59     5      4   140   280   177 126 280 266      7           59     5      4   140   280     177 126 280 266    7            59     5      4    M5    91    70    161
                  5.5                                                                                                                                                                                              127   82    209
                  7.5                                                                                                0                                                              0                              193   114   307
                         200 300 197 186 285         8     65.5          6   200   300   197 186 300 285      8           65.5          6   200   300     197 186 300 285    8            65.5          6
                  11                                                                                                                                                                                               252   158   410
        400 V     15                                                                                                                                                                                               326   172   498
      (3-phase)          240 350 207 216 335               78           10   240   350   207 216 350 335                  78           10   240   350     207 216 350 335                 78            10                            Fan
                  18.5                                                                                                                                                                                             426   208   634
                  22                                              2.3                                                            2.3                                                             2.3         M6    466   259   725
                         275 450 258 220 435               100          17   279   535   258 220 450 435                  100          20   279 514.5 258 220 450 435                     100           19
                  30                                7.5                                                      7.5    85                                                       7.5   64                              678   317   995
                  37                                                    31         635                                                 35         614                                                              784   360   1144
                                                                                                                                                                                                        34
                  45     325 550 283 260 535               105               329         283 260 550 535                  105               329           283 260 550 535                 105                      901   415   1316
                                                                        30         715                              165                34         629.5                            79.5
                  55                                                                                                                                                                                    33        1203   495   1698
Install the Inverter in the installation site described below and maintain optimum conditions.
 Installation Site
    Install the Inverter under the following conditions in a pollution degree 2 environment.
                                                                                                                         1
                                                Table 1.4 Installation Site
                Type                  Ambient Operating Temperature                          Humidity
           NEMA1 / IP20                         -10 to + 40 °C                    95% RH or less (no condensation)
              IEC IP00                          -10 to + 45 °C                    95% RH or less (no condensation)
    Protection covers are attached to the top and bottom of the Inverter. Be sure to remove the protection covers
    before installing a 200 or 400 V Class Inverter with an output of 18.5 kW or less in a panel.
    Observe the following precautions when mounting the Inverter.
     • Install the Inverter in a clean location which is free from oil mist and dust. It can be installed in a totally
       enclosed panel that is completely shielded from floating dust.
     • When installing or operating the Inverter, always take special care so that metal powder, oil, water, or
       other foreign matter does not get into the Inverter.
     • Do not install the Inverter on combustible material, such as wood.
     • Install the Inverter in a location free from radioactive materials and combustible materials.
     • Install the Inverter in a location free from harmful gasses and liquids.
     • Install the Inverter in a location without excessive oscillation.
     • Install the Inverter in a location free from chlorides.
     • Install the Inverter in a location not in direct sunlight.
                                                                                                                         1-9
       Installation Orientation and Space
         Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always pro-
         vide the following installation space to allow normal heat dissipation.
1                       A
                                                                                     B
                                                                                                           Air
                                                                                 A           B
                                   200V class inverter, 3.7 to 55 kW
                                                                              50 mm      120 mm
                                   400V class inverter, 3.7 to 55 kW
                      1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.
                      2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a
                         panel.
                         Always provide enough space for suspension eye bolts and the main circuit lines when installing an
         IMPORTANT
                         Inverter with an output of 22 kW or more in a panel.
1-10
Removing and Attaching the Terminal Cover
Remove the terminal cover to wire cables to the control circuit and main circuit terminals.
Before opening the terminal cover, switch off the power supply and wait at least 5 min. to make sure, that
   IMPORTANT
                  the DC bus is discharged!
                                                                                                                                1
Fig 1.11 Removing the Terminal Cover (Model CIMR-L7X43P7 Shown Above)
   Inverters of 22 kW or More
    Loosen the screws on the left and right at the top of the terminal cover, pull out the terminal cover in the direc-
    tion of arrow 1 and then lift up on the terminal in the direction of arrow 2.
Fig 1.12 Removing the Terminal Cover (Model CIMR-L7X4022 Shown Above)
                                                                                                                               1-11
        Attaching the Terminal Cover
           When the terminal block wiring has been completed, attach the terminal cover by reversing the removal proce-
           dure.
           For Inverters with an output of 18.5 kW or less, insert the tab on the top of the terminal cover into the groove
1          on the Inverter and press in on the bottom of the terminal cover until it clicks into place.
1-12
Removing/Attaching the Digital Operator/
LED Monitor and Front Cover
Fig 1.13 Removing the Digital Operator/LED Monitor (Model CIMR-L7X43P7 Shown Above)
                                                                                                                     1-13
       Removing the Front Cover
         Press the left and right sides of the front cover in the directions of arrows 1 and lift the bottom of the cover in
         the direction of arrow 2 to remove the front cover as shown in the following illustration.
Fig 1.14 Removing the Front Cover (Model CIMR-L7X43P7 Shown Above)
1-14
                  1. Do not remove or attach the Digital Operator/LED Monitor or mount or remove the front cover using meth-
                     ods other than those described above, otherwise the Inverter may break or malfunction due to imperfect
                     contact.
                  2. Never attach the front cover to the Inverter with the Digital Operator/LED Monitor attached to the front
    IMPORTANT
                     cover. Imperfect contact can result.
                     Always attach the front cover to the Inverter by itself first, and then attach the Digital Operator/LED Moni-
                     tor to the front cover.
                                                                                                                                      1
 Inverters of 22 kW or More
    For inverters with an output of 22 kW or more, remove the terminal cover and then use the following proce-
    dures to remove the Digital Operator/LED Monitor and front cover.
Fig 1.16 Removing the Front Cover (Model CIMR-L7X4022 Shown Above)
                                                                                                                                     1-15
1
1-16
                                                                                          2
                                                                                 Wiring
This chapter describes the terminals, main circuit terminal connections, main circuit terminal wiring specifica-
tions, control circuit terminals, and control circuit wiring specifications.
                                         Magnetic                                                                                                      1
                                         Contactor                                                Link
2       3-phase power
        380 to 480V
        50/60Hz
                            L2                                       Line
                                                                     Filter
                                                                                            L2(S)                                   V/T2                                  IM/PM
L3 L3(T) W/T3
PE
                                                                                           S1
                                                                                                                                     TA1
                                    Forward run/stop
                                                                                           S2
                                    Reverse run/stop
                                                                                           S3                                                                                     PG
                                    Nominal Speed                                                                                                                P
                                                                                           S4
                                                                                                                                PG-X2
        Multi function              Inspection Run                                                                                                               P
                                                                                                                               (Optional)
        Inputs                                                                             S5
        (Factory setting)           Intermediate Speed
                                                                                           S6
                                    Leveling Speed
                                                                                           S7
                                    Not used                                                                                         TA3
                                                                                           BB
                                    Hardware Baseblock (note 3)
                                                                                           BB1                                       TA2
                                                                                                         +24V, 8mA                           A Pulse
                                                                                                                                                               Pulse Monitor Output
                                                                                                                                             B Pulse           RS-422
                                                                                                                                                               (100m or less)
                                                                                           SC
                                                                                                            IP24V (24V)                      Z Pulse
                                                                                                                                                           2
                                                                                             CN5(NPN setting)
                                                                                                                                                       3
                                                                                             E(G)
                                                                                                                                      MA
                                                                                                                                                 Fault contact output
                                                                                                                                      MB
                                                       Voltage adjust-                                                                           250VAC, max. 1A
                                                       ment                                                                            MC        30VDC, max. 1A
                                                                                           +V Analog input power
                                         Analog input              2kOhm                      supply +15V, 20mA
                                       (Speed reference)                                                                                M1
                                                               0 to 10 V                                                                     Brake Command
                                                                                           A1 Master speed
                                                2kOhm                                                                                   M2   (Factory setting)
                                                                                              reference 0 to 10V
                                                                         P
                                                                                           AC
                                                                                                                                        M3                             Multi-function
                                                                                                                                             Contactor Control         contact output
                                                                                                  0V                                    M4   (Factory setting)         250VAC, max. 1A
                                                                                                                                                                       30VDC, max. 1A
                                                         Input option cards                 2CN                                         M5
                                                                                                                                             Inverter Ready
                                                                                                                                        M6   (Factory setting)
      Note:
      1. Main circuit terminals are indicatied with double circles and
         control circuit terminals are indicatied with a single circles           1                                                                2
      2. The CN5 factory setting is NPN
      3. To enable the inverter both inputs, BB and BB1 must be closed. If                             Shielded               Twisted-pair
         only one of the inputs is closed, “BB” will be displayed in the                               wires                  wires
         operator panel and the inverter will not start.
2-2
 Circuit Descriptions
    Refer to the numbers indicated in Fig 2.1.
        1        These circuits are hazardous and are separated from accessible surfaces by protective separation
        2        These circuits are separated from all other circuits by protective separation consisting of double and
                 reinforced insulation. These circuits may be interconnected with SELV* (or equivalent) or non-
                 SELV* circuits, but not both.
        3        Inverters supplied by a four-wire-system source (neutral grounded)
                 These circuits are SELV* circuits and are separated from all other circuits by protective separation
                 consisting of double and reinforced insulation. These circuits may only be interconnected with
                                                                                                                                                            2
                 other SELV* (or equivalent) circuits.
      * SELV (Safety Extra Low Voltage) circuits have no direct connection to the primary power and are supplied by a transformer or equivalent isolating
        device. The circuits are designed and protected, so that, under normal and single fault condition, its voltage does not exceed a safe value.
        (See IEC 61010)
                                          SC SC SC BB                  +V    A1 AC             M5 M6 MA MB MC
   IMPORTANT                    E(G)         S1    S2 S3 S4         S5    S6 S7 BB1               M3 M4 M1               M2      E(G)
                                                                                                                                                            2-3
      Terminal Block Configuration
The terminal arrangements are shown in Fig 2.2 and Fig 2.3.
Charge indicator
Ground terminal
Fig 2.2 Terminal Arrangement (200 V/400 V Class Inverter of 3.7 kW)
Ground terminals
2-4
Wiring Main Circuit Terminals
  Wire Sizes
                                           Table 2.1 200 V Class Wire Sizes
                                                                                      Possible Recom-
   Inverter                                                            Tightening              mended
    Model
   CIMR-
                            Terminal Symbol
                                                            Terminal
                                                            Screws
                                                                         Torque
                                                                         (N•m)
                                                                                     Wire Sizes
                                                                                              Wire Size*1
                                                                                     mm2(AWG) mm2 (AWG)
                                                                                                              Wire Type
                                                                                                                                2
              R/L1, S/L2, T/L3,  ,   1,    2, B1, B2,
              U/T1, V/T2, W/T3, PO, NO                                                    4          4
   L7X23P7                                                    M4       1.2 to 1.5
                                                                                      (12 to 10)   (12)
   L7X2015                                                                                10
              B1, B2, PO                                      M5          2.5                       -
                                                                                       (8 to 6)
                                                                                                              Power cables,
                                                                                         25        25       e.g., 600 V vinyl
                                                              M6       4.0 to 5.0                             power cables
                                                                                         (4)       (4)
   L7X2018                                                                            10 to 16
              B1, B2, PO                                      M5          2.5                       -
                                                                                      (8 to 6)
                                                                                         25        25
                                                              M6       4.0 to 5.0
                                                                                         (4)       (4)
   L7X2022                                                                            10 to 16
                 3, PO                                        M6       4.0 to 5.0                   -
                                                                                      (8 to 4)
                                                                                      25 to 35     25
                                                              M8       9.0 to 10.0
                                                                                      (4 to 2)     (4)
   L7X2030                                                                            10 to 16
                 3, PO                                        M6       4.0 to 5.0                   -
                                                                                      (8 to 4)
                                                                                      25 to 35     25
                                                              M8       9.0 to 10.0
                                                                                      (4 to 2)     (4)
                                                                                                                                2-5
                                                                                                           Possible Recom-
      Inverter                                                                          Tightening                  mended
                                                                           Terminal                       Wire Sizes
       Model                        Terminal Symbol                        Screws
                                                                                          Torque                   Wire Size*1
                                                                                                                                        Wire Type
      CIMR-                                                                              (N•m)           mm2(AWG) mm2 (AWG)
                                                                                                            6 to 16
                       3, PO                                                  M8            8.8 to 10.8                      –
                                                                                                           (10 to 4)
      L7X2037
                                                                                                            35 to 70        35
                                                                             M10        17.6 to 22.5
                                                                                                           (2 to 2/0)       (2)
                                                                                                            0.5 to 4        1.5
                   r/l1, Δ/l2                                                 M4            1.3 to 1.4
                                                                                                               95
                                                                                                                           (16)
                                                                                                                            95
                   V/T2, W/T3, R1/L11, S1/L21, T1/L31, NO                                                 (3/0 to 4/0)     (3/0)
                                                                                                            6 to 16
                       3, PO                                                  M8            8.8 to 10.8                      –
                                                                                                           (10 to 4)
      L7X2045                                                                                                                           Power cables,
                                                                                                            50 to 70        50        e.g., 600 V vinyl
                                                                             M10        17.6 to 22.5
                                                                                                           (1 to 2/0)       (1)         power cables
                                                                                                            0.5 to 4        1.5
                   r/l1, Δ/l2                                                 M4            1.3 to 1.4
                                                                                                           (20 to 10)      (16)
                                                                                                            50 to 95      50 × 2P
                   R/L1, S/L2, T/L3,       ,     1, NO                       M12        31.4 to 39.2
                                                                                                          (1/0 to 4/0)   (1/0 × 2P)
                                                                                                              90            90
                   U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31                  M10        17.6 to 22.5
                                                                                                             (4/0)         (4/0)
                                                                                                            6 to 70
      L7X2055          3, PO                                                  M8            8.8 to 10.8                      –
                                                                                                          (10 to 2/0)
                                                                                                            35 to 95        50
                                                                             M10        17.6 to 22.5
                                                                                                           (3 to 4/0)      (1/0)
                                                                                                            0.5 to 4        1.5
                   r/l1, Δ/l2                                                 M4            1.3 to 1.4
                                                                                                           (20 to 10)      (16)
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
2-6
                                                                                                      Possible  Recom-
Inverter                                                                              Tightening                mended
                                                                     Terminal                        Wire Sizes
 Model                        Terminal Symbol                        Screws
                                                                                        Torque                 Wire Size*1
                                                                                                                               Wire Type
CIMR-                                                                                  (N•m)        mm2 (AWG) mm2 (AWG)
L7X4018                                                                                                  10         10
             B1, B2, PO                                                 M5                2.5
                                                                        M6            4.0 to 5.0
                                                                                                         (8)
                                                                                                       10 to 25
                                                                                                                    (8)
                                                                                                                    10
                                                                                                                                                 2
                                                                                                       (8 to 4)     (8)
L7X4037                                                                                                10 to 16
                 3, PO                                                  M6            4.0 to 5.0                     -
                                                                                                       (8 to 4)
                                                                                                       25 to 35     25
                                                                        M8            9.0 to 10.0
                                                                                                       (4 to 2)     (4)
L7X4045                                                                                                10 to 16
                 3, PO                                                  M6            4.0 to 5.0                     -
                                                                                                       (8 to 4)
                                                                                                       25 to 35     25
                                                                        M8            9.0 to 10.0
                                                                                                       (4 to 2)     (4)
L7X4055                                                                                                10 to 16
                 3, PO                                                  M6            4.0 to 5.0                     -
                                                                                                       (8 to 4)
                                                                                                       25 to 35     25
                                                                        M8            9.0 to 10.0
                                                                                                       (4 to 2)     (4)
*1. The wire size is valid for PVC insulated copper cable, 30° ambient temperature
                                                                                                                                                 2-7
         Recommended Crimp Terminal Sizes (Ring type)
      1. Crimp Terminal Sizes
                                                                                              Crimp Terminal Type
               Wire Cross Section (mm2)            Terminal Screws                         Klaukey
                                                                                                                                 JST
                                                                                A                         B
                         0.5 - 1.0                       M4                   620/4                    1620/4                   GS4-1
                            1.5                          M4                   630/4                    1620/4                   GS4-1
                            2.5                          M4                   630/4                    1630/4                  GS4-2.5
                             4                           M4                   650/4                    1650/4                   GS4-6
2                            6
                                                         M4
                                                         M5
                                                                              650/4
                                                                             101 R/5
                                                                                                       1650/4
                                                                                                       1650/5
                                                                                                                                GS4-6
                                                                                                                                GS5-6
                                                         M6                  101 R/6                   1650/6                   GS6-6
                                                         M8                  101 R/8                   1650/8                   GS6-8
                                                         M5                  102 R/5                   1652/5                  GS5-10
                            10                           M6                  102 R/6                   1652/6                  GS6-10
                                                         M8                  102 R/8                   1652/8                  GS8-10
                                                         M5                           *1               1653/5                  GS5-16
                                                                            103 R/5
                            16                           M6                  103 R/6                   1653/6                  GS6-16
                                                         M8                  103 R/8                   1653/8                  GS8-16
                                                         M6                  104 R/6                   1654/6                  GS6-25
                            25
                                                         M8                  104 R/8                   1654/8                  GS8-25
                                                         M6                  105 R/6                   1655/6                  GS6-35
                            35                           M8                  105 R/8                   1655/8                  GS8-35
                                                        M10                  105 R/10                  1655/10                 GS10-35
                                                         M8                  106 R/8                   1656/8                  GS8-50
                            50                          M10                  106 R/10                  1656/10                 GS10-50
                                                        M12                  106 R/12                  1656/12                 GS12-50
                                                         M8                  107 R/8                   1657/8                  GS8-70
                            70                          M10                  107 R/10                  1657/10                 GS10-70
                                                        M12                  107 R/12                  1657/12                 GS12-70
                                                        M10                  108 R/10                  1658/10                 GS10-95
                            95
                                                        M12                  108 R/12                  1658/12                 GS12-95
                                     Select the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.
                                     Line voltage drop is calculated as follows:
IMPORTANT Line voltage drop (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10-3
2-8
 Main Circuit Terminal Functions
    Main circuit terminal functions are summarized according to terminal symbols in Table 2.3. Wire the termi-
    nals correctly for the desired purposes.
                       Table 2.3 Main Circuit Terminal Functions (200 V Class and 400 V Class)
                                                                                Model: CIMR-L7X
                Purpose                         Terminal Symbol
                                                                          200 V Class           400 V Class
                                       R/L1, S/L2, T/L3                   23P7 to 2055           43P7 to 4055
    Main circuit power input
    Inverter outputs
                                       R1/L11, S1/L21, T1/L31
                                       U/T1, V/T2, W/T3
                                                                          2022 to 2055
                                                                          23P7 to 2055
                                                                                                 4022 to 4055
                                                                                                 43P7 to 4055    2
    DC bus terminals                      1,                              23P7 to 2055           43P7 to 4055
    Braking Resistor Unit connection   B1, B2                             23P7 to 2018           43P7 to 4018
    DC reactor connection                 1,    2                         23P7 to 2018           43P7 to 4018
                                                                                                                 2-9
        Main Circuit Configurations
           The main circuit configurations of the Inverter are shown in Table 2.4.
C IM R 䋭L 7X 23 P 7 to 2018 C IM R - L 7X 43 P 7 to 4018
                          B2                                                                     B2
                          B1                                                                     B1
2                            +䋱
                             + 2
                                                                               U /T1
                                                                                                   +1
                                                                                                   + 2
                                                                                                                                              U/T1
                        R /L 1                                                                  R/L1
                        S/L2                                                   V/T 2            S /L2                                         V /T2
                        T/L 3                                                  W /T3            T /L3                                         W /T3
                             -                                                                     -
N0 P0 N0 P0
+ 1 䋫䋱
                      R /L 1                                                                  R /L 1
                                                                                 U/T 1                                                          U /T 1
                      S/L2                                                                     S/L2
                      T /L3                                                      V /T2         T/L 3                                            V/T2
                    R 1/L 11                                                                R 1/L 11
                                                                                W /T 3                                                          W /T 3
                    S1 /L21                                                                 S1 /L21
                    T1 /L 31                                                                T1/L31
                        -                                                                        -
                                              N               P                                                  N0           P0
                                              0               0
                                   C IM R    - L 7X 2037 to 2055
                                                  + 3
+ 1
                     R/L 1
                     S/L 2                                                      U/T1
                     T /L3                                                      V /T2
                   R1 /L11
                                                                                W /T3
                   S1/L21
                   T 1/L31
                         -
                          r/l1
                         Δ2 0 0/                   P ow er         C ontrol
                          l2 0 0                   S upply         C ircuit
                                              N               P
                                              0               0
2-10
 Standard Connection Diagrams
          Standard Inverter connection diagrams are shown in Fig 2.4. These are the same for both 200 V Class and
          400 V Class Inverters. The connections depend on the Inverter capacity.
     CIMR-L7X23P7 to 2018 and 43P7 to 4018                                             CIMR-L7X2022, 2030, and 4022 to 4055
                                                  Braking
                                  DC reactor      Resistor                                                                  Braking Resistor
                                  (optional)      (optinal)                                                                    (optional)
S1/L21
T1/L31
Be sure to remove the short-circuit bar before connecting                                                   The DC reactor is built in.
the DC reactor.
CIMR-L7X2037 to 2055
                                                                 Braking
                                                            Resistor (optional)
                                                                  CDBR Braking
                                                                  Unit (optional)
+ 1 + 3 -
R/L1 U/T1
                                S/L2                   V/T2                         M
                                T/L3                   W/T3
          3 Phase
     200VAC or 400VAC           R1/L11
S1/L21
T1/L31
r / l1
/ l2
Control power is supplied internally from the DC bus at all inverter models.
                                                             Fig 2.4 Main Circuit Terminal Connections
                                                                                                                                                                    2-11
        Wiring the Main Circuits
           This section describes wiring connections for the main circuit inputs and outputs.
Installing Fuses
2 To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the table below.
2-12
Installing a Moulded-Case Circuit Breaker
 If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3) it must be
 suitable for the Inverter.
   • The MCCB should have a capacity of 1.5 to 2 times of the inverter's rated current.
   • For the MCCB's time characteristics selection the inverter's overload protection (one minute at 150% of
     the rated output current) must be considered.
                                                                                                                   2-13
       Wiring the Output Side of the Main Circuit
         The following precautions should be considered for the output circuit wiring.
       Ground Wiring
         The following precautions should be considered for the ground connection.
          • Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100 Ω and that
            of the 400 V Inverter with a ground resistance of less than 10 Ω.
          • Ground wires should not be shared with other devices, such as welding machines or power tools.
          • A ground wire, that complies with technical standards on electrical equipment must be used. The length of
            the ground wire should be as low as possible.
            Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and
            the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
          • When more than one Inverter is used the ground wires should not be looped.
OK NO
2-14
Connecting a Braking Resistor and Braking Unit (CDBR)
  A Braking Resistor and Braking Unit can be connected to the Inverter like shown in the Fig 2.7.
  To prevent overheating of the braking unit/braking resistor, the inverter operation should be stopped when the
  overload contacts are operated.
 200 V and 400 V Class Inverters with 3.7 to 18.5 kW Output Capacity
                                        Braking Resistor
                    Inverter
                                                                         Thermal overload
                                                                         relay contact
                                                                                                                    2
                                 Thermal overload
                                 relay contact
                                                                                                                   2-15
       Connecting Braking Units in Parallel
         When two or more Braking Units are connected in parallel the wiring and jumper settings must be done like
         shown in Fig 2.8. There is a jumper for selecting whether each Braking Unit is to be a master or slave. “Mas-
         ter” must be set for the first Braking Unit only, “Slave” must be set for all other Braking Units (i.e. from the
         second Unit onwards).
                                                                         MASTER                            MASTER
        Inverter                   MASTER
             Braking Unit #1
                            Thermal overload relay               Thermal overload relay              Thermal overload relay
                                  contact                              contact                             contact
B2
B1 / + 3
                                                                                                            U/T1
                                               R/L1
                       L1                                                                                   V/T2
                                               S/L2
                       L2                                                                                   W/T3
                                               T/L3
                       L3
                                               -
                                                                   Power            Control
                                                                   Supply           Circuit
P0
N0
Please refer to page 6-80, Rescue System for details about rescue operation.
2-16
Wiring Control Circuit Terminals
 Wire Sizes
    For remote operation using analog signals, the control line length between the Analog Operator or operation
    signals and the Inverter should be less than 30 m. The controller wires should always be separated from main
    power lines or other control circuits in order to avoid disturbances.
    It is recommended to use shielded twisted-pair wires and ground the shield for the largest area of contact
    between shield and ground.
    The terminal numbers and the appropriate wire sizes are shown in Table 2.6.
                             Table 2.6 Terminal Numbers and Wire Sizes (Same for all Models)                                                                  2
                                                                                                       Recom-
                                                         Tightening        Possible Wire
                                        Terminal                                                     mended Wire
              Terminals                                    Torque             Sizes                                                  Wire Type
                                        Screws                                                          Size
                                                           (N•m)             mm2(AWG)
                                                                                                         mm2(AWG)
*1. Ferrules with plastic sleeves should be used for the signal lines to simplify wiring and improve reliability.
                                                                                      d1
                                                                               8 mm
14 mm
d2
                                                                                                                                                             2-17
        Control Circuit Terminal Functions
           The functions of the control circuit terminals are shown in Table 2.8. Use the appropriate terminals for the cor-
           rect purposes.
2                      S3
                       S4
                               Nominal speed
                               Inspection Run
                                                                       Nominal speed when ON.
                                                                       Inspection RUN when ON.                                         24 VDC, 8 mA
                                                                                                        Functions are                  Photo-coupler
            Digi-                                                      Intermediate speed when
             tal
                       S5      Intermediate speed                                                       selected by setting
                                                                       ON.
            input                                                                                       H1-01 to H1-05.
           signals     S6      Leveling speed                          Leveling speed when ON.
                       S7      Not used                                –
                      BB       Hardware baseblock                      –                                                               –
                          *1   Hardware baseblock 1                    –                                                               –
                     BB1
                       SC      Digital input common                    –                                                               –
                                                                                                                                       15 V
            Ana-       +V      15 V power supply*2                     15 V power supply for analog references
                                                                                                                                       (Max. current: 20 mA)
             log
            input      A1      Frequency reference                     0 to +10 V/100%                                                 0 to +10 V(20 kΩ)
           signals
                      AC       Analog reference neutral                –                                                               –
                               Shield wire, optional ground line
                      E(G)                                       –                                                                     –
                               connection point
                      M1       Brake command
                                                                       Brake command when ON.
                      M2       (1NO contact)
               *1. This terminal is available on inverters with hardware SPEC B only. (page 1-4, Inverter Specifications describes how to find out the inverter
                   hardware version).
               *2. Do not use this power supply for supplying any external equipment.
               *3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in Fig 2.11.
Flywheel diode
2-18
 Sinking/Sourcing Mode (NPN/PNP Selection)
  The input terminal logic can be switched over between sinking mode (0-V common, NPN) and sourcing mode
  (+24V common, PNP) by using the jumper CN5. An external power supply is also supported, providing more
  freedom in signal input methods.
Internal Power Supply – Sinking Mode (NPN) External Power Supply – Sinking Mode (NPN)
S1
                                                                                                            2
                 S1
                                                                     S2
                 S2
                                                                                CN5       IP24V
                                       IP24V                                              (+24V)
                             CN5       (+24V)
                                                                     SC
                 SC
24 VDC
Internal Power Supply – Sourcing Mode (PNP) External Power Supply – Sourcing Mode (PNP)
                                                                     S1
                 S1
                                                                     S2
                 S2
                                                                                CN5       IP24V
                                       IP24V                                              (+24V)
                              CN5      (+24V)
                                                                     SC
                  SC
24 VDC
                                                                                                           2-19
        Control Circuit Terminal Connections
               Connections to Inverter control circuit terminals are shown in Fig 2.12.
                                                                              S1
                                    Forward run/stop
                                                                              S2
                                    Reverse run/stop
                                                                              S3
2         Multi function
                                    Nominal Speed
                                    Inspection Run
                                                                              S4
          Inputs                                                              S5
          (Factory setting)         Intermediate Speed
                                                                              S6
                                    Leveling Speed
                                                                              S7
                                    Not used
                                                                              BB
                                    Hardware Baseblock (note 2)
                                                                              BB1
                                                                                         +24V, 8mA
                                                                              SC
                                                                                            IP24V (24V)
CN5(NPN setting)
                                                                               E(G)
                                                                                                                 MA
                                                                                                                             Fault contact output
                                                                                                                 MB
                                                       Voltage adjust-                                                       250VAC, max. 1A
                                                       ment                                                      MC          30VDC, max. 1A
                                                                              +V Analog input power
                                          Analog input             2kOhm         supply +15V, 20mA
                                        (Speed reference)                                                         M1
                                                               0 to 10 V                                                 Brake Command
                                                                              A1 Master speed
                                                  2kOhm                                                           M2     (Factory setting)
                                                                                 reference 0 to 10V
                                                                         P
                                                                              AC
                                                                                                                  M3                           Multi-function
                                                                                                                         Contactor Control     contact output
                                                                                    0V                            M4     (Factory setting)     250VAC, max. 1A
                                                                                                                                               30VDC, max. 1A
                                                                                                                  M5
                                                                                                                         Inverter Ready
                                                                                                                  M6     (Factory setting)
       Note:
       1. The CN5 factory setting is NPN
       2. To enable the inverter both inputs, BB and BB1 must be closed. If
          only one of the inputs is closed, “BB” will be displayed in the
          operator panel and the inverter will not start.                             Shielded            Twisted-pair
                                                                                      wires               wires
                                    The base block circuit is a two channel circuit, i.e. always both channels (terminal BB and BB1) have to
                                    be enabled to enable the inverter output.
                    INFO
                                    Generally the terminals BB and BB1 can be linked directly at the terminals. However, if an EN81-1 con-
                                    form one motor contactor solution is required, the recommended BB and BB1 terminal wiring depends on
                                    the installation:
                                    1. If the controller and inverter are mounted in the same cabinet the terminals BB and BB1 can be linked
                                       directly at the inverter terminal board. Only one wire from the controller to the inverter base block
                                       input is necessary.
                                    2. If the inverter is mounted separated from the controller cabinet, two physically separated wires for the
                                       BB and BB1 terminal should be used in order to keep redundancy in case of a fault of one of the signal
                                       lines.
2-20
EN81-1 Conform Wiring with One Motor
Contactor
  In order to use the L7X with one motor contactor instead of two while keeping compliance to the
  EN81-1:1998, the following rules have to be followed:
   • The hardware base block function using the terminals BB and BB1 must be used to enable / disable the
     drive. The input logic must be PNP.
   • If the elevator safety chain is opened, the inverter output must be cut. This means that the base block sig-
     nals at the terminals BB and BB1 must be opened, e.g. via an interposing relay.
   • The base block monitor function must be programmed for one of the multi-function outputs (H2- =
     46/47). The regarding digital output contact must be implemented in the contactor supervision circuit of
     the controller in order to prevent a restart in case of an inverter base block or motor contactor malfunction.
                                                                                                                       2
   • All contactors must be conform to the EN81-1:1998, paragraph 13.2.
  Fig 2.13 shows an EN81-1:1998 wiring example.
                  Fig 2.13 EN81-1 Conform Wiring with One Motor Contactor (Example)
             Safety Chain
                Circuit
                                                       Elevator Controller
                                         K01
                                                       24VDC *1
K1
                                                                  BB Monitor
                                                                       (NC)
                                                 Yaskawa
                                               CIMR-L7xxxx
K2
                                                            M
  The wiring rules and the wiring example are approved by the TUEV Sued, Germany. For more details please
  contact your Yaskawa sales representative.
                                                                                                                      2-21
        Control Circuit Wiring Precautions
           The following precautions for wiring the control circuits must be considered.
            • Control circuit and main circuit wiring should be separated (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/
              T2, W/T3,     ,   1,    2, and   3, PO, NO) and other high-power lines.
            • The wiring for control circuit terminals MA, MB, MC, M1, M2, M3, M4, M5, and M6 (contact outputs)
              should be separated from wiring to other control circuit terminals.
            • If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
2           • Twisted-pair or shielded twisted-pair cables should be used for control circuits to prevent operating faults.
            • The cable shields should be connected to the ground with the maximum contact area.
            • Cable shields have to be grounded on both cable ends.
2-22
Wiring Check
 Checks
   Check all wiring after wiring has been completed. Do not perform continuity check on control circuits. Per-
   form the following checks on the wiring.
    • Is all wiring correct?
    • Have no wire clippings, screws, or other foreign material been left?
    • Are all screws tight?
    • Are any wire ends contacting other terminals?
                                                                                                                  2
                                                                                                                 2-23
       Installing and Wiring Option Cards
                 PG speed control cards                        Three phase (phase A, B, Z), line driver inputs
                                                PG-X2                                                                  A
                                                               (RS422), max. response frequency: 300 kHz
                                                 PG-F2                     y                                           A
                                                               Hiperface       or EnDat 2.1 interface card
                                             3G3RV-PDRT2       Intelligent DeviceNet option card                       C
                                                 SI-P1         Option card for Profibus-DP fieldbus                    C
                                                 SI-R1         Option card for InterBus-S fieldbus                     C
                 Communications cards
                                                 SI-S1         Option card for CANOpen fieldbus                        C
                                                  S1-J         Option card for LONworks                                C
                                            3G3RV-P10ST8-E     PLC option card                                         C
                    PLC option card                            PLC option card with DeviceNet communications
                                          3G3RV-P10ST8-DRT-E                                                           C
                                                               port (Slave)
                                                               3 Channel analog input card
                   Analog Input card            AI-14B         Signal level: -10 to 10 V or 0 to 10V                   C
                                                               Resolution: 13 Bit + sign
                                                               2 channel analog output card
                                                 AO-08         Signal level: 0 to 10 V                                 D
                                                               Resolution: 8 Bit
                  Analog Output Cards
                                                               2 channel high resolution analog output card
                                                 AO-12         Signal level: -10 to +10 V                              D
                                                               Resolution: 11 Bit + sign
                                                               6 channel digital output card for monitoring the
                                                 DO-08                                                                 D
                  Digital Output Cards                         inverter status (fault, zero speed, running, etc.)
                                                DO-02C         2 channel relay contact output                          D
        Installation
           Before mounting an Option Card, remove the terminal cover and be sure that the charge indicator inside the
           Inverter is OFF. After that, remove the Digital Operator/LED Monitor and front cover and mount the Option
           Card.
           Refer to documentation provided with the Option Card for the mounting instructions.
2-24
   Preventing C and D Option Card Connectors from Rising
    After installing an Option Card into slot C or D, insert an Option Clip to prevent the side with the connector
    from rising. The Option Clip can be easily removed by holding onto the protruding portion of the Clip and
    pulling it out.
                                     Option Clip
           (to prevent raising of C option card)
Input/Output Specifications
                                                                                                                           2-25
       Wiring the PG-B2 card
        The following illustrations show wiring examples for the PG-B2 using the option cards power supply or an
        external power source for supplying the PG.
                  Three-phase 200 VAC
                        (400VAC)
                                              Inverter
         R/L1
         S/L2
         T/L3
2
                                                                                                                      Power supply 0V
                                                                                                                       Pulse input phase A
                                                                                                                      GND pulse input phase B
                                                                                                                       Pulse input phase B
                                                                                                                      GND pulse input phase B
Fig 2.15 PG-B2 Wiring Using the Option Cards Power Supply
PG
TA1
PG
TA3
        Precautions:
            • The length of the pulse generator's wiring must not be more than 100 meters.
            • The direction of rotation of the PG can be set in user parameter F1-05. The factory setting is A-phase
                leading in forward direction (motor shaft turning counterclockwise seen from motor shaft side).
                                               Fordward rotation of stadard motor (PG)
                                         Forward
                                        command
A - phase
                                                                                              B - phase
                                                        The A_phase leads (CCW) when motor rotation is fordward
            • The pulse monitor output factor can be changed using parameter F1-05.
            • Refer to page 2-31, Wiring Precautions for general precautions.
2-26
PG-X2 Option Card
Input/Output Specifications
      TA1
                       5        Pulse input terminal phase A (–)                                                       2
                       6        Pulse input terminal phase B (+)            Line driver input (RS422 level)
                       7        Pulse input terminal phase B (–)            (maximum input frequency: 300 kHz)
*1. The 5V and 12V power supply should not be used at the same time.
                                                                                                                      2-27
       Wiring the PG-X2 card
        The following illustrations show wiring examples for the PG-X2 using the option cards power supply or an
        external power source for supplying the PG.
          Three-phase
            200 VAC
           (400 VAC)
2 PG-X2
                                                                                0V
                                                                                +5 VDC
                                                                                A+ Phase Imput
                                                                                A- Phase Imput   P
                                                                                B+ Phase Imput
                                                                                B- Phase Imput   P
                                                                                Z+ Phase Imput
                                                                                Z- Phase Imput   P
A Phase Ouput
B Phase Ouput
Z Phase Ouput
                            Fig 2.17 PG-X2 Wiring Using the Option Cards Power Supply
                                           PG-X2
                                            TA1
                                                       AC
                                                            0V   + 5V
0V
+5 V
PG
TA3
        Precautions:
            • The length of the pulse generator's wiring must not be more than 100 meters.
            • The direction of rotation of the PG can be set in user parameter F1-05. The factory setting is A-phase
               leading in forward direction (motor shaft turning counterclockwise seen from motor shaft side).
            • Refer to page 2-31, Wiring Precautions for general precautions.
2-28
PG-F2 Option Card
Supported Encoders
  The PG-F2 option card can be used in combination with the following encoder types:
   • Hiperfacey:     SRS60/70
   • EnDat 2.1:      ECN1313, ECN113, ECN413
Input/Output Specifications
                                                                                                                                             2
                                      Table 2.13 PG-F2 I/O Specifications
                                                   Contents
       Terminal      No.                                                                                        Specifications
                                      Hiperfacey                      EnDat
                                                                                                EnDat:      5VDC (±5%, max. 250 mA)
                      1        Us 7-12V                  5V UP and UP sensor
                                                                                                Hiperfacey: 8VDC (±5%, max. 150mA)
                      2        GND                       0V UN and 0V sensor                    0V
                      3        REFSIN                    B-
         TB1          4        +SIN                      B+
                                                                                                Differential inputs
                      5        REFCOS                    A-
                      6        +COS                      A+
                      7        DATA+                     DATA                                   RS-485 Data channel,
                      8        DATA-                     /DATA                                  Terminating resistance: 130 Ohm
                      1        Pulse monitor A+
                      2        Pulse monitor A-                                                 Open Collector Outputs
         TB3
                      3        Pulse monitor B+                                                 max 24 VDC, 30 mA
                      4        Pulse monitor B-
         TB4         (E)       Shielded sheath connection terminal
                                                                                                                                            2-29
       Wiring the PG-F2 Card
        The following illustration shows PG-F2 option card wiring with Hiperfacey or EnDat 2.1 encoders.
       Three-phase
         200 VAC
        (400 VAC)
PG-X2
2                                                                        0V
                                                                         +5 VDC
                                                                         A+ Phase Imput
                                                                         A- Phase Imput   P
                                                                         B+ Phase Imput
                                                                         B- Phase Imput   P
                                                                         Z+ Phase Imput
                                                                         Z- Phase Imput   P
A Phase Ouput
B Phase Ouput
Z Phase Ouput
        Precautions:
             • The length of the pulse generator's wiring must not be more than 50m for the signal lines and 30m for
                the monitor output at terminal TB3.
             • The direction of rotation of the PG can be set in user parameter F1-05 (PG Rotation). The factory set-
                ting is A-phase/SIN leading in forward direction (motor shaft turning counterclockwise seen from the
                shaft side).
                                                                      SIN
                                                                      COS
                                                                       Pulse A
                                                                       Pulse B
2-30
 Wiring the Terminal Blocks
  Wiring Precautions
    Consider the following precautions for wiring.
     • Shielded twisted-pair wires must be used for signal lines. Use cables which are recommended by the
        encoder manufacturer only.
     • For the cable connection to the encoder connectors which are recommended by the encoder manufacturer
        should be used.
     • Ferrules should be used (refer to Table 2.7).
     • The signal lines of the PG Speed Control Card should be separated from main power lines and other con-
        trol circuits.
     • The shield must be connected (green grounding cable of the option card) to the ground terminal to prevent
        operational errors caused by noise.
     • The wire ends should not be soldered. Doing so may cause contact faults.
     • The PG cards power supply must not be used for anything other than the pulse generator (encoder). Using
        it for another purpose can cause malfunctions due to noise.
     • A separate power supply is required if the PG power supply consumption is higher than 200 mA. (If
        momentary power loss must be handled, use a backup capacitor or other method.)
     • The PG cards maximum input frequency must not be exceeded. The output frequency of the pulse genera-
        tor can be calculated using the following formula.
                                                                                                                                    2-31
2
2-32
                                                                                      3
   LED Monitor / Digital
   Operator and Modes
The Varispeed L7 is equipped with the LED Monitor JVOP-163 which shows the drive status. The optional Digi-
tal Operator JVOP-160-OY can be used to adjust parameters as required.
This chapter describes Digital Operator displays and functions, and provides an overview of operating modes and
switching between modes.
       LED Monitor
         The LED monitor indicates the operation status by combinations of the LED display (Lights up, Blink, and
         Off) at RUN, DS1, and DS2.
          The LED pattern is as follows at each mode.
Alarm Indications
Fault Indications
         Alarm: The figure below shows an example of the LED display when a minor fault occurs.
                Refer to Chapter 6 and take appropriate countermeasures.
                             RUN      DS1    DS2          POWER
         Fault:   The figure below shows an example of the LED display when an OV or UV fault has
                  occurred
                             RUN      DS1    DS2          POWER
3-2
Digital Operator JVOP-160-OY
                                                                           Keys
                                                                           Execute operations such as setting parameters, moni-
                                                                           toring, jogging, and autotuning.
ESC Key Returns to the status before the DATA/ENTER key was pressed.
                                                                                                                                        3-3
              Key                           Name                                                         Function
                                                                         Selects the rotation direction of the motor when the Inverter is oper-
                           FWD/REV Key
                                                                         ated by the Digital Operator.
                                                                         Selects menu items, sets parameter numbers, and increments set val-
                           Increment Key                                 ues.
                                                                         Used to move to the next item or data.
                                                                         Selects menu items, sets parameter numbers, and decrements set val-
                           Decrement Key                                 ues.
                                                                         Used to move to the previous item or data.
DATA/ENTER Key Enters menus and parameters, and set validates parameter changes.
      There are indicators on the upper left of the RUN and STOP keys on the Digital Operator. These indicators
      light or flash to indicate the inverter operation status.
      The RUN key indicator flashes and the STOP key indicator lights during initial excitation or DC braking. The
      relationship between the indicators on the RUN and STOP keys and the Inverter status is shown in Fig 3.3.
Frequency reference
RUN
STOP
Light up
Blink
Off
3-4
 Inverter Modes
    The Inverter's parameters and monitoring functions are organized in five groups which make it easy to read
    and adjust parameters.
    The 5 modes and their primary functions are shown in the Table 3.2.
                                                                                                                                         3-5
       Switching Modes
         The mode selection display appears when the MENU key is pressed. Press the MENU key from the mode
         selection display to switch through the modes in sequence.
         Press the DATA/ENTER key to enter a mode and to switch from a monitor display to the setting display.
                     Display During Rung
                        To run the inverter after viewing/changing parameters press the MENU key and the DATA/ENTER key in
                        sequence to enter the Drive mode. A Run command is not accepted as long as the drive is in any other
            INFO        mode.
                        To enable Run commands from the terminals during programming set parameter b1-08 to “1”.
3-6
 Drive Mode
   In the Drive mode the Inverter can be operated. All monitor parameters (U1-), fault informations and the
   fault history can be displayed in this mode
   When b1-01 (Reference selection) is set to 0, 1 or 3, the selected frequency reference value (d1-) can be
   changed from the frequency setting display using the Increment, Decrement, Shift/RESET and Enter keys.
   After confirming the change by pressing the ENTER key, the display returns to the Monitor display.
 Example Operations
   Example key operations in drive mode are shown in the following figure.
                                                                                                                                                                 3
                                                                Monitor Display                           Frequency Setting Display
      Mode Selection
      Display
   Note:   When changing the display with the Increment/Decrement keys, after the last monitor parameter the display jumps back to the first monitor parameter
           and vice versa (e.g. U1-55 is followed by U1-01).
           The display for the first monitor parameter (frequency reference) will be displayed when power is turned ON. The monitor item displayed at startup
           can be set in o1-02 (Monitor Selection after Power Up).
                                                                                                                                                                 3-7
       Quick Programming Mode
         In quick programming mode the basic parameters required for the elevator operation like speeds, acceleration/
         deceleration times etc. can be monitored and set.
         The parameters can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET
         keys to change the frequency. The parameter is written and the display returns to the monitor display when the
         DATA/ENTER key is pressed.
         Refer to page 5-4, User Parameters Available in Quick Programming Mode for details.
       Example Operations
         Example key operations in quick programming mode are shown in the following figure.
3-8
 Advanced Programming Mode
   In the advanced programming mode all Inverter parameters can be monitored and set.
   A parameter can be changed from the setting displays using the Increment, Decrement, and Shift/RESET
   keys. The parameter is saved and the display returns to the monitor display when the DATA/ENTER key is
   pressed.
   Refer to page 5-1, User Parameters for details about the parameters.
 Example Operations
   Example key operations in advanced programming mode are shown in the following figure.
      Mode Selection Display               Monitor Display                       Setting Display
                                                                                                            3-9
       Setting Parameters
         Here the procedure to change C1-01 (Acceleration Time 1) from 1.5 s to 2.5 s is shown.
                      -DRIVE-
                        ** Main Menu **
               2
                           Operation
3              3
                      -QUICK-
                        ** Main Menu **               Press the MENU key 3 times to enter the advanced programming
                                                      mode.
                         Quick Setting
                       -ADV-
                         ** Main Menu **
               4
                          Programming
                       -ADV-
                          Initialization
               5                                      Press the DATA/ENTER to access the monitor display.
                          A1-00=1
                       Select Language
                       -ADV-
                         Accel / Decel                Press the Increment or Decrement key to display the parameter
               6        C1-01 = 1.50sec               C1-01 (Acceleration Time 1).
                          Accel Time 1
                       -ADV-
                         Accel Time 1                 Press the DATA/ENTER key to access the setting display. The
               7      C1-01 = 0 01.50sec
                        (0.00 ~ 600.0)                current setting value of C1-01 is displayed.
                           "1.50sec"
                       -ADV-
                         Accel Time 1
               8      C1-01 = 0 01.50sec              Press the Shift/RESET key to move the flashing digit to the right.
                        (0.00 ~ 600.0)
                           "1.50sec"
                       -ADV-
                         Accel Time 1
               9      C1-01 = 0 01.50sec              Press the Increment key to change set value to 2.50 s.
                        (0.00 ~ 600.0)
                           "1.50sec"
                       -ADV-
                         Accel Time 1
              10      C1-01 = 0 02.50sec              Press the DATA/ENTER key to save the set data.
                       (0.00 ~ 600.0)
                          "1.50sec"
                       -ADV-
                                                      “Entry Accepted” is displayed for 1 sec after pressing the
              11       Entry Accepted
                                                      DATA/ENTER key.
                       -ADV-
                         Accel Time 1
              12      C1-01 =    2.50sec              The display returns to the monitor display for C1-01.
                        (0.00 ~ 600.0)
                           "1.50sec"
3-10
 Verify Mode
    The Verify mode is used to display the parameters that have been changed from their default settings, either by
    programming or by autotuning. “None” will be displayed if no settings have been changed.
    The parameter A1-02 is the only parameter from the A1- group, which will be displayed in the modified
    constant list if it has been changed before. The other parameters will not be displayed, even if they are differ-
    ent from the default setting.
    In the verify mode, the same procedures as used in the programming mode can be used to change settings. Use
    the Increment, Decrement, and Shift/RESET keys to change a setting. When the DATA/ENTER key is
    pressed the parameter setting are written and the display returns to the Monitor display.
  Example Operations
    In the example below the following settings have been changed from their default settings:
     • C1-01 (Acceleration Time 1)                                                                                       3
     • C1-02 (Acceleration Time 2)
     • E1-01 (Input Voltage Setting)
     • E2-01 (Motor Rated Current).
                                                                                                                        3-11
        Autotuning Mode
          Autotuning automatically measures and sets the required motor data in order to achieve the maximum perfor-
          mance. Always perform autotuning before starting operation when using the vector control modes.
          When V/f control has been selected, stationary autotuning for line-to-line resistance can be selected only.
          When the motor cannot be operated (e.g. if the ropes cannot be removed from the traction sheave), and Open
          Loop or Closed Loop Vector Control shall be used, perform stationary autotuning.
3-12
                                                                                           4
          Start Up Procedure
This chapter describes the basic setup procedure, the motor data autotuning for each control mode and gives
advices if problems occur.
       Start Up
          The following chart shows the basic start up sequence.
START
Mechanical installation
                    Set up the analog/digital I/O’s in the H1-xx,                               Set up the digital I/O’s in the H1-xx
                           H2-xx and H3-xx parameters                                                 and H2-xx parameters
                                                                                                             Set up the
                                     Set up the                                        * Preset speed values (d1-xx)
                  * Acceleration / Deceleration times (C1-xx)                          * Acceleration / Deceleration times (C1-xx)
                  * S-Curves (Jerk) (C2-x)                                             * S-Curves (Jerk) (C2-xx)
                                   Fine Tuning
                             * Brake sequence tuning
                             * Special functions setup
FINISH
4-2
Power Up
 Before Power Up
    The following points should be checked carefully before the power is switched on.
     • The power supply must meet the inverter specification (refer to page 9-2, Specifications by Model).
     • The power supply cables must be tightly connected to the right terminals (L1, L2, L3).
     • The motor cables must be tightly connected to the right terminals on the inverter side (U, V, W) as well as
       on the motor side.
     • The braking unit / braking resistor must be connected correctly.
     • The Inverter control circuit terminal and the control device must be wired correctly.
     • All Inverter control circuit terminals should be switched OFF.
     • When a PG card is used, the PG must be wired correctly.
    When a fault has occurred or an alarm is active a fault or alarm message will appear. In this case, refer to
    Chapter 7, Troubleshooting.
                                            -DRIVE-
                                                                                 A fault or alarm message is shown on the
                                                      UV
    Display for fault operation                                                  display.
                                                MainPower Loss
                                                                                 The example shows a low voltage alarm.
                                                           CAUTION
     • For Permanent Magnet motors do not use any other control mode than Closed Loop Vector for PM
       (A1-02 = 6). Using any other control mode can cause damage to the equipment or can cause dangerous
       behavior.
                                                                                                                                   4-3
      Autotuning
          The motor data autotuning function sets the V/f pattern parameters (E1-), motor data parameters
          (E2-, E5-) and the encoder data (F1-01) automatically. The steps which have to be performed during
          the autotuning depend on the tuning mode selection. Refer to page 5-57, Motor Autotuning: T for an overview
          of the autotuning parameters.
Autotuning Modes
                              Use this tuning mode only, if the motor can rotate freely which means that the ropes must be removed
                              and the brake must be open. The gearbox can remain connected to the motor.
            IMPORTANT
4-4
  Encoder Offset Tuning (T1-01=4)
    This tuning mode is available in Closed Loop Vector control for PM motors only. It automatically sets the off-
    set between the magnetic pole and the encoder zero postion. It can be used to retune the offset after an encoder
    change without changing the motor data settings.
                                                                                                                                4-5
       Autotuning Procedure with Induction Motors
          Fig 4.2 shows the autotuning procedure for an induction motor with or without encoder in V/f-, Open loop
          vector and Closed loop vector control.
START
                                                                     No                                                Yes
                                              V/f Control ?          (A1-02 = 2/3)             Can the motor           (ropes removed?)
                                              (A1-02 = 0)                                      rotate freely ?
Yes No
                                       Enter auto tuning mode and                       Enter auto tuning mode and                   Enter auto tuning mode and
                                        set parameter T1-01 = 2                          set parameter T1-01 = 1                      set parameter T1-01 = 0
4
                                                                                                   Set:                                          Set:
                                                                                       T1-02 - Motor rated power                     T1-02 - Motor rated power
                                                  Set:                                 T1-03 - Motor rated voltage                   T1-03 - Motor rated voltage
                                       T1-02 - Motor rated power                       T1-04 - Motor rated current                   T1-04 - Motor rated current
                                       T1-04 - Motor rated current                     T1-05 - Rated motor frequency                 T1-05 - Rated motor frequency
                                                                                       T1-06 - Motor pole number                     T1-06 - Motor pole number
                                       Press the UP button until                       T1-07 - Motor rated speed                     T1-07 - Motor rated speed
                                    “Tuning Ready” display appears                     T1-08 - PG pulse number*                      T1-08 - PG pulse number*
                                                                                                      (*CLV only)                                  (*CLV only)
            Refer to
            page 7-14, Auto-tuning Faults                                                  Press the RUN button
                                                                                                  Tuning
                                                                       No                       successful ?
                                                                 (Fault code is
                                                                   displayed)
                                                                                                                  Yes
                                                                                                        (” Tuning successful”
                                                                                                             is displayed)
FINISH
4-6
 Autotuning Procedure with PM Motors
    Fig 4.3 shows the autotuning procedure for permanent magnet motors. Before tuning make sure that the con-
    trol mode is set to PM Closed Loop Vector (A1-02 = 6).
                                                     START
                                                   No
                                                                                                 * Check parameter n8-35
                                                                                                 * If EnDat / Hiperface is used
                                                                              Yes
                                               Does a CPF24 fault                                   - check the encoder power supply
                                                    occur?                                          - check the CLOCK and DATA signal wiring
                                                                                                                                                                  4
                                                                                                 * Switch off the power supply.
                                                  No
No
Yes
                                                                          No
                                                                          (Fault code is displayed)
                                                Tuning successful?
                                              Yes
                (”Tuning successful” is displayed)                                         * 1. Forward direction means:
                                                                                                The direction the motor turns with an UP command at terminal
                                      Open the contactors, open the baseblock                   S1 (i.e. with a clockwise rotating 3 phase supply and U-U, V-V,
                                            inputs and close the brake                          W-W wiring between inverter and motor). Usually the direction
                                                                                                is clockwise seen from the motor shaft (traction sheave) side.
                                                                                                Refer to the motor instruction manual or consult the manufac-
                                                     FINISH                                     turer for details about the rotation direction.
                                                                                                                                                                  4-7
       PM Motor Encoder Offset Tuning
          Fig 4.4 shows the autotuning procedure for an encoder offset tuning. This procedure should be performed if
          the encoder has been changed or has not been aligned correctly. Before tuning make sure that PM losed loop
          vector conntrol is selected (A1-02 = 6) and that the E1- and E5- parameters are set up correctly.
                                                    START
                                                                              No
                                             Is it possible to remove
                                                    the ropes ?
Yes
4 occur?
No
No
Yes
                                                        Set:
                                      T1-01 = 4 - Encoder Offset Tuning
                                    Press the UP button until the “Tuning
                                          Ready” display appears.
                                                                                                  Refer to
                                       Close the motor contactor(s) and                            page 7-14, Auto-tuning Faults
                                              press the RUN key.                                  and eliminate the fault source.
                                        Wait until the tuning is finished.
                                                                        No
                                                                        (Fault code is
                                                                        displayed)
                                              Tuning successful?
                                     Yes
                    (”Tuning successful”                                                       * 1. Forward direction means:
                       display is shown)                                                            The direction the motor turns with an UP command at terminal S1 (i.e.
                                     Open the contactors, open the base
                                                                                                    with a clockwise rotating 3 phase supply and U-U, V-V, W-W wiring
                                      block inputs and close the brake                              between inverter and motor). Usually the direction is clockwise seen
                                                                                                    from the motor shaft (traction sheave) side.
                                                                                                    Refer to the motor instruction manual or consult the manufacturer for
                                                                                                    details about the rotation direction.
                                                    FINISH
4-8
 Precautions for Induction Motor Autotuning
   If the Motor Rated Voltage is Higher than the Power Supply Voltage
    If the motor rated voltage is higher than the power supply voltage, lower the base voltage value like shown in
    Fig 4.5 to prevent saturation of the Inverter’s output voltage. Use the following procedure to perform autotun-
    ing:
    1. Input the voltage of the input power supply to T1-03 (Motor rated voltage).
    2. Input the results of the following formula to T1-05 (Motor base frequency):
                                                                                  T1-03
                   T1-05 = Base frequency from motor nameplate × -----------------------------------------------
                                                                 Motor rated voltage
    3. Perform autotuning.
    After the completion of autotuning, set E1-04 (Max. output frequency) to the base frequency from the motor’s
    nameplate.
                                          Output voltage
                                     Rated voltage
                                       from motor
                                        name plate
                                                                                                                               4
Output frequency
                                                                                                        Base frequency
                                                                         Base frequency from            from motor name
                                                                              motor name plate          plate
                                                                -------------------------------------
                                                                             Rate voltage from
                                                                              motor name plate
Fig 4.5 Motor Base Frequency and Inverter Input Voltage Setting
    If speed precision is required at high speeds (i.e., 90% of the rated speed or higher), set T1-03 (Motor rated
    voltage) to the input power supply voltage × 0.9. In this case at high speeds the output current will increase as
    the input power supply voltage is reduced. Be sure to provide sufficient margin in the Inverter current.
                                                                                                                               4-9
        Autotuning Alarms and Faults
            • the rated current does not correspond to the rated power value
              The inverter calculates the motor power using the input current value and data from the internal motor data
              table. The calculated value must be between 50% and 150% of the input value for the rated power.
4-10
Performance Optimization
  The following table gives adjustment advice for performance improvement after the basic setup has been
  done.
                                                                                                                             4-11
             Problem                           Possible Reason                                  Countermeasure
                                                                                     • Increase the torque compensation
                                       • Too fast torque compensation or slip com-     delay time C4-02
                               OLV
                                         pensation                                   • Increase the slip compensation delay
                                                                                       time C3-02
                                       • Too soft or too hard ASR controller set-    • Readjust the ASR P gain C5-01 and
       Jerk caused by over-              tings                                         the ASR integral time C5-02.
       shooting when the
       top speed is reached    CLV                                                   • Readjust the motor data (E2-),
                                                                                       especially the slip (E2-02) and no-
                                       • Wrong motor data
                                                                                       load current values (E2-03) or per-
                                                                                       form an autotuning
                                                                                     • Increase the S-curve at acceleration
                              Common • Too hard acceleration change.
                                                                                       end C2-02.
                                                                                     • Increase the minmum (E1-10) and
                                                                                       medium (E1-08) V/f pattern voltages.
                                V/f    • Too low torque at low speed
                                                                                       Make sure, that the starting and level-
                                                                                       ing current does not rise too high.
                                                                                     • Increase the minmum (E1-10) and
                                                                                       medium (E1-08) V/f pattern voltages.
4                              OLV
                                       • Too low torque at low speed
                                                                                       Make sure, that the starting and level-
                                                                                       ing current does not rise too high.
                                                                                     • Readjust the motor data (E2-),
       Motor stops shortly             • Wrong motor data                              especially the slip (E2-02) and no-
       when the leveling               • Slip overcompensation                         load current values (E2-03) or per-
       speed is reached                                                                form an autotuning
       (undershooting)
                                                                                     • Readjust the motor data (E2-),
                                                                                       especially the slip (E2-02) and no-
                                       • Wrong motor data
                                                                                       load current values (E2-03) or per-
                               CLV                                                     form an autotuning
                                                                                     • Increase the ASR P gain C5-09 and
                                       • Too slow ASR controller                       decrease the ASR integral time
                                                                                       C5-10
                                                                                     • Increase the S-curve at deceleration
                              Common • Too fast deceleration rate change.
                                                                                       end C2-04.
                                                                                     • Increase the brake close delay time
                                       • Brake closed too early, so that the motor
                                                                                       S1-07 and if necessary the DC injec-
                                         runs against the brake
       Jerk at stop           Common                                                   tion time at stop S1-05.
                                       • Motor contactor opens when the brake is
                                                                                     • Check the motor contactor sequence.
                                         not yet completely closed
                                                                                     • Increase the carrier frequency in
                                                                                       parameter C6-02 or C6-11. If the car-
       High frequency                                                                  rier frequency increased higher than
                              Common • The carrier frequency is too low.
       motor noise                                                                     the factory setting, a current derating
                                                                                       must be considered (refer to page 9-
                                                                                       6, Carrier Frequency Derating)
                                                                                     • Check the encoder mounting and the
                               CLV     • Encoder vibrates
                                                                                       orientation to the motor shaft
       Vibrations which
       increase with the               • Mechanical problems                         • Check bearings, gearbox
       speed                  Common • Rotational parts (motor armature, hand-
                                                                                     • Balance the rotating parts
                                         wheel, brake disk/drum) have an unbalance
4-12
                                                                                           5
                    User Parameters
This chapter describes all user parameters that can be set in the Inverter.
5-2
Digital Operation Display Functions and Levels
The following figure shows the Digital Operator display hierarchy for the Inverter.
                                                                                                                     5-3
       User Parameters Available in Quick Programming Mode
               The minimum user parameters required for Inverter operation can be monitored and set in quick programming
               mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
               all other user parameters, are also displayed in advanced programming mode.
                                                                                                                   Control Methods
      Param-         Name                                                                           Change                                     MEMO
       eter                                                                     Setting   Factory   during                           Closed     BUS
                                                   Description                                                     Open Closed
       Num-                                                                     Range     Setting   Opera-                            Loop     Regis-
                                                                                                             V/f   Loop   Loop
        ber          Display                                                                         tion                            Vector      ter
                                                                                                                   Vector Vector
                                                                                                                                      (PM)
                                    Used to set the parameter access level
                                    (set/read.)
               Parameter access     0: Monitoring only (Monitoring drive
               level                   mode and setting A1-01 and A1-04.)
                                    1: Used to select user parameters (Only
      A1-01                            parameters set in A2-01 to A2-32 can     0 to 2      2        Yes     Yes    Yes     Yes       Yes      101H
                                       be read and set.)
                                    2: Advanced
                                       (Parameters can be read and set in
               Access Level
                                       both, quick programming mode (Q)
                                       and advanced programming mode
                                       (A).)
5     C1-01
               Acceleration time 1 Sets the acceleration time to accelerate
               Accel Time 1
                                   from 0 Hz to the maximum output fre-
                                   quency.                                      0.0 to
                                                                                600.00    1.50 s     Yes     Yes    Yes     Yes       Yes
                                                                                                                                               200H
5-4
                                                                                                                Control Methods
Param-          Name                                                                           Change                                      MEMO
 eter                                                                      Setting   Factory   during                             Closed    BUS
                                             Description                                                        Open Closed
 Num-                                                                      Range     Setting   Opera-                              Loop    Regis-
                                                                                                         V/f     Loop   Loop
  ber          Display                                                                          tion                              Vector     ter
                                                                                                                Vector Vector
                                                                                                                                   (PM)
         ASR proportional
                                                                                                                        20.00       -
         (P) gain 2                                                        0.00 to
C5-03
                                                                           300.00
                                                                                       i        Yes       -       -                        21DH
         ASR P Gain 2         Set the proportional gain 2 and the inte-                                                   -        6.00
                              gral time 2 of the speed control loop
      ASR integral (I)        (ASR) for the maximum frequency.             0.000
C5-04 time 2                                                                 to      0.500 s    Yes       -       -      Yes       Yes     21EH
         ASR I Time 2                                                      10.000
         ASR delay time       Sets the filter time constant; the time
                              from the speed loop to the torque com-        0.000
                                                                                     0.020
C5-06                                                                         to                No        -       -       -        Yes     220H
                              mand output. Usually changing this set-                 sec
         ASR Delay Time                                                     0.500
                              ting is not necessary.
      ASR switching fre-                                                    0.0 to
                                                                                                                        0.0 Hz      -
      quency             Sets the frequency for switching                  50.0 Hz
C5-07                    between Proportion Gain 1, 2,3 and                0.0 to      i        No        -       -                        221H
      ASR Gain SW Freq Integral Time 1, 2, 3.                              100.0                                          -       2.0 %
                                                                             %
         ASR proportional
                                                                                                                        40.00       -
         (P) gain 3                                                        0.00 to
C5-09                         Set the proportional gain 3 and the inte-    300.00
                                                                                       i        Yes       -       -                        22EH
         ASR P Gain 3         gral time 3 of the speed control loop                                                       -       12.00
                              (ASR) for the minimum frequency.
         ASR integral (I)     The settings becomes active for deceler-                                                  0.500s
                                                                           0.000                                                    -
         time 3               ation only.
C5-10                                                                        to        i        Yes       -       -                        231H
         ASR I Time 3
                                                                            0 to                        50.00   50.00
                                                                                                                          -
                                                                                                                        50.00
                                                                                                                                  0.300s
                                                                                                                                                    5
                            Sets the frequency reference when the                                                                   -
         erence                                                            120.00                        Hz      Hz      Hz
d1-09                       nominal speed is selected by a digital                     i                                                   288H
                            input.                                          0 to                                                  100.00
         Nomin Speed vn                                                                                   -       -       -
                                                                           100.00                                                   %
         Inspection speed                                                   0 to                        25.00   25.00   25.00
                              Sets the frequency reference when the                                                                 -
         reference                                                         120.00                        Hz      Hz      Hz
d1-14                         inspection speed is selected by a digital                i        Yes                                        28FH
                              input                                         0 to                                                  50.00
         Inspect Speed vi                                                                                 -       -       -
                                                                           100.00                                                  %
         Leveling speed ref-                                                0 to                        4.00    4.00     4.00
                             Sets the frequency reference when the                                                                  -
         erence                                                            120.00                        Hz      Hz       Hz
d1-17                        leveling speed is selected by a digital                   i                                                   292H
                             input                                          0 to
         Level Speed vl                                                                                   -       -       -       8.00%
                                                                           100.00
         Input voltage set-
         ting                 Sets the inverter input voltage. This set    310 to
                                                                                     400 V
E1-01                         value will be the basis for the protection    510        *2       No      Yes      Yes     Yes       Yes     300H
         Input                functions.                                     *2
         Voltage
                                                                                                                                                    5-5
                                                                                                                               Control Methods
      Param-          Name                                                                                    Change                                      MEMO
       eter                                                                               Setting   Factory   during                             Closed    BUS
                                                        Description                                                            Open Closed
       Num-                                                                               Range     Setting   Opera-                              Loop    Regis-
                                                                                                                        V/f    Loop   Loop
        ber          Display                                                                                   tion                              Vector     ter
                                                                                                                               Vector Vector
                                                                                                                                                  (PM)
               Max. output fre-                                                           40.0 to                      50.0    50.0    50.0
                                                                                                                                                   -
               quency (FMAX)                                                               120.0                        Hz      Hz      Hz
                                                                                           (with
                                                                                          PG-F2)
                                                                                            0 to
      E1-04
                                                                                           1200
                                                                                                      i        No                                         303H
                                                                                                                                                  150
               Max Frequency                                                                                             -       -       -
                                                                                           (with                                                  rpm
                                                                                          PG-X2)
                                                                                            0 to
                                                                                           3600
            Max. voltage                                                                  0.0 to
                                                                                                    380.0 V
      E1-05 (VMAX)                                                                        510.0       *2       No      Yes      Yes     Yes       No      304H
                                                                                            *2
               Max Voltage
               Base frequency                                                             0.0 to                       50.0    50.0    50.0
                                                                                                                                                   -
               (FA)                 utput Voltage (V)                                     120.0                         Hz      Hz      Hz
                                      V MAX
                                      E1-05
                                     V BASE
                                                                                           (with
                                      E1-13
                                                                                          PG-F2)
                                                                                            0 to
      E1-06                            VC                                                  1200
                                                                                                      i        No                                         305H
                                      E1-08                                                                                                       150
               Base Frequency                                                                                            -       -       -
                                                                                           (with                                                  rpm
                                     V MIN
                                     E1-10                                                PG-X2)
                                              F MIN
                                              E1-09
                                                          FB      FA     F MAX
                                                                         E1-04
                                                                                            0 to
                                                         E1-07   E1-08
                                                                         Frequency (Hz)
                                                                                           3600
               Mid voltage A
            Min. output fre-
                                                                                          0.0 to                        0.5     0.3
      E1-09 quency (FMIN)                                                                             i        No                        -         -      308H
                                                                                          120.0                         Hz      Hz
               Min Frequency
            Min. output fre-
            quency voltage                                                                0.0 to
                                                                                                                       19.4    5.0 V
      E1-10 (VMIN)                                                                        510.0       i        No                        -         -      309H
                                                                                            *2                         V *2      *2
               Min Voltage
               Base voltage
                                                                                          0.0 to                       0.0 V   0.0 V               -
               (VBASE)
      E1-13                                                                               510.0       i        No                        -                30CH
                                                                                            *2
               Base Voltage                                                                                              -       -               400 V
               Motor rated current Sets the motor rated current in Amps.                  0.85 to
                                   This set value becomes the base value                            7.00 A
      E2-01                                                                                17.00      *4       No      Yes      Yes     Yes        -      30EH
                                   for motor protection and torque limit. It                *3
               Mtr Rated Current is an input data for autotuning.
            Number of motor
                                     Sets the number of motor poles. It is an
      E2-04 poles                                                                         2 to 48     4        No        -       -      Yes        -      311H
                                     input data for autotuning.
               Number of Poles
               Motor line-to-line    Sets the motor phase-to-phase resis-
               resistance            tance.                                               0.000     3.333 Ω
      E2-05                                                                                 to        *4       No      Yes      Yes     Yes        -      312H
                                     This parameter is automatically set dur-
               Term Resistance                                                            65.000
                                     ing autotuning.
5-6
                                                                                                                             Control Methods
Param-          Name                                                                                    Change                                             MEMO
 eter                                                                             Setting    Factory    during                                  Closed      BUS
                                                  Description                                                                Open Closed
 Num-                                                                             Range      Setting    Opera-                                   Loop      Regis-
                                                                                                                     V/f      Loop   Loop
  ber          Display                                                                                   tion                                   Vector       ter
                                                                                                                             Vector Vector
                                                                                                                                                 (PM)
         Motor rated output      Sets the rated output power of the
                                                                                               3.70
         power                   motor.                                           0.00 to      kW
E2-11                                                                                                      No        Yes      Yes       Yes       No       318H
                                 This parameter is an input data for auto-        650.00        *4
         Mtr Rated Power         tuning.
      Motor rated output                                                                       3.70
                                 Sets the rated output power of the               0.00 to
E5-02 power                                                                                    kW          No         -         -        -        Yes      0C2H
                                 motor.                                           300.00        *4
         Rated Power
      Rated Motor Cur-
                                                                                  0.00 to
E5-03 rent                       Sets the rated motor current.                                 7.31        No         -         -        -        Yes      0C3H
                                                                                  200.00
         Rated Current                                                                         A*4
      Number of motor
E5-04 poles                      Sets the motor pole number.                      4 to 48       4          No         -         -        -        Yes      0C4H
         Number of poles
      Motor terminal                                                              0.000       1.326
E5-05 resistance                 Sets the motor line-to-line resistance             to                     No         -         -        -        Yes      0C5H
                                                                                  65.000     Ohm *4
         Term resistance
         d-Axis Inductance                                                                    19.11
                                                                                  0.00 to      mH
E5-06                            Sets the D-axis inductance.                                               No         -         -        -        Yes      0C6H
         d-ax inductance                                                          300.00        *4
                                                                                                                                                                    5
         q-ax inductance                                                                        *4
  *1. The setting ranges for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to 0,
      the setting range is 0.00 to 600.00 (s).
  *2. The given values are for a 400 V class Inverter.
  *3. The setting range is from 10% to 200% of the Inverter rated output current. The given values are for a 3.7 kW 400 V Class Inverter.
  *4. The factory setting depends on the Inverter capacity. The given value is for a 3.7 kW 400 V Class Inverter.
                                                                                                                                                                    5-7
      User Parameter Tables
 Setup Settings: A
         Initialize Mode: A1
                                                                                                         Control Methods
                    Name
      Param-                                                                              Change                           Closed   MEMO-
       eter                                                           Setting   Factory   during         Open     Closed    Loop
                                            Description                                                                              BUS       Page
       Num-                                                           Range     Setting   Opera-   V/f   Loop      Loop     Vec-
                    Display                                                                                                         Register
        ber                                                                                tion          Vector   Vector     tor
                                                                                                                            (PM)
5-8
                                                                                                   Control Methods
               Name
Param-                                                                             Change                            Closed   MEMO-
 eter                                                          Setting   Factory    during         Open     Closed    Loop
                                     Description                                                                               BUS       Page
 Num-                                                          Range     Setting   Opera-    V/f   Loop      Loop     Vec-
              Display                                                                                                         Register
  ber                                                                                tion          Vector   Vector     tor
                                                                                                                      (PM)
  User-set Parameters: A2
         The parameters set by the user are listed in the following table.
                                                                                                   Control Methods
Param-         Name                                                                Change
 eter                                                          Setting   Factory   during                            Closed MEMO-
                                      Description                                                  Open     Closed           BUS         Page
 Num-                                                          Range     Setting   Opera-                             Loop
                                                                                             V/f    Loop     Loop
  ber          Display                                                              tion                             Vector Register
                                                                                                   Vector   Vector
                                                                                                                      (PM)
                                                                                                                                                5-9
        Application Parameters: b
                RUN com-
                                Sets the run command input
                mand source
                                method.
                selection                                              0, 1 or
       b1-02                    0: Digital Operator                                1        No      A       A        A        A       181H      6-3
                                1: Control circuit terminal (digital      3
                Run Source         multifunction inputs)
                                3: Option Card
                Run com-
                                Used to set an operation prohibi-
                mand selec-     tion in programming modes.
                tion in
                                0: Operation prohibited.
       b1-08    programming     1: Operation permitted (Disabled       0 or 1      1        No      A       A        A        A       187H       -
                modes              when Digital Operator is the
                RUN CMD at         selected Run command source
                                   (b1-02 = 0)).
                PRG
5-10
  Timer Function: b4
                                                                                                                           Control Methods
Param       Name                                                                                            Change
                                                                                                                                             Closed   MEMO-
 eter                                                                                   Setting   Factory   during         Open     Closed
                                                 Description                                                                                  Loop     BUS       Page
Num-                                                                                    Range     Setting   Opera-   V/f   Loop      Loop
            Display                                                                                                                          Vector   Register
 ber                                                                                                         tion          Vector   Vector
                                                                                                                                              (PM)
  Dwell Functions: b6
                                                                                                                           Control Methods
Param        Name                                                                                           Change
                                                                                                                                             Closed   MEMO-
 eter                                                                                   Setting   Factory   during         Open Close
                                                  Description                                                                                 Loop     BUS       Page
Num-                                                                                    Range     Setting   Opera-   V/f    Loop d Loop
            Display                                                                                                                          Vector   Register
 ber                                                                                                         tion          Vector Vector
                                                                                                                                              (PM)
        Dwell fre-
        quency at start                                                                 0.0 to
b6-01                                                                                             0.0 Hz     No      A       A        A        A       1B6H      6-23
        Dwell Ref @                                                                     120.0
        Start
b6-02
        Dwell time at
        start
                           Run command
                           Output frequency
                                                      ON
                                                                        OFF
                                                                                        0.0 to
                                                                                                   0.0 s     No      A       A        A        A       1B7H      6-23
                                                                                                                                                                          5
        Dwell Time                                                                       10.0
        @ Start
        Dwell fre-                                    b6-01     b6-03            Time
  Torque Monitor: b8
                                                                                                                           Control Methods
Param        Name                                                                                           Change
                                                                                                                                             Closed   MEMO-
 eter                                                                                   Setting   Factory   during         Open Close
                                                  Description                                                                                 Loop     BUS       Page
Num-                                                                                    Range     Setting   Opera-   V/f    Loop d Loop
            Display                                                                                                                          Vector   Register
 ber                                                                                                         tion          Vector Vector
                                                                                                                                              (PM)
        Torque moni-
        tor gain                                                                         0 to
b8-17                                                                                              1.00      No       -      -        -        A       1F9H      6-23
        Torque Mon                                                                       2.00
        Gain
                                                                                                                                                                        5-11
        Tuning Parameters: C
          Acceleration/Deceleration: C1
                                                                                                                          Control Methods
       Param-          Name                                                                           Change
        eter                                                                    Setting    Factory    during                                 Closed MEMO-
                                                    Description                                                           Open Closed                BUS            Page
        Num-                                                                    Range      Setting    Opera-                                  Loop
                                                                                                                   V/f    Loop   Loop
         ber          Display                                                                          tion                                  Vector Register
                                                                                                                          Vector Vector
                                                                                                                                              (PM)
5      C1-06
                Decel Time 3
                                    the multi-function input “accel/
                                    decel time 2” is set to ON.
                                                                                                         No         A        A        A         A        205H       6-21
         *1. The setting range for acceleration/deceleration times depends on the setting of C1-10. If C1-10 is set to 1, the setting range for acceleration/deceleration
             times becomes 0.0 to 6000.0 seconds.
5-12
   S-Curve Acceleration/Deceleration: C2
                                                                                                  Control Methods
Param       Name                                                                   Change
                                                                    Set-  Fac-                                      Closed MEMO-
 eter                                                                              during         Open Closed
                                      Description                   ting  tory                                       Loop   BUS       Page
Num-                                                                               Opera-   V/f   Loop    Loop
           Display                                                 Range Setting                                    Vector Register
 ber                                                                                tion          Vector Vector
                                                                                                                     (PM)
      S-curve char-
      acteristic time
      at accelera-                                                 0.00
C2-01 tion start                                                    to    0.50 s    No      Q      Q       Q          Q     20BH      6-23
                                                                   2.50
        S-Crv Acc @
        Start
      S-curve char-
                      Set the S-curve times at speed changes
      acteristic time
                      to reduce the jerk. The S-curves can be      0.00
      at accelera-
C2-02 tion end        set separately for every kind of speed        to    0.50 s    No      Q      Q       Q          Q     20CH      6-23
                      change.                                      2.50
      S-Crv Acc @
      End
      S-curve char-
      acteristic time
      at decelera-                                                 0.00
C2-03 tion start                                         Time       to    0.50 s    No      Q      Q       Q          Q     20DH      6-23
                                                                   2.50
        S-Crv Dec @         accel
        Start
                            decel
      S-curve char-
      acteristic time
      at decelera-    When the S-curve characteristic time is      0.00
                                                                                                                                               5
C2-04 tion end        set, the accel/decel times will increase      to    0.50 s    No      Q      Q       Q          Q     20EH      6-23
                      by only half of the S-curve characteristic   2.50
      S-Crv Dec @
                      times at start and end.
      End
      S-curve Char-
      acteristic time
      below level-                                                 0.00
C2-05 ing speed                                                     to    0.50 s    No      Q      Q       Q          Q     232H      6-23
                                                                   2.50
        Scurve @
        leveling
                                                                                                                                             5-13
         Motor Slip Compensation: C3
                                                                                                          Control Methods
                  Name
       Param                                                                               Change                           Closed   MEMO-
        eter                                                           Setting   Factory   during         Open Closed        Loop
                                            Description                                                                               BUS       Page
       Num-                                                            Range     Setting   Opera-   V/f   Loop   Loop        Vec-
                  Display                                                                                                            Register
        ber                                                                                 tion          Vector Vector       tor
                                                                                                                             (PM)
5
                                                                       10000       ms
                               • Reduce the setting when Slip
               Slip Comp          Compensation responsiveness is
               Time               low.
                               • When speed is not stable, increase
                                  the setting.
               Slip compen-
               sation limit    Sets the slip compensation limit as a    0 to
       C3-03                                                                     200%       No       -      A       -         -       211H      6-30
               Slip Comp       percentage of motor rated slip.          250
               Limit
               Slip compen-
                               0: Disable
               sation selec-   1: Enabled
               tion during     When the slip compensation during
               regeneration    regeneration function has been acti-
       C3-04                   vated and regeneration capacity         0 or 1      1        No       -      A       -         -       212H      6-30
                               increases momentarily, it might be
                               necessary to use a braking option
               Slip Comp
                               (braking resistor, braking resistor
               Regen
                               unit or braking unit.)
             Output volt-
             age limit
             operation         0: Disabled
                               1: Enabled. (The motor flux will be
       C3-05 selection                                                 0 or 1      1        No       -      A       A         -       213H      6-30
                                  lowered automatically when the
               Output V           output voltage become saturated.)
               limit Sel
5-14
  Torque Compensation: C4
                                                                                                   Control Methods
Param-         Name                                                                 Change
                                                                                                                     Closed   MEMO-
 eter                                                           Setting   Factory   during         Open     Closed
                                       Description                                                                    Loop     BUS       Page
 Num-                                                           Range     Setting   Opera-   V/f   Loop      Loop
              Display                                                                                                Vector   Register
  ber                                                                                tion          Vector   Vector
                                                                                                                      (PM)
         Starting torque
         compensation
         (REV)                                                      -
                             Sets the torque compensation
C4-04                                                           200.0%     0.0%      No       -      A        -        -       218H      6-31
                             value at start in REV direction
         RTorqCmp @                                              to 0.0
         Start
         Starting torque
         compensation        Sets starting torque start-up
         time constant       time.
C4-05                                                          0 to 200   10 ms      No       -      A        -        -       219H      6-31
                             When 0 ~ 4 ms is set, it is oper-
         TorqCmpDelayT       ated without filter.
                                                                                                                                                5-15
          Speed Control (ASR): C5
                    Name                                                                                      Control Methods
       Param                                                                                   Change
                                                                            Set-      Fac-                                      Closed MEMO-
        eter                                                                                   during         Open     Closed
                                                Description                 ting      tory                                       Loop   BUS       Page
       Num-        Display                                                                     Opera-   V/f   Loop      Loop
                                                                           Range     Setting                                    Vector Register
        ber                                                                                     tion          Vector   Vector
                                                                                                                                 (PM)
               ASR propor-                                                                                               Q
                                                                                                                                  -
               tional (P) gain 1                                           0.00 to                                     40.00
       C5-01
                                                                           300.00
                                                                                       i        Yes      -      -                       21BH      6-33
                                Set the proportional gain 1 and the                                                               Q
               ASR P Gain 1                                                                                              -
                                integral time 1 of the speed control                                                             3.00
               ASR integral (I) loop (ASR) for the maximum fre-            0.000                                         Q
                                quency.                                                                                           -
               time 1                                                        to                                        0.500
       C5-02
                                                                           10.000
                                                                                       i        Yes      -      -                       21CH      6-33
                                                                                                                                  Q
               ASR I Time 1                                                 sec                                          -
                                                                                                                                0.300
             ASR propor-                                                                                                 Q
                                                                                                                                  -
             tional (P) gain 2 Set the proportional gain 2 and the         0.00 to                                     20.00
       C5-03                   integral time 2 of the speed control        300.00
                                                                                       i        Yes      -      -                       21DH      6-33
                                                                                                                                  Q
             ASR P Gain 2      loop (ASR) for the minimum fre-                                                           -
                                                                                                                                 3.00
                               quency.
             ASR integral (I) The setting is active only for accel-        0.000
             time 2            eration.                                      to
       C5-04                                                                      0.500 s       Yes      -      -        Q        Q     21EH      6-33
                                                                           10.000
               ASR I Time 2                                                 sec
5-16
  Carrier Frequency: C6
                                                                                                   Control Methods
Param        Name                                                                   Change
                                                                  Set-     Fac-                                      Closed   MEMO-
 eter                                                                               during         Open     Closed
                                         Description              ting     tory                                       Loop     BUS       Page
Num-                                                                                Opera-   V/f    Loop     Loop
            Display                                              Range    Setting                                    Vector   Register
 ber                                                                                 tion          Vector   Vector
                                                                                                                      (PM)
      Carrier fre-
      quency selec-
      tion                0: Same carrier frequency setting as
      @Inspection         in normal operation
C6-12 Run                 (IM : C6-02, PM : C6-11)                0, 1      1        No      A       A        A        A       22FH      6-2
        LowCarr
        @
        Inspect
                          1: 2 kHz fix
                                                                                                                                                  5
                                                                                                                                                5-17
        Reference Parameters: d
         Preset Reference: d1
                                                                                                        Control Methods
       Param-        Name                                                              Change                                      MEMO-
                                                                              Fac-                                        Closed
        eter                                                       Setting             during           Open     Closed             BUS     Pag
                                              Description                     tory                                         Loop
        Num-                                                       Range               Opera-    V/f    Loop      Loop             Regis-    e
                    Display                                                  Setting                                      Vector
         ber                                                                            tion            Vector   Vector              ter
                                                                                                                           (PM)
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00                       0.00     0.00     0.00      -
                ence 1                                             *1,*2                         Hz       Hz       Hz
       d1-01                       Sets the frequency reference.               i        Yes                                        280H     6-5
                                                                    0 to
                                                                                                                             A
                Reference 1                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00
                                 Sets the frequency reference                                   0.00     0.00     0.00      -
                ence 2                                              *1,*2
                                 when multi-step speed command                                   Hz       Hz       Hz
       d1-02
                                 1 is ON for a multi-function
                                                                               i        Yes                                        281H     6-5
                                                                    0 to
                                 input.                                                                                      A
                Reference 2                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00
                                 Sets the frequency reference                                   0.00     0.00     0.00      -
                ence 3                                              *1,*2                        Hz       Hz       Hz
                                 when multi-step speed command
       d1-03
                                 2 is ON for a multi-function
                                                                               i        Yes                                        282H     6-5
                                                                    0 to
                                 input.                                                                                      A
                Reference 3                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
5               Frequency refer-
                ence 4
                                 Sets the frequency reference
                                                                    0 to
                                                                   120.00
                                                                    *1,*2
                                                                                                 A
                                                                                                0.00
                                                                                                 Hz
                                                                                                          A
                                                                                                         0.00
                                                                                                          Hz
                                                                                                                   A
                                                                                                                  0.00
                                                                                                                   Hz
                                                                                                                            -
                                 when multi-step speed com-
       d1-04
                                 mands 1 and 2 are ON for multi-
                                                                               i        Yes                                        283H     6-5
                                                                    0 to
                                 function inputs.                                                                            A
                Reference 4                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00                       0.00     0.00     0.00      -
                ence 5           Sets the frequency when multi-     *1,*2                        Hz       Hz       Hz
       d1-05                     step speed command 3 is ON for                i        Yes                                        284H     6-5
                                 a multi-function input.            0 to
                                                                                                                             A
                Reference 5                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00
                                 Sets the frequency reference                                   0.00     0.00     0.00      -
                ence 6                                              *1,*2
                                 when multi-step speed com-                                      Hz       Hz       Hz
       d1-06
                                 mands 1 and 3 are ON for multi-
                                                                               i        Yes                                        285H     6-5
                                                                    0 to
                                 function inputs.                                                                            A
                Reference 6                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00
                                 Sets the frequency reference                                   0.00     0.00     0.00      -
                ence 7                                              *1,*2                        Hz       Hz       Hz
                                 when multi-step speed com-
       d1-07
                                 mands 2 and 3 are ON for multi-
                                                                               i        Yes                                        286H     6-5
                                                                    0 to
                                 function inputs.                                                                            A
                Reference 7                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                         A        A        A
                Frequency refer-                                   120.00
                                 Sets the frequency reference                                   0.00     0.00     0.00      -
                ence 8                                              *1,*2
                                 when multi-step speed com-                                      Hz       Hz       Hz
       d1-08
                                 mands 1, 2, and 3 are ON for
                                                                               i        Yes                                        287H     6-5
                                                                    0 to
                                 multi-function inputs.                                                                      A
                Reference 8                                        100.00                         -        -       -
                                                                                                                          0.00 %
                                                                     %
                                                                    0 to                          Q       Q        Q
                Nominal speed                                      120.00                       50.00   50.00    50.00      -
                                   Sets the frequency reference     *1,*2                        Hz      Hz       Hz                        6-7
       d1-09                       when the nominal speed is                   i        Yes                                        288H
                                                                                                                                            6-8
                                   selected by a digital input.     0 to                                                    Q
                Nomin Speed vn                                     100.00                         -        -       -      100.00
                                                                     %                                                      %
5-18
                                                                                                                   Control Methods
Param-        Name                                                                           Change                                                MEMO-
                                                                                   Fac-                                                  Closed
 eter                                                                  Setting               during                 Open      Closed                BUS       Pag
                                           Description                             tory                                                   Loop
 Num-                                                                  Range                 Opera-        V/f       Loop      Loop                Regis-      e
              Display                                                             Setting                                                Vector
  ber                                                                                         tion                  Vector    Vector                 ter
                                                                                                                                          (PM)
                                                                        0 to                               A          A          A
         Intermediate                                                  120.00                             0.00       0.00       0.00        -
         speed 1              Sets the frequency reference              *1,*2                              Hz         Hz         Hz                            6-7
d1-10                         when the intermediate speed 1 is                      i          Yes                                                  28BH
                                                                                                                                                               6-8
                              selected by a digital input.              0 to
                                                                                                                                            A
         Interm Speed v1                                               100.00                               -          -          -
                                                                                                                                         0.00 %
                                                                         %
                                                                        0 to                               A          A          A
         Intermediate                                                  120.00                             0.00       0.00       0.00        -
         speed 2              Sets the frequency reference              *1,*2                              Hz         Hz         Hz                            6-7
d1-11                         when the intermediate speed 2 is                      i          Yes                                                  28CH
                                                                                                                                                               6-8
                              selected by a digital input.              0 to
                                                                                                                                            A
         Interm Speed v2                                               100.00                               -          -          -
                                                                                                                                         0.00 %
                                                                         %
                                                                        0 to                               A          A          A
         Intermediate                                                  120.00                             0.00       0.00       0.00        -
         speed 3              Sets the frequency reference              *1,*2                              Hz         Hz         Hz                            6-7
d1-12                         when the intermediate speed 3 is                      i          Yes                                                  28DH
                                                                                                                                                               6-8
                              selected by a digital input.              0 to
                                                                                                                                            A
         Interm Speed v3                                               100.00                               -          -          -
                                                                                                                                         0.00 %
                                                                         %
                                                                        0 to                               A          A          A
         Releveling                                                    120.00                             0.00       0.00       0.00        -
         speed                Sets the frequency reference              *1,*2                              Hz         Hz         Hz                            6-7
d1-13                         when the releveling speed is                          i          Yes                                                  28EH
                                                                                                                                                               6-8
                              selected by a digital input.              0 to
         Relevel Speed                                                                                                                      A
                                                                       100.00                               -          -          -
         vr                                                                                                                              0.00 %
         Inspection speed
                                                                         %
                                                                        0 to
                                                                       120.00
                                                                                                           Q
                                                                                                         25.00
                                                                                                                      Q
                                                                                                                    25.00
                                                                                                                                 Q
                                                                                                                               25.00        -
                                                                                                                                                                       5
                              Sets the frequency reference              *1,*2                             Hz         Hz         Hz                            6-7
d1-14                         when the inspection speed is                          i          Yes                                                  28FH
                                                                                                                                                              6-11
                              selected by a digital input.              0 to                                                               Q
         Inspect Speed vi                                              100.00                               -          -          -      50.00
                                                                         %                                                                %
                                                                        0 to                               A          A          A
         Rescue Opera-                                                 120.00                             5.00       5.00       5.00        -
         tion Speed           Sets the frequency reference              *1,*2                              Hz         Hz         Hz
d1-15                         when rescue operation is enabled                      i          Yes                                                  290H      6-80
                              by a digital input.                       0 to                                                               A
         Rescue OP Spd                                                 100.00                               -          -          -      10.00
                                                                         %                                                                %
                                                                        0 to                               Q          Q          Q
         Leveling Speed                                                120.00                             4.00       4.00       4.00        -
                              Sets the frequency reference              *1,*2                              Hz         Hz         Hz                            6-7
d1-17                         when the leveling speed is                            i          Yes                                                  292H
                                                                                                                                                               6-8
                              selected by a digital input.              0 to
                                                                                                                                            Q
         Level Speed vl                                                100.00                               -          -          -
                                                                                                                                         8.00 %
                                                                         %
                              Speed reference priority selection
         Speed priority       0: Use Multi-Speed reference
         selection               (d1-01 to d1-08)
                              1: High Speed reference has pri-
                                                                                                                                                               6-5
                                 ority.
d1-18                                                                   0 to 3       1         Yes          A         A          A          A       2A7H       6-7
                              2: Leveling speed reference has
                                                                                                                                                               6-8
                                 priority.
         SpeedPriority-       3: Use multi-speed reference
         Sel                     With no speed selected, the up/
                                 down signal is switched off
         Second motor
         speed                Sets the speed reference if motor        0.00 to      0.00
d1-19                                                                                           No          A         A          A          -       2A8H      6-57
         Spd@Door             2 is selected.                           120.00        Hz
         Motor
  *1. The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz). If the display unit is changed, the setting range values also
      change
  *2. The maximum setting value depends on the setting of the maximum output frequency (E1-04).
                                                                                                                                                                     5-19
         Field Forcing: d6
                                                                                                             Control Methods
       Param-      Name                                                                       Change
        eter                                                              Setting   Factory   during         Open              Closed MEMO-
                                             Description                                                             Closed            BUS       Page
        Num-                                                              Range     Setting   Opera-         Loop               Loop
                                                                                                       V/f            Loop
         ber      Display                                                                      tion          Vec-              Vector Register
                                                                                                                     Vector
                                                                                                              tor               (PM)
                Field forc-
                ing function   Enables or disables field forcing func-
                selection      tion.
       d6-03                                                              0 or 1      0        No       -     A       A          -     2A2H      6-39
                               0: Disabled
                Field Force    1: Enabled
                Sel
5-20
 Motor Parameters: E
   V/f Pattern 1: E1
                                                                                                          Chang            Control Methods
Param         Name                                                                                                                                    MEMO
                                                                                       Set-      Fac-     e dur-                             Closed
 eter                                                                                                                      Open     Closed             BUS
                                                 Description                           ting      tory      ing                                Loop             Page
Num-                                                                                                                V/f    Loop      Loop             Regis-
              Display                                                                 Range     Setting   Opera-                             Vector
 ber                                                                                                                       Vector   Vector              ter
                                                                                                           tion                               (PM)
        Input voltage
        setting              Sets the Inverter input voltage.                         310 to
                                                                                                400 V                                                          6-62
E1-01                        This setting is used as a reference                       510        *1       No       Q        Q        Q        Q      300H
        Input                                                                           *1                                                                     6-65
                             value for protection functions.
        Voltage
        Max. output fre-                                                                                             Q       Q        Q
                                                                                      40.0 to
        quency                                                                                                     50.00   50.00    50.00      -
                                                                                       120.0
        (FMAX)                                                                                                      Hz      Hz       Hz
                                                                                       (PG-
                                                                                        F2)                                                                    6-62
E1-04                                                                                   0 to      i        No                                         303H
                                                                                                                                                               6-65
                                                                                       1200                                                    Q
        Max Frequency                                                                                                -       -        -       150
                                                                                       (PG-                                                   rpm
                                                                                        X2)
                                                                                        0 to
                                                                                       3600
      Max. output
      voltage                                                                         0.0 to    380.0
                             utput Voltage (V)
E1-05 (VMAX)                                                                          510.0       V        No       Q        Q        Q        -      304H     6-62
                               V MAX
                                                                                        *1        *1
                                                                                                                                                                        5
                               E1-05
                              V BASE
        Max Voltage            E1-13
                                                                                                                     Q       Q        Q
        Base frequency          VC                                                    0.0 to
                               E1-08                                                                               50.00   50.00    50.00      -
        (FA)                                                                          120.00
                                                                                                                    Hz      Hz       Hz                        6-62
E1-06                         V MIN
                              E1-10
                                                                                                  i        No                                         305H
                                                                                                                                                               6-65
                                                                                      20 to                                                    Q
                                       F MIN         FB         FA     F MAX
        Base Frequency                 E1-09        E1-07      E1-08   E1-04          7200                           -       -        -       150
                                                                       Frequency (H   rpm                                                     rpm
      Mid. output fre- To set V/f characteristics in a straight
      quency (FB)      line, set the same values for E1-07 and                        0.0 to
E1-07                  E1-09. In this case, the setting for E1-                                 3.0 Hz     No       A        A        -        -      306H     6-62
      Mid Frequency                                                                   120.0
                       08 will be disregarded.
      A
                       Always ensure that the four frequen-
      Mid. output fre- cies are set in the following manner:                                                        Q       Q
      quency voltage E1-04 (FMAX) ≥ E1-06 (FA) > E1-07                                0.0 to
                                                                                                                   37.3    25.0
E1-08 (VB)
                       (FB) ≥ E1-09 (FMIN)
                                                                                       510        i        No       V       V         -        -      307H     6-62
                                                                                        *1
                                                                                                                    *1       *1
        Mid Voltage A
                                                                                                                     Q
        Min. output fre-                                                              0.0 to                                 Q      A
                                                                                                           No       0.5                        -
        quency (FMIN)                                                                 120.0                                0.3 Hz 0.0 Hz                       6-62
E1-09                                                                                             i                 Hz                                308H
                                                                                                                                                               6-65
                                                                                       0 to                                                    A
        Min Frequency                                                                                      No        -       -        -
                                                                                       7200                                                  0 rpm
      Min. output fre-                                                                                              Q
      quency voltage                                                                  0.0 to                                 Q
                                                                                                                   19.4
E1-10 (VMIN)                                                                          510.0       i        No       V
                                                                                                                           5.0 V      -        -      309H     6-62
                                                                                        *1                                   *1
                                                                                                                    *1
        Min Voltage
      Base voltage                                                                    0.0 to
                             Sets the output voltage of the base fre-                                                A       A                 Q
E1-13 (VBASE)
                             quency (E1-06).
                                                                                      510.0     i*2        No
                                                                                                                   0.0 V   0.0V
                                                                                                                                      -
                                                                                                                                             200 V
                                                                                                                                                      30CH     6-62
                                                                                        *1
        Base Voltage
                                                                                                                                                                      5-21
         Motor 1 Setup: E2
                                                                                                            Control Methods
       Param-      Name                                                                     Change                                     MEMO-
        eter                                                            Setting   Factory    during                           Closed    BUS
                                            Description                                                     Open Closed                         Page
        Num-                                                            Range     Setting   Opera-                             Loop    Regis-
                                                                                                      V/f    Loop  Loop
         ber      Display                                                                     tion                            Vector     ter
                                                                                                            Vector Vector
                                                                                                                               (PM)
                         Sets the motor rated current.
                Motor rated
                current  This set value will become the refer-
                                                                        0.85 to
                         ence value for motor protection and                      7.00 A
       E2-01                                                             17.00      *2        No      Q      Q       Q          -      30EH     6-62
                         torque limits.                                   *1
             Motor Rated
                         This parameter is an input data for
             FLA
                         autotuning.
                         Sets the motor rated slip.
                Motor rated
                slip     This set value will become the refer-
                                                                        0.00 to   2.70 Hz
       E2-02             ence value for the slip compensation.                      *2        No      Q      Q       Q          -      30FH     6-62
                                                                         20.00
             Motor Rated This parameter is automatically set
             Slip        during autotuning.
                Motor no-
                load current   Sets the motor no-load current.          0.00 to
                                                                                  2.30 A
       E2-03                   This parameter is automatically set       6.99       *2        No      Q      Q       Q          -      310H     6-62
                No-Load        during autotuning.                         *3
                Current
                Number of
                motor poles    Sets the number of motor poles.
       E2-04                   This value is an input data for autotun- 2 to 48   4 poles     No       -      -      Q          -      311H     6-62
                Number of      ing.
                Poles
             Motor line-
             to-line resis- Sets the motor phase-to-phase resis-         0.000    3.333 Ω
5      E2-05 tance
                            tance.
                            This parameter is automatically set
             Term Resis- during autotuning.
                                                                           to
                                                                        65.000
                                                                                    *2        No      Q      Q       Q          -      312H     6-62
             tance
                Motor leak     Sets the voltage drop due to motor
                inductance     leakage inductance as a percentage of
                                                                        0.0 to    19.3%
       E2-06                   the motor rated voltage.                             *2        No       -     A       A          -      313H     6-62
                Leak Induc-                                              40.0
                               This parameter is automatically set
                tance          during autotuning.
             Motor iron
             saturation    Sets the motor iron saturation coeffi-
                           cient at 50% of magnetic flux.               0.00 to
       E2-07 coefficient 1                                                         0.50       No       -     A       A          -      314H     6-62
                           This parameter is automatically set           0.50
             Saturation    during rotating autotuning.
             Comp1
             Motor iron
             saturation    Sets the motor iron saturation coeffi-
             coefficient 2 cient at 75% of magnetic flux.               0.50 to
       E2-08                                                                       0.75       No       -     A       A          -      315H     6-62
                           This parameter is automatically set           0.75
             Saturation    during rotating autotuning.
             Comp2
             Motor iron
             loss for
             torque com-                                                 0 to     130 W
       E2-10 pensation         Sets motor iron losses.                              *2        No      A       -       -         -      317H     6-62
                                                                        65535
                Tcomp Iron
                Loss
5-22
                                                                                                                               Control Methods
Param-       Name                                                                                             Change                                      MEMO-
 eter                                                                                    Setting    Factory   during                             Closed    BUS
                                                  Description                                                                  Open Closed                         Page
 Num-                                                                                    Range      Setting   Opera-                              Loop    Regis-
                                                                                                                        V/f    Loop    Loop
  ber       Display                                                                                            tion                              Vector     ter
                                                                                                                               Vector Vector
                                                                                                                                                  (PM)
         Motor rated
         output           Sets the rated output power of the
         power            motor.                                                         0.00 to     3.70
E2-11                                                                                                 *2        No      Q       Q       Q          -      318H     6-62
                          This parameter is an input data for                            650.00
         Mtr Rated        autotuning.
         Power
      Motor iron
      saturation
                                                                                         1.30 to
E2-12 coefficient 3 This parameter is automatically set                                              1.30       No       -      A       A          -      328H     6-62
                                                                                          1.60
      Saturation    during rotating autotuning.
         Comp3
   *1. The setting range is 10% to 200% of the Inverter's rated output current. The given value is for a 400 V inverter with 3.7 kW.
   *2. The factory setting depends upon the Inverter capacity. The given value is for a 400 V inverter with 3.7 kW.
   *3. The setting range depends on the inverter capacity and on the setting of E2-01. The maximum value is E2-01 minus 0.01A. The given setting range is
       for a 400 V inverter with 3.7 kW.
   V/f Pattern 2: E3
                                                                                                                               Control Methods
Param         Name                                                                                            Change                                      MEMO-
                                                                                           Set-      Fac-                                        Closed
 eter                                                                                                         during           Open Closed                 BUS
                                                    Description                            ting      tory                                         Loop             Page
Num-                                                                                                          Opera-    V/f    Loop    Loop               Regis-
              Display                                                                     Range     Setting                                      Vector
 ber                                                                                                           tion            Vector Vector                ter
                                                                                                                                                  (PM)
         Control modeSets the contol mode for motor 2.
         selection   0: V/f control
E3-01                2: Open Loop Vector control
      Control Method 3: Closed Loop Vector control for
                        induction motors
                                                                                           0 to 3      0       No       A        A       A          -      319H    6-62
                                                                                                                                                                            5
      Max. output fre-
      quency                                                                              40.0 to    50.00
E3-02 (FMAX)                                                                                                   No       A        A       A          -     31AH     6-62
                                                                                           120.0      Hz
         Max Frequency
      Max. output
      voltage                                                                              0.0 to    400.0
E3-03 (VMAX)                                                                               510.0       V       No       A        A       A          -     31BH     6-62
                              Output Voltage (V)                                             *1       *1
                                 V MAX
         Max Voltage             E3-03
      Base frequency
                                                                                          0.0 to     50.00
E3-04 (FA)
                                   VC
                                  E3-06                                                                        No       A        A       A          -     31CH     6-62
                                                                                          120.00      Hz
         Base Frequency          V MIN
                                 E3-08
                                          F MIN        FB               F MAX
      Mid. output fre-                    E3-07       E3-05
                                                                 FA
                                                                E3-04   E3-02
                                                                        Frequency (Hz)     0.0 to                        A        A
E3-05 quency (FB)                                                                                     i        No                        -          -     31DH     6-62
                                                                                           120.0                       (2.5)    (3.0)
         Mid Frequency
                       To set V/f characteristics in a straight
      Mid. output fre-                                                                                                  A        A
                       line, set the same values for E3-05                                 0.0 to
      quency voltage                                                                                                   30.0     26.4
E3-06 (VB)             and E3-07. In this case, the setting                                 510       i        No       V        V       -          -      31EH    6-62
                       for E3-06 will be disregarded.                                        *1
                                                                                                                        *1       *1
      Mid Voltage      Always ensure that the four frequen-
      Min. output fre- cies are set in the following manner:                                                            A
                       E3-02 (FMAX) ≥ E3-04 (FA) > E3-                                     0.0 to                                A      A
E3-07 quency (FMIN)                                                                                   i        No      1.2                          -      31FH    6-62
                       05 (FB) ≥ E3-07 (FMIN)                                              120.0
                                                                                                                       Hz
                                                                                                                               0.5 Hz 0.0 Hz
      Min Frequency
      Min. output fre-
      quency voltage                                                                       0.0 to                       A        A
E3-08 (VMIN)                                                                               510.0      i        No      18.0    4.8 V     -          -      320H    6-62
                                                                                             *1
                                                                                                                       V *1      *1
         Min Voltage
                                                                                                                                                                          5-23
         Motor 2 Setup: E4
                                                                                                                       Control Methods
       Param-      Name                                                                            Change
         eter                                                                Setting    Factory    during                                 Closed MEMO-
                                               Description                                                             Open Closed                BUS           Page
        Num-                                                                 Range      Setting    Opera-                                  Loop
                                                                                                                V/f     Loop  Loop
         ber      Display                                                                           tion                                  Vector Register
                                                                                                                       Vector Vector
                                                                                                                                           (PM)
                         Sets the motor rated current.
                Motor rated
                current  This set value will become the refer-
                                                                             0.85 to
                         ence value for motor protection and                             7.00 A
       E4-01                                                                  17.00        *2         No         A       A         A         -       321H       6-62
                         torque limits.                                         *1
             Motor Rated
                         This parameter is an input data for
             FLA
                         autotuning.
                         Sets the motor rated slip.
                Motor rated
                slip     This set value will become the refer-
                                                                             0.00 to    2.70 Hz
       E4-02             ence value for the slip compensation.                             *2         No         A       A         A         -       322H       6-62
                                                                              20.00
             Motor Rated This parameter is automatically set
             Slip        during autotuning.
                Motor no-
                load current    Sets the motor no-load current.              0.00 to
                                                                                         2.30 A
       E4-03                    This parameter is automatically set           13.99        *2         No         A       A         A         -       323H       6-62
                No-Load         during autotuning.                              *3
                Current
                Number of
                motor poles     Sets the number of motor poles.
       E4-04                    This value is an input data for autotun- 2 to 48         4 poles      No         -        -        A         -       324H       6-62
                Number of       ing.
                Poles
             Motor line-
             to-line resis- Sets the motor phase-to-phase resis-              0.000     3.333 Ω
5      E4-05 tance
                            tance.
                            This parameter is automatically set
             Term Resis- during autotuning.
                                                                                to
                                                                             65.000
                                                                                           *2         No         A       A         A         -       325H       6-62
             tance
                Motor leak      Sets the voltage drop due to motor
                inductance      leakage inductance as a percentage of
                                                                              0.0 to     19.3%
       E4-06                    the motor rated voltage.                                   *2         No         -       A         A         -       326H       6-62
                Leak Induc-                                                    40.0
                                This parameter is automatically set
                tance           during autotuning.
                Motor rated
                power                                                        0.00 to      3.70
       E4-07                    Sets the motor rated power.                                           No         A       A         A         -       327H       6-62
                Mtr Rated                                                    650.00       kW
                Power
         *1. The setting range is 10% to 200% of the Inverter's rated output current. The given value is for a 400 V inverter with 3.7 kW.
         *2. The factory setting depends upon the Inverter capacity. The given value is for a 400 V inverter with 3.7 kW.
         *3. The setting range depends on the inverter capacity and on the setting of E2-01. The maximum value is E2-01 minus 0.01A. The given setting range is for a
             400 V inverter with 3.7 kW.
5-24
   PM Motor Setup: E5
                                                                                                                   Control Methods
Param-      Name                                                                               Change
                                                                                                                                      Closed       MEMO-
 eter                                                                   Setting     Factory    during              Open Closed
                                         Description                                                                                   Loop         BUS       Page
 Num-                                                                   Range       Setting    Opera-       V/f    Loop   Loop
           Display                                                                                                                    Vector       Register
  ber                                                                                           tion               Vector Vector
                                                                                                                                       (PM)
         Motor rated
         power                                                          0.00 to     3.7kW
E5-02                    Sets the motor rated power.                                   *1         No         -        -         -        Q         32AH       6-65
                                                                        300.00
         Rated power
         Number of
         motor poles
E5-04                    Sets the number of motor poles.                2 to 48     4 poles       No         -        -         -        Q          32CH      6-65
         Number of
         Poles
      Motor line-
      to-line resis-                                                     0.000 1.326 Ω
                     Sets the motor phase-to-phase resis-
E5-05 tance                                                                to     *1              No         -        -         -        Q         32DH       6-65
                     tance.                                             65.000
      Term Resis-
      tance
         D-Axis
         Inductance                                                                  19.11
                                                                        0.00 to       mH
E5-06                    Sets the motors d-axis inductance                                        No         -        -         -        Q          32EH      6-65
         Leak Induc-                                                    600.00         *1
         tance
         Q-Axis
                                                                                     26.08
                                                                                                                                                                       5
         Inductance                                                     0.00 to
E5-07                    Sets the motors q-axis inductance                            mH          No         -        -         -        Q          32FH      6-65
         Leak Induc-                                                    600.00         *1
         tance
         Motor volt-
         age constant                                                                478.6
                                                                        50.0 to       mV
E5-09                    Sets the motor voltage constant.                                         No         -        -         -        Q          330H      6-65
         Voltage con-                                                   4000.0         *1
         stant
  *1. The factory setting depends upon the Inverter capacity. The given value is for a 400V class inverter with 3.7 kW.
  *2. The setting range is 10% to 200% of the Inverter's rated output current. The given value is for a 400 V class inverter of 3.7 kW is given.
                                                                                                                                                                     5-25
        Option Parameters: F
5               selection at
                overspeed (OS)
                               0: Ramp to stop (Deceleration to
                                  stop using the deceleration time
                                  1, C1-02.)
       F1-03                   1: Coast to stop                          0 to 3     1        No       -      -      A          A     382H      6-77
                               2: Fast stop (Emergency stop using
                                  the deceleration time in C1-09.)
                PG Overspeed
                               3: Continue operation (To protect
                Sel               the motor or machinery, avoid to
                                  use this setting.)
5-26
                                                                                                       Control Methods
Param-        Name                                                                      Change
 eter                                                              Setting    Factory   during                           Closed MEMO-
                                        Description                                                    Open Closed               BUS       Page
 Num-                                                              Range      Setting   Opera-                            Loop
                                                                                                 V/f   Loop   Loop
  ber        Display                                                                     tion                            Vector Register
                                                                                                       Vector Vector
                                                                                                                          (PM)
         Overspeed
         detection level   Sets the overspeed detection
F1-08                      method.                                 0 to 120   115%       No       -      -      A          A     387H      6-77
         PG Overspd
         Level             Motor speeds that continue to
                           exceed the value set in F1-08 (set
         Overspeed         as a percentage of the maximum
         detection delay   output frequency) for the time set
         time                                                       0.0 to
F1-09                      in F1-09 are detected as overspeed                  0.0 s     No       -      -      A          A     388H      6-77
                                                                     2.0
         PG Overspd        faults.
         Time
         Excessive
                         Sets the speed deviation detection
         speed deviation
F1-10    detection level method.                                   0 to 50     10%       No       -      -      A          A     389H      6-77
                         Any speed deviation above the F1-
         PG Deviate      10 set level (set as a percentage of
         Level           the maximum output frequency)
         Excessive       that continues for the time set in
         speed deviation F1-11 is detected as a speed devia-
         detection delay tion.                                      0.0 to
F1-11    time            The speed deviation is the differ-                    0.5 s     No       -      -      A          A     38AH      6-77
                                                                     10.0
                         ence between actual motor speed
         PG Deviate
                         and the speed reference command.
         Time
         Number of PG
         gear teeth 1      Sets the number of teeth on the
F1-12
         PG#Gear
         Teeth1
                           gears if there are gears between the
                           PG and the motor.
                             PG Input Pulses x 60     x F1-13
                                                                    0 to
                                                                                0        No       -      -      A         No     38BH      6-76
                                                                                                                                                    5
         Number of PG              F1-01                F1-12       1000
         gear teeth 2
F1-13                      A gear ratio of 1 will be used if one                0        No       -      -      A         No     38CH      6-76
         PG#Gear           of these parameters is set to 0.
         Teeth2
         PG open-cir-
         cuit detection    Used to set the PG disconnection
         delay time        detection time. PGO will be              0.0 to
F1-14                                                                          2.0 s     No       -      -      A          A     38DH      6-76
                           detected if the detection time            10.0
         PGO Detect        exceeds the set time.
         Time
         DV3 fault        Sets the number of scans (5ms)
         detection selec- until a DV3 fault (wrong direction)
         tion             is detected.
F1-18                                                               0 to 5      1        No       -      -      No         A     3ADH      6-77
                          0: No DV3 detection
         DV3 detect sel n: A DV3 fault is detected after n x
                             5msec.
                                                                                                                                                  5-27
                                                                                                             Control Methods
       Param-        Name                                                                     Change
        eter                                                             Setting    Factory   during                           Closed MEMO-
                                               Description                                                   Open Closed               BUS       Page
        Num-                                                             Range      Setting   Opera-                            Loop
                                                                                                       V/f   Loop   Loop
         ber        Display                                                                    tion                            Vector Register
                                                                                                             Vector Vector
                                                                                                                                (PM)
                Magnet posi-
                tion offset       Sets the Offset between the rotor
       F1-22                                                             0 to 360    60 °      No       -      -       -         A     3B1H      6-76
                Mag Theta         magnet and encoder zero position.
                Comp
                                  Used to memorize encoder and
                Encoder copy      motor data in the encoder memory
                selection         (for Hiperface and EnDat encod-
       F1-25                      ers)                                    0 to 3      0        No       -      -       -         A     3B4H      6-78
                                  0: Normal operation
                                  1: WRITE (Inverter to encoder)
                Enc Copy Sel
                                  2: COPY (Encoder to inverter)
                                  3: VERIFY
                Encoder copy
                write permis-     Sets wether saving parameters in
                sion selection    the encoder is permitted or not.
       F1-26                                                              0 or 1      0        No       -      -       -         A     3B5H      6-78
                                  0: Write prohibited
                Write Allow-      1: Write permitted
                able
5-28
  Analog Monitor Cards: F4
                                                                                                      Control Methods
Param                                                                                  Change                                  MEMO
 eter                                                              Setting   Factory   during         Open            Closed    BUS
               Name                       Description                                                        Closed                     Page
Num-                                                               Range     Setting   Opera-         Loop             Loop    Regis-
                                                                                                V/f           Loop
 ber                                                                                    tion          Vec-            Vector     ter
                                                                                                              Vector
                                                                                                       tor             (PM)
        Channel 1 monitor                                                                       A      A       A
                                                                 1 to 56                                                -
        selection             Using an AO-08 option card the                                    2      2       2
F4-01                         possible outputs signal is 0 to              i            No                                     391H     6-26
                                                                                                                        A
        AO Ch1 Select         +10V only. The setting of F4-07    1 to 75                         -              -
                                                                                                                        5
                              and F4-08 has no effect.
        Channel 1 gain        Sets the channel 1 item bias to    0.0 to
F4-02                                                                    100.0%         Yes     A      A       A        A      392H     6-26
        AO Ch1 Gain           100%/10 V when the analog moni- 1000.0
                              tor card is used.
      Channel 2 monitor
                              This function is enabled when the  1 to 56                        A      A       A        -
F4-03 selection               analog monitor card is used.                  3           No                                     393H     6-26
        AO Ch2 Select                                            1 to 75                         -      -       -       A
        Channel 2 gain        Monitor selection: Sets the number
                                                                 0.0 to
F4-04                         of the monitor item to be output.          50.0%          Yes     A      A       A        A      394H     6-26
        AO Ch2 Gain                                              1000.0
                              (Numerical portion  of U1-
      Channel 1 output        
)                                -110.0
F4-05 monitor bias            4, 10, 11, 12, 13, 14, 25, 28, 34,    to    0.0%          Yes     A      A       A        A      395H     6-26
                              35, 39 and 40 cannot be set.        110.0
        AO Ch1 Bias
                              Gain: Sets the percentage of the
        Channel 2 output        monitor item, which is equal to
        monitor bias            10V output.
                                                                   -110.0
F4-06                                                                to       0.0%      Yes     A      A       A        A      396H     6-26
                              Bias: Sets the percentage of the     110.0
                                monitor item, which is equal to
        AO Ch2 Bias
                                0V output.
                                                                                                                                                 5
      Analog output sig-
      nal level for chan-     Selects the analog output signal
F4-07 nel 1                   level for channel 1 (effective for   0 or 1      0        No      A      A       A        A      397H     6-26
                                                                                                                                               5-29
         Digital Output Card (DO-02 and DO-08): F5
                       Name                                                                                Control Methods
                                                                                            Change                                    MEMO
        Con-                                                                       Fac-                                      Closed
                                                                        Setting             during         Open Closed                 BUS
        stant                                  Description                         tory                                       Loop           Page
                      Display                                           Range               Opera-   V/f    Loop  Loop                Regis-
       Number                                                                     Setting                                    Vector
                                                                                             tion          Vector Vector                ter
                                                                                                                              (PM)
                Channel 1 output    Effective when a Digital Output
                selection           Card (DO-02 or DO-08) is used.
       F5-01                                                            0 to 47     0        No      A      A       A          A      399H    -
                                    Set the number of the multi-func-
                DO Ch1 Select       tion output to be output.
                Channel 2 output    Effective when a Digital Output
                selection           Card (DO-02 or DO-08) is used.
       F5-02                                                            0 to 47     1        No      A      A       A          A      39AH    -
                                    Set the number of the multi-func-
                DO Ch2 Select       tion output to be output.
                Channel 3 output    Effective when a DO-08 Digital
                selection           Output Card is used.
       F5-03                                                            0 to 47     2        No      A      A       A          A      39BH    -
                                    Set the number of the multi-func-
                DO Ch3 Select       tion output to be output.
                Channel 4 output    Effective when a DO-08 Digital
                selection           Output Card is used.
       F5-04                                                            0 to 47     4        No      A      A       A          A      39CH    -
                                    Set the number of the multi-func-
                DO Ch4 Select       tion output to be output.
                Channel 5 output    Effective when a DO-08 Digital
                selection           Output Card is used.
       F5-05                                                            0 to 47     6        No      A      A       A          A      39DH    -
                                    Set the number of the multi-func-
                DO Ch5 Select       tion output to be output.
                Channel 6 output    Effective when a DO-08 Digital
                selection           Output Card is used.
5      F5-06
                DO Ch6 Select
                                    Set the number of the multi-func-
                                    tion output to be output.
                                                                        0 to 47     37       No      A      A       A          A      39EH    -
5-30
  Serial Communications Settings: F6
                                                                                                     Control Methods
Param-          Name                                                                  Change
                                                                    Set-     Fac-                                      Closed MEMO-
 eter                                                                                 during         Open Closed
                                          Description               ting     tory                                       Loop   BUS       Page
 Num-                                                                                 Opera-   V/f   Loop   Loop
               Display                                             Range    Setting                                    Vector Register
  ber                                                                                  tion          Vector Vector
                                                                                                                        (PM)
         EF0 Detection
         Stopping method       0: Deceleration to stop using the
         for external error       deceleration time in C1-02
         from Communica-       1: Coast to stop
F6-03                                                              0 to 3     1        No      A      A       A          A     3A4H       -
         tions Option Card     2: Emergency stop using the
                                  deceleration time in C1-09
         EF0 Fault Action      3: Continue operation
         Trace Sampling
         Time                                                       0 to
F6-04                                          -                              0        No      A      A       A          A     3A5H       -
                                                                   60000
         Trace Sample Tim
F6-05
         Current monitor
         unit selection
                               Sets the unit of current monitor
                               0: Ampere                           0 or 1     0        No      A      A       A          A     3A6H       -
                                                                                                                                                  5
         Current Unit Sel      1: 100%/8192
                                                                                                                                                5-31
        Terminal Function Parameters: H
5-32
                                                                                                                    Control Methods
Setting                                                                                                             Open            Closed
                                                       Function                                                             Closed                Page
Value                                                                                                               Loop             Loop
                                                                                                              V/f            Loop
                                                                                                                     Vec-           Vector
                                                                                                                            Vector
                                                                                                                      tor            (PM)
  87      High Speed Limit Switch (UP)                                                                       Yes        Yes      Yes      Yes     6-29
  88      High Speed Limit Switch (Down)                                                                     Yes        Yes      Yes      Yes     6-29
  89      PG direction change over (0: Clockwise, 1: Counterclockwise)                                        No        No       Yes       No     6-56
                                                                                                                                                         5-33
                                                                                                                       Control Methods
       Setting                                                                                                                           Closed
                                                             Function                                                  Open Closed                Page
       Value                                                                                                                              Loop
                                                                                                                 V/f    loop  Loop
                                                                                                                                         Vector
                                                                                                                       Vector Vector
                                                                                                                                          (PM)
         11      Fault reset command active                                                                      Yes    Yes     Yes       Yes     6-59
         12      Timer function output                                                                           Yes    Yes     Yes       Yes     6-54
         13      fref/fset agree 2 (detection width L4-04 is used)                                               Yes    Yes     Yes       Yes     6-27
                 fref/fset agree 2 (ON: Output frequency = L4-03, with detection width L4-04 is used, and dur-
         14                                                                                                      Yes    Yes     Yes       Yes     6-27
                 ing frequency agree)
         15      Frequency detection 3 (ON: Output frequency ≤ -L4-03, detection width L4-04 is used)            Yes    Yes     Yes       Yes     6-27
         16      Frequency detection 4 (ON: Output frequency ≥ -L4-03, detection width L4-04 is used)            Yes    Yes     Yes       Yes     6-27
         17      Car stuck/undertorque detection 1 NC (NC Contact, OFF: Torque detection)                        Yes    Yes     Yes       Yes     6-41
         18      Car stuck/undertorque detection 2 NO (NO Contact, ON: Torque detection)                         Yes    Yes     Yes       Yes     6-41
         19      Car stuck/undertorque detection 2 NC (NC Contact, OFF: Torque detection)                        Yes    Yes     Yes       Yes     6-41
        1A       During reverse run (ON: During reverse run)                                                     Yes    Yes     Yes       Yes     6-59
         1B      During baseblock 2 (OFF: During baseblock)                                                      Yes    Yes     Yes       Yes     6-60
         1C      Motor 2 selected (ON: Motor 2 (E3- and E4-) is selected)                                    Yes    Yes     Yes       No      6-65
        1D       During regenerative operation                                                                   No     No      Yes       Yes     6-60
         1E      Restart enabled (ON: Automatic fault restart enabled)                                           Yes    Yes     Yes       Yes     6-84
         1F      Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)          Yes    Yes     Yes       Yes     6-45
         20      Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)                        Yes    Yes     Yes       Yes     6-48
         30      During torque limit (current limit) (ON: During torque limit)                                   No     Yes     Yes       Yes     6-44
5 33
         37
                 Zero-servo end (ON: Zero-Servo completed)
                 During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excita-
                 tion, operation stop)
                                                                                                                 No
                                                                                                                 Yes
                                                                                                                        No
                                                                                                                        Yes
                                                                                                                                Yes
                                                                                                                                Yes
                                                                                                                                          Yes
                                                                                                                                          Yes
                                                                                                                                                  6-16
6-58
5-34
  Analog Inputs: H3
                Name                                                                                     Control Methods
                                                                                          Change                                    MEMO
 Con-                                                                                                                      Closed
                                                                      Setting   Factory   during         Open     Closed             BUS
 stant                                      Description                                                                     Loop           Page
                Display                                               Range     Setting   Opera-   V/f   Loop      Loop             Regis-
Number                                                                                                                     Vector
                                                                                           tion          Vector   Vector              ter
                                                                                                                            (PM)
         AI-14B Channel3
         gain
                                below for the available functions.
                                Sets the input level according to
                                the 100% value of the function
                                                                                                                                                    5
H3-06                                                                 0.0 to
  *1                            set in parameter H3-05 when the              100.0%        Yes     A       A        A        A      415H   6-26
                                                                      1000.0
                                voltage at channel 3 of the
         AI-14 CH3 Gain
                                AI-14B option card is 10 V.
                                                                                                                                                  5-35
                        Name                                                                                           Control Methods
                                                                                                        Change                                     MEMO
        Con-                                                                                                                              Closed
                                                                                   Setting    Factory   during         Open      Closed             BUS
        stant                                          Description                                                                         Loop           Page
                        Display                                                    Range      Setting   Opera-   V/f    Loop      Loop             Regis-
       Number                                                                                                                             Vector
                                                                                                         tion          Vector    Vector              ter
                                                                                                                                           (PM)
                 Analog input filter      Sets delay filter time constant for
       H3-12     time constant            the three analog input channels of       0.00 to      0.03
         *1                                                                                              No      A       A         A        A      41BH   6-26
                                          the AI-14B option card.                   2.00          s
                 CH1-3 FilterTime         Effective for noise control etc.
                 Terminal A1 func-        Sets the multi-function analog
                 tion selection           input function for terminal A1.
       H3-15                                                                        0 or 1       0       No      No     No         A        A      434H   6-26
                                          0: Frequency Reference
                 Terminal A1 Func         1: Torque compensation
                 Terminal A1 input        Sets the frequency reference
                 gain                     value when 10 V is input as a per- 0.0 to
       H3-16                                                                        100.0%               Yes     A       A         A        A      435H   6-26
                                          centage of the maximum output      1000.0
                 Terminal A1 Gain         frequency set in E1-04.
                 Terminal A1 input        Sets the frequency reference
                 bias                     value when 0 V is input as a per-        -100.0
       H3-17                                                                         to        0.0%      Yes     A       A         A        A      436H   6-26
                                          centage of the maximum fre-
                 Terminal A1 Bias                                                  +100.0
                                          quency set in E1-04.
*1. This parameter is available only if an analog input option board AI-14B is installed.
              H3-05,H3-09 Settings
                                                                                                                                 Control Methods
       Setting                                                                                                                   Open            Closed
                                     Function                                          Contents (100%)                                   Closed           Page
       Value                                                                                                                     Loop             Loop
                                                                                                                         V/f              Loop
                                                                                                                                 Vec-            Vector
                                                                                                                                         Vector
5        2
                 Auxiliary frequency reference (is used as
                 multi speed reference 2)
                                                                     Maximum output frequency (AI-14B use only)          Yes
                                                                                                                                  tor
                                                                                                                                  Yes      Yes
                                                                                                                                                  (PM)
Yes 6-6
5-36
 Protection Function Parameters: L
  Motor Overload: L1
                                                                                                               Control Methods
Para-        Name                                                                              Change
meter                                                                   Setting     Factory    during                            Closed MEMO-
                                          Description                                                          Open Closed               BUS         Page
Num-                                                                    Range       Setting    Opera-                             Loop
                                                                                                         V/f    Loop  Loop
 ber        Display                                                                             tion                             Vector Register
                                                                                                               Vector Vector
                                                                                                                                  (PM)
                     Sets whether the motor thermal over-
                     load protection function is enabled or
      Motor pro-     disabled.
                                                                                                         Q      Q       Q
      tection selec- 0: Disabled                                         0 to 3                                                    -
                     1: General-purpose motor protection                                                 1      1       1
      tion
                        (fan cooled motor)
                     2: Inverter motor protection (exter-
L1-01                   nally cooled motor)                                           i           No                                      480H       6-45
                     3: Vector motor protection
                        When the Inverter power supply is
                        turned off, the thermal value is
      MOL Fault         reset, so even if this parameter is                                                                        A
                        set to 1, protection may not be                  0 or 5                           -      -       -
      Select                                                                                                                       5
                        effective.
                     5: Permanent magnet constant torque
                        motor protection
        Rescue Opera-
        tion DC bus
                              Sets the DC bus voltage during            0 to
L2-11   Voltage                                                                    0 VDC          No     A      A       A          A      4CBH       6-80
                              rescue operation.                        400*1
        Volt@batterydr
*1. These are values for a 200 V class Inverter. The value for a 400 V class Inverter is the double.
                                                                                                                                                            5-37
         Stall Prevention: L3
                                                                                                           Control Methods
       Para-        Name                                                                   Change
       meter                                                           Setting   Factory   during                            Closed MEMO-
                                            Description                                                    Open Closed               BUS       Page
       Num-                                                            Range     Setting   Opera-                             Loop
                                                                                                     V/f   Loop   Loop
        ber        Display                                                                  tion                             Vector Register
                                                                                                           Vector Vector
                                                                                                                              (PM)
         Reference Detection: L4
                                                                                                           Control Methods
       Param         Name                                                                  Change
        eter                                                           Setting   Factory   during                            Closed MEMO-
                                              Description                                                  Open Closed               BUS       Page
       Num-                                                            Range     Setting   Opera-                             Loop
                                                                                                     V/f    Loop  Loop
        ber          Display                                                                tion                             Vector Register
                                                                                                           Vector Vector
                                                                                                                              (PM)
               Speed agreement      Effective when "fout/fset agree    0.0 to                         A     A        A
                                                                                                                               -
               detection level      1", "Frequency detection 1" or     120.0                        0.0Hz 0.0Hz    0.0Hz
       L4-01                                                                       i        No                                       499H      6-27
                                    "Frequency detection 2" is set     0.0 to                                                  A
               Spd Agree Level      for a multi-function output.                                      -      -       -
                                                                       100.0                                                 0.0%
5-38
                                                                                                        Control Methods
Param          Name                                                                    Change
 eter                                                              Setting   Factory    during                            Closed MEMO-
                                         Description                                                    Open Closed               BUS       Page
Num-                                                               Range     Setting   Opera-                              Loop
                                                                                                  V/f   Loop   Loop
 ber           Display                                                                   tion                             Vector Register
                                                                                                        Vector Vector
                                                                                                                           (PM)
                                                                   -120.0
      Speed agreement                                                                              A     A     A
                            Effective when "fout/fset agree          to                                                     -
      detection level (+/-)                                                                      0.0Hz 0.0Hz 0.0Hz
                            2", "Frequency detection 3" or         +120.0
L4-03                                                                          i         No                                       49BH      6-27
                            "Frequency detection 4" is set         -100.0
                                                                                                                            A
      Spd Agree Lvl+-       for a multi-function output.             to                            -      -       -
                                                                                                                          0.0%
                                                                   +100.0
      Speed agreement      Effective when "fref/fout agree         0.0 to                          A     A     A
      detection width (+/-                                                                                                  -
                           2" "fout/fset agree 2", "Fre-            20.0                         2.0Hz 2.0Hz 2.0Hz
      )
L4-04                      quency detection 3" or "Fre-                        i         No                                       49CH      6-27
                           quency detection 4" is set for a        0.0 to                                                   A
      Spd Agree Wdth+-                                                                             -      -       -
                           multi-function output.                  40.0%                                                  4.0%
   Fault Restart: L5
                                                                                                        Control Methods
Param-          Name                                                                   Change
 eter                                                              Setting   Factory   during                             Closed MEMO-
                                          Description                                                   Open Closed               BUS       Page
 Num-                                                              Range     Setting   Opera-                              Loop
                                                                                                  V/f   Loop    Loop
  ber          Display                                                                  tion                              Vector Register
                                                                                                        Vector Vector
                                                                                                                           (PM)
         Number of auto
                               Sets the number of auto reset
         restart attempts
                               attempts.
                               The auto resetable faults are:
L5-01                                                              0 to 10      2        No        A      A       A         A     49EH      6-84
                                                                                                                                                     5
                               OV, UV1, GF, OC, OL2, OL3,
                               OL4, UL3, UL4, PF, LF, SE1,
         Num of Restarts       SE2, SE3
                                                                                                                                                   5-39
         Torque Detection: L6
                                                                                                             Control Methods
       Param-        Name                                                                     Change
        eter                                                             Setting    Factory   during                           Closed MEMO-
                                               Description                                                   Open Closed               BUS       Page
        Num-                                                             Range      Setting   Opera-                            Loop
                                                                                                       V/f   Loop   Loop
         ber         Display                                                                   tion                            Vector Register
                                                                                                             Vector Vector
                                                                                                                                (PM)
                                   0: Torque detection disabled.
                                   1: Car stuck detection only with
                                      speed agreement; operation
                                      continues (warning is output).
                Torque             2: Car stuck detected continu-
                                      ously during operation; opera-
                detection selec-
                                      tion continues
                tion 1                (warning is output).
                                   3: Car stuck detection only with
                                      speed agreement; output
                                      stopped upon detection.
                                   4: Car stuck detected continu-
                                      ously during operation; output
                                      stopped upon detection.
       L6-01                                                              0 to 8      4        No      A      A       A          A     4A1H      6-41
                                   5: Undertorque detection only
                                      with speed agreement; opera-
                                      tion continues (warning is out-
                                      put).
                                   6: Undertorque detected continu-
                                      ously during operation; opera-
                Torq Det 1 Sel        tion continues
                                      (warning is output).
                                   7: Undertorque detection only
                                      with speed agreement; output
                                      stopped upon detection.
                                   8: Undertorque detected continu-
5               Torque detec-
                                      ously during operation; output
                                      stopped upon detection.
                                   Vector control: Motor rated
                tion level 1       torque is set as 100%.
       L6-02                                                             0 to 300   150%       No      A      A       A          A     4A2H      6-41
                                   V/f control: Inverter rated current
                Torq Det 1 Lvl     is set as 100%.
             Torque detec-
                                   Sets the overtorque/undertorque        0.0 to
       L6-03 tion time 1                                                            10.0 s     No      A      A       A          A     4A3H      6-41
                                   detection time.                         10.0
                Torq Det 1 Time
                Torque detec-
                tion selection 2
       L6-04                                                              0 to 8      0        No      A      A       A          A     4A4H      6-41
                Torq Det 2 Sel
                Torque detec-
                tion level 2       See L6-01 to L6-03 for a descrip-       0 to
       L6-05                       tion.                                            150%       No      A      A       A          A     4A5H      6-41
                                                                           300
                Torq Det 2 Lvl
             Torque detec-
                                                                          0.0 to
       L6-06 tion time 2                                                            10.0 s     No      A      A       A          A     4A6H      6-41
                                                                           10.0
                Torq Det 2 Time
5-40
  Torque Limits: L7
                                                                                                                                         Control Methods
Param         Name                                                                                                        Change
                                                                                                        Set-     Fac-                    Open            Closed MEMO-
 eter                                                                                                                     during                 Closed
                                                Description                                             ting     tory                    Loop             Loop   BUS     Page
Num-                                                                                                                      Opera-   V/f            Loop
             Display                                                                                   Range    Setting                  Vec-            Vector Register
 ber                                                                                                                       tion                  Vector
                                                                                                                                          tor             (PM)
      Forward drive
                                                                                                        0 to
L7-01 torque limit                                                                                              300%       No       -     A       A      A      4A7H    6-44
                             Sets the torque limit value as a per-                                      300
        Torq Limit Fwd
                             centage of the motor rated torque.
      Reverse drive          Four individual regions can be set.
                                                                                                        0 to
L7-02 torque limit                                                                                              300%       No       -     A       A      A      4A8H    6-44
                                                                                                        300
        Torq Limit Rev                                   Output torque
Positive torque
        Forward regener-
        ative torque limit                                                                              0 to
L7-03                                     Regenerative
                                                                                               Motor            300%       No       -     A       A      A      4A9H    6-44
        Torq Lmt Fwd            Reserve
                                             state
                                                                                               speed    300
                                                                                            Forward
        Rgn                                                              Regenerative
                                                                            state
        Reverse regener-
                                                                         Negative Torque
                                                                                                                                                                                5-41
         Hardware Protection: L8
                                                                                                            Control Methods
       Param-          Name                                                                  Change
                                                                                                                              Closed   MEMO-
        eter                                                             Setting   Factory   during         Open Closed
                                                Description                                                                    Loop     BUS       Page
        Num-                                                             Range     Setting   Opera-   V/f   Loop   Loop
                      Display                                                                                                 Vector   Register
         ber                                                                                  tion          Vector Vector
                                                                                                                               (PM)
                Input open-phase
                protection selec-
5               tion                  0: Disabled
                                      1: Enabled (Detects if input
                                      current open- phase, super sup-
       L8-05                                                              0,1        1        No      A      A       A          A       4B1H      6-49
                                      ply voltage imbalace or main
                                      circuit electrostatic capacitor
                                      deterioration occurs)
                Ph Loss In Sel
                                 0: Disabled
                                 1: Enabled, 1 Phase Observa-
             Output open-phase      tion
             detection selection 2: Enabled, 2 and 3 Phase
                                    Observation
                                 An output open-phase is
       L8-07                     detected at less than 5% of             0 to 2      2        No      A      A       A         A-       4B3H      6-49
                                 Inverter rated current.
                                 When the applied motor capac-
                                 ity is small compared to the
             Ph Loss Out Sel     Inverter capacity, the detection
                                 may not work properly and
                                 should be disabled.
5-42
                                                                                                                 Control Methods
Param-          Name                                                                         Change
                                                                                                                                   Closed   MEMO-
 eter                                                                  Setting    Factory    during              Open Closed
                                            Description                                                                             Loop     BUS       Page
 Num-                                                                  Range      Setting    Opera-       V/f     Loop  Loop
               Display                                                                                                             Vector   Register
  ber                                                                                         tion               Vector Vector
                                                                                                                                    (PM)
      Ground fault
                                0: Disabled
L8-09 detection selection                                              0 or 1        1          No        A        A      A          A       4B5H      6-50
                                1: Enabled
         Ground Fault Sel
*1. The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 3.7 kW is given. 5
                                                                                                                                                              5-43
        Special Adjustments: n2 / n5
                Speed feedback
                detection control   Set the time constant 1 to decide
                (AFR) time con-                                                                             0 to
       n2-02                        the rate of change in the speed                                                      50 ms       No        -          A        -          -        585H      6-35
                stant                                                                                       2000
                                    feedback detection control.
                AFR Time
5               Speed feedback
                detection control
                                                                                                            0 to
       n2-03    (AFR) time con-                                                                                         750 ms       No        -          A        -          -        586H      6-35
                stant 2                                                                                     2000
AFR Time 2
         Feed Forward: n5
                        Name                                                                                                                               Control Methods
                                                                                                                                     Change                                            MEMO
        Con-                                                                                                                                                                 Closed
                                                                                                               Setting     Factory   during               Open     Closed               BUS
        stant                                                Description                                                                                                      Loop               Page
                       Display                                                                                 Range       Setting   Opera-        V/f    Loop      Loop               Regis-
       Number                                                                                                                                                                Vector
                                                                                                                                      tion                Vector   Vector                ter
                                                                                                                                                                              (PM)
                Feed forward con-      Enables or disables the feed for-                                                                                               A
                                                                                                                                                                                  -
                trol selection         ward control.                                                                                                                   1
        n5-01                                                                                                  0 or 1        i        No            -         -                         5B0H     6-36
                                       0: Disabled                                                                                                                                A
                Feedfoward Sel         1: Enabled                                                                                                                      -
                                                                                                                                                                                  0
                                        Set the time required to acceler-
                                        ate the motor at the rated torque
                Motor acceleration      (T100) to the rated speed (Nr).
                time
                                        J: GO2/4, P: Motor rated output
                                                                             2                                  0.001
        n5-02                                 2π ⋅ J [ kgm ] ⋅ N r [ rpm ]                                        to       0.154 s    No            -         -        A          A     5B1H     6-36
                                        t a = -----------------------------------------------------------                    *1
                                                          60 ⋅ T 100 [ Nm ]                                    60.000
                                        However,
                Motor Accel Time
                                              60 P [ kW ]                   3
                                        100 = 2π ⋅ N [ rpm ] ⋅ 10 [ Nm
                                              ------ ----------------------
                                                         r
5-44
                 Name                                                                                            Control Methods
                                                                                              Change                                          MEMO
 Con-                                                                                                                               Closed
                                                                         Setting    Factory   during            Open      Closed               BUS
 stant                                        Description                                                                            Loop               Page
                Display                                                  Range      Setting   Opera-      V/f   Loop       Loop               Regis-
Number                                                                                                                              Vector
                                                                                               tion             Vector    Vector                ter
                                                                                                                                     (PM)
         Motor acceleration      Enables or diables the tuning for
         time tuning             the motor acceleration time
n5-05                            N5-02.                                   0 or 1       0         No        -       -         A         A      5B4H      6-36
         N5-02 Tuning            0: Disabled
                                 1: Enabled
*1. The factory setting depends on the inverter capacity. The value for a 200 V Class Inverter of 3.7 kW is given.Automatic Frequency Regulator: n2
                                                                                                                                                               5-45
        PM Motor Adjustments: n8 / n9
                Automatic Current
                Regulator q axis      Sets the integral time for the
                integral time                                               0 to
        n8-30                         q-axis current regulator             100.0
                                                                                     10.0 ms    No       -      -        -        A      55DH     6-37
                                      (ACR)
                ACR q Itime
                Automatic Current
                Regulator d axis P    Sets the proportional gain for
                gain                                                       0 to       1000
        n8-32                         d-axis current regulator             2000       rad/s
                                                                                                No       -      -        -        A      55FH     6-37
                                      (ACR)
                ACR d gain
5               Automatic Current
                Regulator q axis
                integral time
                                      Sets the integral time for the
                                                                            0 to
        n8-33                         d-axis current regulator             100.0
                                                                                     10.0 ms    No       -      -        -        A      560H     6-37
                                      (ACR)
                ACR d Itime
                Inductance measur-
                                      Sets the frequency for the volt-
                ing frequency
                                      age to be applied to the motor       0 to
        n8-45                                                                        200Hz      No       -      -        -        A      56CH      -
                                      during inductance tuning.            1000
                Induct Meas Freq      Disabled when n8-61 is set to 1
                Inductance mea-
                                      Sets the current which is used for
                surement current
                                      the inductance measurement dur-
                level                                                      0.0 to
        n8-46                         ing rotating auto tuning. The                  10.0 %     No       -      -        -        A      .56DH     -
                                                                            99.9
                                      value is set in % of the motor
                Induct Meas Lev       rated current.
5-46
  PM Motor Adjustment 2: n9
                                                                                                Control Methods
Param-         Name                                                              Change
                                                                                                                  Closed   MEMO-
 eter                                                        Setting   Factory   during         Open Closed
                                       Description                                                                 Loop     BUS       Page
 Num-                                                        Range     Setting   Opera-   V/f    Loop  Loop
              Display                                                                                             Vector   Register
  ber                                                                             tion          Vector Vector
                                                                                                                   (PM)
         A/D conversion
         start delay timer
                             Sets the A/D conversion delay   0.0 to
n9-60                                                                  0.0 µs     No       -      -       -         A      64DH       6-38
                             time.                             40
         AD
         DelayT@Start
         Detected Current
         Averaging Selec- 0: Disabled
n9-74    tion                                                 0-1        0        No       -      -       -         A       65BH       -
                          1: Enabled
         CurrAvaraginSel
                                                                                                                                             5-47
        Digital Operator/LED Monitor Parameters: o
         Monitor Selections: o1
                                                                                                               Control Methods
       Para-         Name                                                                       Change
                                                                                                                                 Closed   MEMO-
       meter                                                                Setting   Factory   during         Open Closed
                                              Description                                                                         Loop     BUS       Page
       Num-                                                                 Range     Setting   Opera-   V/f   Loop    Loop
                    Display                                                                                                      Vector   Register
        ber                                                                                      tion          Vector Vector
                                                                                                                                  (PM)
                                   Set the number of the 4rd. moni-
               Monitor selection                                            4 to 56                      A      A       A          -
                                   tor item to be displayed in the
       o1-01                       Drive Mode. (U1-)                                  6        Yes                                       500H      6-67
                                   (On LED operator JVOP-161
               User Monitor Sel                                             4 to 75                       -      -       -         A
                                   only.)
                                   Sets the monitor item to be dis-
               Monitor selection   played when the power is turned
               after power up      on.
       o1-02                       1: Frequency reference                   1 to 4      1        Yes     A      A       A          A       501H      6-67
                                   2: Output frequency
               Power-On Moni-      3: Output current
               tor                 4: The monitor item set for o1-
                                      01
5              of reference set-
               ting and monitor
                                      put frequency is 100%)
                                   2: min-1 (2 poles)
                                   3: 0.000 m/s
                                                                                                         A
                                                                                                         0
                                                                                                                A
                                                                                                                0
                                                                                                                        A
                                                                                                                        0
                                                                                                                                   -
5-48
  Digital Operator: o2
                                                                                                       Control Methods
Param-         Name                                                                     Change
                                                                                                                         Closed   MEMO-
 eter                                                               Setting   Factory   during         Open Closed
                                          Description                                                                     Loop     BUS       Page
 Num-                                                               Range     Setting   Opera-   V/f   Loop    Loop
              Display                                                                                                    Vector   Register
  ber                                                                                    tion          Vector Vector
                                                                                                                          (PM)
         LOCAL/               Enables/Disables the Digital
         REMOTE key           Operator Local/Remote key
         enable/disable       0: Disabled
o2-01                         1: Enabled (Switches between          0 or 1      0        No      A      A       A          A       505H      6-68
         Local/Remote            the Digital Operator and the
                                 parameter settings
         Key
                                 b1-01, b1-02.)
         Cumulative oper-
         ation time setting   Sets the cumulative operation          0 to
o2-07                                                                          0 hr.     No      A      A       A          A       50BH      6-69
                              time in hour units.                   65535
         Elapsed Time Set
         Cumulative oper-
         ation time selec-    0: Accumulated inverter power
         tion                    on time.
o2-08                                                               0 or 1      1        No      A      A       A          A       50CH      6-69
                              1: Accumulated inverter run
         Elapsed Time            time.
         Run
                                                                                                                                                    5-49
                                                                                                              Control Methods
       Param-         Name                                                                    Change
                                                                                                                                Closed   MEMO-
        eter                                                              Setting   Factory   during          Open Closed
                                                 Description                                                                     Loop     BUS       Page
        Num-                                                              Range     Setting   Opera-    V/f   Loop   Loop
                      Display                                                                                                   Vector   Register
         ber                                                                                   tion           Vector Vector
                                                                                                                                 (PM)
                Fan operation   Sets the initial value of the fan
                time setting    operation time.                             0 to
       o2-10                                                                          0 hr.     No       A      A       A         A       50EH      6-69
                                The operation time is accumu-              65535
                Fan ON Time Set lated starting from this set value.
          Copy Function: o3
                                                                                                              Control Methods
       Param-       Name                                                                      Change
                                                                                                                                Closed   MEMO-
        eter                                                              Setting   Factory    during         Open Closed
                                              Description                                                                        Loop     BUS       Page
        Num-                                                              Range     Setting   Opera-    V/f    Loop  Loop
                   Display                                                                                                      Vector   Register
         ber                                                                                    tion          Vector Vector
                                                                                                                                 (PM)
                Copy func-
                tion selec-     0: Normal operation
                tion            1: READ (Inverter to Operator)
       o3-01                                                              0 to 3      0         No      A      A       A          A       515H      6-69
                                2: COPY (Operator to Inverter)
                Copy Func-      3: Verify (compare)
5               tion Sel
                Read per-
                mission
                selection       0: READ prohibited
       o3-02                                                              0 or 1      0         No      A      A       A          A       516H      6-69
                                1: READ permitted
                Read
                Allowable
         Brake Sequence: S1
                                                                                                              Control Methods
       Para-         Name                                                                     Change
       meter                                                              Setting   Factory   during                            Closed MEMO-
                                               Description                                                    Open Closed               BUS         Page
       Num-                                                               Range     Setting   Opera-                             Loop
                                                                                                        V/f   Loop   Loop
        ber         Display                                                                    tion                             Vector Register
                                                                                                              Vector Vector
                                                                                                                                 (PM)
                Zero speed      Sets the speed level at which the                                        A       A
                level at stop                                              0.0 to                                       A      A
       S1-01                    DC injection / zero speed operation
                                                                            10.0
                                                                                      i         No      1.2     0.5
                                                                                                                      0.1 Hz 0.1 Hz
                                                                                                                                          680H      6-13
                DC Inj I @start starts during stop.                                                     Hz      Hz
                DC injection
                braking current    Sets the DC injection braking cur-
                                                                            0 to
       S1-02    at start           rent as a percentage of the Inverter              50%        No       A      A        -         -      681H      6-40
                                                                            100
                                   rated current.
                DC Inj I @start
                DC injection
                braking current    Sets the DC injection braking cur-
                                                                            0 to
       S1-03    at stop            rent as a percentage of the Inverter              50%        No       A      A        -         -      682H      6-40
                                                                            100
                                   rated current.
                DC Inj I @stop
                DC injection   Used to set the time to perform DC
                braking/ Zero  injection braking at start in units of
                speed time at  1 second.                                   0.00
       S1-04    start          Used to stop coasting motor and               to      0.40 s     No       A      A       A          A      683H      6-13
                               restart it. When the set value is 0,        10.00
                DC Inj T@start DC injection braking at start is not
                               performed.
5-50
                                                                                                    Control Methods
Para-        Name                                                                    Change
meter                                                            Setting   Factory   during                           Closed MEMO-
                                      Description                                                   Open Closed               BUS       Page
Num-                                                             Range     Setting   Opera-                            Loop
                                                                                              V/f   Loop   Loop
 ber        Display                                                                   tion                            Vector Register
                                                                                                    Vector Vector
                                                                                                                       (PM)
        DC injection  Used to set the time to perform DC
        braking/ Zero injection braking at stop in units of
        speed time at 1 second.                                   0.00
S1-05   stop          Used to prevent coasting after the           to      0.60 s     No      A       A       A         A      684H     6-13
                      stop command is input. When the            10.00
        DC Inj T@stop set value is 0.00, DC injection
                      braking at stop is not performed.
        SE2 det T
                          output current is measured. If it is
                          below 25% of the no-load current
                          (E2-03) setting a SE2 fault will be
                                                                 S1-04 -
                                                                  S1-06                                                                          5
                          output.
                          Used to set the delay time for the
        SE3 detection     detection of a SE3 fault.
        delay time        At the time S1-15 after the fwd/rev
                                                                    0
                          command was given, the inverter
S1-15                                                              to      200ms      No      A       A       A         -     68EH      6-47
                          starts to observe the output current    5000
                          continuously. If it falls below 25%
        SE3 det T
                          of the no-load current (E2-03) set-
                          ting a SE3 will be output.
        RUN delay                                                 0.00
                          Sets the delay time from the Run
        time                                                       to
S1-16                     signal input to the internal run                 0.10sec    No      A       A       A         A     68FH      6-13
                                                                  1.00
        Run Delay T       enable.
        DC injection
        current gain at
        regenerative      Used to set the DC injection gain         0
S1-17   operation         when inverter is in the regenerative     to      100%       No       -      A       -         -      690H     6-40
                          mode.                                   400
        DC Inj
        gain@gen
        DC injection
        current gain at
        motoring oper-    Used to set the DC injection gain         0
S1-18   ation             when inverter is in the motoring         to       20%       No       -      A       -         -      691H     6-40
                          mode.                                   400
        DC Inj
        gain@mot
        Output contac-
        tor open delay                                            0.00
        time              Sets the contactor control output
S1-19                                                              to      0.10sec    No      A       A       A         A      692H     6-13
                          delay time after stop.
        Cont open                                                 1.00
        delay
                                                                                                                                               5-51
                                                                                                            Control Methods
       Para-        Name                                                                     Change
       meter                                                             Setting   Factory   during                           Closed MEMO-
                                             Description                                                    Open Closed               BUS       Page
       Num-                                                              Range     Setting   Opera-                            Loop
                                                                                                      V/f   Loop   Loop
        ber        Display                                                                    tion                            Vector Register
                                                                                                            Vector Vector
                                                                                                                               (PM)
                               Adjust the strength of the zero-
               Zero-servo gain servo lock at the starting of travel.
               @ start         When Closed Loop Vector control
                               is selected, a position control loop
       S1-20                   is created at start and stop. Increas- 0 to 100       5        No       -      -       A         A     693H      6-13
                               ing the zero-servo gain increases
               ZeroSev-        the strength of the lock at the start-
               Gain@Strt       ing of the travel. Increasing to
                               much can cause oscillation.
                                 Sets the bandwidth of the Zero
               Zero-servo        Servo completion output.
               completion        Enabled when the “zero-servo
               width             completion (end)” is set for a
                                 multi-function output. The zero-
                                 servo completion signal is ON            0 to
       S1-21                                                                         10       No       -      -       A         A      694H     6-13
                                 when the current position is within     16383
                                 the range (the zero-servo position +
               Zero Servo        zero-servo completion width.)
               Count             Set S1-21 to 4 times of the allow-
                                 able displacement pulse amount at
                                 the PG.
               Starting torque   Sets the increase time for the ana-
               compensation      log input torque compensation sig-        0
       S1-22   increase time     nal. Sets the time the torque            to       500ms      No       -      -       A         A      695H     6-13
                                                                         5000
5              Torque incr T
               Torque com-
                                 reference needs to reach 300%
                                 torque reference.
5-52
                                                                                                     Control Methods
Para-        Name                                                                     Change
meter                                                             Setting   Factory   during                           Closed MEMO-
                                      Description                                                    Open Closed               BUS         Page
Num-                                                              Range     Setting   Opera-                            Loop
                                                                                               V/f   Loop   Loop
 ber        Display                                                                    tion                            Vector Register
                                                                                                     Vector Vector
                                                                                                                        (PM)
        Torque com-
        pensation fade-   Sets the frequency level at which
        out level                                                 0.0 to
S1-29                     the torque compensation value is                  0.0Hz      No       -      -       A         A       69CH      6-15
                                                                  120.0
        Torq Fadeout-     started to fade out to zero.
        Freq
        Torque com-       Sets the time constant which is
        pensation fade-   used to fade out the torque com-
        out time          pensation value.                                   1000
S1-30                                                             0~5000               No       -      -       A         A       69DH      6-15
                          The set value is the time used to                  msec
        Torq Fadeout-     decrease the compensation value
        Time              from 300% to 0%.
        Torque limit
        time at stop      Sets the time which is used to
S1-31                     reduce the torque limit to 0 after      0~1000    0 msec     No       -      -       -         A       69EH      6-17
        TrqLimit T        zero speed .
        @Stop
        Zero servo gain Adjust the strength of the
        at Stop         zero-servo lock at the end of travel.
                        When Closed Loop Vector control
                        is selected, a position control loop
                        is created at start and stop.
S1-32                                                         0 to 100        5        No       -      -       A         A       69FH      6-13
        ZeroSrv-        Increasing the zero-servo gain at
        Gain@Stop       stop increase the strength of the
                        look at the end of the travel.
        Zero Servo
                        Increasing is too much can cause
                        oscilation.
                          Adjust the strength of the position
                                                                                                                                                    5
        Gain 2            loop gain at the starting of travel.
                          Increasing the zero-servo gain2
                                                                  0.00 to
S1-33                     increases the strength of the lock at              0.00      No       -      -       -         A       6A0H      6-13
                                                                   30.00
        ZeroSrvGain2      the starting of the travel apart from
                          zero-servo gain at start . Increasing
                          it too much can cause oscillation.
        SE4 Detection     SE4 is detected when the Brake
        Time              open signal and Brake release
                          check mismatch for longer than the      0.00 to    0.50
S1-34                                                                                  No      A       A       A         A       6A1H      6-13
                          time set in S1-34.                       10.00     sec
        SE4 det T         SE4 detection is disabled when
                          0.00 sec is set to S1-34
  Slip Compensation: S2
                                                                                                     Control Methods
Para-        Name                                                                     Change
                                                                                                                       Closed   MEMO-
meter                                                             Setting   Factory   during         Open Closed
                                       Description                                                                      Loop     BUS       Page
Num-                                                              Range     Setting   Opera-   V/f   Loop   Loop
            Display                                                                                                    Vector   Register
 ber                                                                                   tion          Vector Vector
                                                                                                                        (PM)
        Motor rated                                                300
        speed                                                       to       1380
S2-01                     Sets the motor rated speed.                                  No      A       -       -         -      6AEH       6-38
                                                                   1800      rpm
        Rated rpm
        Slip compensa-
        tion gain in      Sets the slip compensation gain in
                          motoring mode.                           0.0
S2-02   motoring mode                                              to         0.7      Yes     A      A        -         -      6AFH       6-38
                          It can be used to improve the lev-
        SlipComp                                                   5.0
                          eling accuracy.
        gainMot
        Slip compensa-
        tion gain in   Sets the slip compensation gain in
        regenerative   regenerative mode.                          0.0
S2-03   mode                                                       to         1.0      Yes     A      A        -         -       6B0H      6-38
                       It can be used to improve the
                                                                   5.0
        SlipComp gain- leveling accuracy.
        Gen
                                                                                                                                                  5-53
                                                                                                            Control Methods
       Para-         Name                                                                   Change
                                                                                                                              Closed   MEMO-
       meter                                                            Setting   Factory   during          Open Closed
                                              Description                                                                      Loop     BUS       Page
       Num-                                                             Range     Setting   Opera-    V/f   Loop   Loop
                    Display                                                                                                   Vector   Register
        ber                                                                                  tion           Vector Vector
                                                                                                                               (PM)
                Slip compensa-
                tion torque       Sets the delay time for the slip
                                                                          0.0
                detection delay   compensation torque detection.
       S2-05                                                              to      1.0 sec    No       A      A        -         -       6B2H      6-38
                                  The torque detection is started at
                TorqueDet                                                10.0
                                  S2-05 sec. after speed agree
                Delay T
                Slip compensa-
                tion torque       Sets the time for which the torque
                                                                        0.00 to    0.50
       S2-06    detection time    is measured for the slip compensa-                         No       A      A        -         -       6B3H      6-38
                                                                         2.00      sec
                                  tion calculation.
                Torque detect T
                Slip compensa-
                tion delay time                                            0
                                  Sets the Slip compensation delay
       S2-07                                                              to      200ms      No        -     A        -         -       6B4H      6-38
                SlipCompDe-       time.                                 10000
                lay T
5      S3-01    tion
                Short floor sel
                                  0: disabled
                                  1: enabled (Standard)
                                  2: enabled (Advanced)
                                                                        0 or 1       0        No      A       A       A         A      6BDH       6-18
                Inspection
                deceleration      Sets the deceleration time for the    0.0 to
       S3-03    time                                                              0.0sec      No      A       A       A         A       6BFH      6-11
                                  inspection run.                        2.0
                Dec ramp inspec
                Nominal/Level- Sets the speed level for Nominal/
                ing speed detec- Leveling speed detection when          0.0 to
       S3-04    tion level                                                        0.0Hz       No      A       A       A         A       6C0H      6-6
                                 multispeed inputs are used.            120.0
                Vn/Vl level sel (d1-18=0/3)
                Nominal speed
                for short floor   Sets the nominal speed value
                                                                        0.0 to
       S3-05    calculation       which is used for the short floor               0.0Hz       No      A       A       A         A       6C1H      6-16
                                                                        120.0
                                  calculation.
                Vn@ Short floor
                Light load        Enables or disables the Light load
                search for res-   search function for rescue opera-
       S3-06    cue operation     tion.                                 0 or 2       0        No      A       A       A         A       6C2H      6-83
                                  0: disabled
                LightLoad         1: enabled
                Search            2: enabled (for motor 1 only)
                Light load
                search time       Sets the light load search time for   0.0 to
       S3-07                                                                      1.0 sec     No      A       A       A         A       6C3H      6-83
                LightLd Srch-     the rescue operation.                  5.0
                Time
                Output phase    Sets the output phase order.
       S3-08    order           0: Output phase order is U-V-W          0 or 1       0        No      A       A       A         A       6C4H      6-66
                Exchg Phase Sel 1: Output phase order is U-W-V
                Frequency refer- Enables or disables the frequency
                ence loss detec- reference loss detection when d1-
       S3-09    tion             18 = 1 and H1-K83.                   0 or 1       1        No      A       A       A         A       6C5H      6-8
                                 0: Disabled
                FRL selection    1: Enabled
5-54
                                                                                                          Control Methods
Param-         Name                                                                        Change
                                                                                                                            Closed   MEMO-
 eter                                                                 Setting   Factory    during         Open Closed
                                          Description                                                                        Loop     BUS       Page
 Num-                                                                 Range     Setting    Opera-   V/f   Loop    Loop
              Display                                                                                                       Vector   Register
  ber                                                                                       tion          Vector Vector
                                                                                                                             (PM)
         Light load
         search fre-
         quency              Sets the light load speed for the        0.00 to
S3-10                                                                           3.00 Hz     No      A      A       A          A       6C6H      6-80
                             rescue operation.                         20.00
         LightLd Srch-
         Freq
         Rescue opera-
         tion torque limit Sets the torque limit for the rescue
S3-11                                                           0 to 300        100 %       No       -     A       A          A       6C7H      6-80
         Rescue OP         operation.
         TLM
         Base Block          Sets the behaviour of the inverter
         restart selection   if a Base Block command is set
                             during run.
                             0: Disabled
S3-12                           The Run command must be               0 or 1       0        No      A      A       A          A       6C8H      6-52
                                cycled to restart.
         BB Restart          1: Enable
                                The inverter restarts when the
                                Base Block signal is released
                                and the Run signal is still active.
         Traction sheave
         diameter            Sets the diameter of the traction        100 to      400
S3-13                                                                                       No      A      A       A          A       6C9H      6-68
                             sheave.                                   2000       mm
         Sheave diameter
         Roping              Sets the roping ratio of the eleva-
S3-14
         Roping Ratio
                             tor
                             1: 1:1
                             2: 1:2
                                                                      1 or 2       2        No      A      A       A          A      6CAH       6-68
                                                                                                                                                         5
         Gear Ratio                                                   0.10 to
S3-15                        Sets the mechanical gear ratio.                     1.000      No      A      A       A          A      6CBH       6-68
         Gear Ratio                                                    10.00
                                                                                                                                                       5-55
                                                                                                             Control Methods
       Param-        Name                                                                    Change
                                                                                                                               Closed   MEMO-
        eter                                                             Setting   Factory    during         Open Closed
                                               Description                                                                      Loop     BUS       Page
        Num-                                                             Range     Setting   Opera-    V/f    Loop  Loop
                    Display                                                                                                    Vector   Register
         ber                                                                                   tion          Vector Vector
                                                                                                                                (PM)
                Distance calcu-
                lation accelera-   Sets the acceleration time gain for
                                                                         50.0 to
       S3-21    tion time gain     the optimal speed calculation of                150.0%      No      A      A       A          A      6D1H       6-19
                                                                          200.0
                                   the advanced short floor function.
                Tacc Gain
                Distance calcu-
                lation decelera-   Sets the deceleration time gain for
                                                                         50.0 to
       S3-22    tion time gain     the optimal speed calculation of                150.0%      No      A      A       A          A      6D2H       6-19
                                                                          200.0
                                   the advanced short floor function.
                Tdec Gain
                Distance calcu-
                lation decelera-   Sets the deceleration time gain for
                                                                         50.0 to
       S3-23    tion time gain     the optimal speed calculation of                150.0%      No      A      A       A          A      6D3H       6-19
                                                                          200.0
                                   the advanced short floor function.
5-56
 Motor Autotuning: T
  T1: Autotuning 1
                                                                                                               Control Methods
Param-         Name                                                                        Change
                                                                                                                                  Closed        MEMO-
 eter                                                                Setting    Factory    during              Open Closed
                                          Description                                                                              Loop          BUS       Page
 Num-                                                                Range      Setting    Opera-       V/f     Loop  Loop
              Display                                                                                                             Vector        Register
  ber                                                                                       tion               Vector Vector
                                                                                                                                   (PM)
  *1. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 3.7 kW is given.)
  *2. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
  *3. The setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200 V Class Inverter for 0.4 kW is given.)
                                                                                                                                                                  5-57
         T2: Autotuning 2
                                                                                                                       Control Methods
       Param-         Name                                                                         Change
                                                                                                                                         Closed   MEMO-
        eter                                                                 Setting    Factory    during              Open Closed
                                                 Description                                                                              Loop     BUS       Page
        Num-                                                                 Range      Setting    Opera-       V/f    Loop    Loop
                     Display                                                                                                             Vector   Register
         ber                                                                                        tion               Vector Vector
                                                                                                                                          (PM)
             Motor output                                                                 3.70
                                     Sets the output power of the            0.00 to
       T2-01 power                                                                        kW          No         -        -      -        Yes      730H      4-4
                                     motor in kilowatts.                      75.00        *1
                Mtr Rated Power
             Motor base fre-
                                                                              20 to       150
       T2-02 quency                  Sets the motor base frequency.                                   No         -        -      -        Yes      731H      4-4
                                                                              3600        rpm
                Base Frequency
             Motor rated volt-
                               Sets the rated voltage of the                   0 to     200.0 V
       T2-03 age                                                                           *2         No         -        -      -        Yes      732H      4-4
                               motor.                                         480.0
             Rated Voltage
                Motor rated cur-
                rent                 Sets the rated current of the           0.00 to    14.60 A
       T2-04                                                                               *1         No         -        -      -        Yes      733H      4-4
                Rated                motor.                                  200.00
                Current
             Number of motor
                                                                             2 to 48
       T2-05 poles           Sets the number of motor poles.                            4 poles       No         -        -      -        Yes      734H      4-4
                                                                              poles
                Number of Poles
                Motor voltage        Sets the motor voltage constant
                                                                                         239.3
                constant ke          if T2-99 was set to 0 before.           50.0 to
       T2-08                                                                            mVsec/        No         -        -      -        Yes      737H      4-4
                                     (Otherwise this parameter is not        2000.0
                Voltage constant                                                          rad
                                     displayed)
5            Number of PG
       T2-09 pulses
                                     Sets the number of PG pulses
                                                                             512,
                                                                            1024*2       2048         No         -        -      -        Yes      738H      4-4
                                     per revolution.
                PG Pulses/Rev                                               or 2048
                Motor voltage        Selects if the voltage constant is
                constant calcula-    calculated during auto tuning or
                tion selection       if it has to input manually.
       T2-10                                                                 0 or 1        1          No         -        -      -        Yes      72FH      4-4
                                     0: Manual input in parameter
                VoltConst-              T2-08
                CalcSel              1: Automatic calculation
         *1. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 3.7 kW is given.)
         *2. Can be set only if HIPEFACEy is selected as encoder type.
5-58
 Monitor Parameters: U
                                                                                                          0.01
         Motor speed                                                   10 V: Max. frequency                               A       A         -
                                   Monitors the detected motor                                             Hz
U1-05                                                                  (0 to ± 10 V possible)                     No                                44H
                                   speed.*1
         Motor Speed
         Output voltage            Monitors the output voltage         10 V: 200 VAC (400 VAC)
                                                                                                          0.01
                                                                                                           %
                                                                                                                          -       -         A
                                                                                                                                                                5
U1-06                                                                                                    0.1 V     A      A       A         A       45H
         Output Voltage            reference value.                    (0 to +10 V output)
         DC bus voltage            Monitors the main DC bus            10 V: 400 VDC (800 VDC)
U1-07                                                                                                     1V       A      A       A         A       46H
         DC Bus Voltage            voltage.                            (0 to +10 V output)
*1. The unit is set in o1-03 (frequency units of reference setting and monitor)
                                                                                                                        Control Methods
Param-         Name
                                                                                                                                          Closed   MEMO-
 eter                                                                  Output Signal Level During        Min.           Open Closed
                                          Description                                                                                      Loop     BUS
 Num-                                                                 Multi-Function Analog Output       Unit     V/f    Loop  Loop
              Display                                                                                                                     Vector   Register
  ber                                                                                                                   Vector Vector
                                                                                                                                           (PM)
                              Shows input ON/OFF status.
                                                  1: FWD command
         Input terminal                           (S1) is ON
         status                                   1: REV command
                                                  (S2) is ON
                                                  1: Multi input 1
                                                  (S3) is ON
U1-10                                             1: Multi input 2   (Cannot be output.)                  -       A      A       A          A       49H
                                                  (S4) is ON
                                                  1: Multi input 3
                                                  (S5) is ON
                                                  1: Multi input 4
         Input Term Sts                           (S6) is ON
                                                  1: Multi input 5
                                                  (S7) is ON
                                                                                                                                                              5-59
                                                                                                                       Control Methods
       Param-        Name
                                                                                                                                         Closed   MEMO-
        eter                                                                Output Signal Level During    Min.         Open Closed
                                               Description                                                                                Loop     BUS
        Num-                                                               Multi-Function Analog Output   Unit   V/f   Loop    Loop
                     Display                                                                                                             Vector   Register
         ber                                                                                                           Vector Vector
                                                                                                                                          (PM)
                                    Shows output ON/OFF status.
                                                      1: Multi-function
                                                      contact output 1
                Output terminal                       (M1-M2) is ON
                status                                1: Multi-function
                                                      contact output 2
                                                      (M3-M4) is ON
                                                      1: Multi-function
       U1-11                                          contact output 3     (Cannot be output.)              -    A      A       A          A       4AH
                                                      (M5-M6) is ON
                                                      Not used
                                                      (Always 0).
                                                      1: Error output
                                                      (MA/MB-MC) is
                Output Term Sts                       ON
                                                       Run
                                                       1: Zero speed
                Operation status
                                                       1: Reverse
                                                       1: Reset signal
                                                          input
                                                       1: Speed agree
       U1-12                                           1: Inverter ready   (Cannot be output.)              -    A      A       A          A       4BH
                                                       1: Minor fault
5-60
                                                                                                        Control Methods
Param-        Name
                                                                                                                          Closed   MEMO-
 eter                                                       Output Signal Level During    Min.          Open Closed
                                    Description                                                                            Loop     BUS
 Num-                                                      Multi-Function Analog Output   Unit    V/f    Loop  Loop
             Display                                                                                                      Vector   Register
  ber                                                                                                   Vector Vector
                                                                                                                           (PM)
      Frequency refer- Monitors the frequency refer-
                                                                                          0.01H
      ence after soft- ence after the soft starter.                                               A      A       A          -
                                                                                             z
      starter          This frequency value does not      10 V: Max. frequency
U1-20                                                                                                                               53H
                       include compensations, such as     (0 to ± 10 V possible)
      SFS Output       slip compensation.                                                 0.01%    -      -       -         A
                       The unit is set in o1-03.
      Inverter Heat-
      sink Tempera-       Shows the inverter heatsink
                          temperature measured by the
U1-41 ture                                                (Cannot be output)               °C     A      A       A          A       68H
                          IGBT thermal protection sen-
         Actual Fin       sor.
         Temp
                                                                                                                                              5-61
                                                                                                                         Control Methods
       Param-        Name
                                                                                                                                           Closed   MEMO-
        eter                                                                 Output Signal Level During    Min.          Open Closed
                                                Description                                                                                 Loop     BUS
        Num-                                                                Multi-Function Analog Output   Unit    V/f   Loop    Loop
                     Display                                                                                                               Vector   Register
         ber                                                                                                             Vector Vector
                                                                                                                                            (PM)
                ASR output
                             Monitors the output from the
                without filter                                  10 V: Rated secondary cur-
                             speed control loop (i.e., the pri-
       U1-44                                                    rent of motor                              0.01%    -      -      A          A       6BH
                             mary filter input value). 100%
                                                                (-10 V to 10 V)
             ASR Out w/o Fil is displayed for rated second-
                             ary current of the motor.
             Max Current
             during accelera-
                                    Monitors the maximum current           10 V: Rated current of motor
       U1-51 tion                                                                                          0.1 A   A      A       A          A       72H
                                    during acceleration.                   (0 V to 10 V)
                MaxCur-
                rent@Acc
             Max Current
             during decelera-
                              Monitors the maximum current                 10 V: Rated current of motor
       U1-52 tion                                                                                          0.1 A   A      A       A          A       73H
                              during deceleration.                         (0 V to 10 V)
             MaxCur-
5            rent@Dec
             Max Current
             during Top
                                    Monitors the maximum current           10 V: Rated current of motor
       U1-53 speed                                                                                         0.1 A   A      A       A          A       74H
                                    at top speed.                          (0 V to 10 V)
                MaxCur-
                retn@Run
             Max Current
             during leveling
                                    Monitors the maximum current           10 V: Rated current of motor
       U1-54 speed                                                                                         0.1 A   A      A       A          A       75H
                                    at Vl speed.                           (0 V to 10 V)
                Max Amp
                at Vl sped
                Number of trav-     Monitors the lift operation
                els                 counter.
       U1-55                                                               (Cannot be output.)               -     A      A       A          A       76H
                                    Using parameter O2-15 the
                No of travels       counter can be cleared.
             AI-14B channel         Monitors the input level of ana-
       U1-56 1 input level          log input 1 on a AI-14B option 10 V: 100%
         *1                                                                                                0.1%    A      A       A          A       77H
                AI-14 Ch1           board. A value of 100% is equal (-10 to 10 V)
                InpLvl              to 10V input.
             Car acceleration
                              Shows the elevator car acceler-              10V: 9.8 m/s²                   0.01
       U1-57 rate                                                                                                  A      A       A          A       57H
                              ation rate value.                            (-10V to 10 V)                  m/s²
             Cage accel
             q-axis motor
             current refer-         Monitors the q-axis current ref- 10 V: Motor rated current
       U1-74 ence                                                                                          0.1%    A      A       A          A       7C6H
                                    erence.                          (-10 to 10 V)
                Iq Reference
             d-axis motor
             current refer-         Monitors the d-axis current ref- 10 V: Motor rated current
       U1-75 ence                                                                                          0.1%    A      A       A          A       7C7H
                                    erence.                          (-10 to 10 V)
                Id Reference
5-62
   Fault Trace: U2
                                                                                                                  Control Methods
Param-          Name
                                                                         Output Signal Level Dur-                                   Closed   MEMO-
 eter                                                                                               Min.          Open Closed
                                             Description                ing Multi-Function Analog                                    Loop     BUS
 Num-                                                                                               Unit    V/f   Loop   Loop
                Display                                                           Output                                            Vector   Register
  ber                                                                                                             Vector Vector
                                                                                                                                     (PM)
         Current fault
U2-01                            The content of the current fault.                                    -     A      A       A          A       80H
         Current Fault
         Last fault
U2-02                            The error content of the last fault.                                 -     A      A       A          A       81H
         Last Fault
      Reference fre-
                                 The reference frequency when                                       0.01
U2-03 quency at fault                                                                                       A      A       A          A       82H
                                 the last fault occurred.                                            Hz
         Frequency Ref
      Output frequency at
                          The output frequency when the                                             0.01
U2-04 fault                                                                                                 A      A       A          A       83H
                          last fault occurred.                                                       Hz
      Output Freq
         Output current at
         fault                   The output current when the last
U2-05                                                                                               0.1 A   A      A       A          A       84H
         Output                  fault occurred.
         Current
         Motor speed at fault The motor speed when the last                                         0.01
U2-06                                                                                                        -     A       A          A       85H
         Motor Speed          fault occurred.                                                        Hz
      Cumulative opera-
                                 The operating time when the last                                     1
U2-14 tion time at fault                                                (Cannot be output.)                 A      A       A          A       8DH
                                 fault occurred.                                                     hr.
         Elapsed Time
                               The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
          IMPORTANT
                                                                                                                                                        5-63
         Fault History: U3
       Param-                Name                                                                                                         MEMO-
                                                                                                Output Signal Level During
        eter                                                    Description                                                   Min. Unit    BUS
                                                                                               Multi-Function Analog Output
       Number             Display                                                                                                         Register
                Last fault
       U3-01                                The error content of 1st last fault.                                                  -        90H
                Last Fault
                Cumulative operation
                time at fault               The total operating time when the 1st previous                                        1
       U3-05                                                                                                                               94H
                                            fault occurred.                                                                      hr.
                Elapsed Time 1
5
                Accumulated time of
                third fault                 The total operating time when the 3rd previous                                        1
       U3-07                                                                                                                               96H
                                            fault occurred.                                                                      hr.
                Elapsed Time 3
                Accumulated time of
                fourth/oldest fault         The total operating time when the 4th previous                                        1
       U3-08                                                                                                                               97H
                                            fault occurred.                                                                      hr.
                Elapsed Time 4
                                    The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
                IMPORTANT
5-64
 Settings which change with the Control Mode (A1-02)
                                                                                                               Factory Setting
Parameter                                                                                                                Closed       Closed
                                    Name                            Setting Range     Unit                 Open Loop
 Number                                                                                      V/f Control                Loop Vec-   Loop Vec-
                                                                                                             Vector
                                                                                              A1-02=0                    tor A1-     tor (PM)
                                                                                                            A1-02=2
                                                                                                                          02=3       A1-02=5
  C3-01       Slip compensation gain                                  0.0 to 2.5       -        1.0           1.0         1.0          1.0
  C4-02       Torque compensation delay time                         0 to 10000       msec      200           20            -           -
  C5-01       ASR P gain 1                                          1.00 to 300.00     -          -            -         40.00       12.00
  C5-02       ASR Integral time 1                                  0.000 to 10.000    sec         -            -         0.500       0.300
  C5-03       ASR P gain 2                                          1.00 to 300.00     -          -            -         20.00        6.00
  C5-07       ASR gain switching frequency                           0.0to 120.0      i           -            -         0.0 Hz      2.0 %
  C5-09       ASR P gain 3                                          1.00 to 300.00     -          -            -         40.00       12.00
  C5-10       ASR Integral time 3                                  0.000 to 10.000    sec         -            -         0.500       0.300
                                                                   0 to 120.00 Hz     Hz       50.00         50.00       50.00          -
  E1-04       Max. Frequency
                                                                   20 to 7200 rpm     rpm         -            -           -          150
                                                                   0 to 120.00 Hz     Hz       50.00         50.00       50.00          -
  E1-06       Base Frequency
                                                                   20 to 7200 rpm     rpm         -            -           -          150
  E1-08                                                 *1           0.0 to 510.0      V        37.4          25.0         -            -
              Mid. output frequency voltage (VB)
                                                                   0 to 120.00 Hz     Hz        0.5           0.3         0.0           -
  E1-09       Min. output frequency (FMIN)
                                                                   20 to 7200 rpm     rpm         -            -           -           0
  E1-10
  E1-13
              Min. output frequency voltage (VMIN)
              Base Frequency
                                                                     0.0 to 510.0
                                                                     0.0 to 510.0
                                                                                       V
                                                                                       V
                                                                                                19.4
                                                                                                0.0
                                                                                                              5.0
                                                                                                              0.0          -
                                                                                                                            -           -
                                                                                                                                      400         5
  E2-05       Mid. output frequency (FB)                           0 to 120.00 Hz     Hz        2.5           3.0          -            -
  E3-06       Mid. output frequency voltage (VB)*1                   0.0 to 510.0      V        30.0          26.4         -            -
  E3-07       Min. output frequency (FMIN)                           0.0 to 120.0     Hz        1.2           0.5         0.0           -
  E3-08                                                      *1      0.0 to 510.0      V        18.0          4.8          -            -
              Min. output frequency voltage (VMIN)
                                                                     0 to 60000        -          -            -          1024          -
  F1-01       PG constant
                                                                  512, 1024*2, 2048    -          -            -           -          2048
                                                                                                  -            -           0            -
  F1-05       PG rotation direction                                     0 or 1         -
                                                                                                  -            -           -           1
                                                                       1 to 56                   2             2           2            -
  F1-04       AO-12 Channel 1 Signal selection                                         -
                                                                       1 to 75                    -            -           -           5
                                                                        0 to 3                   1             1           1            -
  L1-01       Motor protection selection                                               -
                                                                        0 or 5                    -            -           -           5
                                                                     0 to 120.00      Hz        0.0           0.0         0.0           -
 L4-01/03     Speed agreement detection level
                                                                     0.0 to 100.0      %          -            -           -           0.0
                                                                     0.0 to 20.0      Hz        2.0           2.0         2.0           -
 L4-02/04     Speed agreement detection width
                                                                     0.0 to 40.o       %          -            -           -           4.0
                                                                        0 to 2         -         2             2           2            -
  L8-09       Output open phase detection selection
                                                                        0 or 1         -          -            -           -           0
  n5-01       Feed forward control selection                            0 or 1         -          -            -           1           0
  o1-03       Frequency monitor/reference display                    0 to 39999        -         0             0           0           1
  o1-04       V/f pattern frequency parameter unit                      0 or 1         -          -            -           0           1
  S1-01       Zero speed level                                      0.00 to 10.00     Hz        1.2           0.5         0.1          0.5
                                                                                                                                                5-65
          200 V and 400 V Class Inverters of 3.7 to 45 kW*
       Para                                                                                                                                     Open    Closed
       meter                                                                                                                                                     Closed
               Unit                                                         Factory Setting                                                     Loop     Loop
       Num-                                                                                                                                                       Loop
                                                                                                                                                Vec-     Vec-
                                                                                                                                                                  Vec-
        ber                                                                                                                                      tor      tor
                                                                                                                                                                   tor
        E1-                                                                                                                                     Con-     Con-
                                                                                                                                                                  (PM)
                -       0      1       2       3       4       5      6        7      8        9      A      B       C      D      E      F      trol     trol
        03
               Hz     50.0    60.0    60.0    72.0   50.0    50.0    60.0     60.0   50.0     50.0   60.0   60.0    90.0   120.0 180.0   50.0   50.0     50.0      -
       E1-04
               rpm      -       -       -      -       -       -       -       -      -        -      -       -      -       -     -      -       -       -       150
       E1-05
        *1      V     200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 190.0                           190.0   190.0    200.0
               Hz     50.0    60.0    50.0    60.0   50.0    50.0    60.0     60.0   50.0     50.0   60.0   60.0    60.0   60.0   60.0   50.0   50.0     50.0      -
       E1-06
               rpm      -       -       -      -       -       -       -       -      -        -      -       -      -       -     -      -       -       -       150
       E1-07   Hz      2.5     3.0    3.0     3.0    25.0    25.0    30.0     30.0   2.5      2.5    3.0    3.0     3.0     3.0   3.0    3.0     3.0      -        -
        *1
               rpm      -       -       -      -       -       -       -       -      -        -      -       -      -       -     -      -       -       -        -
       E1-08
        *1      V     14.0    14.0    14.0    14.0   35.0    50.0    35.0     50.0   18.0     23.0   18.0   23.0    14.0   14.0   14.0   18.6   12.5      -        -
               Hz      1.3     1.5    1.5     1.5     1.3     1.3     1.5     1.5    1.3      1.3    1.5    1.5     1.5     1.5   1.5    0.5     0.3     0.0       -
       E1-09
               rpm      -       -       -      -       -       -       -       -      -        -      -       -      -       -     -      -       -       -        0
       E1-10
        *1      V      7.0     7.0    7.0     7.0     6.0     7.0     6.0     7.0    9.0      11.0   9.0    13.0    7.0     7.0   7.0    9.7     2.5      -        -
E1-13 V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 200.0
*1. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
5      Para
       meter
       Num-
             Unit                                                           Factory Setting
                                                                                                                                                Open
                                                                                                                                                Loop
                                                                                                                                                Vec-
                                                                                                                                                        Closed
                                                                                                                                                         Loop
                                                                                                                                                         Vec-
                                                                                                                                                                 Closed
                                                                                                                                                                  Loop
                                                                                                                                                                  Vec-
        ber                                                                                                                                      tor      tor
                                                                                                                                                                   tor
        E1-                                                                                                                                     Con-     Con-
                                                                                                                                                                  (PM)
              -        0       1       2       3       4      5       6        7      8        9      A      B       C      D      E      F      trol     trol
        03
               Hz     50.0    60.0   60.0    72.0    50.0    50.0    60.0     60.0   50.0     50.0   60.0   60.0    90.0   120.0 180.0   50.0   50.0     50.0      -
       E1-04
               rpm      -      -       -       -       -       -      -        -      -        -      -       -      -       -     -      -       -       -       150
       E1-05
        *1      V     200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 190.0                           190.0   190.0    200.0
               Hz     50.0    60.0   50.0    60.0    50.0    50.0    60.0     60.0   50.0     50.0   60.0   60.0    60.0   60.0   60.0   50.0   50.0     50.0      -
       E1-06
               rpm      -      -       -       -       -       -      -        -      -        -      -       -      -       -     -      -       -       -       150
       E1-07   Hz     2.5     3.0     3.0     3.0    25.0    25.0    30.0     30.0   2.5      2.5    3.0    3.0     3.0     3.0   3.0    3.0     3.0      -        -
        *1
               rpm      -      -       -       -       -       -      -        -      -        -      -       -      -       -     -      -       -       -        -
       E1-08
        *1      V     12.0    12.0   12.0    12.0    35.0    50.0    35.0     50.0   15.0     20.0   15.0   20.0    12.0   12.0   12.0   16.0   12.5      -        -
               Hz     1.3     1.5     1.5     1.5     1.3     1.3    1.5      1.5    1.3      1.3    1.5    1.5     1.5     1.5   1.5    0.5     0.3     0.0       -
       E1-09
               rpm      -      -       -       -       -       -      -        -      -        -      -       -      -       -     -      -       -       -        0
       E1-10
        *1      V     6.0     6.0     6.0     6.0     5.0     6.0    5.0      6.0    7.0      9.0    7.0    11.0    6.0     6.0   6.0    8.3     2.5      -        -
E1-13 V 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 200.0
*1. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
5-66
 Factory Settings Changing with Inverter Capacity (o2-04)
                                                                                                                                  5-67
       Parameter Number                 Name                   Unit           Factory Setting
              -                    Inverter Capacity           kW      30      37        45      55
            o2-04                    kVA selection              -      B       C         D       E
            C6-02         Carrier frequency                     -      2       2         2       2
            E2-01
                          Motor rated current                   A     105.0   131.0    160.0    190.0
           (E4-01)
            E2-02
                          Motor rated slip                     Hz     1.80    1.33      1.60    1.43
           (E4-02)
            E2-03
                          Motor no-load current                 A     21.9    38.2      44.0    45.6
           (E4-03)
            E2-05
                          Motor line-to-line resistance        W      0.064   0.039    0.030    0.022
           (E4-05)
            E2-06
                          Motor leak inductance                %      20.8    18.8      20.2    20.5
           (E4-06)
                          Motor iron loss for torque compen-
            E2-10                                              W      699     823       852     960
                          sation
            E5-02         PM motor rated power                 kW     30.00   37.00    45.00    55.00
            E5-03         PM motor rated current                A     103.5   133.1    149.4    181.6
            E5-04         PM number of poles                    -      4       4         4       4
            E5-05         PM motor line-to-line resistance     Ohm    0.041   0.027    0.022    0.016
            E5-06         PM d-axis inductance                 mH     0.129   0.091    0.090    0.072
            E5-07         PM q-axis inductance                 mH     0.200   0.141    0.139    0.111
5           E5-09
            L8-02
                          PM voltage constant
                          Overheat pre-alarm level
                                                               mV
                                                               °C
                                                                      2.604
                                                                       70
                                                                              2.451
                                                                               85
                                                                                       2.760
                                                                                         90
                                                                                                2.771
                                                                                                 80
            L8-06         Input open-phase protection level    %       20      18        20      17
       n5-02 (A1-02=3)    Motor acceleration time              sec    0.323   0.320    0.387    0.317
       n5-02 (A1-02=5)    Motor acceleration time              sec    0.126   0.124    0.188    0.186
5-68
400 V Class Inverters
                                                                                                                     5-69
       Parameter Number                 Name                   Unit                   Factory Setting
5           E5-09
            L8-02
                          PM voltage constant
                          Overheat pre-alarm level
                                                               mV
                                                               °C
                                                                      5.137
                                                                       80
                                                                              5.223
                                                                               80
                                                                                      5.208
                                                                                       72
                                                                                               4.902
                                                                                                 80
                                                                                                        5.520
                                                                                                         82
                                                                                                                5.544
                                                                                                                 73
            L8-06         Input open-phase protection level    %       17      20      20        20      20      20
       n5-02 (A1-02=3)    Motor acceleration time              sec    0.317   0.355   0.323    0.320    0.387   0.317
       n5-02 (A1-02=5)    Motor acceleration time              sec    0.098   0.096   0.126    0.124    0.188   0.186
5-70
                                                                      6
Parameter Settings by
            Function
     Carrier Frequency Derating and Current Limitation ............6-2
     Control / Brake Sequence...................................................6-3
     Acceleration and Deceleration Characteristics .................6-21
     Adjusting Analog Input Signals .........................................6-26
     Speed Detection and Speed Limitation.............................6-27
     Improving the Operation Performance..............................6-30
     Protective Functions .........................................................6-41
     Inverter Protection.............................................................6-48
     Input Terminal Functions ..................................................6-52
     Output Terminal Functions................................................6-58
     Motor and V/f Pattern Setup .............................................6-62
     Digital Operator/LED Monitor Functions ...........................6-67
     PG Option Cards...............................................................6-75
     Rescue System.................................................................6-80
     Automatic Fault Reset.......................................................6-84
     Memobus Communications ..............................................6-86
      Carrier Frequency Derating and
      Current Limitation
        Related Parameters
                                                                                                 Change                 Control Methods
            Parameter                                                               Factory       during                Open Closed       Closed
                                                 Name                                                                                      Loop
               No.                                                                  Setting      Opera-          V/f    Loop    Loop      Vector
                                                                                                   tion                 Vector Vector      (PM)
              C6-02                  Carrier frequency selection                        3            No           Q       Q       Q         Q
6         If the carrier frequency is increased the rated current is decreased and vice versa (refer to page 9-6, Carrier
          Frequency Derating). The overload capability is always 150% of the derated inverter current for 30 sec. If this
          over load limit is exceeded the inverter trips with an inverter overload fault (OL2).
                         • If the torque at low frequencies is too low, check whether the current runs into the limitation explained
                           above. If so, check the motor data settings (E2-) and the V/f pattern (E1-).
                         • If the current still runs into the limit it might be necessary to install a one size bigger inverter.
          IMPORTANT      • For selecting an inverter please consider the low frequency current limit as described above and select
                           an inverter with an appropriate current margin.
6-2
Control / Brake Sequence
 Travel stop
   The inverter can be stopped as follows:
    • The direction command (UP or Down) signal is removed.
    • The speed reference selection signal is removed if digital inputs are used for speed reference selection.
    • If d1-18 is set to 3 and all speed inputs are removed
Related Parameters
   Parameter                                                  Factory
                                                                         Change
                                                                                          Control Methods
                                                                                          Open       Closed   Closed
                                                                                                                       6
                                   Name                                  during                                Loop
      No.                                                     Setting               V/f   Loop        Loop
                                                                        Operation                             Vector
                                                                                          Vector     Vector    (PM)
     b1-02              RUN command source selection            1          No       Q       Q          Q        Q
                                                                                                                       6-3
       Speed Reference Source Selection
        Related Parameters
                                                                              Change            Control Methods
          Parameter                                                 Factory   during                              Closed
                                                                                                Open     Closed
                                          Name                                                                     Loop
             No.                                                    Setting   Opera-     V/f     Loop     Loop
                                                                                                                  Vector
                                                                               tion             Vector   Vector    (PM)
            b1-01           Frequency reference source selection       0        No       Q        Q        Q        Q
6-4
 Speed Selection Sequence Using Digital Inputs
    If the digital inputs are used for speed selection, the speed selection method and the speed priority depends on
    the setting of parameter d1-18.
                                                                                                      Control Methods
                                                                                Change                                  Closed
    Parameter                                                       Factory                           Open     Closed
                                     Name                                       during                                   Loop
       No.                                                          Setting                     V/f   Loop      Loop
                                                                               Operation                                Vector
                                                                                                      Vector   Vector    (PM)
      d1-18                 Speed Priority Selection                    1           No          Q       Q        Q        Q
   If d1-18 = 0
    8 preset speed steps (defined in the parameters d1-01 to d1-08) can be selected using 3 binary coded digital
    inputs. The Up/Down command starts the inverter. It stops when the Up/Down command is removed.
   If d1-18 = 3
    7 preset speed steps (defined in the parameters d1-02 to d1-08) can be selected using 3 binary coded digital
    inputs. The Up/Down command starts the inverter. It is stopped when the Up/Down command is removed or
    when no speed is selected (all D/Is off).
   Related Parameters
                                                                                                      Control Methods
                                                                                Change                                  Closed
    Parameter                                                       Factory                           Open     Closed
                                     Name                                       during                                   Loop
       No.                                                          Setting                     V/f   Loop      Loop
                                                                               Operation                                Vector
     d1-01 to
      d1-08
                     Multi-Step speed 1 to 8 reference value
                                                                     0.00 Hz
                                                                                    Yes
                                                                                                A
                                                                                                      Vector
                                                                                                        A
                                                                                                               Vector
                                                                                                                 A
                                                                                                                         (PM)
                                                                                                                          -      6
                                                                     0.00%                       -      -        -        A
                       Parameter
          Terminal                      Set Value                                     Details
                        Number
                S4       H1-02               3         Multi-step speed command 1
                S5       H1-03               4         Multi-step speed command 2
                S6       H1-04               5         Multi-step speed command 3
                                                                                                                                 6-5
       Speed Selection Table
        The following table shows the combinations of the digital input and the according speed.
        If b1-02 is set to “1”, speed 1 is input as analog reference at terminal A1 or Channel CH1 of an analog input
        option card AI-14B if it is installed.
        If an AI-14B option card is used and the functions for channel CH2 and CH3 are set to “Auxiliary Frequency
        2” (H3-05/09=2) and “Auxiliary Frequency 3” (H3-05/09=3).
Related Parameters
6       Parameter
           No.
                                         Name
                                                                         Factory
                                                                         Setting
                                                                                    Change
                                                                                    during
                                                                                                           Control Methods
                                                                                                           Open      Closed     Closed
                                                                                                                                 Loop
                                                                                                   V/f      Loop      Loop
                                                                                   Operation                                    Vector
                                                                                                           Vector    Vector      (PM)
          S3-04           Nominal/Leveling speed detection level         0.00 Hz       No           A         A        A          A
        If the
         • reference speed >= S3-04 the selected speed is regarded as nominal speed
         • reference speed < S3-04 the selected speed is regarded as leveling speed
6-6
Separate Speed Selection Inputs, High Speed Has Priority (d1-18=1)
  If d1-18 is set to 1, 6 different speeds can be set and selected using four digital inputs.
 Related Parameters
                                                                                           Control Methods
                                                                    Change                                                   Digital Input
  Parameter                                         Factory                                Open     Closed        Closed
                             Name                                   during                                                  Setting (H1-01
     No.                                            Setting                       V/f       Loop     Loop       Loop Vec-
                                                                   Operation                                                  to H1-05)
                                                                                           Vector   Vector       tor (PM)
                                                    50.00 Hz                       Q          Q             Q       -
    d1-09                Nominal Speed                                Yes                                                           80
                                                    100.00%                        -          -             -      Q
                                                     0.00 Hz                       A          A             A       -
    d1-10            Intermediate Speed 1                             Yes                                                           81
                                                     0.00%                         -          -             -      A
                                                     0.00 Hz                       A          A             A       -
    d1-11            Intermediate Speed 2                             Yes                                                           -*1
                                                     0.00%                         -          -             -      A
                                                     0.00 Hz                       A          A             A       -
    d1-12            Intermediate Speed 3                             Yes                                                           -*1
                                                     0.00%                         -          -             -      A
                                                     0.00 Hz                       A          A             A       -
    d1-13             Releveling Speed                                Yes                                                           82
                                                     0.00%                         -          -             -      A
                                                     4.00 Hz                       Q          Q             Q       -
    d1-17                Leveling Speed                               Yes                                                           83
                                                     8.00%                         -          -             -      Q
                 Frequency reference loss
                 detection when d1-18 = 1 and
    S3-09        H1-K83.                              1             No           A          A             A      A                   -
                 0: Disabled
                 1: Enabled
 Higher Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
  If d1-18 is set to 1 and one multi-function digital input is set to leveling speed selection (H1-=83), the
  inverter decelerates to the leveling speed (d1-17) when the selected speed signal is removed. Inspection Speed
  can not be selected as travel speed. The higher speed has priority over the leveling speed, i.e. as long as a
  higher speed is selected, the leveling signal is disregarded (see the fig. below)
  The inverter stops when the leveling signal or the Up/Down signal is removed.
                                DC Injection/                                                                    DC Injection/
                                 zero servo                                                                       zero servo
                 Speed
        Hardware BB
            Up/Down
      Leveling speed                                                                                                    No effect
     Selected speed                                                                                                     Input is set
                                                                                                                                             6-7
        The following speed selection table shows the different speeds and the according digital inputs.
                                                             Nominal Intermed. Intermed. Intermed. Relevel.     Leveling
                       Terminal function                      Speed   Speed 1 Speed 2 Speed 3       Speed        Speed           0Hz
                                                              d1-09    d1-10     d1-11     d1-12    d1-13        d1-17
         Nominal Speed command (H1-=80)                       1          0           1         0         0        0             0
         Intermediate speed command (H1-=81)                  0          1           1         1         0        0             0
         Releveling speed command (H1-=82)                    0          0           1         1         1        0             0
         Leveling speed command (H1-=83)                     X           X          X          X         X        1             0
       Higher Speed Priority is Selected and a Leveling Speed Input is Not Selected (H1-K83)
        When the leveling speed command is not selected for any digital input, the inverter decelerates to the leveling
        speed (d1-17) when the selected speed signal is removed. Inspection Speed can not be selected as travel speed
        To select the leveling speed as travel speed the frequency reference loss detection must be disabled (S3-09=0).
        The inverter stops when the direction signal Up/Down is removed.
        When no speed selection input is set the leveling speed is taken as the speed reference.
                                          DC injection/                                                        DC injection/
                                           zero servo                                                           zero servo
                         Speed
                  Hardware BB
                      Up/Down
                Selected speed
        The following speed selection table shows the different speeds and the according digital inputs.
                                                                    Nominal    Intermed. Intermed. Intermed.   Relevel.        Leveling
6 Terminal function
The inverter stops when the direction signal (UP or DOWN signal) is removed.
                               With this configuration the drive stops with a “FRL” (frequency reference loss fault) when no speed
                               reference input is selected during the start.
          IMPORTANT            To disable the FRL detection, set parameter S3-09 to “0”.
       Leveling Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
        If d1-18 is set to “2” and one multi-function digital input is set to leveling speed (H1-=83) the inverter
        decelerates to the leveling speed (d1-17) when the leveling speed selection input is activated. The leveling sig-
        nal has priority over the selected speed, i.e. the selected speed is disregarded. The selected travel speed must
        be different from inspection speed.
6-8
 The inverter stops when the leveling speed command is removed.
                                      DC Injection/                                                                DC Injection/
                                       zero servo                                                                   zero servo
                      Speed
              Hardware BB
                   Up/Down
            Leveling speed                                                                                Leveling speed has priority
Selected speed
 The following speed selection table shows the different speeds and the according digital inputs.
                                                       Nominal Intermed. Intermed. Intermed. Relevel.               Leveling
                Terminal function                       Speed   Speed 1 Speed 2 Speed 3       Speed                  Speed              0Hz
                                                        d1-09    d1-10     d1-11     d1-12    d1-13                  d1-17
 Nominal Speed command (H1-=80)                           1         0           1           0           0              0                  0
 Intermediate speed command (H1-=81)                      0         1           1           1           0              0                  0
 Releveling speed command (H1-=82)                        0         0           1           1           1              0                  0
 Leveling speed command (H1-=83)                         X          X           X           X           X              1                  0
Leveling Speed Priority is Selected and a Nominal Speed Input is Not Selected (H1-K80))
 If d1-18 is set to “2” and no digital input is set to nominal speed selection, the speed reference with speed
 selection input set is nominal speed (d1-09). When the leveling speed signal is set, the inverter starts to decel-
 erate to the leveling speed. The leveling speed signal has priority over all other speed signals, i.e. the interme-
 diate speed 1 and 2 and the releveling signals are disregarded when leveling speed is selected.
 The inverter can be stopped by removing the leveling speed signal or the Up/Down command.
 CAUTION: This sequence can be risky if e.g. the speed selection doesn’t work for any reason (broken wire
 etc.).
                                                                                                                                                6
                                    DC Injection/                                                                  DC Injection/
                                     zero servo                                                                     zero servo
                     Speed
             Hardware BB
                  Up/Down
           Leveling speed
 The following speed selection table shows the different speeds and the according digital inputs.
                                                            Nominal   Intermed.       Intermed.   Intermed.    Relevel.         Leveling
                   Terminal function                         Speed     Speed 1         Speed 2     Speed 3      Speed            Speed
                                                             d1-09      d1-10           d1-11       d1-12       d1-13            d1-17
   Nominal Speed command (H1-=80)                             N/A       N/A           N/A         N/A           N/A              N/A
   Intermediate speed command (H1-=81)                         0         1                         1              0                   X
   Releveling speed command (H1-=82)                           0         0                         1              1                   X
   Leveling speed command (H1-=83)                             0         0                         0              0                   1
                                                                                                                                                6-9
        Emergency Stop
          If a digital input terminal (H1-) is set to 15 or 17 (emergency stop), this input can be used to fast stop the
          inverter in the case of emergency. In this case the emergency stop deceleration time set in C1-09 is used. If the
          emergency stop is input with an NO contact, set the multi-function input terminal (H1-) to 15, if the emer-
          gency stop is input with an NC contact, set the multi-function input terminal (H1-) to 17.
          After the emergency stop command has been input, the operation cannot be restarted until the Inverter has
          stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
        Related parameters
                                                                                                 Control Methods
                                                                                Change                              Closed
          Parameter                                                  Factory                      Open     Closed
                                             Name                               during                               Loop
             No.                                                     Setting               V/f    Loop      Loop
                                                                               Operation                            Vector
                                                                                                  Vector   Vector    (PM)
            C1-09                      Emergency stop time            1.50 s      No       A        A        A        A
6-10
 Inspection RUN
   The inspection run can be activated in two ways:
   1. A digital input can be used if parameter d1-18 = 1 or 2. Therefore a inspection speed must be set and any of
      the digital inputs must be set to “Inspection Run Selection” (H1-=84) (see below).
   2. A speed reference comparison value (parameter S3-19) decides if inspection run is activated or not. This
      function work only if parameter d1-18 = 0 or 3 and if the inspection speed command is not assigned to any
      digital input (H1-K84).
 Related parameters
                                                                                                Control Methods
                                                                               Change                             Closed
   Parameter                                                       Factory                      Open     Closed
                                         Name                                  during                              Loop
      No.                                                          Setting                V/f    Loop     Loop
                                                                              Operation                           Vector
                                                                                                Vector   Vector    (PM)
                                                                   25.00 Hz               A       A        A        -
      d1-14                         Inspection Speed                             No
                                                                   50.00%                  -       -       -        A
     S3-03                    Inspection Deceleration time         0.0 sec       No       A       A        A        A
     S3-19                Inspection speed detection upper level   0.00 Hz       No       A       A        A        A
                                                                                                                           6-11
        The falling edge of the Inspection Speed command or UP/DOWN commands triggers the contactor open com-
        mand, the motor brake close command and the base block.
                                     Inspection RUN                                                             Inspection RUN
                            (Stop by Up/Down signal removal)                                           (Stop by Up/Down signal removal)
                                     DC Injection/                                                               DC Injection/
                    Speed             zero servo                                                 Speed            zero servo
Hardware BB Hardware BB
                                  DC Injection/                                                           DC Injection/
                                   zero servo                                                              zero servo
                 Speed                                                                       Speed
                                                                                       Hardware BB
6
            Hardware BB
           Up/Down (D/I)                                                               Up/Down (D/I)
6-12
 Brake Sequence
    The L7 supports two types of brake sequences, one with torque compensation at start using an analog input
    value and one without torque compensation at start.
 Related Parameters
                                                                                                                  Control Method
                                                                                 Change
  Parameter                                                       Factory                                         Open     Closed  Closed
                                   Name                                           during
     No.                                                          setting                           V/f           Loop      Loop Loop Vec-
                                                                                operation
                                                                                                                  Vector   Vector tor (PM)
    H3-15      Terminal A1 function selection                         0             No               -              -            A           A
                                                                                                     A              A            A           A
    S1-01      Zero speed level                                      i              No
                                                                                                   1.2 Hz         0.5 Hz       0.1 Hz      0.5 Hz
    S1-02      DC injection braking current at start                50%             No               A              A            -           -
    S1-03      DC injection braking current at sop                  50%             No               A              A            -           -
    S1-04      DC injection braking/Zero speed time at start       0.40 sec         No               A              A            A           A
    S1-05      DC injection braking/Zero speed time at stop        0.60 sec         No               A              A            A           A
    S1-06      Brake open delay time                               0.20 sec         No               A              A            A           A
    S1-07      Brake close delay time                              0.10 sec         No               A              A            A           A
    S1-16      Run delay time                                      0.10 sec         No               A              A            A           A
    S1-17      DC injection current gain at regeneration            100%            No               -              A            -           -
    S1-18      DC injection current gain at motoring                20%             No               -              A            -           -
    S1-19      Output contactor open delay time                    0.10 sec         No               A              A            A           A
    S1-20      Zero-servo gain start                                  5             No               -              -            A           A
    S1-21      Zero-servo completion width                           10             No               -              -            A           A
               Starting torque compensation increase time/
    S1-22                                                          500 ms           No               -              -            A           A
    S1-23
               starting torque fade-out time
               Torque compensation gain in Down direction            1.0            No               -              -            A           A       6
    S1-24      Torque compensation bias in Up direction             0.0%            No               -              -            A           A
    S1-25      Torque compensation bias in Down direction           0.0%            No               -              -            A           A
    S1-29      Torque fade out speed level                         0.0 Hz           No               -              -            A           A
    S1-30      Torque fade out compensation time                  1000 msec         No               -              -            A           A
    S1-31      Torque limit fade out time at stop                  0 msec           No               -              -            -           A
    S1-32      Zero servo gain stop                                   5             No               -              -            A           A
    S1-33      Zero servo gain 2                                    0.00            No               -              -            -           A
    S1-34      SE4 Detection Time                                 0.50 sec          No               A              A            A           A
                                                                                                                                                    6-13
                                                                                                                            Control Methods
                                                                                                                            Open Closed Closed
        Set Value                                                          Function                                                       Loop
                                                                                                                      V/f    Loop   Loop
                                                                                                                                          Vector
                                                                                                                            Vector Vector  (PM)
            40        Brake release command                                                                          Yes        Yes              Yes          Yes
            41        Output contactor close command                                                                 Yes        Yes              Yes          Yes
                                                              S1-04                                                                         S1-05
                                         S1-16
                                                                                                                                                                S1-19
                                                            Zero servo/                                                                   Zero servo/
                                                            DC Injection                                                                  DC inhection
                                                              at start                                    Leveling Speed                    at stop
                             Speed
                                                       Brake open
                                                       Delay time
                                                                                                                            Brake close
                                                                                                                             delay time
                                                         S1-06
                                                                                                                               S1-07
                              RUN
6
                                         t1               t2        t3                 t4                 t5           t6      t7                  t8       t9
Fig 6.2 Timing chart of Brake sequence without torque compensation at start
         The timing chart above is divided in time zones. The following table explains the sequence in each time zone.
           Timing                                                                           Description
                      The inverter gets the direction signal (UP/DOWN)
                      The inverter gets the hardware base block disable signal (Not BB condition).
                      The inverter receives the speed reference signal.
              t1
                      The inverter sets the contactor closed signal.
                      The inverter waits for the contactor confirmation signal. If no digital input is set to contactor confirmation
                      signal (H1-=86), the sequence is proceeded after exceeding the operation start delay time (S1-16).
                      When the RUN delay time (S1-16) has elapsed, DC injection (Open Loop) or zero servo operation (position lock in
              t2      Closed Loop) is started.
                      When the brake open delay time (S1-06) has elapsed, the inverter sets the brake open command.
                      The inverter keeps DC injection/zero speed operation until
              t3      * the time S1-04 – S1-06 has elapsed if S1-06 < S1-04 or
                      * the time S1-06 has elapsed if S1-06 > S1-04 (try to avoid this setting since the motor could be driven against the brake)
              t4      The speed is increased to the selected speed and is kept constant until the leveling speed is selected.
                      The speed is decreased to the leveling speed and is kept constant until the stop signal is given (depending on d1-18 either
              t5      by removing the direction signal, by removing the leveling signal or by deleting the speed inputs, see page 6-5, Speed
                      Selection Sequence Using Digital Inputs)
              t6      The speed is decreased to the zero speed level.
                      When the zero speed level is reached (S1-01), the DC injection (Open Loop) or zero servo operation (position lock in
              t7      Closed Loop) is applied for the time set in S1-05.
                      When the brake close delay time (S1-07) has elapsed, the brake open command is removed.
                      The inverter continues DC Injection (Open Loop) or zero speed operation (Closed Loop) until the time S1-06 – S1-07 has
              t8
                      elapsed. After that the inverter output is shut down and the hardware base block signal must be set.
              t9      After the output contactor open delay time (S1-19) has elapsed, the output contactor close signal is removed.
6-14
Brake Sequence with Torque Compensation at Start
 (Closed Loop Vector for IM and PM only)
% S1-24
       terminal A1                                                                                               UP
        H3-15=1                   H3-16
                                                                                                   +      +   direction
        torque
                                                                                                                                Torque compensation
     compensation                 H3-17
                                                                               S1-23                           Down
                                                 0           10V                          +
                                                                   Torque compensation gain     +             Direction
                                                                        during lowering
                                                                                           S1-25
                                                                                         Torque compensation
                                                                                          bias during lowering
  Brake Sequence
    The figure below shows the timing chart for this brake sequence.
                                                                                                                                                             Contactor open delay
                                                                              Selected Speed
                               RUN delay time
S1-19
                                                    S1-04                                                                                      S1-05
                                  S1-16
                  Speed
                                                                                                                                 Brake close
                                                                                                                                  delay time
                                                 Torque Comp
                                                 increase time
                                                     S1-22
RUN
t1 t2 t3 t4 t5 t6 t7 t8 t9
Fig 6.3 Timing chart of Brake sequence with torque compensation at start
                                                                                                                                                                                    6-15
         The timing chart above is divided in time zones. The following table explains the sequence in each time zone
          Timing                                                            Description
                   The inverter gets the direction signal (UP/DOWN)
                   The inverter gets the hardware base block signal disable signal (Not BB condition).
                   The inverter receives the speed reference signal.
            t1
                   The inverter sets the contactor close signal.
                   The inverter waits for the contactor confirmation signal. If no digital input is set to contactor confirmation
                   signal (H1-=86), the sequence is proceeded after exceeding the operation start delay time (S1-16).
                   The zero speed control operation is started.
                   The analog torque compensation input is latched and the torque compensation value is increased from zero to the latch
            t2
                   value using the time constant set in parameter S1-22.
                   After reaching the torque compensation level at start, the inverter sets the brake open command.
            t3     The brake opens and the zero speed operation (no position lock) is continued until S1-04 has elapsed.
                   The speed is increased to the selected speed and is kept constant until the leveling speed is selected.
            t4     During acceleration, when the torque fade out speed level S1-29 is reached, the torque compensation value is fade out to 0
                   using the time constant set in S1-22.
                   The speed is decreased to the leveling speed and is kept constant until the stop signal is given (depending on d1-18 either by
            t5     removing the direction signal, by removing the leveling signal or by deleting the speed inputs, see page 6-5, Speed Selection
                   Sequence Using Digital Inputs).
            t6     The speed is decreased to the zero speed level.
                   When the Zero Speed Level (S1-01) is reached, zero servo operation (position lock in Closed Loop) is applied for the time
            t7
                   set in S1-05. When the brake close delay time (S1-07) has elapsed, the brake open command is removed.
                   The inverter continues the zero speed operation until the time S1-06 – S1-07 has elapsed. After that the inverter output is
            t8
                   shut down and the hardware base block signal must be set.
            t9     After the output contactor open delay time (S1-19) has elapsed, the output contactor close signal is removed.
        Torque Limit Fade Out Function (Closed Loop Vector for PM)
         The torque limit fade out function smoothly reduced the torque limit to 0 after the zero speed time at stop has
6        elapsed. It thereby can help to prevent shocks or vibrations when the motor stops and the brake is closed. The
         used time constant can be set in parameter S1-31. The function can be used in Closed Loop Vector control for
         PM motors only (A1-02 = 6).
6-16
SE4 Detection
  A Brake Answer Fault (SE4 Fault) will be detected when one of the digital multi-function outputs is pro-
  grammed to Brake Release command (H2-xx = 40) and one of the digital multi-function inputs is programmed
  to Brake Release Check (H1-xx = 79) and both signals do not match for a longer time than set in S1-34 (SE4
  Detection Time).
  The Brake Asnwer Fault is not detected when:
   • the second motor is selected
   • S1-34 is set to 0.0 sec
   • none of the digital multi-function inputs is set to 79 (Brake Release Check)
                                                                                                               6-17
        Short Floor Operation
           The short floor operation is activated if the leveling speed command is set before the nominal speed was
           reached. The L7 inverter supports 2 methods of short floor operation:
            • Simple short floor operation which can be enabled by setting S3-01 = 1.
               When the leveling speed input is set and the reached speed is higher than 40% of the nominal speed, the
               inverter decelerates to 40% and keeps this speed for a calculated time before it decelerates to the leveling
               speed and finally stops. If the reached speed is below 40% of the nominal speed, the inverter accelerates to
               40% speed and keeps it for a calculated time before it decelerates to the leveling speed.
               If the leveling input is set during constant speed run and the speed reference is lower than 40% of the nom-
               inal speed, the speed is hold for a calculated time in order to minimize the leveling distance. If the speed
               reference is higher than 40% but lower than the nominal speed, the speed is decreased to t 40% first, is
               hold for a calculated time an then decreased to the leveling speed.
            • Advanced short floor operation which can be enabled by setting S3-01 = 2.
               If the leveling speed command is set the inverter calculates the optimal speed using the speed reference,
               two gain factors (S3-21/22) and a time constant (S3-20). If the leveling input is set before the optimal
               speed has been reached, the inverter accelerates to the optimal speed and keeps it for the time constant S3-
               20. If the leveling input is set when the optimal speed was exceeded, the inverter keeps the reached speed
               for a certain time before it decelerates to the leveling speed.
           The table below shows the behavior of the short floor functions under different conditions.
                Condition                      Standard Short Floor                                    Advanced Short Floor
                                 Leveling Signal before 40% of the nominal speed            Leveling speed signal before VOpt is reached
                                                 has been reached
                                                                                                                                     VNominal
                                                                      vNominal
                                                                                                         S3-20
                                                                                                                                     VOpt
                                                                      40% x
                                                                      VNominal
6                                fout
                                                                      VLeveling
                                                                                     fout
                                                                                                                                      VLeveling
                                                                                     Leveling
                                 Leveling                                            command
                                 command
          During Acceleration
                                Leveling Signal after 40% of the nominal speed has     Leveling speed signal after VOpt has been reached
                                                   been reached.
                                                                                                                                      VNominal
                                                                      vNominal
                                                                                                                                      VOpt
                                                                      40% x
                                                                      VNominal                                           Optimal speed profile
                                                                                                                         (S2-20 calculated)
                                                                      VLeveling
                                                                                                                                      VLeveling
                                 fout
                                                                                     fout
                                Leveling                                             Leveling
                                command                                              command
6-18
       Condition                                Standard Short Floor                                       Advanced Short Floor
                           Leveling command during run with constant speed
                           higher than 40%
                                                                        vNominal
                                                                        40% x
                                                                        VNominal
                                                                        VLeveling
                             fout
                            Leveling
                            command
                                                                       40% x
                                                                       VNominal
                                                                       VLeveling
                            fout
                            Leveling
                            command
Related parameters
                                                                                                                      Control Methods
                                                                                                Change                                   Closed
  Parameter                                                                         Factory                            Open     Closed
                                              Name                                              during                                    Loop
     No.                                                                            Setting                  V/f        Loop     Loop
                                                                                               Operation                                 Vector
                                                                                                                       Vector   Vector
                                                                                                                                          (PM)
                                                                                    50.00 Hz                 Q           Q        Q        -
    d1-09
    d1-18
                                         Nominal Speed
                                                                                                  No         A
                                                                                                              -
                                                                                                                         A
                                                                                                                          -       -
                                                                                                                                  A
                                                                                                                                           Q
                                                                                                                                           A
                                                                                                                                                   6
    S3-01                              Short floor operation                           0          No         A           A        A        A
    S3-04               Nominal / Leveling Speed detection level                     0.0 Hz       No         A           A        A        A
    S3-05               Nominal speed for short floor calculation                    0.0Hz        No         A           A        A        A
    S3-20                     Minimum constant speed time                           0.0 sec.      No         A           A        A        A
    S3-21           Distance calculation acceleration time gain                     150.0%        No         A           A        A        A
    S3-22           Distance calculation deceleration time gain                     150.0%        No         A           A        A        A
                                                                                                                                                  6-19
       Setup the Acceleration and Deceleration Gain (S3-21, S3-22)
        These parameters are used for the optimal speed calculation to compensate the S-curves (S-curves are not con-
        sidered in the optimal speed calculation).
         • Increase the gains S3-21 and S3-22 if the leveling time is too short or the calculated optimal speed is too
           high.
         • Decreases the gains S3-21 and S3-22 if the leveling time is too short of the calculated optimal speed is too
           low.
                         1. S-Curves are not considered in the optimal speed calculation and have to be compensated by the
                            gains S3-21 and S3-22.
                         2. A too low gain setting can result in a too high optimal speed and too short leveling time. Very low
                            settings can lead to an overrun. Do not set the values lower than 100% (100% means, that the S-
          IMPORTANT
                            curve is not compensated.
                         3. If parameter d1-18 is set to 0 or 3 and the leveling speed input is released during short floor oper-
                            ation, the inverter accelerates or decelerates to the selected reference speed.
                         4. If the Dwell function (b6- parameters) is activated, the dwell function is performed during short
                            floor operation but it is not considered in the optimal speed calculation. The influence of the Dwell
                            function must be compensated using the gains S3-21 and S3-22.
                         5. The advanced short floor function does not work during rescue operation and inspection run.
                         6. If the speed reference is input using an analog input the advanced short floor function should not
                            be used.
                         7. If the advanced short floor function is used, the following parameter settings should be in given
                            range:
                            9.6 Hz O E1-04 O 100 Hz
                            4.8 Hz O d1-08 O 100Hz
                            0.1 sec. O C1- O 50 sec.
6-20
Acceleration and Deceleration Characteristics
  Related Parameters
                                                                                                                    Control Methods
                                                                                               Change
                                                                                                                                      Closed
    Parameter                                                                       Factory    during               Open Closed
                                                Name                                                                                   Loop
       No.                                                                          Setting    Opera-        V/f     Loop   Loop      Vector
                                                                                                tion                Vector Vector      (PM)
      C1-01          Acceleration time 1                                                          Yes         Q       Q       Q         Q
      C1-02          Deceleration time 1                                                          Yes         Q       Q       Q         Q
      C1-03          Acceleration time 2                                                          Yes         A       A       A         A
      C1-04          Deceleration time 2                                                          Yes         A       A       A         A
                                                                                     1.5 sec
      C1-05          Acceleration time 3                                                          No          A       A       A         A
      C1-06          Deceleration time 3                                                          No          A       A       A         A
      C1-07          Acceleration time 4                                                          No          A       A       A         A
      C1-08          Deceleration time 4                                                          No          A       A       A         A
      C1-10          Acceleration/deceleration time setting unit                         1        No          A       A       A         A
                                                                                                                                               6-21
       Switching Over the Acceleration and Deceleration Time Using Multi-Function Input
        Commands
         When two digital input terminals are set to “Accel./Decel. time switch over 1 and 2” (H1-=7 and 1A), the
         acceleration/deceleration times can be switched over even during operation by a binary combination of the
         inputs. The following table shows the acceleration/deceleration time switching combinations.
          Acceleration/Deceleration             Acceleration/Deceleration
                                                                                           Acceleration Time                     Deceleration Time
          Time Selection 1 Terminal             Time Selection 2 Terminal
                       OFF                                     OFF                                 C1-01                                 C1-02
                        ON                                     OFF                                 C1-03                                 C1-04
                       OFF                                     ON                                  C1-05                                 C1-06
                        ON                                     ON                                  C1-07                                 C1-08
                                 Decel. Time
                              Switching Freq.
                                       C1-11
RUN
C1-02
                                                                            C2-01
                                                          C1-07
                                    No S-Curve
                                                                    C1-11
                                                                                                         S1-26
         Note:   When C1-11 is set much higher than S1-26, the motor speed cannot reach C1-11 and the motor can not accelerate to the selected speed. Therefore
                 always set C1-11 equal or lower than S1-26!
6-22
 Acceleration and S-curve Settings
    Five different S-curve times are used to reduce the jerk when the speed changes.
  Related Parameters
                                                                                                                Control Methods
                                                                                           Change
                                                                                                                                  Closed
   Parameter                                                                   Factory     during                Open Closed
                                           Name                                                                                    Loop
      No.                                                                      Setting     Opera-        V/f      Loop   Loop     Vector
                                                                                            tion                 Vector Vector     (PM)
     C2-01     S-curve characteristic time at acceleration start                   0.5 s        No         Q         Q      Q       Q
     C2-02     S-curve characteristic time at acceleration end                     0.5 s        No         Q         Q      Q       Q
     C2-03     S-curve characteristic time at deceleration start                   0.5 s        No         Q         Q      Q       Q
     C2-04     S-curve characteristic time at deceleration end                     0.5 s        No         Q         Q      Q       Q
     C2-05     S-curve characteristic time below leveling                          0.5 s        No         Q         Q      Q       Q
                                                                   C2-04
                                                                                   C2-05
         C2-01                                                                              Leveling Speed
  Related Parameters
                                                                                                               Control Methods
                                                                                        Change                                    Closed
   Parameter                                                           Factory                                 Open      Closed
                                          Name                                          during                                     Loop
      No.                                                              Setting                       V/f        Loop      Loop
                                                                                       Operation                                  Vector
                                                                                                               Vector    Vector    (PM)
     b6-01     Dwell frequency at start                                    0.0 Hz          No        A           A         A        A
     b6-02     Dwell time at start                                         0.0 s           No        A           A         A        A
     b6-03     Dwell frequency at stop                                     0.0 Hz          No        A           A         A        A
     b6-04     Dwell time at stop                                          0.0 s           No        A           A         A        A
                                                                                                                                           6-23
         Applying an Output Speed Dwell
           The dwell function at start is applied when the speed level set in parameter b6-01 is reached. The dwell speed
           is kept for the time set in parameter b6-02. The dwell function at stop is applied when the speed reaches the
           level set in parameter b6-03. The dwell speed is kept for the time set in parameter b6-04. The setting is shown
           in Fig 6.7.
                                                  Run command      ON
                                                                                        OFF
Output frequency
                                                                                b6-03
                                                                        b6-01
                                                                                              Time
b6-02 b6-04
6        Related Parameters
                                                                                                                Control Methods
                                                                                               Change                             Closed
          Parameter                                                              Factory                        Open     Closed
                                              Name                                             during                              Loop
             No.                                                                 Setting                  V/f    Loop     Loop
                                                                                              Operation                           Vector
                                                                                                                Vector   Vector    (PM)
            L3-01     Stall prevention selection during acceleration                1              No     A       A        -        -
            L3-02     Stall prevention level during acceleration                  150%             No     A       A        -        -
6-24
Time Chart
  The following figure shows the output frequency characteristics when L3-01 is set to 1.
                    Output current
                             Stall level during
                             acceleration
                  L3-02
            85% of L3-02
                                             *1
                                                                *2
Time
Setting Precautions
   • Set the parameters as a percentage taking the inverter rated current to be 100%.
   • Do not increase the stall prevention level unnecessarily. An extremely high setting can reduce the inverter
     lifetime. Also do not disable the function.
   • If the motor stalls with the factory settings check the V/f pattern settings (E1-) and the motor setup
     (E2-).
                                                                                                                        6
   • If the stall level has to be increased very much to get the elevator running, consider to use a one size bigger
     inverter.
                                                                                                                       6-25
       Adjusting Analog Input Signals
         Related Parameters
                                                                                                         Control Methods
                                                                                        Change                             Closed
          Parameter                                                          Factory                     Open     Closed
                                               Name                                     during                              Loop
             No.                                                             Setting               V/f    Loop     Loop
                                                                                       Operation                           Vector
                                                                                                         Vector   Vector    (PM)
            H3-01     Frequency reference AI-14B CH1signal level selection     0          No       A       A        A        A
            H3-02     Frequency reference AI-14B CH1 input gain              100.0%       Yes      A       A        A        A
            H3-03     Frequency reference AI-14B CH1 input bias               0.0%        Yes      A       A        A        A
            H3-04     AI-14B CH3 signal level selection                        0          No       A       A        A        A
            H3-05     AI-14B CH3 function selection                            2          No       A       A        A        A
            H3-06     AI-14B CH3 input gain                                  100.0%       Yes      A       A        A        A
            H3-07     AI-14B CH3 input bias                                   0.0%        Yes      A       A        A        A
            H3-08     AI-14B CH2 signal level selection                        3          No       A       A        A        A
            H3-09     AI-14B CH2 function selection                            0          No       A       A        A        A
            H3-10     AI-14B CH2 input gain                                  100.0%       Yes      A       A        A        A
            H3-11     AI-14B CH2 input bias                                   0.0%        Yes      A       A        A        A
            H3-12     Analog input filter time constant for the AI-14B       0.03 s       No       A       A        A        A
            H3-15     Terminal A1 function selection                           0          No        -      -        A        A
            H3-16     Terminal A1 input gain                                 100.0%       Yes      A       A        A        A
6-26
Speed Detection and Speed Limitation
 Related Parameters
                                                                                           Control Methods
                                                                       Change
                                                                                                             Closed
    Parameter                                                Factory    during             Open     Closed
                                           Name                                                               Loop
       No.                                                   Setting   Opera-     V/f       Loop     Loop    Vector
                                                                         tion              Vector   Vector    (PM)
      L4-01     Speed agreement detection level               0.0 Hz     No        A         A        A        A
      L4-02     Speed agreement detection width               2.0 Hz     No        A         A        A        A
      L4-03     Speed agreement detection level (±)           0.0 Hz     No        A         A        A        A
      L4-04     Speed agreement detection width (±)           2.0 Hz     No        A         A        A        A
 Setting Precautions
    • With L4-01 an absolute speed agreement level is set, i.e. a speed agreement is detected in both directions
      (Up and Down).
    • With L4-03 a signed speed agreement level is set, i.e. a speed agreement is detected only in the set direc-
      tion (positive level → Up direction, negative level → Down direction).
                                                                                                                      6-27
       Time Charts
          The following table shows the time charts for each of the speed agreement functions.
          Related                                          L4-01: Speed Agree Level                                                                    L4-03: Speed Agree Level +/–
         parameter                                         L4-02: Speed Agree Width                                                                     L4-04: Speed Agree Width
                     fref/fout Agree 1                                                                               fref/fout Agree 2
                          Frequency                                                                                       Frequency
                          reference                                                                                       reference
                                     Output                                                                                          Output
                                  frequency or                                                 L4-02                              frequency or                               L4-04
                                  motor speed                                                                                     motor speed
        fref/fout
        Agree
L4-02 L4-04
                      fref/fout    Agree 1
                                                       OFF                                                            fref/fout    Agree 2
                                                                                                                                                      OFF
                                                                     ON                                                                                            ON
L4-03 L4-03
                          Output frequency
                           or motor speed                                                                                Output frequency
                                                                                                                          or motor speed
        fout/fset
        Agree                                                                         L4-01
L4-02
                                                                ON                                                                                    OFF    ON
                                                     OFF
                             fout/fset Agree 1                                                                                    fout/fset Agree 1
6
                     Frequency (FOUT) Detection 1                                                                    Frequency (FOUT) Detection 3
                     (L4-01 > | Output frequency |)                                                                  (L4-03 > Output frequency)
                                                                                                L4-02
                                                                                                                                                                                 L4-04
                                                                                                           L4-01                                                                         L4-03
                     Output frequency
                                                                                                                                         Output frequency
                     or motorspeed
                                                                                                                                           or motor speed
L4-01
L4-02
                                                                                                           L4-01
                                                                                                                                                                                         L4-03
                                           Output frequency
                                             or motorspeed
                                                                                                                                        Output frequency
                                                                                                                                          or motor speed
L4-01
L4-02
                                             Freq.Detection 2    OFF          ON
                                                                                                                                  Freq Detection 4          OFF         ON
6-28
 Limiting the Elevator Speed to the Leveling Speed (d1-17)
    To use a high speed limit in the UP or DOWN direction to the leveling speed, one of the digital inputs must be
    set to “High speed limit switch Up” or “High speed limit Down” (H1- = 87/88).
                                                                                                                      6-29
       Improving the Operation Performance
         Related Parameters
                                                                                                                                                                                        Control Methods
                                                                                                                                             Change
          Parameter                                                                                                   Factory                                                           Open     Closed  Closed
                                                               Name                                                                          during
             No.                                                                                                      Setting                                           V/f             Loop      Loop Loop Vec-
                                                                                                                                            Operation
                                                                                                                                                                                        Vector   Vector tor (PM)
            C3-01        Slip compensation gain                                                                           1.0                     Yes                    A                    A    -       -
            C3-02        Slip compensation delay time                                                                 2000 ms                      No                    A                    A    -       -
            C3-03        Slip compensation limit                                                                        200%                       No                    A                    A    -       -
            C3-04        Slip compensation during regeneration                                                              1                      No                     -                   A    -       -
            C3-05        Output voltage limit operation selection                                                           0                      No                     -                   A   A        -
              The motor data can be set automatically using the autotuning function.
                                                                                                                         120
6-30
  Adjusting Slip Compensation Limit (C3-03)
    Using parameter C3-03 the upper limit for the slip compensation can be set as a percentage, taking the motor
    rated slip as 100%.
    If the speed is lower than the target value but does not change even after adjusting the slip compensation gain,
    the slip compensation limit may have been reached. Increase the limit, and check the speed again. Always
    make sure that the value of the slip compensation limit and reference frequency does not exceed the tolerance
    of the machine.
    The following diagram shows the slip compensation limit for the constant torque range and fixed output range.
                               Slip compensation limit
                          E1-04
                         ---------- X C3-03
                          E1-06
C3-03
                                                               E1-06                            E1-04
                                                                                            Output frequency
                                                         E1-06 : Base frequency
                                                         E1-04 : Maximun output frequency
                                                                                                                       6-31
       Related Parameters
                                                                                                   Control Methods
                                                                                  Change                             Closed
        Parameter                                                      Factory                     Open     Closed
                                            Name                                  during                              Loop
           No.                                                         Setting               V/f    Loop     Loop
                                                                                 Operation                           Vector
                                                                                                   Vector   Vector    (PM)
          C4-01       Torque compensation gain                          1.00        Yes      A       A        -        -
          C4-02       Torque compensation delay time constant          2000 ms      No       A       A        -        -
        V/f control
           • If the cable is very long, increase the set value.
           • If the motor capacity is smaller than the Inverter capacity (max. applicable motor capacity), increase the
             set value.
           • If the motor vibrates, reduce the set value.
        Setting precautions
           • Adjust this parameter so that the output current during low-speed rotation does not exceed the Inverter
             rated output current range.
           • Adjust the value in steps of 0.05 only.
6-32
 Starting Torque Compensation Function (C4-03 to C4-05)
    A starting torque compensation can be applied to speed up the torque establishment at start in Open Loop Vec-
    tor control.
  Related Parameters
                                                                                                                                      Control Methods
                                                                                                      Change                                                 Closed
   Parameter                                                                             Factory                                      Open          Closed
                                            Name                                                      during                                                  Loop
      No.                                                                                Setting                          V/f          Loop          Loop
                                                                                                     Operation                                               Vector
                                                                                                                                      Vector        Vector    (PM)
     C4-03     Starting torque compensation value (forward direction)                      0.0             No               -             A           -        -
     C4-04     Starting torque compensation value (reverse direction)                      0.0             No               -             A           -        -
     C4-05     Starting torque compensation time constant                                 1 ms             No               -             A           -        -
OFF ON
C4-05 X 4
                      E1-09
                 Output frequency                                                                                               E1-09
                                                             I                                                          Torque
               Motor                                                                                                    Limits
               Speed                                 C5-02/04/10 C5-08
                                                                 I-Limit
                                                                                                                                                                      6-33
       Related Parameters
                                                                                                            Control Methods
                                                                                         Change                               Closed
         Parameter                                                         Factory                          Open     Closed
                                                 Name                                    during                                Loop
            No.                                                            Setting                  V/f      Loop     Loop
                                                                                        Operation                             Vector
                                                                                                            Vector   Vector    (PM)
                                                                             40.00                                     Q        -
           C5-01       ASR proportional (P) gain 1                                         Yes       -         -
                                                                             12.00                                     -        Q
                                                                           0.500 sec.                                  Q        -
           C5-02       ASR integral (I) time 1                                             Yes       -         -
                                                                           0.300 sec.                                  -        Q
                                                                             20.00                                     Q        -
           C5-03       ASR proportional (P) gain 2                                         Yes       -         -
                                                                             6.00                                      -        Q
           C5-04       ASR integral (I) time 2                             0.500 sec.     Yes        -         -       Q        Q
                                                                            0.0 Hz                                     Q        -
           C5-07       ASR switching frequency                                             No        -         -
                                                                             2.0%                                      -        Q
           C5-08       ASR integral limit                                    400%          No        -         -       A        A
                                                                             40.00                                     Q        -
           C5-09       ASR proportional (P) gain 3                                         Yes       -         -
                                                                             12.00                                     -        Q
                                                                           0.500 sec.                                  Q        -
           C5-10       ASR integral (I) time 3                                             Yes       -         -
                                                                           0.300 sec.                                  -        Q
           C5-11       ASR gain for encoder offset tuning                    5.00          No        -         -       -        A
         When the ride starts with the nominal speed selected, the ASR P gain and I time change from C5-03/04 to C1-
         01/02 at nominal speed. When the speed selection changes to leveling speed, the P gain and I time are changed
         from C1-01/02 to C1-09/10.
         If parameter d1-18 is set to 0 or 3, the nominal/leveling speed detection function must be enabled (refer to
         page 6-6, Nominal / Leveling Speed Detection with Multi Speed Inputs) in order to use the ASR 3 settings.
6-34
     • Increase C5-09 if ASR is slow in the low speed area or if undershooting occurs at leveling speed. If vibra-
       tions occur in the low speed area during deceleration decrease the value.
                             Iq             ST
                                                                K
                                           1+ ST
                                                               N2-01
                                          N2-02
                                          N2-03
  Related Parameters
                                                                                                      Control Methods
                                                                                   Change                               Closed
   Parameter                                                            Factory                       Open     Closed
                                      Name                                         during                                Loop
      No.                                                               Setting               V/f     Loop      Loop
                                                                                  Operation                             Vector
                                                                                                      Vector   Vector    (PM)
     n2-01     Speed feedback detection control (AFR) gain               1.00        No        -        A        -        -
     n2-02     Speed feedback detection control (AFR) time constant 1   50 ms        No        -        A        -        -
                                                                                                                                 6-35
         Setting the AFR Time Constants (n2-02)
           Parameter n2-02 sets the time constant for the AFR control. If adjustments are necessary,
            • Increase the setting if hunting occurs or the speed is over-compensated
            • Decrease the setting if the compensation is too slow
           Normally there is no need to change this setting.
         Related Parameters
                                                                                                  Control Methods
                                                                               Change                                Closed
           Parameter                                             Factory                          Open     Closed
                                        Name                                   during                                 Loop
              No.                                                setting                  V/f      Loop     Loop
                                                                              operation                              Vector
                                                                                                  Vector   Vector     (PM)
                                                                    1                                         A         -
             n5-01      Feed forward control selection                           No        -         -
                                                                    0                                         -         A
             n5-02      Motor acceleration time               kVA dependent      No        -         -        A         A
             n5-03      Feed forward proportional gain             1.0           No        -         -        A         A
             n5-05      Motor acceleration time auto tuning         0            No        -         -        A         A
Adjustments
6-36
    Use the following procedure:
    1. Set n5-05 to “1” to enable the auto tuning and go back to the speed reference display.
    2. Set the base block input.
    3. Enable the inspection speed input. “FFCAL” will blink in the display to signalize that the calculation is
       active.
    4. Set an UP command. The inverter will accelerate the motor up to the nominal speed. Release the UP com-
       mand a few seconds after the top speed has been reached.
    5. When the motor has stopped, apply a DOWN command. The inverter will accelerate the motor in the
       opposite direction to the nominal speed. Release the DOWN command a few seconds after the nominal
       speed has been reached.
    To abort the tuning set parameter n5-05 to “0”.
Related Parameters
     Parameter
        No.
                                    Name
                                                                 Factory
                                                                 setting
                                                                                Change
                                                                                during         V/f
                                                                                                       Open
                                                                                                        Loop
                                                                                                                  Closed
                                                                                                                   Loop
                                                                                                                           Closed
                                                                                                                            Loop
                                                                                                                           Vector
                                                                                                                                     6
                                                                               operation               Vector     Vector    (PM)
       n8-29      ACR q axis proportional gain                  1000 rad/s         No           -         -          -       A
       n8-30      ACR q axis integral time                       10.0 ms           No           -         -          -       A
       n8-32      ACR d axis proportional gain                  1000 rad/s         No           -         -          -       A
       n8-33      ACR d axis integral time                       10.0 ms           No           -         -          -       A
  Adjustments
    Normally there is no need to change these values. However, if short cycle vibrations occur which can’t be
    eliminated by the ASR controller setup, it might help to adjust ACR values like follows:
     • If the motor generates very strange high frequency noise (not carrier frequency related), reduce both ACR
       gains (n8-29 and n8-32) for the same value. If the gain is reduced too much, the performance will be
       reduced.
     • If vibrations occur, reduce both integral times (n9-30 and n9-33) for the same value.
                                                                                                                                    6-37
        A/D Conversion Delay Time Tuning
           The A/D conversion delay timer sets a delay for the current signal A/D conversion.
         Related Parameters
                                                                                 Change              Open     Closed   Closed
            Parameter                                              Factory                                              Loop
                                          Name                                   during        V/f    Loop     Loop    Vector
               No.                                                 setting
                                                                                operation            Vector   Vector    (PM)
              n9-60     Current signal A/D conversion delay time   0.0 µsec.       No           -      -        -        A
         Adjustments
           Normally an adjustment is no need to change this value. However, if cyclic oscillations like shown in Fig 6.13
           occur during constant speed run, the A/D conversion delay can be increased in order to eliminate the vibra-
           tions.
Torque Signal
Motor Speed
6-38
  Related Parameters
                                                                               Change                      Open      Closed    Closed
     Parameter                                               Factory                                                            Loop
                                     Name                                      during          V/f          Loop      Loop     Vector
        No.                                                  setting
                                                                              operation                    Vector    Vector     (PM)
       S2-01      Motor Rated rpm                            1380rpm              No           A             -         -         -
       S2-02      Slip Compensation Gain at Motoring           0.7                No           A             A         -         -
       S2-03      Slip Compensation Gain at Regenerating       1.0                No           A             A         -         -
       S3-05      Slip Compensation Torque Detection Delay   1.0 sec.             No           A             A         -         -
       S3-06      Slip Compensation Torque Detection Time    0.5 sec.             No           A             A         -
       S2-07      Slip Compensation primary Delay Time       200ms                No            -            A         -         -
  Adjustments
    The Slip compensation values can be set separately for motoring and regenerative operation. Before adjusting
    this function the general setup should have been done (Motor Setup, V/f pattern, Speeds, ASR settings etc.).
    To adjust the Slip compensation function do the following in motoring and regenerative mode:
     • Set the motor speed in S2-01 if V/f control is used.
     • Try to measure the actual motor speed during leveling.
     • If the motor speed is lower than the leveling speed reference increase S2-02 in motoring mode or decrease
       S2-03 in regenerative mode.
     • If the motor speed is higher than the leveling speed reference decrease S2-02 in motoring mode or increase
       S2-03 in regenerative mode.
     • S2-05 and S2-06 should not be modified, except if the stop accuracy is poor and the constant speed time
       after the speed agree is shorter than S2-05 + S2-06.
 Field Forcing                                                                                                                          6
    The field forcing function controls the motor flux and compensates the flux establishment delay of the motor.
    Thereby it improves the motor responsiveness to changes in the speed reference or the load.
    Field forcing is applied during all operation conditions except DC Injection.
    Using parameter d6-06 a field forcing limit can be applied. A setting of 100% is equal to the no-load current
    set in parameter E2-03.
  Related Parameters
                                                                                                            Control Methods
                                                                                    Change                                     Closed
   Parameter                                                            Factory                              Open Closed
                                         Name                                       during                                      Loop
      No.                                                               Setting                      V/f      Loop  Loop
                                                                                   Operation                                   Vector
                                                                                                             Vector Vector      (PM)
     d6-03     Field forcing selection                                    0            No             -          A         A     -
     d6-06     Field forcing limit                                       400%          No             -          A         A      -
                                                                                                                                        6-39
        Adjusting the DC Injection Current
           The DC current injection is used in V/f and Open Loop Vector Control in order to hold the motor when the
           brake is opened or closed.
         Related Parameters
                                                                                                        Control Methods
                                                                                       Change                             Closed
          Parameter                                                         Factory                     Open     Closed
                                                Name                                   during                              Loop
             No.                                                            Setting               V/f    Loop     Loop
                                                                                      Operation                           Vector
                                                                                                        Vector   Vector    (PM)
            S1-02     DC injection current level at start                    50%         No       A       A        -        -
            S1-03     DC injection current level at stop                     50%         No       A       A        -        -
            S1-17     DC injection gain at stop in regenerative operation    100%        No        -      A        -        -
            S1-18     DC injection gain at stop in motoring operation        20%         No        -      A        -        -
6-40
Protective Functions
  Related Parameters
                                                                                                Control Methods
                                                                               Change                             Closed
   Parameter                                                        Factory                     Open     Closed
                                      Name                                     during                              Loop
      No.                                                           Setting               V/f    Loop     Loop
                                                                              Operation                           Vector
                                                                                                Vector   Vector    (PM)
               Stall prevention selection during running function
     L3-05                                                            1          No       A       -        -        -
               selection
     L3-06     Stall prevention level during running                 150%        No       A       -        -        -
  Precautions
    If the motor capacity is smaller than the Inverter capacity or the motor stalls when operating at the factory set-
    tings, lower the stall prevention level during operation.
  Setting Precautions
     • Set the parameters as a percentage taking the inverter rated current to be 100%.
                                                                                                                            6
     • Do not increase the stall prevention level unnecessarily. An extremely high setting can reduce the inverter
       lifetime. Also do not disable the function.
     • If the motor stalls with the factory settings check the V/f pattern (E1-) and the motor setup (E2-).
     • If the stall level has to be increased very much to get the elevator running, check the mechanical system or
       consider using a one size bigger inverter.
                                                                                                                           6-41
       Related Parameters
                                                                                                                      Control Methods
                                                                                               Change                                        Closed
         Parameter                                                                 Factory                                Open     Closed
                                                   Name                                         during                                        Loop
            No.                                                                    Setting                    V/f          Loop     Loop
                                                                                              Operation                                      Vector
                                                                                                                          Vector   Vector     (PM)
           L6-01        Torque detection selection 1                                  4           No          A             A        A         A
           L6-02        Torque detection level 1                                    150%          No          A             A        A         A
           L6-03        Torque detection time 1                                     10.0 s        No          A             A        A         A
           L6-04        Torque detection selection 2                                  0           No          A             A        A         A
           L6-05        Torque detection level 2                                    150%          No          A             A        A         A
           L6-06        Torque detection time 2                                      0.1 s        No          A             A        A         A
L6-01 and L6-04 Set Values and Operator Display (JVOP-160-OY only)
6        The relationship between alarms displayed on the digital operator when overtorque or undertorque is detected,
         and the set values in L6-01 and L6-04, is shown in the following table.
                                                                                                                   Operator Display
            Set                                                                                               Overtorque/    Overtorque/
                                                            Function
           Value                                                                                              Undertorque Undertorque
                                                                                                              Detection 1    Detection 2
               0      Overtorque/undertorque detection disabled.                                                      –                  –
                      Overtorque/Car stuck detection only with speed agree; operation continues (warning is
               1                                                                                              OL3 flashes          OL4 flashes
                      output).
                      Overtorque/Car stuck detected continuously during operation; operation continues
               2                                                                                              OL3 flashes          OL4 flashes
                      (warning is output).
                      Overtorque/Car stuck detection only with speed agree; output is stopped upon detec-
               3                                                                                              OL3 lights up        OL4 lights up
                      tion.
                      Overtorque/Car stuck detected continuously during operation; output is stopped upon
               4                                                                                              OL3 lights up        OL4 lights up
                      detection.
               5      Undertorque detection only with speed agree; operation continues (warning is output).   UL3 flashes          UL4 flashes
                      Undertorque detected continuously during operation; operation continues (warning is
               6                                                                                              UL3 flashes          UL4 flashes
                      output).
               7      Undertorque detection only with speed matching; output is stopped upon detection.       UL3 lights up        UL4 lights up
               8      Undertorque detected continuously during operation; output is stopped upon detection. UL3 lights up          UL4 lights up
6-42
Timing Charts
  Fig 6.15 and Fig 6.16 show the timing charts for over torque and under torque detection.
                             Motor current (output torque)
L6-02 or L6-05
               Overtorque detection 1 NO
             or overtorque detection 2 NO                          ON                             ON
                        *Overtorque detection switch off bandwidth is approximately 10% of the Inverter rated output
                        current (or motor rated torque).
L6-02 or L6-05
                        *Undertorque detection switch off bandwidth is approximately 10% of the Inverter rated output
                                                                                                                         6
                        current (or motor rated torque).
                                                                 DC Injection
                                                  Speed           zero servo
                                                                                                                        6-43
        Limiting the Motor Torque (Torque Limit Function)
           This function allows limitation of motor shaft torque independently for each of the four quadrants. The torque
           limit can be set as a fixed value using parameters or as a variable value using an analog input. The torque limit
           function can be used with Open Loop Vector and Closed Loop Vector control only.
         Related Parameters
                                                                                                                                   Control Methods
                                                                                                          Change dur-                                 Closed
                                                                                           Factory Set-                            Open      Closed
           Parameter No.                            Name                                                  ing Opera-                                   Loop
                                                                                               ting                       V/f      Loop      Loop
                                                                                                             tion                                     Vector
                                                                                                                                   Vector    Vector    (PM)
              L7-01        Forward drive torque limit                                         300%*            No             -      A         A        A
              L7-02        Reverse drive torque limit                                         300%*            No             -      A         A        A
              L7-03        Forward regenerative torque limit                                  300%*            No             -      A         A        A
              L7-04        Reverse regenerative torque limit                                  300%*            No             -      A         A        A
              L7-06        Torque limit integral time constant                                200 ms           No             -      A         -        -
                           Torque limit integral operation during accel./
              L7-07                                                                                0           No             -      A         -        -
                           decel. selection
                                                                                             L7-01
                                                           L7-04
                                                                                        Fordward
                                                               Reserve
                                                                                          Drive
                                                             Regenerative
                                                                                                       Output Speed
                                                                                    Fordward
                                                              Reverse              Regenerative
                                                               Drive
                                                                                             L7-03
                                                           L7-02
6-44
  Adjusting the Torque Limit Integral Time (L7-06)
    In Open Loop Vector control, during constant speed the limit function works with an integral control part
    (during acceleration and deceleration just a P-control is used). Normally there is no need to change this set-
    ting.
      • Increase the setting if vibrations or short cycle oscillations occur when the motor is running at the set
          torque limit
      • Decrease the setting if long cycle oscillations occur when the motor is running at the set torque limit.
  Setting Precautions
      • When the output torque reaches the torque limit, control and compensation of the motor speed is disabled
          to prevent the output torque from exceeding the torque limit. The torque limit has the priority.
      • The torque limit accuracy is ±5% at an output frequency of 10 Hz or above. When output frequency is
          lower than 10 Hz, the accuracy is lower.
Related Parameters
    Parameter                                                                      Factory
                                                                                                 Change
                                                                                                                                  Control Methods
                                                                                                                                  Open        Closed
                                                                                                                                                       Closed
                                                                                                                                                                 6
                                             Name                                                during                                                 Loop
       No.                                                                         Setting                            V/f          Loop        Loop
                                                                                                Operation                                              Vector
                                                                                                                                  Vector      Vector    (PM)
      E2-01       Motor 1 rated current                                           7.00 A *1          No               Q             Q           Q        -
*1. Factory settings depend on Inverter capacity. (The given value is for a 400 V Class Inverter with 3.7 kW.)
                                                                                                                                                                6-45
       Setting Motor Overload Protection Characteristics (L1-01)
         Set the overload protection function in L1-01 according to the used motor.
         As the motors thermal behavior depends on the motor type, the thermal motor protection characteristics must
         be properly selected.
         Set L1-01 to:
         0: to disable the thermal motor protection function.
         1: to enable the thermal motor protection for a fan cooled general purpose motor (self-cooled).
         2: to enable the thermal motor protection for an inverter motor (externally cooled).
         3: to enable the thermal motor protection for a special vector motor (externally cooled).
         5: to enable the thermal motor protection for a permanent magnet motor
Cold start
Hot Start
6-46
 Output Current Observation
    The inverter can observe the output current and thereby detect e.g a wrong motor contactor sequence or bad
    motor connection. There are two observation functions, one for the start and one during run.
  Related Parameters
                                                                                                   Control Methods
                                                                               Change                                  Closed
    Parameter                                                      Factory                          Open     Closed
                                       Name                                    during                                   Loop
       No.                                                         Setting                  V/f      Loop     Loop
                                                                              Operation                                Vector
                                                                                                    Vector   Vector     (PM)
      S1-14     SE2 detection time                                 200 ms        No         A         A         A         -
      S1-15     SE3 detection time                                 200 ms        No         A         A         A         -
  Related Parameters
                                                                                                   Control Methods
                                                                               Change                                  Closed
    Parameter                                                      Factory                          Open     Closed
                                       Name                                    during                                   Loop
       No.                                                         Setting                  V/f      Loop     Loop
                                                                              Operation                                Vector
                                                                                                    Vector   Vector     (PM)
      S3-16     Over acceleration detection level                  1.5 m/s²      No          -         -        -        A
      S3-17     Over acceleration time constant                   0.05 sec.      No          -         -        -        A
      S3-18     Over acceleration detection method                    0          No          -         -        -        A
                      It is imperative to set up the parameters S3-13, S3-14 and S3-15 (traction sheave diameter, roping and
                      gear ratio) in order to make this function working properly!
      IMPORTANT
                                                                                                                                6-47
       Inverter Protection
         Related Parameters
                                                                                                                        Control Methods
                                                                                                Change                                      Closed
          Parameter                                                                  Factory                             Open      Closed
                                                       Name                                     during                                       Loop
             No.                                                                     Setting                 V/f         Loop       Loop
                                                                                               Operation                                    Vector
                                                                                                                         Vector    Vector    (PM)
            L8-02        Overheat pre-alarm level                                    95°C *1      No         A               A        A        A
            L8-03        Inverter overheat (OH) pre-alarm operation selection          3          No         A               A        A        A
                                DC Bus                                                                                 L8-06
                                Voltage
                                                                        10 seconds
6-48
  Related Parameters
                                                                                                                          Change
       Parameter                                                                             Setting        Factory                    Access
                                                   Name                                                                   during
        Number                                                                               Range          Setting                     Level
                                                                                                                         Operation
*1. The factory setting depends on the Inverter Capacity. The value for a of 3.7kW 400 V Class Inverter is given
  Related Parameters
                                                                                                                             Control Methods
   Parameter
      No.
                                              Name
                                                                                     Factory
                                                                                     Setting
                                                                                                    Change
                                                                                                    during
                                                                                                   Operation
                                                                                                                   V/f
                                                                                                                             Open Closed
                                                                                                                              Loop  Loop
                                                                                                                             Vector Vector
                                                                                                                                                Closed
                                                                                                                                                 Loop
                                                                                                                                                Vector
                                                                                                                                                          6
                                                                                                                                                 (PM)
     L8-07       Output open-phase detection selection                                   2             No           A          A       A          A
     L8-20       Output phase loss detection time                                     0.2 sec          No           A          A       A          A
                                                                                                                                                         6-49
        Ground Fault Detection
           This function detects the earth leakage current by calculating the sum of the three output currents. Normally it
           should be 0. If the earth leakage current gets too high, the inverter output is switched off and a GF fault is
           shown on the display. The fault contact is activated.
         Related Parameters
                                                                                                   Control Methods
                                                                                  Change                             Closed
          Parameter                                                    Factory                     Open     Closed
                                               Name                               during                              Loop
             No.                                                       Setting               V/f    Loop     Loop
                                                                                 Operation                           Vector
                                                                                                   Vector   Vector    (PM)
            L8-09     Ground detection selection                          1         No       A       A        A        A
         Precautions
            • It is not recommended to disable this function.
            • A Ground Fault can also be detected if the contactors at the inverter output are opened when the output is
              still active. Therefore, to prevent false Ground Fault detection check the sequence and make sure, that the
              output is switched of or base blocked before opening the contactors.
6-50
 Cooling Fan Control
    This function controls the fan which is mounted to the inverters heatsink.
  Related Parameters
                                                                                                                    Control Methods
                                                                                                   Change                             Closed
   Parameter                                                                            Factory                     Open     Closed
                                                             Name                                  during                              Loop
      No.                                                                               Setting               V/f   Loop      Loop
                                                                                                  Operation                           Vector
                                                                                                                    Vector   Vector    (PM)
     L8-10     Cooling fan control selection                                               0            No    A       A        A        A
     L8-11     Cooling fan control delay time                                           60 sec          No    A       A        A        A
  Related Parameters
                                                                                                                    Control Methods
   Parameter
      No.
                                                             Name
                                                                                        Factory
                                                                                        Setting
                                                                                                   Change
                                                                                                   during
                                                                                                  Operation
                                                                                                              V/f
                                                                                                                    Open
                                                                                                                    Loop
                                                                                                                             Closed
                                                                                                                              Loop
                                                                                                                                      Closed
                                                                                                                                       Loop
                                                                                                                                      Vector
                                                                                                                                                6
                                                                                                                    Vector   Vector    (PM)
     L8-12     Ambient Temperature                                                       45° C       No       A       A        A        A
    At high ambient temperatures an output current derating has to be considered. The derating depends on the
    ambient temperature. The derating curve is shown in Fig 6.21. To ensure a safe inverter protection at high
    ambient temperatures, always set parameter L8-15 to the actual ambient temperature.
                                                10 0
                   Output Current in % of the
                                                 80
                        Rated Current
60
40
20
                                                  0
                                                       0     10      20    30      40     50       60
                                                                    Temperatur (°C)
                                                           Fig 6.21 Ambient Temperature Derating Curve
                                                                                                                                               6-51
       Input Terminal Functions
           The digital multifunction inputs can be set to several functions using the H1-01 to H1-05 parameters (terminal
           S3 to S7 function selection). The following section describes the input functions not mentioned in any other
           section.
         Related Parameters
                                                                                       Change                Control Methods
            Parameter                                                       Factory    during                Open Close Closed
                                                       Name                                                                 Loop
               No.                                                          Setting    Opera-       V/f       Loop d Loop
                                                                                                                           Vector
                                                                                        tion                 Vector Vector (PM)
               H1-01      Terminal S3 function selection                      80        No           A          A             A           A
               H1-02      Terminal S4 function selection                      84        No           A          A             A           A
               H1-03      Terminal S5 function selection                      81        No           A          A             A           A
               H1-04      Terminal S6 function selection                      83        No           A          A             A           A
               H1-05      Terminal S7 function selection                       F        No           A          A             A           A
         Related Parameters
                                                                                        Change                Control Methods
          Parameter                                                          Factory    during                 Open Close Closed
                                                       Name                                                                  Loop
             No.                                                             Setting    Opera-        V/f       Loop d Loop
                                                                                                                             Vector
         Hardware Baseblock
           When hardware baseblock is activated, the power supply of the IGBT driver circuit is cut off and the motor
           starts to coast. To use this baseblock function the digital input S8 must be used. The input is a NC input, i.e. if
           terminal S8 is open, the inverter is base block condition.
         Software Baseblock
           When software baseblock is used, the inverter output is cut by a software function. To use this baseblock func-
           tion one of the digital inputs must be set to baseblock, i.e. one of the parameters H1-01 to H1-05 (digital input
           terminal S3 to S7 function selection) must be set to 8 or 9 (Baseblock command NO/NC). The input can be
           used with a NC as well as with a NO contact.
6-52
     • If S1-12 = 0 the Up/Down command has to be cycled.
Up/Down OFF ON
Baseblock ON OFF
                                                      S1-16 +              S1-16 +
                                                      S1-04                S1-04
                            Output frequency
                                                OFF         ON
                         During Run 2 Output
     • If S1-12=1 the Up/Down command must not be cycled. The inverter automatically restarts when base-
       block is deactivated and the Up/Down command is still active.
Up/Down OFF ON
Baseblock ON OFF
                                                      S1-16 +              S1-16 +
                                                      S1-04                S1-04
                           Output frequency
                                                OFF         ON
                         During Run 2 Output
                                                                                                                                    6-53
                                  Input Level              Error Detection Method
                                                                                                          Operation During Error Detection
                                 (See Note 1.)                  (See Note 2.)
             Set
                                                                         Detection           Decelerate                                                      Continue
            Value                                          Constant                                              Coast to           Emergency
                      NO Contact        NC Contact                     During Oper-           to Stop                                                       Operation
                                                           Detection                                            Stop (Error)        Stop (Error)
                                                                           ation              (Error)                                                       (Warning)
             27              -               Yes                -               Yes                 -                 Yes                  -                    -
             28            Yes                   -             Yes                -                 -                  -                  Yes                   -
             29              -               Yes               Yes                -                 -                  -                  Yes                   -
             2A            Yes                   -              -               Yes                 -                  -                  Yes                   -
             2B              -               Yes                -               Yes                 -                  -                  Yes                   -
             2C            Yes                   -             Yes                -                 -                  -                   -                   Yes
             2D              -               Yes               Yes                -                 -                  -                   -                   Yes
             2E            Yes                   -              -               Yes                 -                  -                   -                   Yes
             2F              -               Yes                -               Yes                 -                  -                   -                   Yes
           * 1. Sets the input level at which errors are detected. (NO contact: External error when ON; NC contact: External error when OFF).
           * 2. Set the detection method to detect errors using either constant detection or detection during operation.
                Constant detection: Detects while power is supplied to the Inverter.
                Detection during operation: Detects only during Inverter operation.
         Related Parameters
                                                                                                                                        Control Methods
                                                                                                         Change
6
              Parameter                                                                   Factory                                       Open        Closed          Closed
                                                       Name                                              during                                                      Loop
                 No.                                                                      Setting                           V/f         Loop        Loop
                                                                                                        Operation                                                   Vector
                                                                                                                                        Vector      Vector           (PM)
6-54
  Setting Example
    When the timer function input is ON for longer than b4-01, the timer output function is turned ON. When the
    timer function input is OFF for longer than b4-02, the timer output function is turned OFF. An example of
    timer function operation is given in the following diagram.
  Related Parameters
                                                                                                    Control Methods
      Parameter
         No.
                                        Name
                                                               Factory
                                                               Setting
                                                                           Change
                                                                           during
                                                                          Operation     V/f
                                                                                                    Open
                                                                                                    Loop
                                                                                                               Closed
                                                                                                               Loop
                                                                                                                        Closed
                                                                                                                         Loop
                                                                                                                        Vector
                                                                                                                                  6
                                                                                                    Vector     Vector    (PM)
                                                                                                                                 6-55
          SE1 fault (SE1:Contactor Feed-back Faults)
           There are 3 possible fault conditions.
           Case 1: The motor contactor was closed (Contactor feedback input was on) before the contactor close
                   command was output.
           Case 2: The motor contactor cannot be closed within the contactor close delay time.
           Case 3: The motor contactor is opened during inverter run.
           Case 4: The contactor confirmation input was enabled before the contactor close output was set.
                                                                      DC Injection/
                                                                      Zero Servo
                                               Speed      Run Delay
                                     Up/DownSpeed
                                 Inverter enable (D/I)
                                   Speed Selection
                             Contactor Control (D/O)
                                                                                             Case 1
                                                                                             Case 2
                          Contactor confirmation (D/I)
                                                                                             Case 3
                                                                                             Case 4
6          The PG direction is clockwise (CW) when the input is open and counterclockwise (CCW) when the input is
           closed. The parameter F1-05 has no effect if this function is activated.
6-56
 Motor 2 Selection
    If a digital input is set to “Motor 2 selection” (H1- = 16), this input can be used to switch over between
    motor 1 and motor 2 settings (E1/E2- and E3/E4-). A digital output can be used to monitor the selec-
    tion (H2- = 1C).
    If motor 2 is selected, the speed set in d1-19 will be the speed reference. d1-19 has priority over all speed
    inputs except the service speed input.
    The output signal sequence (brake control, contactor etc.) is the same as for motor 1.
    This function is not available for Closed Loop Vector for PM motors.
    If motor 2 is selected, the brake sequence is active and rescue operation can be performed.
  Related Parameters
                                                                                        Control Methods
                                                                         Change
                                                                                                            Closed     Set by
     Parameter                                                 Factory   during         Open       Closed
                                   Name                                                                      Loop       Auto-
        No.                                                    Setting   Opera-   V/f    Loop       Loop
                                                                                                            Vector     tuning
                                                                          tion          Vector     Vector
                                                                                                            for PM
       d1-19     Motor 2 speed reference                       0.00 Hz    No       A      A          A            -      No
                                                                                                                                6-57
       Output Terminal Functions
          The digital multifunction outputs can be set to several functions using the H2-01 to H2-03 parameters (termi-
          nal M1 to M6 function selection). These functions are described in the following section.
        Related Parameters
                                                                                                                                Control Methods
                                                                                                         Change
                                                                                                                                                      Closed
          Parameter                                                                          Factory      during                Open Closed
                                                       Name                                                                                            Loop
             No.                                                                             Setting     Opera-         V/f     Loop   Loop           Vector
                                                                                                           tion                 Vector Vector          (PM)
            H2-01      Terminal M1-M2 function selection                                         0          No          A          A          A          A
            H2-02      Terminal M3-M4 function selection                                         1          No          A          A          A          A
            H2-03      Terminal M5-M6 function selection                                         2          No          A          A          A          A
Baseblock ON OFF
6
                                                              DC Inj                         DC Inj
                                    Output frequency
                                                              ON
                                 During Run 1 Output OFF
                                                                    ON
                                 During Run 2 Output OFF
                      OFF                               The output frequency is higher than the zero speed level*.
                      ON                                The output frequency is lower than the zero speed level*.
* The Zero Speed Level depends on the control mode. It is 0.1 Hz for Closed Loop Vector, 0.5 Hz for Open Loop Vector and 1.2 Hz for V/f control.
6-58
Inverter Operation Ready (Setting: 6)
  If a multifunction output is set to this function, the output is switched ON when the initialisation of the
  inverter at startup has been finished without any faults.
Up/Down command
BB Monitor 1
BB Monitor 2
                                                                                                                        6-59
       During Base Block 2 (Setting: 1B)
         If a multifunction output set to this function is switched OFF as long as a Baseblock command is input.
6-60
Motor Contactor Control Command (Setting: 41)
  This output can be used to control the motor contactors. The output is closed when the contactors shall be
  closed. Refer also to page 6-13, Brake Sequence.
                                                                                                                               6-61
       Motor and V/f Pattern Setup
           The L7 inverter supports 2 motor settings (main motor and door motor, E2/E4- parameters) for V/f con-
           trol, Open Loop Vector and Closed Loop Vector for IM. The active motor setup can be selected by a digital
           input.
           Closed Loop Vector Control for PM supports 1 motor setting (main motor, E5- parameters) only.
         Related Parameters
                                                                                                 Control Methods
                                                                                Change                             Closed   Set by
          Parameter                                              Factory                         Open     Closed
                                              Name                              during                              Loop     Auto-
             No.                                                 Setting                   V/f   Loop      Loop
                                                                               Operation                           Vector   tuning
                                                                                                 Vector   Vector
                                                                                                                   for PM
            d1-19     Motor 2 speed reference                    0.00 Hz          No       A       A        A        -       No
            E1-01     Input voltage setting                     400 V     *1      No       Q       Q        Q        Q       No
            E3-01     Motor 2 control mode selection                0             No       A       A        A        A       No
           E1-04/                                                                          Q/      Q/       Q/       Q/
                      Max. output frequency (FMAX)               50.0 Hz          No                                         Yes
           E3-02                                                                           A       A        A        A
6          E1-05/
           E3-03
                      Max. voltage (VMAX)                       380.0 V *1        No
                                                                                           Q/
                                                                                           A
                                                                                                   Q/
                                                                                                   A
                                                                                                            Q/
                                                                                                            A
                                                                                                                     Q/
                                                                                                                     A
                                                                                                                             Yes
           E1-06/                                                                          Q/      Q/       Q/       Q/
                      Base frequency (FA)                        50.0 Hz          No                                         Yes
           E3-04                                                                           A       A        A        A
           E1-07/
           E3-05
                      Mid. output frequency (FB)                3.0 Hz *1         No       A       A        -        -       Yes
           E1-08/                                                37.3 V                    Q/      Q/
                      Mid. output frequency voltage (VB)                          No                        -        -       Yes
           E3-06                                                  *1,*2                    A       A
           E1-09/                                                                          Q/      Q/
           E3-07
                      Min. output frequency (FMIN)              0.5 Hz *2         No
                                                                                           A       A
                                                                                                            A        A       Yes
           E1-10/                                                19.4 V                    Q/      Q/
                      Min. output frequency voltage (VMIN)                        No                        -        -       Yes
           E3-08                                                  *1,*2                    A       A
            E1-13     Base voltage (VBASE)                        0.0 V           No       A       A        -        Q       Yes
           E2-01/                                                                          Q/      Q/       Q/
           E4-01
                      Motor rated current                       7.00 A *3         No
                                                                                           A       A        A
                                                                                                                     -       Yes
            E2-02
            E4-02
                      Motor rated slip                          2.70 Hz *3        No       A       A        A        -       Yes
           E2-03/
           E4-03
                      Motor no-load current                     2.30 A *3         No       A       A        A        -       Yes
           E2-04/                                                                                  Q/       Q/
                      Number of motor poles (Number of poles)    4 poles          No        -                        -       Yes
           E4-04                                                                                   A        A
           E2-05/
           E2-05
                      Motor line-to-line resistance             3.333 Ω *3        No       A       A        A        -       Yes
           E2-06/
                      Motor leak inductance                       19.3%           No        -      A        A        -       Yes
           E4-06
            E2-07     Motor iron saturation coefficient 1         0.50            No        -      A        A        -      Yes*4
            E2-08     Motor iron saturation coefficient 2         0.75            No        -      A        A        -      Yes*4
            E2-09     Motor mechanical losses                     0.0%            No        -       -       A        -       No
6-62
                                                                                                                Control Methods
                                                                                        Change                                         Closed     Set by
 Parameter                                                                Factory                                Open        Closed
                                       Name                                             during                                          Loop       Auto-
    No.                                                                   Setting                       V/f       Loop        Loop
                                                                                       Operation                                       Vector     tuning
                                                                                                                 Vector      Vector
                                                                                                                                       for PM
   E2-10       Motor iron loss for torque compensation                   130 W *3          No           A           -          -             -     No
   E2-11/                                                                                               Q/         Q/          Q/
   E4-07
               Motor rated output power                                  3.70 kW*3         No
                                                                                                        A          A           A
                                                                                                                                             -     Yes
                                                                                                                                                           6-63
       Setting the V/f Pattern
         If E1-03 is set to F, the V/f pattern can be set individually using the parameters E1-04 to E1-10 (see Fig 6.25).
                                 Output voltage (V)
                                E1-05
                               (VMAX)
                               E1-13
                              (VBASE)
                               E1-08
                                (VB)
                               E1-10
                              (VMIN)
Frequency (Hz)
                       To set the V/f characteristics linear, set E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
             INFO
        Setting Precautions
         When a user-defined V/f pattern is used, consider the following points:
6          • By changing the control method, the parameters E1-07 to E1-10 are changed to the factory settings for the
             selected control method.
           • Be sure to set the four frequencies as follows:
             E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
6-64
  Motor Line-to-Line Resistance Setting (E2-05, E4-05)
    E2-05 is set automatically during motor line-to-line resistance autotuning. When it can not be performed for
    any reason, consult the motor manufacturer for the line-to-line resistance value. The set value should be calcu-
    late the motor test report line-to-line resistance value and the following formula:
     • E-type insulation: [Line-to line resistance (Ω) at 75°C of test report] × 0.92 (Ω)
     • B-type insulation: [Line-to line resistance (Ω) at 75°C of test report] × 0.92 (Ω)
     • F-type insulation: [Line-to line resistance (Ω) at 115°C of test report] × 0.87 (Ω)
  Related Parameters
                                                                                                               Control Methods
                                                                                         Change                                     Closed   Set by
    Parameter                                                           Factory                                 Open       Closed
                                        Name                                             during                                      Loop     Auto-
       No.                                                              Setting                        V/f      Loop        Loop
                                                                                        Operation                                   Vector   tuning
                                                                                                                Vector     Vector    (PM)
      E1-01        Input voltage setting                                400 V *1           No           Q          Q         Q        Q       No
      E1-04        Max. output frequency (FMAX)                         150 rpm            No           Q          Q         Q        Q       Yes
      E1-06        Base frequency (FA)                                  150 rpm            No           Q          Q         Q        Q       Yes
      E1-09        Min. output frequency (FMIN)                          0 rpm             No           Q          Q         A        A       Yes
      E1-13        Base voltage (VBASE)                                 400 V*1            No           A          A         -        Q       Yes
                                                                                                                                                      6-65
          Motor Rated Power (E5-02)
           Set E5-02 to the rated power value as written on the motor nameplate or in the motor data sheet.
6        Related Parameters
                                                                                                      Control Methods
                                                                                  Change                                Closed
           Parameter                                                   Factory                        Open     Closed
                                            Name                                   during                                Loop
              No.                                                      Setting                 V/f    Loop      Loop
                                                                                 Operation                              Vector
                                                                                                      Vector   Vector    (PM)
             F1-05     Encoder direction change                                      No        No       No       Q           Q
             S3-08     Output phase order                                 0          No        A        A        A           A
                              If Closed Loop Vector Control for PM motors is used, always perform an encoder offset tuning
                              after parameter S3-08 of F1-05 has been changed.
             IMPORTANT
6-66
Digital Operator/LED Monitor Functions
  Related Parameters
                                                                                            Change         Control Methods
   Parameter                                                                      Factory   during         Open Close Closed
                                                 Name                                                                    Loop
      No.                                                                         Setting   Opera-   V/f    Loop d Loop
                                                                                                                         Vector
                                                                                             tion          Vector Vector (PM)
     o1-01        Monitor selection                                                 6        Yes     A        A      A       A
     o1-02        Monitor selection after power up                                  1        Yes     A        A      A       A
                                                                                                     A        A      A
                                                                                                                             -
                                                                                                     0        0      0
     o1-03       Frequency units of reference setting and monitor                   i        No
                                                                                                                             A
                                                                                                      -       -      -
                                                                                                                             1
                                                                                                                     A
                                                                                                      -       -              -
                                                                                                                     0
     o1-04        Setting unit for frequency reference related parameters           i        No
                                                                                                                             A
                                                                                                      -       -      -
                                                                                                                             1
     o1-05        LCD Display contrast                                              3        Yes     A        A      A       A
     o2-02        STOP key during control circuit terminal operation                0        No      A        A      A       A
     o2-03        User parameter initial value                                      0        No      A        A      A       A
     o2-04       Inverter kVA selection                                             0*1      No      A        A      A       A
     o2-05        Frequency reference setting method selection                      0        No      A        A      A       A
                  Operation selection when digital operator/LED Monitor is dis-
     o2-06                                                                          0        No      A        A      A       A
                  connected
     o2-07        Cumulative operation time setting                                 0        No      A        A      A       A
     o2-08
     o2-09
                  Cumulative operation time selection
                  Initialize Mode
                                                                                    0
                                                                                    2
                                                                                             No
                                                                                             No
                                                                                                     A
                                                                                                     A
                                                                                                              A
                                                                                                              A
                                                                                                                     A
                                                                                                                     A
                                                                                                                             A
                                                                                                                             A     6
     o2-10        Fan operation time setting                                        0        No      A        A      A       A
     o2-12        Fault trace initialize                                            0        No      A        A      A       A
     o2-15        “Number of Travels” monitor initialize                            0        No      A        A      A       A
     S3-13        Traction sheave diameter                                        400 mm     No      A        A      A       A
     S3-14        Roping ratio                                                      2        No      A        A      A       A
     S3-15        Gear ratio                                                       1.000     No      A        A      A       A
                                                                                                                                  6-67
          • U1-20 (Output Frequency after Soft Start)
          • d1-01 to d1-17 (Frequency references)
        Display in Hz
         Set o1-03 to “0” to change the display unit of the above mentioned parameters to Hz.
        Display in%
         Set o1-03 to “1” to change the display unit for the above mentioned parameters to % related to the maximal
         frequency/speed set in parameter E1-04.
        Display in rpm
         Set o1-03 to the number of poles of the used motor to display the mentioned parameters in rpm.
        Display in m/s
         Set o1-03 to 3 to enable the display in m/s. The inverter uses the parameters S3-13 (traction sheave diameter),
         S3-14 (roping ratio) and S3-15 (gear ratio) to calculate the m/s display. To achieve an accurate display value
         these parameters must be set accurately.
       Changing the Units for Frequency Parameters Related to V/f settings (o1-04)
         Using parameter o1-04 the unit of the frequency parameters for the V/f setting can be set. If o1-04 is set to 0
         the unit is “Hz”. If o1-04 is set to 1 it is “rpm”. The parameter is available in Closed Loop Vector control only.
6-68
  Setting the Frequency Reference using the UP and DOWN Keys without Using the
   Enter Key (o2-05)
    This function is active when frequency references are input from the Digital Operator. When o2-05 is set to 1,
    the selected frequency reference can be incremented and decremented the UP and DOWN keys without using
    the Enter key. The function work only if parameter b1-01 is set to 0.
  Related Parameters
                                                                                               Control Methods
                                                                             Change
                                                                                                                 Closed
    Parameter                                                      Factory   during            Open Closed
                                           Name                                                                   Loop
       No.                                                         Setting   Opera-    V/f     Loop   Loop       Vector
                                                                              tion             Vector Vector      (PM)
      o3-01     Copy function selection                               0        No       A        A       A         A
      o3-02     Read permitted selection                              0        No       A        A       A         A
                                                                                                                          6-69
       Storing Inverter set values in the Digital Operator (READ)
         To store Inverter set values in the Digital Operator use the following method.
          Step
                                                        Explanation                                         Digital Operator Display
          No.
                                                                                                             -ADV-
                                                                                                             ** Main Menu **
           1     Press the Menu Key and select advanced programming mode.
                                                                                                                 Programming
                                                                                                             -ADV-
                                                                                                                  Initialization
           2     Press the DATA/ENTER Key.
                                                                                                                 A1 - 00=1
                                                                                                              Select Language
                                                                                                             -ADV-
                 Press the Increment and Decrement Key until parameter o3-01 is displayed (Copy Function      COPY Function
           3
                 Selection).                                                                                      o3 - 01=0
                                                                                                             Copy Funtion Sel
                                                                                                             -ADV-
                                                                                                             Copy Function Sel
           4     Press the DATA/ENTER Key and select the constants setting display.
                                                                                                                  o3-01= 0         *0*
                                                                                                                 COPY SELECT
                                                                                                             -ADV-
                                                                                                             Copy Function Sel
           5     Change the set value to 1 using the Increment Key.
                                                                                                                  o3-01= 1         *0*
                                                                                                              INV      OP READ
                                                                                                             -ADV-
                                                                                                                     READ
           6     Set the changed data using the DATA/ENTER Key. The READ function starts.
                                                                                                           INV     OP READING
6
                                                                                                             -ADV-
                                                                                                                     READ
           7     If the READ function ends normally, “End” is displayed on the Digital Operator.
                                                                                                           READ COMPLETE
                                                                                                             -ADV-
                                                                                                             Copy Function Sel
           8     The display returns to o3-01 when a key is pressed.                                              o3 - 01=0        *0*
                                                                                                                 COPY SELECT
         If an error is displayed, press any key to cancel the error display and return to the o3-01 display. Refer to
         page 7-16, Digital Operator Copy Function Faults for corrective actions.
       Writing Parameter Set Values Stored in the Digital Operator to the Inverter (COPY)
         To write parameter set values stored in the Digital Operator to the Inverter, use the following method.
          Step
                                                        Explanation                                         Digital Operator Display
          No.
                                                                                                             -ADV-
                                                                                                             ** Main Menu **
           1     Press the MENU Key and select advanced programming mode.
                                                                                                                 Programming
                                                                                                             -ADV-
                                                                                                                  Initialization
           2     Press the DATA/ENTER Key.
                                                                                                                 A1 - 00 = 1
                                                                                                              Select Language
6-70
Step
                                              Explanation                                        Digital Operator Display
No.
                                                                                                  -ADV-
       Press the Increment and Decrement Key until parameter o3-01 is displayed (Copy Function        COPY Function
  3
       Selection).                                                                                     o3 - 01 = 0
                                                                                                  Copy Funtion Sel
                                                                                                  -ADV-
                                                                                                  Copy Function Sel
  4    Press the DATA/ENTER Key and select the constants setting display.
                                                                                                       o3-01= 0       *0*
                                                                                                      COPY SELECT
                                                                                                  -ADV-
                                                                                                  Copy Function Sel
  5    Change the set value to 2 using the Increment Key.
                                                                                                        o3-01= 2      *0*
                                                                                                      OP   INV WRITE
                                                                                                  -ADV-
                                                                                                           COPY
  6    Set the changed data using the DATA/ENTER Key. The COPY function starts.
                                                                                                 OP     INV COPYING
                                                                                                  -ADV-
                                                                                                           COPY
  7    If the COPY function ends normally, “End” is displayed on the Digital Operator.
                                                                                                 COPY COMPLETE
                                                                                                  -ADV-
                                                                                                  Copy Function Sel
  8    The display returns to o3-01 when a key is pressed.
                                                                                                       o3 - 01 =0     *0*
                                                                                                      COPY SELECT
If an error is displayed, set the parameters again. Refer to page 7-16, Digital Operator Copy Function Faults
for corrective actions.                                                                                                      6
                                                                                                                            6-71
         Comparing Inverter Parameters and Digital Operator Parameter Set Values (VERIFY)
           To compare Inverter parameters and Digital Operator parameter set values, use the following method.
            Step
                                                           Explanation                                              Digital Operator Display
            No.
                                                                                                                      -ADV-
                                                                                                                      ** Main Menu **
             1      Press the MENU Key and select advanced programming mode.
                                                                                                                         Programming
                                                                                                                      -ADV-
                                                                                                                         Initialization
             2      Press the DATA/ENTER Key.
                                                                                                                         A1 - 00 = 1
                                                                                                                       Select Language
                                                                                                                      -ADV-
                    Press the Increment and Decrement Key until the parameter o3-01 is displayed (Copy Func-           COPY Function
             3
                    tion Selection).                                                                                     o3 - 01=0
                                                                                                                       Copy Funtion Sel
                                                                                                                      -ADV-
                                                                                                                      Copy Function Sel
             4      Press the DATA/ENTER Key and select the function setting display.
                                                                                                                          o3-01= 0        *0*
                                                                                                                       COPY SELECT
                                                                                                                      -ADV-
                                                                                                                      Copy Funtion Sel
             5      Change the set value to 3 using the Increment Key.
                                                                                                                          o3-01= 3        *0*
                                                                                                                    OP         INV VERIFY
                                                                                                                      -ADV-
                                                                                                                              VERIFY
             6      Set the changed data using the DATA/ENTER Key. The VERIFY function starts.
                                                                                                                    DATA VERIFYING
-ADV-
6            7      If the VERIFY function ends normally, “End” is displayed on the Digital Operator.
                                                                                                                              VERIFY
                                                                                                                   VERIFY COMPLETE
                                                                                                                      -ADV-
                                                                                                                      Copy Function Sel
             8      The display returns to o3-01 when a key is pressed.
                                                                                                                         o3 - 01 = 0      *0*
                                                                                                                       COPY SELECT
           If an error is displayed, press any key to cancel the error display and return to the o3-01 display. Refer to
           page 7-16, Digital Operator Copy Function Faults for corrective actions.
Application Precautions
                             When using the copy function, check that the following settings are the same between the Inverter data and the
                             Digital
                             • Inverter product and type
                 INFO        • Software number
                             • Inverter capacity and voltage class
                             • Control method
6-72
    If one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selection) is set to 1B (write
    parameters permitted), parameters can be written from the digital operator when the terminal that has been set
    is ON. When the set terminal is OFF, writing parameters other than the frequency reference is prohibited.
    However, the parameters can be read.
  Related Parameters
                                                                           Change          Control Methods
   Parameter                                                     Factory   during                             Closed
                                                                                            Open     Closed
                                        Name                                                                   Loop
      No.                                                        Setting   Opera-    V/f     Loop     Loop
                                                                                                              Vector
                                                                            tion            Vector   Vector    (PM)
     A1-01     Parameter access level                               2       Yes       A       A        A        A
 Setting a Password
    When a password is set in A1-05 and if the set values in A1-04 and A1-05 do not match, only the settings of
    parameters A1-01 to A1-03, or A2-01 to A2-32 can be modified.
    The setting of all parameters except A1-00 can be prohibited using the password function in combination with
    setting parameter A1-01 to 0 (Monitor only).
  Related Parameters
                                                                           Change          Control Methods
   Parameter                                                     Factory   during                             Closed
                                                                                            Open     Closed
                                        Name                                                                   Loop
      No.                                                        Setting   Opera-    V/f     Loop     Loop
                                                                                                              Vector
                                                                            tion            Vector   Vector    (PM)
     A1-01     Parameter access level                               2        No       A       A        A        A
     A1-04
     A1-05
               Password
               Password setting
                                                                    0
                                                                    0
                                                                             No
                                                                             No
                                                                                      A
                                                                                      A
                                                                                              A
                                                                                              A
                                                                                                       A
                                                                                                       A
                                                                                                                A
                                                                                                                A
                                                                                                                        6
  Setting a Password
    The password can be set in parameter A1-05. Normally A1-05 is not displayed. To display and modify A1-05
    the MENU and Reset key must be pressed together in the A1-04 display.
                                                                                                                       6-73
        Displaying User-set Parameters Only
           The A2 parameters (user-set parameters) and A1-01 (parameter access level) can be used to establish a param-
           eter set that contains only the most important parameters.
           Set the number of the parameter to which should appear in the A2- parameters, and then set A1-01 to 1.
           The advanced programming mode now allows to read and modify A1-01 to A1-03 and the parameters set in
           A2-01 to A2-32 only.
         Related Parameters
                                                                                                 Control Methods
                                                                                Change                             Closed
          Parameter                                                  Factory                     Open     Closed
                                                Name                            during                              Loop
             No.                                                     Setting               V/f    Loop     Loop
                                                                               Operation                           Vector
                                                                                                 Vector   Vector    (PM)
            A2-01
             to       User setting parameters                           -         No       A       A        A
            A2-32
6-74
PG Option Cards
   To have a more precise speed control the inverter can be equipped with a PG option card for the connection of
   a pulse generator. Three different PG cards can be used, the PG-B2, the PG-X2 and the PG-F2 card. Refer to
   page 2-24, Option Card Models and Specifications to see details.
 PG Setup
 Related Parameters
                                                                               Change            Control Methods
   Parameter                                                         Factory   during                               Closed
                                                                                                  Open     Closed
                                         Name                                                                        Loop
      No.                                                            Setting   Opera-      V/f     Loop     Loop
                                                                                                                    Vector
                                                                                tion              Vector   Vector    (PM)
                                                                                                             Q
                                                                                                                      -
                                                                                                            1024
     F1-01     PG constant                                              i        No        No      No
                                                                                                                     Q
                                                                                                             -
                                                                                                                    2048
                                                                                                             Q
                                                                                                                      -
                                                                                                             0
     F1-05     PG rotation                                              i        No        No      No
                                                                                                                      Q
                                                                                                             -
                                                                                                                      1
     F1-06     PG division rate (PG pulse monitor)                      1        No        No      No        A        A
     F1-21     Absolute encoder resolution                              2        No        No      No       No        A
     F1-22     Magnet position offset                                  60°       No        No      No       No        A
                  If Open Loop Vector control for IM is used and a PG-B2/X2 card is installed, the speed detected by the
                  PG card is displayed in the monitor parameter U1-05. Therefore the PG constant has to be set in parame-
                  ter F1-01. The direction of the speed detection can be changed by parameter F1-05.
   IMPORTANT
                  To change the U1-05 value to the internally calculated speed value remove the PG card.
                                                                                                                             6-75
       Suit the PG Rotation Direction and Motor Rotation Direction (F1-05)
         Parameter F1-05 can be used to change the encoder signal direction if it is wrong.
          • If F1-05 is set to 0 the inverter expects channel A to lead 90° before channel B (Sin-channel leads 90°
             before Cos-channel on PG-F2 card) if a forward command is applied (FWD means counterclockwise rota-
             tion seen from the shaft side).
          • If F1-05 is set to 1 the inverter expects channel B to lead 90° before channel B (Cos-channel leads 90°
             before Sin-channel on PG-F2 card) if a forward command is applied.
                            If Closed Loop Vector Control for PM motors is used, an encoder offset autotuning must be per-
                            formed if parameter F1-05 is changed.
           IMPORTANT
         The division ratio can be set within the following range: 1/32 ≤ F1-06 ≤ 1. For example, if the division ratio is
         1/2 (set value 2), half of the number of pulses from the PG are output at the pulse monitor.
       Setting Number of Gear Teeth Between PG and Motor (F1-12 and F1-13)
6        If there are gears between the motor and PG, the gear ratio can be set using F1-12 and F1-13.
         When the number of gear teeth has been set, the number of motor rotations within the Inverter is calculated
         using the following formula.
         No. of motor rotations (r/min.) = No. of input pulses from PG × 60 / F1-01 × F1-13 (No. of gear teeth on PG
         side) / F1-12 (No. of gear teeth on motor side)
6-76
 Fault Detection
  Related Parameters
                                                                             Change         Control Methods
   Parameter                                                      Factory    during                            Closed
                                                                                             Open     Closed
                                           Name                                                                 Loop
      No.                                                         Setting    Opera-   V/f     Loop     Loop
                                                                                                               Vector
                                                                              tion           Vector   Vector    (PM)
     F1-02     Operation selection at PG open circuit (PGO)          1          No     -       -        A        A
     F1-03     Operation selection at overspeed (OS)                 1          No     -       -        A        A
     F1-04     Operation selection at deviation (DEV)                3          No     -       -        A        A
     F1-08     Overspeed detection level                           115%         No     -       -        A        A
     F1-09     Overspeed detection time                           0.0 sec.      No     -       -        A        A
     F1-10     Speed deviation detection level                     10%          No     -       -        A        A
     F1-11     Speed deviation detection time                     0.5 sec.      No     -       -        A        A
     F1-14     PG open-circuit detection delay time                2.0 s        No     -       -        A        A
     F1-18     DV3 detection selection                               1          No     -       -        -        A
     F1-19     DV4 detection selection                             1024         No     -       -        -        A
     F1-21     Absolute encoder resolution                           2          No     -       -        -        A
     F1-22     Magnet position offset                               60°         No     -       -        -        A
     F1-24     PGO detection Level at stop                          20%         No     -       -        -        A
  Detecting a Speed Deviation between the Motor and Speed Reference (F1-04, F1-10
   and F1-11)
    A speed deviation fault is detected when the speed deviation (i.e., the difference between the speed reference
    and the actual motor speed) is too large. Speed deviation (DEV) is detected only after a speed agreement
    (speed reference and actual motor speed are within the setting range of L4-02) and if a speed deviation higher
    than the set value in F1-10 continues for longer than the time set in F1-11. After a speed deviation is detected,
    the Inverter stops according to the setting in F1-04.
  Detecting a Wrong Rotation Direction DV3 (F1-18, Closed Loop Vector for PM only)
    A DV3 fault indicates a wrong motor rotation direction. It is detected if
     • the speed deviation is higher than 30% and
     • the internal torque reference value and the acceleration have opposite signs
    The fault is detected after the time F1-18 x 5 ms.
                                                                                                                        6-77
         Detecting a Wrong Rotation Direction DV4 (F1-19, Closed Loop Vector for PM only)
           A DV4 fault indicates a wrong motor rotation direction. It is detected if
            • the reference direction and the motor rotation direction have opposite signs and
            • the deviation is higher than the value of parameter F1-19 (set in encoder pulses).
         Related Parameters
                                                                                   Change            Control Methods
          Parameter                                                      Factory    during                               Closed
                                                                                                      Open      Closed
                                                  Name                                                                    Loop
             No.                                                         Setting   Opera-      V/f     Loop      Loop
                                                                                                                         Vector
                                                                                     tion             Vector    Vector    (PM)
            F1-25      Encoder copy selection                               0          No      No       No       No        A
            F1-26      Encoder write protection                            0           No      No       No       No        A
         Saved Parameters
           The following parameters are saved in the encoder memory:
             • E1-04         Motor maximal speed                        • E5-06        Motor d axis inductance Ld
             • E1-06         Motor rated speed                          • E5-07        Motor q axis inductance Lq
             • E1-13         Motor rated voltage                        • E5-09        Motor voltage constant Ke
6            • E5-02
             • E5-03
                             Motor rated power
                             Motor rated current
                                                                        • F1-01
                                                                        • F1-05
                                                                                       PG pulse constant
                                                                                       PG rotation direction
             • E5-04         Motor pole number                          • F1-21        Absolute encoder selection
             • E5-05         Motor line-to-line resistance              • F1-22        Magnet position offset
6-78
Verify Saved Parameters
  To compare the parameters stored in the inverter and encoder the parameter F1-23 must be set to 3 (“EVRFY,
  DATA VERIFYING” is displayed during the verify process).
  If the data are identically, the display will show “EVRFY, VERIFY COMPLETE”.
  If the data do not match, “EVRFY, VERIFY ERROR” will be displayed.
                                                                                                               6-79
       Rescue System
          Using rescue operation the car can be moved to the next floor if the power supply fails. In this case the inverter
          must be supplied by a UPS or a battery and the rescue operation must be enabled by a digital input (H1- =
          85). The DC bus voltage during rescue operation has to be set in parameter L2-11. A light load detection func-
          tion can be used to detect the light load direction for the car evacuation.
        Related Parameters.
                                                                                                                      Control Methods
                                                                                           Change                                         Closed
            Parameter                                                        Factory                                  Open     Closed
                                               Name                                        during                                          Loop
               No.                                                           setting                      V/f          Loop     Loop
                                                                                          operation                                       Vector
                                                                                                                      Vector   Vector      (PM)
              d1-05      Rescue operation speed                                5 Hz           No           A             A         A        A
              L2-11      DC bus voltage during rescue operation                 0V            No           A             A         A        A
              S3-06      Light Load Search for rescue operation                  0            No           A             A         A        A
              S3-07      Light Load Search time for rescue operation          1.0 sec.        No           A             A         A        A
              S3-10      Light Load Search speed                              3.00 Hz         No           A             A         A        A
              S3-11      Rescue operation torque limit                         100%           No           -             A         A        A
              S3-24      Light load search method                                0            No           A             A         -         -
                            When an AC power supply (e.g. a single phase UPS like example 1 or 2 below) is used,
                            make sure that the rectified voltage meets the voltage range above.
            IMPORTANT
6-80
Rescue operation wiring examples
         The following diagrams show some wirings examples for rescue operation.
                           Elevator
                                                                                                        Contactor B
                           Control
                           System                                              Inverter                 Contactor A
                                              A        B2
     N         UPS                                     B1
              1X230
               VAC
                                                                                                       U/T1
                                                         R/L1
     L1                                                                                                V/T2
                                                         S/L2
     L2                                                                                                W/T3
                                                         T/L3
     L3
                                      B                  -
                                                                         Power        Control
                                                                         Supply       circuit
                                                       P0
N0
                                                         Sx
                      Rescue Operation
                        Enable Input                     SC
         The contactors must be operated, so that contactor B is always opened, before A is closed. When the rescue
         operation is finished, the contactor A must be opened, before B is closed.
         If the UPS power is weak or Light load detection is not used, it can happen that the inverter trips with a UV2
         fault. In this case increase the UPS power, use the light load detection function or use the configuration in
         example 2.
     Example 2:               1 Phase, 230 V UPS Power Supply, Low power UPS or Light Load detection not
                                                                                                                             6
                                 used
                                          A       B2                                                    Contactor A
N           UPS                                   B1                                                   Contactor B
           1X230
            VAC                                                                                        Contactor C
                                                                                                U/T1
                                                  R/L1
L1                                                                                              V/T2
                                                  S/L2
L2                                                                                              W/T3
                                                  T/L3
L3
                                 B                -
                                                                Power Supply      Control
                            Rectifier Diode                                       circuit
                             and Capacity         P0
                                         C
                                                  N0
                                                  Sx
            Rescue Operation
                Enable Input                      SC
         The contactors must be operated, so that contactor B is always opened, before A and C are closed. Contactor C
         can be closed after A but not before. When the rescue operation is disabled, the contactors A and C must be
         opened, before B is closed.
                                                                                                                            6-81
         Example 3:                       Two Batteries, Main battery voltage lower than 280 VDC.
                   Wiring                                                          Inverter                                                  Contactor Sequence
                                                      B2                                                                                       Contactor B
                                                                                                                                               Contactor A
                                                      B1
                               A                                                                                                                Contactor C
                                                      +2
                                                      +1                                                                           U/T1
                                     Main power
                                                  B
                                                      R/L1
          Main                        L1                                                                                           V/T2
         Battery
                                                      S/L2
                                       L2                                                                                          W/T3
                                                      T/L3
                                      L3
                                                       -
                                                                         Power Supply              Control
                                                                                                   circuit
                                                      P0
                Controller
              Supply Battery
                                          C
                                                      N0
                        Rescue Opertion               Sx
                           Enable Input
                                                      SC
             The contactors must be operated, so that contactor B is always opened, before A and C are closed. Contactor C
             can be closed after A but not before. When the rescue operation is disabled, the contactors A and C must be
             opened, before B is closed.
6
                                                                                                                                       U/T1
                                   Main power     B
                                                      R/L1
        Main                          L1                                                                                               V/T2
       Battery                                        S/L2
                                      L2                                                                                               W/T3
                                                      T/L3
                                      L3
                                                       -
                                                                          Power Supply                Control
                                                                                                      Circuit
                                                      P0
N0
                                                      Sx
                    Rescue Operation
                        Enable Input                  SC
             The contactors must be operated, so that contactor B is always opened, before A is closed. When the rescue
             operation is disabled, the contactor A must be opened, before B is closed.
       Precautions
             Because of the possibly low DC bus voltage during rescue operation, the heatsink cooling fans may not work.
             A continuous operation under this condition can result in over heat faults and inverter damage.
6-82
Torque Limits during Rescue Operation
  Depending on the rescue system it might be useful to apply a torque limit. The torque limit for rescue opera-
  tion can be set in parameter S3-11. It is active only if the rescue operation digital input is set an has no effect
  to the normal operation.
                            DI Rescue
                             operation
                              External
                        Controller Fwd                        Torque is measured
                          or Rev Run                          after speed agree for
                                                              the time S3-07
                                                   FWD
                       Internal Fwd Run
                                                                        REV           Car evacuation in forward direction
                       Internal Rev Run
                            DI Rescue
                             operation
                               External
                         Controller Fwd                       Torque is measured
                           or Rev Run                         after speed agree for
                                                              the time S3-07
                                                   FWD
                       Internal Fwd Run
                                                                        REV           Car evacuation in reverse direction
                       Internal Rev Run
                                                                                                                            6-83
       Automatic Fault Reset
          The inverter can reset faults automatically. The maximum number of resets can be selected as well as the oper-
          ation mode of the fault relay.
          Auto-resetable Fault codes are: UV1, GF, OC, OV, OL2, OL3, OL4, UL3, UL4, PF, LF, SE1, SE2, SE3
        Related Constants.
                                                                                                                Control Methods
                                                                                       Change                                       Closed
            Parameter                                                      Factory                              Open     Closed
                                                Name                                   during                                        Loop
               No.                                                         setting                   V/f         Loop     Loop
                                                                                      operation                                     Vector
                                                                                                                Vector   Vector      (PM)
              L5-01       Number of restarts                                 2            No          A            A         A         A
              L5-02       Restart operation selection                        1            No          A            A         A         A
              L5-05       UV1 auto reset selection                           0            No          A            A         A         A
        Working Principle
          Whenever a fault occurs, the inverter output is cut and the brake is closed. A fault is output. When the auto-
          matic fault reset is enabled, the fault is reset 2 seconds after the Up/Down signal has been removed. The
          inverter can be restarted. This can be repeated for the number of times set in L5-02. The restart counter is reset
          when the power supply is switched off.
6 Fault
                                                           DC Injection/
                                                            Zero servo
                                               Speed
                                           Up/Down
                            Brake Open Command
                                       Fault Output
                                        Auto-Reset
6-84
Fault Restart Indication
  When the fault retry function is used, the inverter tries to reset the fault every 5 ms. If a digital output is pro-
  grammed for the “Restart enable” function (H2-=1E), the output is set as long as the inverter tries to reset
  the fault. After a successful fault reset the output is cleared.
                                                                                                                         6-85
       Memobus Communications
        Communications Specifications
           The MEMOBUS communications specifications are shown in the following table.
                        Item                                                   Specifications
         Interface                       RS-232 (not isolated)
                                         Baud rate:         9,600 bps
                                         Data length:       8 bits fixed
         Communications Parameters
                                         Parity:            none
                                         Stop bits:         1 bit fixed
         Communications Protocol         MEMOBUS
         Number of Connectable Units     1
        Memobus Operations
           MEMOBUS communications can perform the following operations:
             • Monitoring operation status of the inverter
             • Setting and reading parameters (for the parameter register numbers refer to the L7X manual)
6  Message Content
        Message Format
           In MEMOBUS communications, the master sends commands to the slave, and the slave responds. The mes-
           sage format is configured for both sending and receiving as shown below, and the length of data packets
           depends on the command (function) content.
                                                             Slave address
Function code
Data
Error check
         Slave Address
           The slave address can not be set in the inverter. The slave address field in the message can contain any address
           from 0 to 31.
6-86
Function Code
 The function code specifies commands. The three function codes shown in the table below are available.
                                                             Command Message           Response Message
Function Code
                                  Function
(Hexadecimal)                                             Min. (Bytes) Max. (Bytes) Min. (Bytes) Max. (Bytes)
Data
 Configure consecutive data by combining the memory register address (test code for a loop back address) and
 the data the register contains. The data length changes depending on the command details.
Error Check
 Errors during communications are detected using CRC-16 (cyclic redundancy check, checksum method).
 The result of the checksum calculation is stored in a data-word (16 bit), which starting value is FFFH. The
 value of this word is manipulated using Exclusive OR- and SHIFT operations together with the data package
 that should be sent (slave address, function code, data) and the fixed value A001H. At the end of the calcula-
 tion the data-word contains the checksum value.
 The checksum is calculated in the following way:
 1. The starting value of the 16 Bit data-word, that is used for the calculation, has to be set to FFFFH.
 2. An Exclusive OR operation has to be performed with the starting value and the slave address.
 3. The result has to be shifted to the right until the overflow bit becomes 1.
 4. When this bit becomes 1, an Exclusive OR operation with the result of step 3 and the fix value A001H has
    to be performed.
 5. After 8 shift operations (every time when the overflow bit becomes 1, an Exclusive OR like in step 4 has to     6
    be done), perform an Exclusive OR operation with the result of the former operations and the next data
    package (8 bit function code). Again the result of this operation has to be shifted 8 times and if needed it
    has to be interconnected with the fix value A001H using an Exclusive OR operation.
 6. The same steps have to be performed with the data, first with the higher byte and then with the lower byte
    until all data are proceeded.
 7. The result of these operations is the checksum. It consists of a high and a low byte.
                                                                                                                   6-87
       The following example clarifies the calculation method. It shows the calculation of a CRC-16 code with the
       slave address 02H (0000 0010) and the function code 03H (0000 0011). The resulting CRC-16 code is D1H
       for the lower and 40H for the higher byte. The example calculation in this example is not done completely
       (normally data would follow the function code).
                                  Calculations        Overflow       Description
                              1111 1111 1111 1111                    Initial value
                                          0000 0010                    Address
                              1111 1111 1111 1101                    ExOr Result
                              0111 1111 1111 1110        1              Shift 1
                              1010 0000 0000 0001
                              1101 1111 1111 1111                    ExOr Result
                              0110 1111 1111 1111        1             Shift 2
                              1010 0000 0000 0001
                              1100 1111 1111 1110                    ExOr Result
                              0110 0111 1111 1111        0             Shift 3
                              0011 0011 1111 1111        1             Shift 4
                              1010 0000 0000 0001
                              1001 0011 1111 1110                    ExOr Result
                              0100 1001 1111 1111        0             Shift 5
                              0010 0100 1111 1111        1             Shift 6
                              1010 0000 0000 0001
                              1000 0100 1111 1110                    ExOr Result
                              0100 0010 0111 1111        0             Shift 7
                              0010 0001 0011 1111        1             Shift 8
                              1010 0000 0000 0001
                              1000 0001 0011 1110                    ExOr Result
                                        0000 0011                   Function Code
                              1000 0001 0011 1101                    ExOr Result
6                             0100 0000 1001 1110
                              1010 0000 0000 0001
                                                         1             Shift 1
6-88
MEMOBUS Message Example
  An example of MEMOBUS command/response messages is given below.
                                                                                                                   6-89
       Writing to Multiple Inverter Memory Registers
        The writing of inverter memory registers works similar to the reading process, i.e. the address of the first reg-
        ister that has to be written and the number of registers must be set in the command message.
        The data registers which shall be written must be consecutive, starting from the specified address in the com-
        mand message. The data order must be higher 8 bits, then lower 8 bits. The data must be in memory register
        address order.
        The following table shows an example of a message where a forward operation has been set with a frequency
        reference of 60.0 Hz for the inverter with the slave address 01H.
                                                           Response Message                             Response Message
                Command Message
                                                       (During Normal Operation)                         (During Error)
            Slave Address            01H               Slave Address          01H                  Slave Address           01H
            Function Code            10H              Function Code           10H                  Function Code           90H
                       Higher        00H                         Higher       00H                    Error code            02H
       Start Address                             Start Address
                       Lower         01H                         Lower        01H                              Higher      CDH
                                                                                               CRC-16
                       Higher        00H                         Higher       00H                              Lower       C1H
         Quantity                                  Quantity
                       Lower         02H                         Lower        02H
              No. of data            04H                         Higher       10H
                                                   CRC-16
                       Higher        00H                         Lower        08H
        Lead data
                       Lower         01H
                       Higher        02H
        Next data
                       Lower         58H                                           * No. of data = 2 x (quantity)
                       Higher        63H
         CRC-16
                       Lower         39H
For the number of data value in the command message the double value of the data quantity must be
6 IMPORTANT
6-90
Monitor Data
  The following table shows the monitor data. Monitor data can only be read.
 Register Address.                                                                 Contents
                     Inverter status signal
                            Bit 0         During run
                            Bit 1         Zero speed
                            Bit 2         During reverse operation
                            Bit 3         Reset signal active
                            Bit 4         During speed agree
      0010H
                            Bit 5         Inverter ready
                            Bit 6         Minor fault
                            Bit 7         Major fault
                         Bits 8 to D      Not used
                            Bit E         ComRef status
                            Bit F         ComCtrl status
                     Operator status
                            Bit 0         During OPE alarm
                            Bit 1         During fault
      0011H
                            Bit 2         Operator in programming mode
                            Bit 3         0: Digital operator attached    1: PC connected
                          Bit 4 to F      Not used
      0012H          OPE Fault Number
      0013H          Not used
                     Fault Content 1
                            Bit 0         PUF, DC bus fuse blown
                            Bit 1         UV1
                            Bit 2         UV2
                            Bit 3         UV3
                            Bit 4         Not used
                            Bit 5         GF, Ground fault
                            Bit 6         OC, Over current
      0014H                 Bit 7         OV, DC bus over voltage
                            Bit 8
                            Bit 9
                                          OH, Inverter heatsink overheat pre-alarm
                                          OH1, Inverter heatsink overheat
                                                                                               6
                            Bit A         OL1, Motor overload
                            Bit B         OL2, Inverter overload
                            Bit C         OL3, Overtorque detection 1
                            Bit D         OL4, Overtorque detection 2
                            Bit E         RR, Internal braking transistor fault
                            Bit F         RH, Inverter mounted braking resistor overheat
                     Fault Content 2
                            Bit 0         EF3, External fault set on terminal S3
                            Bit 1         EF4, External fault set on terminal S4
                            Bit 2         EF5, External fault set on terminal S5
                            Bit 3         EF6, External fault set on terminal S6
                            Bit 4         EF7, External fault set on terminal S7
                            Bit 5         Not used
                            Bit 6         Not used
      0015H                 Bit 7         OS, Overspeed detected
                            Bit 8         DEV, Speed deviation detected
                            Bit 9         PGO, PG disconnected
                            Bit A         PF, Input phase loss
                            Bit B         LF, Output open phase
                            Bit C         OH3, Motor overheat pre-alarm (PTC analog input)
                            Bit D         OPR, Digital operator disconnected
                            Bit E         ERR, EPROM error
                            Bit F         Not used
                                                                                              6-91
       Register Address.                                                              Contents
                           Fault Content 3
                                  Bit 0      CE, Memobus communications error
                                  Bit 1      BUS, Bus option communications error
                                 Bit 2/3     Not used
                                  Bit 4      CF, Control fault
            0016H                 Bit 5      SVE, Zero servo fault
                                  Bit 6      EF0, External fault from optional input card
                                  Bit 7      Not used
                                  Bit 8      UL3, Undertorque detection 1
                                  Bit 9      UL4, Undertorque detection 2
                               Bit A to F    Not used
                           CPF Fault Content 1
                                 Bit 0/1     Not used
                                  Bit 2      CPF02
                                  Bit 3      CPF03
            0017H
                                  Bit 4      Not used
                                  Bit 5      CPF05
                                  Bit 6      CPF06
                               Bit 7 to F    Not used
                           CPF Fault Content 2
                                  Bit 0      CPF20
                                  Bit 1      CPF21
            0018H
                                  Bit 2      CPF22
                                  Bit 3      CPF23
                               Bit 4 to F    Not used
                           Alarm Content 1
                                  Bit 0      UV, DC bus undervoltage
                                  Bit 1      OV, DC bus overvoltage
                                  Bit 2      OH, Inverter heatsink overheat pre-alarm
                                  Bit 3      OH2, Inverter overheat alarm input by a digital input
                                  Bit 4      OL3, Overtorque detection 1
6           0019H
                                  Bit 5
                                  Bit 6
                                  Bit 7
                                             OL4, Overtorque detection 2
                                             EF, Forward/Reverse input set at the same time
                                             BB, Baseblock active
                                  Bit 8      EF3, External alarm set on terminal S3
                                  Bit 9      EF4, External alarm set on terminal S4
                                 Bit A       EF5, External alarm set on terminal S5
                                 Bit B       EF6, External alarm set on terminal S6
                                 Bit C       EF7, External alarm set on terminal S7
                                Bit D/E      Not used
                                 Bit F       OS, Overspeed alarm
                           Alarm Content 2
                                  Bit 0      DEV, Speed deviation
                                  Bit 1      PGO, PG disconnected
                                  Bit 2      OPR, Digital operator disconnected
                                  Bit 3      CE, Memobus communications error
                                  Bit 4      BUS, Communications error
                                  Bit 5      CALL, Memobus communications on standby
            001AH
                                  Bit 6      OL1, Motor overload
                                  Bit 7      OL2, Inverter overload
                               Bit 8 to B    Not used
                                 Bit C       CALL, Communications on standby
                                 Bit D       UL3, Undertorque detection 1
                                 Bit E       UL4, Undertorque detection 2
                                 Bit F       Not used
            001BH          Not used
6-92
Register Address.                                                                Contents
                    Inverter status
                           Bit 0        Forward operation
                           Bit 1        Reverse operation
                           Bit 2        Inverter startup complete    1: Completed 2: Not completed
                           Bit 3        Error
     0020H
                           Bit 4        Data setting error
                           Bit 5        Multi-function contact output 1 (terminal M1 - M2)    1: ON 0: OFF
                           Bit 6        Multi-function contact output 2 (terminal M3 - M4)    1: ON 0: OFF
                           Bit 7        Multi-function contact output 3 (terminal M5 - M6)    1: ON 0: OFF
                        Bits 8 to F     Not used
                    Error details
                           Bit 0        Overcurrent (OC), Ground fault (GF)
                           Bit 1        Main circuit overvoltage (OV)
                           Bit 2        Inverter overload (OL2)
                           Bit 3        Inverter overheat (OH1, OH2)
                           Bit 4        Braking transistor/resistance overheat (rr, rH)
                           Bit 5        Fuse blown (PUF)
                           Bit 6        Not used
                           Bit 7        External error (EF, EFO)
     0021H
                           Bit 8        Control board error (CPF)
                           Bit 9        Motor overload (OL1) or overtorque 1 (OL3) detected
                           Bit A        PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)
                           Bit B        Main circuit undervoltage (UV) detected
                                        Main circuit undervoltage (UV1), control power supply error (UV2), inrush prevention circuit error (UV3),
                           Bit C
                                        power loss
                           Bit D        Missing output phase (LF)
                           Bit E        MEMOBUS communications error (CE)
                           Bit F        Operator disconnected (OPR)
                    Data link status
                           Bit 0        Writing data
                           Bit 1        Not used
     0022H                 Bit 2        Not used
                           Bit 3
                           Bit 4
                                        Upper and lower limit errors
                                        Data integrity error
                                                                                                                                                     6
                        Bits 5 to F     Not used
                    Frequency refer-
     0023H                              Monitors U1-01
                    ence
     0024H          Output frequency    Monitors U1-02
     0025H          Output voltage      Monitors U1-06
     0026H          Output current      Monitors U1-03
     0027H          Output power        Monitors U1-08
     0028H          Torque reference    Monitors U1-09
     0029H          Not used
     002AH          Not used
                    Control terminals input status
                           Bit 0        Input terminal S1                  1: ON 0: OFF
                           Bit 1        Input terminal S2                  1: ON 0: OFF
                           Bit 2        Multi-function input terminal S3     1: ON 0: OFF
     002BH                 Bit 3        Multi-function input terminal S4     1: ON 0: OFF
                           Bit 4        Multi-function input terminal S5     1: ON 0: OFF
                           Bit 5        Multi-function input terminal S6     1: ON 0: OFF
                           Bit 6        Multi-function input terminal S7     1: ON 0: OFF
                        Bits 7 to F     Not used
                                                                                                                                                    6-93
       Register Address.                                                                Contents
                             Inverter status
                                    Bit 0         Operation                            1: Operating
                                    Bit 1         Zero speed                           1: Zero speed
                                    Bit 2         Frequency agree                      1: Agreement
                                    Bit 3         User-defined speed agree             1: Agreement
                                    Bit 4         Frequency detection 1:               1: Output frequency ≤ L4-01
                                    Bit 5         Frequency detection 2:               1: Output frequency ≥ L4-01
                                    Bit 6         Inverter startup completed           1: Startup completed
            002CH                   Bit 7         Undervoltage detection               1: Detected
                                    Bit 8         Baseblock                            1: Inverter output baseblock
                                    Bit 9         Frequency reference mode             1: Not communication 0: Communication option
                                    Bit A         Run command mode                     1: Not communication 0: Communication option
                                    Bit B         Overtorque detection                 1: Detected
                                    Bit C         Frequency reference lost             1: Lost
                                    Bit D         Restart enabled                      1: Restarting
                                    Bit E         Error (including MEMOBUS communications time-out)           1:Error occurred
                                    Bit F         MEMOBUS communications time-out1: Timed out
                             Multi-function contact output status
                                    Bit 0         Multi-function contact output 1 (terminal M1-M2)     1: ON     0: OFF
            002DH                   Bit 1         Multi-function contact output 2 (terminal M3-M4)     1: ON     0: OFF
                                    Bit 2         Multi-function contact output 3 (terminal M5-M6)     1: ON     0: OFF
                                 Bits 3 to F      Not used
        002EH - 0030H        Not used
            0031H            Main circuit DC voltage
            0032H            Torque Monitor U1-09
            0033H            Power Monitor U1-08
        0034H - 003AH        Not used
            003BH            CPU software number
            003CH            Flash software number
                             Communications error details
                                    Bit 0         CRC error
6           003DH
                                    Bit 1
                                    Bit 2
                                    Bit 3
                                                  Invalid data length
                                                  Not used
                                                  Parity error
                                    Bit 4         Overrun error
                                    Bit 5         Framing error
                                    Bit 6         Time-out
                                 Bits 7 to F      Not used
            003EH            kVA setting
            003FH            Control method
Note: Communications error details are stored until an error reset is input.
6-94
 Inverter Error Codes
    The content of a current fault and faults that have occurred earlier can be read out by Memobus using the Fault
    Trace (U2-) and the Fault History (U3-) parameters. The fault codes are shown in the table below.
         Fault                                       Fault                                         Fault
                      Fault Description                             Fault Description                      Fault Description
         Code                                        Code                                          Code
         01H                  PUF                    14H                     EF6                   37H             SE1
         02H                  UV1                     15H                    EF7                   38H             SE2
         03H                  UV2                     18H                     OS                   39H             SE3
         04H                  UV3                     19H                   DEV                    83H           CPF02
         06H                   GF                    1AH                    PGO                    84H           CPF03
         07H                   OC                    1BH                      PF                   85H           CPF04
         08H                   OV                    1CH                      LF                   86H           CPF05
         09H                   OH                    1DH                     OH3                   87H           CPF06
         0AH                  OH1                     1EH                    OPR                   88H           CPF07
         0BH                  OL1                     1FH                    ERR                   89H           CPF08
         0CH                  OL2                     21H                     CE                   8AH           CPF09
         0DH                  OL3                     22H                    BUS                   8BH           CPF10
         0EH                  OL4                     25H                     CF                   91H           CPF20
         0FH                   RR                     26H                    SVE                   92H           CPF21
         10H                   RH                     27H                    EF0                   93H           CPF22
         11H                   EF3                    28H                    FBL                   94H           CPF23
         12H                   EF4                    29H                    UL3
         13H                   EF5                   2AH                     UL4
                                                                                                                                           6
 ENTER Command
    When parameters are written in the Inverter from a PC/PLC using MEMOBUS communications, the parame-
    ters are temporarily stored in the parameter data area of the Inverter. To enable these parameters in the param-
    eter data area, an ENTER command must be used.
    There are two types of ENTER commands:
     • ENTER commands that enable parameter data in RAM only (changes will be lost after power loss)
     • ENTER commands that write data into the EEPROM (non-volatile memory) of the Inverter and enable the
       data in RAM at the same time.
        Register Address.                                                   Contents
             0900H          Write parameter data to EEPROM, RAM is refreshed
             0910H          Parameter data are not written to EEPROM, but refreshed in RAM only.
                      • The EEPROM can be written up to 100,000 times only. Do not frequently execute ENTER commands (0900H)
                        which write into the EEPROM.
                      • The ENTER command registers are write-only registers. Consequently, if these registers are read out, error code
      IMPORTANT         02H is returned.
                      • An ENTER command is not required if reference or broadcast data are sent to the inverter.
                                                                                                                                          6-95
        Communication Error Codes
          The following table shows MEMOBUS communications error codes.
          Error Code                                                        Contents
                        Function code error
             01H
                        A function code other than 03H, 08H, or 10H has been set by the PLC.
6-96
                                                                                          7
                           Troubleshooting
This chapter describes the fault displays and countermeasures for Inverter and motor problems.
           This section describes the fault and alarm functions of the Inverter. These functions include fault detection,
           alarm detection, programming error detection and auto-tuning error detection.
       Fault Detection
           When the Inverter detects a fault, the fault contact output is operated and the Inverter output is switched OFF
           and the motor coasts to stop. (The stopping method can be selected for some faults.) A fault code is displayed
           on the Digital Operator/LED Monitor.
           The faults can be categorized in two groups:
            • Faults that can be reset without cycling the power using an input or the reset key at the Digital Operator
              (resetable faults)
            • Faults that require to cycle the power (non-resetable faults)
           When a fault has occurred refer to the following to identify the fault and to correct the causes.
           To reset a fault it is necessary to remove the RUN signal and correct the fault reason. Otherwise a Reset is not
           accepted or the Inverter trips with the same fault again.
           The following tables shows a list of faults and corrective actions.
7-2
                                               Table 7.1 Resetable Faults
     Display                       Meaning                              Probable Causes                           Corrective Actions
                                                              The deceleration time is set too short      Increase the deceleration time (C1-
                                                              and the regenerative energy from the        02/04/06/08) or connect a braking
                    DC Bus Overvoltage                        motor is too large.                         option.
                    The DC bus voltage has exceeded the
                    overvoltage detection level.                                                    Check the power supply and
     OV
                                                              The power supply voltage is too high. decrease the voltage to meet the
DC Bus Overvolt     Default detection levels are:
                                                                                                    inverter’s specifications.
                    200 V class: 410 VDC
                    400 V class: 820 VDC                      The braking chopper / braking resistor Check the braking chopper / resis-
                                                              is not working.                        tor.
                                                              External load was pulling down the          Remove all connection to the con-
                    Control Power Supply Undervoltage                                                     trol terminals and cycle the power
     UV2                                                      Inverter’s power supplies or there was
CTL PS Undervolt    Undervoltage of the control circuit                                                   to the Inverter.
                                                              an internal short in the power/gate drive
                    while the Inverter was running.
                                                              board.                                      Replace the Inverter.
                                                                                                                                                 7-3
                                                    Table 7.1 Resetable Faults
           Display                      Meaning                              Probable Causes                       Corrective Actions
                                                                                                            Check for dirt build-up on the fans
                                                                   The temperature is too high.
                                                                                                            or heatsink.
                          Heatsink Overheat
                          The temperature of the Inverter's cool- There is a heat source nearby.            Reduce the ambient temperature
                          ing fin exceeded the setting in L8-02                                             around the drive.
             OH           and L8-03 is set to 0,1 or 2.
      Heatsink Overtemp                                           The Inverter's cooling fan(s) is/are bro-
                                                                  ken.
                                                                                                            Replace the cooling fan(s).
                                                                  The Inverter's internal cooling fan is
                          Inverter's Cooling Fan Stopped
                                                                  broken (18.5 kW and larger).
                          Dynamic Braking Transistor              Defective or failed dynamic braking     Cycle power to the Inverter.
            RR
       DynBrk Transistr   The built-in dynamic braking transistor resistor caused braking transistor dam-
                          failed.                                 age.                                    Replace the Inverter.
7           OL2
        Inv Overload
                          Inverter Overload
                          The Inverter output current exceeded
                          the Inverter’s overload capability.
                                                                                                             (C1-).
                                                                   The voltage settings of the V/f pattern Check the V/f characteristics (E1-
                                                                   is incorrect.                           ).
7-4
                                              Table 7.1 Resetable Faults
     Display                       Meaning                              Probable Causes                        Corrective Actions
                    Undertorque Detection 2                                                            Ensure the values in L6-05 and L6-
                    The Inverter’s output current (V/f con-                                            06 are appropriate.
     UL4            trol) or the output torque (Vector con-
                                                              Motor was underloaded.
Undertorq Det 2     trol) fell below L6-05 for longer than                                             Check application/machine status
                    the time set in L6-06 and L6-04 is set to                                          to eliminate fault.
                    7 or 8.
                                                              The acceleration time and deceleration Lengthen the acceleration time and
                    Excessive Speed Deviation                 time are too short.                    deceleration time.
                    Detected when F1-04 is set to 0, 1 or 2
                                                            The load is locked.                        Check the mechanical system.
     DEV            and A1-02 is set to 3 or 6
Speed Deviation     The speed deviation is higher than the The settings of F1-10 and F1-11 are not     Check the settings of F1-10 and F1-
                    setting of F1-10 for a time longer than appropriate.                               11.
                    the setting of F1-11.
                                                                                                       Check the sequence and if the brake
                                                            Wrong brake control sequence. The
                                                                                                       is opened when the inverter starts to
                                                            motor runs against the closed brake.
                                                                                                       increase the speed.
      DV3
                    Wrong rotation direction
                    Detected when the speed deviation is
                    higher than 30% and the torque refer-
                                                              Incorrect PG wiring                      Correct the wiring
                    Wrong rotation direction                 The magnet position offset setting in     Verify the PG direction and execute
                    Detected when F1-19 is not 0, the        F1-22 is wrong                            an encoder offset auto tuning
      DV4           speed reference and motor speed have
                    opposite signs and the detection thresh- The load is too large                     Reduce the load and check the
                    old set in F1-19 is exceeded.                                                      brake
                                                                                                                                               7-5
                                                      Table 7.1 Resetable Faults
            Display                        Meaning                           Probable Causes                      Corrective Actions
                           Control Fault
                           A torque limit was reached continu-    Motor parameters were not set prop-
             CF
                           ously for 3 seconds or longer during a                                          Check the motor parameters.
        Out of Control                                            erly.
                           deceleration stop in Open Loop Vector
                           control.
                                                                                                         Check for an external fault condi-
                                                                An external fault condition was present, tion.
             EF0           External fault input from Communica-
                                                                input from a communication option
        Opt External Flt   tions Option Card                                                             Verify the parameters.
                                                                card.
                                                                                                         Verify communication signals
             EF3
                           External fault at terminal S3
         Ext Fault S3
             EF4
                           External fault at terminal S4
         Ext Fault S4
                                                                   An “external fault” was input from a
             EF5                                                                                           Eliminate the cause of the external
                           External fault at terminal S5           multi-function input terminal (S3 to
         Ext Fault S5                                                                                      fault condition.
                                                                   S7).
             EF6
                           External fault at terminal S6
         Ext Fault S6
             EF 7
                           External fault at terminal S7
         Ext Fault S7
            SE2            The output current at start was below   The output contactor was not closed at
                                                                                                          Check the output contactor.
       Sequence Error 2    25% of no-load current.                 start.
7           SE3
       Sequence Error 3
                           The output current during run was
                           below 25% of no-load current.
                                                                   The output contactor was opened dur-
                                                                   ing run.
                                                                                                        Check the output contactor.
                           The Brake Release Command and the The feedback signal from the brake is
             SE4
                           Brake Release Check signals do not not switched ON while the Brake              Check the brake sequence.
      Brake Answer Fault
                           match.                             Relase command is switched ON.
7-6
                                               Table 7.2 Not Resetable Faults
                                                             The Option Card is not connected prop- Turn off the power and re-
     CPF06                                                   erly.                                  install the Option Card again.
                     Option Card Connection Fault
   Option Error
                                                             The Inverter or Option Card is dam-      Replace the Option Card or the
                                                             aged.                                    Inverter.
     CPF08
     WAT-Err
                     Watchdog Timer Fault
                                                                                 -
Option card A/D converter is faulty. Cycle the Inverter power supply.
                                                                                                                                              7-7
                                                 Table 7.2 Not Resetable Faults
7-8
 Alarm Detection
     Alarms are Inverter protection functions that indicate unusual conditions without switching off the drive and
     operating the fault output contact. The alarm automatically disappears when its cause is eliminated.
     During an alarm condition, the Digital Operator/LED Monitor alarm display flashes and an alarm output is
     generated at the multi-function outputs (H2-01 to H2-03) if programmed.
     When an alarm occurs, take appropriate countermeasures according to the table below.
                     DC Bus Undervoltage
                     The following conditions occurred
                     • The DC bus voltage was below the
                       Undervoltage Detection Level Set-
         UV            ting (L2-05).                         For the probable reasons please have a For the corrective actions please
  DC Bus Undervolt   • The MC of the inrush current pre-     look at UV1, UV2 and UV3 in table      have a look at UV1, UV2 and UV3
     (flashing)        vention circuit was opened.           7.1.                                   in table 7.1
                     • The control power supply voltage
                       was below the CUV level.
                     UV Alarm is detected only, when the
                     drive is in stop condition
                     DC Bus Overvoltage
                     The DC bus voltage exceeded the over-
         OV          voltage detection level.                                                      Check the power supply and
  DC Bus Overvolt    200 V class: 410 VDC                    The power supply voltage is too high. decrease the voltage to meet the
     (flashing)      400 V class: 820 VDC                                                          Inverter’s specifications
                     An OV Alarm is detected only, when
                     the drive is in stop condition.
                                                                                                                                           7-9
                                                      Table 7.3 Alarm Detection
           Display                        Meaning                             Probable causes                       Corrective Actions
7            DEV
       Speed Deviation
          (flashing)
                                                                    The load is too large                    Reduce the load
7-10
                                             Table 7.3 Alarm Detection
   Display                      Meaning                           Probable causes                        Corrective Actions
     EF3
 Ext Fault S3    External fault at terminal S3
  (flashing)
     EF4
 Ext Fault S4    External fault at terminal S4
  (flashing)
                                                        An external fault was input by a multi-
     EF5                                                function input terminal                 Eliminate the cause of the external
 Ext Fault S5    External fault at terminal S5
  (flashing)                                            (S3 to S7) which is programmed for the fault condition
                                                        external fault function alarm output.
     EF6
 Ext Fault S6    External fault at terminal S6
  (flashing)
     EF7
 Ext Fault S7    External fault at terminal S7
  (flashing)
                                                                                                                                      7-11
        Operator Programming Errors
            An Operator Programming Error (OPE) occurs when two or more parameter related to each other are set inap-
            propriate or an individual parameter setting is incorrect. The Inverter does not operate until the parameter set-
            ting is set correctly; however, no other alarm or fault outputs will occur. If an OPE occurs, change the related
            parameter by checking the cause shown in Table 7.4. When an OPE error is displayed, press the ENTER key
            to see U1-34 (OPE Detected). This monitor displays the parameter that is causing the OPE error.
                                                Table 7.4 Operator Programming Errors
              Display                        Meaning                            Probable Causes                      Corrective Actions
                                                                                                             Enter the correct kVA setting by
                                                                      The control board was replaced and the referring to page 5-67, Factory Set-
                                                                      kVA parameter (o2-04) is incorrect.    tings Changing with Inverter
             OPE01                                                                                           Capacity (o2-04)
                              Inverter kVA Setting Error
           kVA Selection
                                                                                                             Compare U1-14 and the software
                                                                      A not suitable software has beenn
                                                                                                             number in the nameplate. Replace
                                                                      installed on the inverter.
                                                                                                             the software if necessary.
7             OPE03
             Terminal
                              Multi-function Input
                              Selection Error
                                                                      • Functions were selected duplicative.
                                                                      • External Baseblock NO (8) and
                                                                        External Baseblock NC (9) were
                                                                                                             Verify the parameter settings in H1-
                                                                                                             
                                                                        selected at the same time.
                                                                      • The Emergency Stop Command NO
                                                                        (15) and NC(17) are set simulta-
                                                                        neously.
7-12
                                      Table 7.4 Operator Programming Errors
    Display                       Meaning                         Probable Causes                   Corrective Actions
                                                                                             Check parameters (E1-). A fre-
     OPE10                                              V/f parameter settings were out of   quency/voltage value may be set
                    V/f Parameter Setting Error
 V/f Ptrn Setting                                       range.                               higher than the maximum fre-
                                                                                             quency/voltage.
                                                                                                                                   7-13
        Auto-tuning Faults
           Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digi-
           tal operator and the motor coasts to stop. No fault or alarm outputs will be operated.
                                                     Table 7.5 Auto-tuning Faults
            Display                      Meaning                              Probable causes                        Corrective Actions
                                                                   There is an error in the data input for
                                                                                                             Check the input data.
                                                                   autotuning.
                                                                   There is an error in the relationship
                                                                                                             Check the Inverter and motor
                                                                   between the motor output and the
                                                                                                             capacity.
                                                                   motor rated current.
              Fault        Motor data fault
                                                                   There is an error between the no-load
                                                                   current setting and the input motor
                                                                                                            Check the motor rated current and
                                                                   rated current (when auto-tuning for
                                                                                                            no-load current.
                                                                   line-to-line resistance is performed for
                                                                   vector control)
7-14
                                                   Table 7.5 Auto-tuning Faults
       Display                          Meaning                            Probable causes                      Corrective Actions
                                                                 Auto-tuning was not completed in the
                                                                 specified time.                      • Check the motor wiring.
                                                                                                      • Check the motor rated current
                                                                 Auto-tuning result is outside the      input value
   Leakage Induc-        The leakage inductance measurement
                                                                 parameter setting range.
     tance Fault         caused an error.
                                                                 The leakage inductance tuning current Reduce or increase the current level
                                                                 was too high or too low (Closed Loop for leakage inductance tuning by
                                                                 Vector for PM only)                   changing parameter n8-46.
                                                                 The motor speed exceeded 20 rpm at
                                                                 the auto tuning start.
                         All encoders                            The magnetic pole position tuning
                                                                 could not be performed in the specified
                                                                                                         • Remove the ropes and repeat the
                                                                 time.
                                                                                                           tuning
                                                                 The difference between two measure- • Check the encoder rotation direc-
                         Encoder with Z-pulse                    ments of the magnet pole position was     tion and if necessary change
   Z_SRCH_ERR                                                    higher than 3°.                           F1-05.
(PM motor tuning only)
                                                                 The difference between two measure-
                                                                 ments of the magnet pole position was
                                                                 higher than 5°.
                         Serial encoders                                                               •   Check the encoder wiring (order,
                                                                 An encoder serial communication error     shield etc.)
                                                                 has occurred during the tuning.       •   Check the encoder power supply.
                                                                                                       •   Replace the encoder.
                                                                                                                                               7
                                                                                                      Check and correct the motor set-
                                                                 The torque reference exceeded 100% tings
       End - 1           V/f Settings Alarm
                                                                 and the no-load current exceeded 70% If the motor and the machine are
   V/f Over Setting      Displayed after auto-tuning is complete during auto-tuning.
                                                                                                      connected, disconnect the motor
                                                                                                      from the machine.
                                                                                                                                              7-15
        Digital Operator Copy Function Faults
              These faults can occur during the digital operator COPY function. When a fault occurs, the fault content is dis-
              played on the operator. The fault or alarm contact output is not operated.
                            CPE              The Inverter type or software number was different Use stored data of the same product (L7) and soft-
                       ID UNMATCHED          from the stored data in the digital operator       ware number (U1-14) only.
                            VAE              The capacity of the Inverter and the capacity of the Use stored data for the same Inverter capacity only
                     INV. KVA UNMATCH        stored data in the Digital Operator are different.   (o2-04).
                                     The control method of the Inverter and the control Use stored data for the same control
                          CRE
                                     method of the stored data in the Digital Operator
         COPY      CONTROL UNMATCHED                                                    method (A1-02).
                                     are different.
        Function
                                             A parameter setting written to the Inverter was dif-
                           CYE
                                             ferent from the setting stored in the Digital Opera- Retry the COPY function (o3-01 = 2)
                        COPY ERROR
                                             tor.
7        Verify
        Function
                           VYE
                       VERIFY ERROR
                                             The set value of the digital operator and the Inverter
                                             do not match
                                                                                                    Retry the Verify function (o3-01 = 3)
7-16
 Machine Data Copy Function Faults
    These faults can occur during the machine data (encoder) COPY function. When a fault occurs, the fault con-
    tent is displayed on the operator. The fault or alarm contact output is not operated.
                                                                                                                                      7-17
       Troubleshooting
           Due to parameter setting errors, faulty wiring etc., the Inverter and motor may not operate as expected when
           the system is started. If that occurs, use this section as a reference and perform the appropriate countermea-
           sures.
           If a fault code is displayed, refer to page 7-2, Protective and Diagnostic Functions.
         The display does not change when the Increment and Decrement keys are pressed.
           The following causes are possible:
7          This is a Digital Operator/LED Monitor communication error. The connection between the Digital Operator/
           LED Monitor and the Inverter may be faulty. Remove the Digital Operator/LED Monitor and then re-install it.
7-18
 If the Motor Does Not Operate Properly
    The following causes are possible:
  The motor does not operate when an external operation signal is input.
    The frequency reference is 0.00 Hz or a no speed is selected by the digital inputs. Check the input signals and
    the frequency reference settings.
    Also make sure to set the Baseblock signal. The inverter does not accept any input if it is base blocked.
                                                                                                                         7-19
        If Motor Deceleration is Slow
           The following causes are possible:
7-20
 If Peripheral Devices are Influenced by the Starting or Running Inverter
    The following solutions are possible:
     • Change the Inverter's Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to
       reduce the amount of transistor switching noise.
     • Install an Input Noise Filter at the Inverter's input power terminals.
     • Install an Output Noise Filter at the Inverter's motor terminals.
     • Use shielded motor cables or a conduit. Metal shields electrical noise.
     • Check the grounding of the Inverter and motor.
     • Separate main circuit wires from control circuit wires.
  Oscillation and hunting occur with Closed Loop Vector control for IM and PM
    The gain adjustment may be insufficient. Adjust the speed control loop (Automatic Speed Regulator, ASR) by
    changing the C5- parameters. If the oscillation points overlap with those of the machine and cannot be
    eliminated, increase the ASR Delay Time, and then readjust the ASR gains.
    If auto-tuning has not been performed, proper performance may not be achieved for Closed Loop Vector Con-
    trol. Perform auto-tuning or set the motor parameters manually.
                                                                                                                      7-21
7
7-22
                                                                                     8
                       Maintenance and
                             Inspection
This chapter describes basic maintenance and inspection for the Inverter
       Periodic Inspection
           Check the following items during periodic maintenance.
             • The motor should not vibrate or make unusual noises.
             • There should be no abnormal heat generation from the Inverter or motor.
             • The ambient temperature should be within the Inverter’s specifications.
             • The output current value shown in U1-03 should not be higher than the motor or the Inverter rated current
               for extended period of time.
             • The cooling fan in the Inverter should be operating normally.
           Before attempting any maintenance checks, make sure that the three-phase power is disconnected. With power
           removed from the unit, the DC bus capacitors will stay charged for several minutes. The charge LED in the
           Inverter will light red until the DC bus voltage is below 10VDC. To ensure that the DC bus is completely dis-
           charged, measure between the positive and negative bus with a DC voltmeter. Be sure not to touch terminals
           immediately after the power has been turned off. Doing so can result in electric shock.
                                                                                       Clean off any dirt and dust with an air gun using dry air at
               Cooling fins         Are the fins dirty or dusty?                       a pressure of 4 x 105 to 6 x 105 Pa
                                                                                       (4 to 6 bar, 55 to 85 psi).
                                                                                       Clean off any dirt and dust with an air gun using dry air at
                                    Is there any conductive dirt or oil mist on the    a pressure of 4 x 105 to 6 x 105 Pa
                All PCBs
                                    PCBs?                                              (4 to 6 bar, 55 to 85 psi).
                                                                                       Replace the boards if they cannot be made clean.
              Input Diodes                                                             Clean off any dirt and dust with an air gun using dry air at
                                  Is there any conductive dirt or oil mist on the
         Output Transistors Power                                                      a pressure of 4 x 105 to 6 x 105 Pa
                 Modules          modules or components?
                                                                                       (4 to 6 bar, 55 to 85 psi).
8           DC bus capacitors
                                    Are there any irregularities, such as discoloration
                                    or odor?
                                                                                        Replace the capacitor or Inverter.
8-2
 Periodic Maintenance of Parts
      In order to keep the Inverter operating normally over a long time, and to prevent down time due to an unex-
      pected failure, it is necessary to perform periodic inspections and replace parts according to their service life.
      The data indicated in the following table is to be used as a general guideline only. Periodic inspection stan-
      dards vary depending on the Inverter’s installation environment conditions and usage. The Inverter’s sug-
      gested maintenance periods are noted below.
  DC bus fuse
                                                               10 years                     Replace with new part.
  Control power fuse
      Note:   The standard replacement period is based on the following usage conditions:
              Ambient temperature:Yearly average of 30°C/86°F
              Load factor: 80%
              Operating rate: 12 hours per day
                                                                                                                                8-3
       Cooling Fan Replacement
                           2
                                                  1
Fan cover
8-4
200 V and 400 V Class Inverters of 22 kW or More
  The heatsink cooling fan is attached to the top of the heatsink inside the Inverter. The cooling fan(s) can be
  replaced without removing the Inverter from the installation panel.
                                                                                                                     8
            Control card                                               Connector
Gate driver
                                                                                                                     8-5
       Removing and Mounting the Terminal Card
          The Terminal Card can be removed and mounted without disconnecting the control wiring.
8
                       Always confirm that the input power is removed and the Charge LED is off before removing or
                       mounting the terminal card.
          IMPORTANT
8-6
                                                                                               9
                                         Specifications
This chapter describes the basic specifications of the Inverter.
       Specifications by Model
                                        Specifications are given by model in the following tables.
                                     200V Class
                                                                                        Table 9.1 200 V Class Inverters
                                      Model Number
                                                                 23P7        25P5       27P5        2011        2015        2018       2022        2030        2037       2045        2055
                                      CIMR-L7X 
      Max. applicable motor out-
                                                                  3.7         5.5        7.5          11         15         18.5         22         30          37          45         55
      put (kW)*1
                                     Max. output voltage                                                3-phase; 200, 208, 220, 230, or 240 VAC
                                     (V)                                                                    (Proportional to input voltage.)
                                     Allowable frequency
                                                                                                                            ±5%
                                     fluctuation
                                        * 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure
                                             that the Inverter's rated current is higher than the motor's rated current.
                                        * 2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
9-2
                               400 V Class
                                                                                  Table 9.2 400 V Class Inverters
                                Model Number
                                                          43P7       44P0       45P5       47P5       4011      4015         4018     4022      4030       4037       4045       4055
                                CIMR-L7X 
Max. applicable motor out-
                                                           3.7        4.0        5.5        7.5        11        15          18.5      22         30        37         45         55
put (kW) *1
                               Allowable voltage
                                                                                                                 + 10%, - 15%
                               fluctuation
                               Allowable frequency
                                                                                                                       ±5%
                               fluctuation
                                  * 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure
                                       that the Inverter's rated current is higher than the motor's rated current.
                                  * 2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
                                                                                                                                                                                          9-3
       Common Specifications
                                   The following specifications apply to both 200 V and 400 V class Inverters.
                                                                              Table 9.3 Common Specifications
                                 Model Number
                                                                                                           Specification
                                 CIMR-L7X 
                                                                                                        Sine wave PWM
                                Control method
                                                                     Closed Loop Vector control for IM and PM motors, Open Loop Vector control, V/f control
                                                                                                                8 kHz
                                Carrier Frequency
                                                               higher carrier frequency possible with current derating (refer to page 9-6, Carrier Frequency Derating)
Torque limits Provided (4 quadrant steps can be changed by constant settings.) (Vector control)
                                Torque accuracy                                                                 ± 5%
      Control Characteristics
                                Acceleration/Decelera-
                                                               0.01 to 600.00 s (4 selectable combinations of independent acceleration and deceleration time settings)
                                tion time
                                                       Over torque/under torque detection, torque limits, 8-speed control (maximum), 4 acceleration and deceleration
                                                       times, S-curve acceleration/deceleration, auto-tuning (rotational or stationary), dwell function, cooling fan ON/
                                Main control functions OFF control, slip compensation, torque compensation, auto-restart after fault, DC braking for starting and stop-
                                                       ping, automatic fault reset and parameter copy function, special Lift functions and sequences, short floor operation,
                                                       rescue operation with light load direction search, machine data copy function (save in encoder memory)
9                               Instantaneous overcur-
                                rent protection
                                                                                        Stops at approximately 200% of rated output current.
Overload protection OL2 fault at 150% of rated output current for 30 sec
Stall prevention Stall prevention during acceleration, deceleration and running independently.
Charge indicator Glows when the main circuit DC voltage is approximately 10 VDC or more.
9-4
                                                    Table 9.3 Common Specifications
               Model Number
                                                                                 Specification
               CIMR-L7X 
                                                                Enclosed wall-mounted type (IP20): All models
Protective structure                   Enclosed wall-mounted type (NEMA 1): 18.5 kW or less (same for 200 V and 400 V class Inverters)
                                              Open chassis type (IP00): 22 kW or more (same for 200 V and 400 V class Inverters)
              Ambient operating
                                                                      95% max. (with no condensation)
Environment
humidity
Altitude 1000 m, max. 3000 m with derating (refer to page 9-7, Altitude Derating).
                                                                                                                                         9-5
      Derating
                                                  10 0
                     Output Current in % of the
                                                   80
                          Rated Current
60
40
20
                                                    0
                                                         0            10        20        30            40          50         60
Temperatur (°C)
100%
75%
                                                                                                                                     Carrier
                                                                                                                                     frequency
                                                             0
9                                                                 2                  5           8           10                 15
                                                                                                                                      (kHz)
9-6
 Altitude Derating
    The standard inverter specification is valid for altitudes up to 1000m above sea level. If the inverter is used in
    regions with higher altitude, the allowable input voltage, output current and ambient temperature are derated
    as shown below.
  Example
    The following example shows the derating of a 400V, 7.5 kW, inverter (L7X47P5)
                                                                                                                         9-7
      AC Reactors for EN 12015 Compatibility
          The following table shows the AC reactors which have to be applied in order to fulfill the requirements of the
          EN 12015.
                                         H
                                                                                                         H
                 L1                                W1                         L1                                      W1
                  L                                 W                         L                                        W
Drawing A Drawing B
9
                          L2                                     W1
                          L1                                      W
                          L
Drawing C
9-8
EN 954-1 / EN81-1 Certificates
                                 9-9
9
9-10
 9
9-11
9
9-12
 9
9-13
9
9-14
                                                                                   10
                                                                Appendix
This chapter provides precautions for the Inverter, motor, and peripheral devices and also provides lists of con-
stants.
        Selection
           Observe the following precautions when selecting an Inverter.
         Installing Reactors
           A large peak current can flow in the power input circuit when the Inverter is connected to a large-capacity
           power transformer (600 kVA or higher) or when switching a phase shifting capacitor. Excessive peak current
           can destroy the converter section. To prevent this, install a DC or AC reactor to improve the power supply
           power factor.
           If a thyristor converter, such as a DC drive, is connected in the same power supply system, connect a DC or
           AC reactor regardless of the power supply conditions shown in the following diagram.
                                                4000
                                          Power supply   DC or AC reactor
                                                         required
                                                 (kVA)
                                                                             DC or AC reactor not
                                                 600                         required
                                                   0
                                                                    60                              400
        Installation
           Observe the following precautions when installing an Inverter.
         Installation in Enclosures
           Install the Inverter in a clean location where it is not subjected to oil mist, dust, and other contaminants, or
           install the Inverter in a completely enclosed panel. Provide cooling measures and sufficient panel space so that
           the temperature surrounding the Inverter does not exceed the allowable temperature. Do not install the Inverter
           on wood or other combustible materials.
         Installation Direction
           Mount the Inverter vertically to a wall or other vertical surface.
        Settings
           Observe the following precautions when making settings for an Inverter.
         Upper Limits
           The maximum output frequency can be set up to 120Hz. Setting the output frequency too high can damage the
10         machine. So pay attention to the mechanical system and observe required limits for the output frequency.
10-2
 Acceleration/Deceleration Times
   The motor's acceleration and deceleration times are determined by the torque generated by the motor, the load
   torque, and the load's inertial moment (GD2/4). If the stall prevention functions are activated during accelera-
   tion or deceleration, it might be necessary to increase the acceleration or deceleration time.
   To reduce the acceleration or deceleration times, increase the capacity of the motor and Inverter.
 Handling
   Observe the following precautions during wiring or maintenance of an Inverter.
 Wiring Check
   The Inverter will be internally damaged if the power supply voltage is applied to output terminal U, V, or W.
   Check wiring for any mistakes before supplying power. Check all wiring and control sequences carefully.
10
                                                                                                                      10-3
       Motor Application Precautions
         Noise
           The noise generated in the motor depends on the carrier frequency. The higher the setting, the less is the gen-
           erated noise.
         Pole-changing Motor
           The rated input current of pole-changing motors differs from that of standard motors. Select an appropriate
           Inverter according to the maximum current of the motor.
         Single-phase Motor
           Do not use an Inverter for a single-phase motor. These motors are often equipped with capacitors Any capaci-
           tor directly connected to the inverter output may damage the Inverter.
10
10-4
User Constants
   The factory settings of each parameter are given in the following table. They are for a 200 V Class Inverter
   with 3.7 kW.
                                                                                      Factory
    No.                                                  Name                                        Setting
                                                                                      Setting
   A1-00     Language selection for Digital Operator display                              0
   A1-01     Parameter access level                                                       2
   A1-02     Control method selection                                                     0
   A1-03     Initialize                                                                   0
   A1-04     Password                                                                     0
   A1-05     Password setting                                                             0
  A2-01 to
             User specified parameters                                                    –
   A2-32
   b1-01     Reference source selection                                                   0
   b1-02     RUN command source selection                                                 1
   b1-06     Control input scan                                                           1
   b1-08     Run command selection in programming modes                                   1
   b2-08     Magnetic flux compensation volume                                           0%
   b4-01     Timer function ON-delay time                                              0.0 sec.
   b4-02     Timer function OFF-delay time                                             0.0 sec.
   b6-01     Dwell frequency at start                                                  0.0 Hz
   b6-02     Dwell time at start                                                       0.0 sec.
   b6-03     Dwell frequency at stop                                                   0.0 Hz
   b6-04     Dwell time at stop                                                        0.0 sec.
   C1-01     Acceleration time 1                                                      10.0 sec.
   C1-02     Deceleration time 1
   C1-03     Acceleration time 2
   C1-04     Deceleration time 2
   C1-05     Acceleration time 3
                                                                                        1.5 s
   C1-06     Deceleration time 3
   C1-07     Acceleration time 4
   C1-08     Deceleration time 4
   C1-09     Emergency stop time
   C1-10     Accel/decel time setting unit                                                1
   C1-11     Accel/decel time switching frequency                                      0.0 Hz
   C2-01     S-curve characteristic time at acceleration start                         0.5 sec.
   C2-02     S-curve characteristic time at acceleration end                           0.5 sec.
   C2-03     S-curve characteristic time at deceleration start                         0.5 sec.
   C2-04     S-curve characteristic time at deceleration end                           0.5 sec.
   C2-05     S-curve Characteristic time below leveling speed                         0.50 sec.
   C3-01     Slip compensation gain                                                      1.0
   C3-02     Slip compensation delay time                                            2000 msec
   C3-03
   C3-04
             Slip compensation limit
             Slip compensation selection during regeneration
                                                                                       200%
                                                                                          1                       10
   C3-05     Output voltage limit operation selection                                     1
   C4-01     Torque compensation gain                                                   1.00
   C4-02     Torque compensation delay time constant                                 200 msec *1
   C4-03     Starting torque compensation (FWD)                                         0.0%
   C4-04     Starting torque compensation (REV)                                         0.0%
   C4-05     Starting torque compensation time constant                               10 msec
                                                                                                                  10-5
                                                                  Factory
       No.                                                Name                Setting
                                                                  Setting
       C5-01   ASR proportional (P) gain 1                         40 *1
       C5-02   ASR integral (I) time 1                             0.5 *1
       C5-03   ASR proportional (P) gain 2                         20 *1
       C5-04   ASR integral (I) time 2                             0.5 *1
       C5-06   ASR delay time                                    0.004 msec
       C5-07   ASR switching frequency                             0.0 Hz
       C5-08   ASR integral (I) limit                              400%
       C5-09   ASR proportional (P) gain 3                         40.00
       C5-10   ASR integral (I) time 3                           0.500 sec.
       C5-15   ASR gain (P) during encoder offset tuning            5.00
       C6-02   Carrier frequency selection                           1
       C6-06   PWM method selection                                  0
       C6-11   Carrier frequency for PM motor control                4
       d1-01   Frequency reference 1                              0.00 Hz
       d1-02   Frequency reference 2                              0.00 Hz
       d1-03   Frequency reference 3                              0.00 Hz
       d1-04   Frequency reference 4                              0.00 Hz
       d1-05   Frequency reference 5                              0.00 Hz
       d1-06   Frequency reference 6                              0.00 Hz
       d1-07   Frequency reference 7                              0.00 Hz
       d1-08   Frequency reference 8                              0.00 Hz
       d1-09   Frequency reference 9 Vn                          50.00 Hz
       d1-10   Frequency reference 10 V1                          0.00 Hz
       d1-11   Frequency reference 11 V2                          0.00 Hz
       d1-12   Frequency reference 12 V3                          0.00 Hz
       d1-13   Frequency reference 13 Vr                          0.00 Hz
       d1-14   Frequency reference 14 Inspection                   25 Hz
       d1-17   Jog frequency reference / Leveling speed           4.00 Hz
       d1-18   Speed priority selection                              1
       d1-19   Second motor speed                                 0.00 Hz
       d6-03   Field forcing function selection                      0
       d6-06   Field forcing function Limit                        400%
       E1-01   Input voltage setting                                 *1
10     E1-10
       E1-13
               Min. output frequency voltage (VMIN)
               Base voltage (VBASE)
                                                                     *1
                                                                   0.0 V
       E2-01   Motor rated current                                   *1
10-6
                                                           Factory
No.                                                 Name              Setting
                                                           Setting
E2-07   Motor iron saturation coefficient 1                  0.50
E2-08   Motor iron saturation coefficient 2                  0.75
E2-09   Monitor mechanical losses                           0.0%
E2-10   Motor iron loss for torque compensation               *1
                                                                                10-7
                                                                                         Factory
       No.                                                Name                                       Setting
                                                                                         Setting
       F1-26   Encoder copy write permission                                                0
       F4-01   Channel 1 monitor selection                                                  2
       F4-02   Channel 1 gain                                                            100.0%
       F4-03   Channel 2 monitor selection                                                  3
       F4-04   Channel 2 gain                                                             50.0%
       F4-05   Channel 1 output monitor bias                                              0.0%
       F4-06   Channel 2 output monitor bias                                              0.0%
       F4-07   Analog output signal level for channel 1                                     0
       F4-08   Analog output signal level for channel 2                                     0
       F5-01   Channel 1 output selection                                                   0
       F5-02   Channel 2 output selection                                                   1
       F5-03   Channel 3 output selection                                                   2
       F5-04   Channel 4 output selection                                                   4
       F5-05   Channel 5 output selection                                                   6
       F5-06   Channel 6 output selection                                                   37
       F5-07   Channel 7 output selection                                                   0F
       F5-08   Channel 8 output selection                                                   0F
       F5-09   DO-08 output mode selection                                                  0
       F6-01   Operation selection after communications error                               1
       F6-02   Input level of external error from Communications Option Card                0
       F6-03   Stopping method for external error from Communications Option Card           1
       F6-04   Trace sampling from Communications Option Card                               0
       F6-05   Current monitor unit selection                                               0
       F6-06   Torque reference/torque limit selection from communications option card      0
       H1-01   Terminal S3 function selection                                               80
       H1-02   Terminal S4 function selection                                               84
       H1-03   Terminal S5 function selection                                               81
       H1-04   Terminal S6 function selection                                               83
       H1-05   Terminal S7 function selection                                               F
       H2-01   Terminal M1-M2 function selection                                            40
       H2-02   Terminal M3-M4 function selection                                            41
       H2-03   Terminal M5-M6 function selection                                            6
       H3-01   Frequency reference AI-14B CH1signal level selection                         0
       H3-02   Frequency reference AI-14B CH1 input gain                                 100.0%
       H3-03   Frequency referenceAI-14B CH1 input bias                                   0.0%
       H3-04   AI-14B CH3 signal level selection                                            0
       H3-05   AI-14B CH3 function selection                                                2
       H3-06   AI-14B CH3 input gain                                                     100.0%
       H3-07   AI-14B CH3 input bias                                                      0.0%
       H3-08   AI-14B CH2 signal level selection                                            0
10     H3-09
       H3-10
               AI-14B CH2 function selection
               AI-14B CH2 input gain
                                                                                            3
                                                                                         100.0%
       H3-11   AI-14B CH2 input bias                                                      0.0%
       H3-12   Analog input filter time constant for the AI-14B                          0.03 sec.
       H3-15   Terminal A1 function selection                                               0
       H3-16   Terminal A1 input gain                                                    100.0%
       H3-17   Terminal A1 input bias                                                     0.0%
       L1-01   Motor protection selection                                                   1
10-8
                                                                 Factory
No.                                                 Name                       Setting
                                                                 Setting
L1-02   Motor protection time constant                           1.0 min
L2-05   Undervoltage detection level                              190 V
L2-11   Battery Voltage                                            0V
L3-01   Stall prevention selection during accel                     1
L3-02   Stall prevention level during accel                       150%
L3-05   Stall prevention selection during running                   1
L3-06   Stall prevention level during running                     150%
L4-01   Speed agreement detection level                           0.0 Hz
L4-02   Speed agreement detection width                           2.0 Hz
L4-03   Speed agreement detection level (+/-)                     0.0 Hz
L4-04   Speed agreement detection width (+/-)                     2.0 Hz
L5-01   Number of auto restart attempts                             2
L5-02   Auto restart operation selection                            0
L5-05   Under voltage fault (UV1) restart selection                 1
L6-01   Torque detection selection 1                                0
L6-02   Torque detection level 1                                  150%
L6-03   Torque detection time 1                                  0.1 sec.
L6-04   Torque detection selection 2                                0
L6-05   Torque detection level 2                                  150%
L6-06   Torque detection time 2                                  0.1 sec.
L7-01   Forward drive torque limit                                300%
L7-02   Reverse drive torque limit                                300%
L7-03   Forward regenerative torque limit                         300%
L7-04   Reverse regenerative torque limit                         300%
L7-06   Torque limit time constant                               200 ms
L7-07   Torque Limit Operation during accel/decel                   0
L8-02   Overheat pre-alarm level                                 75 °C*1
L8-03   Operation selection after overheat pre-alarm                3
L8-07   Output open-phase protection selection                      2
L8-09   Ground protection selection                                 1
L8-10   Cooling fan control selection                               0
L8-11   Cooling fan control delay time                            60 sec.
L8-12   Ambient temperature                                       45 °C
L8-18   Soft CLA selection                                          1
L8-20   LF detection time                                        0.2 sec.
n2-01   Speed feedback detection control (AFR) gain                1.00
n2-02   Speed feedback detection control (AFR) time constant     50 msec
n5-01   Feed forward control selection                              1
n5-02   Motor Accel Time                                        0.178 sec.
n5-03   Feed forward proportional gain                             1.00
n5-05
n8-29
        Motor acceleration time tuning
        Current regulator q-axis P gain
                                                                    0
                                                               1000 rad/sec.
                                                                                         10
n8-30   Current regulator q-axis I time                          10.0 ms
n8-32   Current regulator d-axis P gain                        1000 rad/sec.
n8-33   Current regulator d-axis I gain                          10.0 ms
n8-35   Magnet position detection method                            5
n8-46   Inductance measurement current level                      10.0%
n9-60   A/D converter start delay time                           0.0 µsec.
                                                                                         10-9
                                                                                           Factory
        No.                                                Name                                       Setting
                                                                                           Setting
        o1-01   Monitor selection                                                             6
        o1-02   Monitor selection after power up                                              1
        o1-03   Frequency units of reference setting and monitor                              0
        o1-04   Setting unit for frequency parameters related to V/f characteristics          0
        o1-05   LCD Display contrast adjustment                                               3
        o2-01   LOCAL / REMOTE key enable/disable                                             0
        o2-02   STOP key during control circuit terminal operation                            0
        o2-03   User parameter initial value                                                  0
        o2-04   kVA selection                                                                 0
        o2-05   Frequency reference setting method selection                                  0
        o2-06   Operation selection when digital operator / LED monitor is disconnected       0
        o2-07   Cumulative operation time setting                                           0 hr.
        o2-08   Cumulative operation time selection                                           0
        o2-09   Initialize Mode                                                               2
        o2-10   Fan operation time setting                                                  0 hr.
        o2-12   Fault trace initialize                                                        0
        o2-15   “No of Travels” monitor initialize                                            0
        o3-01   Copy function selection                                                       0
        o3-02   Read permission selection                                                     0
        S1-01   Zero speed level at stop                                                   0.5 Hz
        S1-02   DC injection braking current at start                                       50%
        S1-03   DC injection braking current at stop                                        50%
        S1-04   DC injection braking time at start                                         0.40 sec
        S1-05   DC injection braking time at stop                                           0.60
        S1-06   Brake release delay time                                                    0.20
        S1-07   Brake close delay time                                                      0.10
        S1-14   SE2 detection delay time                                                  200 msec
        S1-15   SE3 detection delay time                                                  200 msec
        S1-16   Run delay time                                                            0.10 sec.
        S1-17   DC injection current gain at regenerative operation                         100%
        S1-18   DC injection current gain at motoring operation                             20%
        S1-19   Output contactor open delay time                                          0.10 sec.
        S1-20   Zero servo gain                                                               5
        S1-21   Zero servo completion width                                                  10
        S1-22   Starting torque compensation increase time                                500 msec
        S1-23   Torque compensation gain during lowering                                    1.000
        S1-24   Torque compensation bias during raising                                     0.0%
        S1-25   Torque compensation bias during lowering                                    0.0%
        S1-26   Dwell speed at start reference                                             0.0 Hz
        S1-27   Door zone speed level                                                      0.0 Hz
10      S1-28
        S1-29
                SE1 detection selection
                Torque compensation fade out level
                                                                                              0
                                                                                           0.0 Hz
        S1-30   Torque compensation fade out time                                         1000 msec
        S1-31   Torque limit time at stop                                                  0 msec
        S2-01   Motor rated speed                                                         1380 rpm
        S2-02   Slip compensation gain in motoring mode                                      0.7
        S2-03   Slip compensation gain in regenerative mode                                  1.0
        S2-05   Slip compensation torque detection delay time                              1.0 sec.
10-10
                                                                                 Factory
No.                                                      Name                                 Setting
                                                                                 Setting
S2-06     Slip compensation torque detection time                                 0.5 sec.
S2-07     Slip compensation delay time                                           200 msec
S3-01     Short floor operation selection                                            0
S3-03     Inspection deceleration ramp time                                       0.0 sec.
S3-04     Nominal/Leveling speed detection level                                  0.0 Hz
S3-05     Nominal speed for short floor calculation                               0.0 Hz
S3-06     Light load direction search for rescue operation                           0
S3-07     Light load search time                                                  1.0 sec.
S3-08     Output phase order                                                         0
S3-09     Frequency reference missing (FRL) fault detection                          1
S3-10     Light load search frequency                                            3.00 Hz
S3-11     Rescue operation torque limit                                           100%
S3-12     Base block restart selection                                               0
S3-13     Traction sheave diameter                                               400 mm
S3-14     Roping                                                                     2
S3-15     Gear Ratio                                                               1.000
S3-16     Over acceleration detection level                                      1.5 m/s²
S3-17     Over acceleration deceleration time constant                           0.05 sec.
S3-18     Over acceleration detection method selection                               0
S3-19     Inspection speed upper limit                                           25.0 Hz
S3-20     Short floor minimum constant speed time                                 0.0 sec.
S3-21     Distance calculation acceleration time gain                             150.0%
S3-22     Distance calculation deceleration time gain                             150.0%
S3-24     Light load direction search method                                         0
T1-01     Autotuning mode selection                                                  0
T1-02     Motor output power                                                        *1
                                                                                                         10
T2-09     Number of PG pulses                                                      2048
T2-10     Motor voltage constant calculation selection                               1
*1. The factory setting depends on the inverter model and the control method.
                                                                                                        10-11
10
10-12
1-13
       Sales and Service Network in Europe and Worldwide
       European Headquarter
       Yaskawa Electric Europe GmbH
       Am Kronberger Hang 2, 65824 Schwalbach, Germany
       Tel.: +49 (0) 6196 - 569 300, Fax.: +49 (0) 6196 - 569 398
European Subsidiaries
       UK
       Yaskawa Electric Europe GmbH,
       Unit 3, Centurion Court, Brick Close, Kiln Farm
       Milton Keynes Bucks, MK11 3JB, United Kingdom
       Tel.: +44 (0) 1908 - 565 874, Fax.: +44 (0) 1908 - 565 891
       Italy
       Yaskawa Electric Europe GmbH
       Via Trabucchi 28, 41013 Castelfranco E. (MO), Italy
       Tel.: +39 059 - 92 21 21, Fax.: +39 059 - 92 21 68
       Internet
       www.yaskawa.eu.com
Headquarters Worldwide
       Tokyo Office
       Yaskawa Electric Corporation, New Pier Takeshiba South Tower
       1-16-1, Kaigan, Minatoku, Tokyo 105-6891, Japan
       Tel.: +81 (0) 3 - 5402 4511, Fax.: +81 (0) 3 - 5402 4580
       www.yaskawa.co.jp
       American Headquarter
       Yaskawa Electric America Inc., 2121 Norman Drive South
       Waukegan, Il 60085, U.S.A.
       Tel.: +1 (847)- 887-7000, Fax.: +1 (847)- 887-7370
       www.yaskawa.com
1-14