P18 4 (1PP) GB (0908)

This document provides output ratings and technical specifications for a generating set model from FG Wilson. It includes prime and standby ratings for 380-415V/50Hz and 220/127V/60Hz output as well as definitions of prime and standby ratings. The generating set uses a Perkins 404D-22G1 engine and LL1014L alternator with key specifications listed. Dimensions and weights are also provided.

Uploaded by

MH..2023
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
307 views1 page

P18 4 (1PP) GB (0908)

This document provides output ratings and technical specifications for a generating set model from FG Wilson. It includes prime and standby ratings for 380-415V/50Hz and 220/127V/60Hz output as well as definitions of prime and standby ratings. The generating set uses a Perkins 404D-22G1 engine and LL1014L alternator with key specifications listed. Dimensions and weights are also provided.

Uploaded by

MH..2023
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Output Ratings

Generating Set Model Prime Standby


380-415V,50Hz 16.5 kVA 18.0 kVA
13.2 kW 14.4 kW
220/127V, 60 Hz 19.4 kVA 21.3 kVA
15.5 kW 17.0 kW

Ratings Definitions
Ratings at 0.8 power factor. www.FGWilson.com
Prime
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this
model can supply 10% overload power for 1 hour in 12 hours.

Standby
These ratings are applicable for supplying continuous electrical
power (at variable load) in the event of a utility power failure. No
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).

Technical Data
Engine Make & Model: Perkins 404D-22G1
Alternator Model: LL1014L
No. of Cylinders/Alignment: 4 / In Line
Displacement: litres (cu.in) 2.2 (135.2)
Bore/Stroke: mm (in) 84.0 (3.3)/100.0 (3.9)
Compression Ratio: 23.3:1
Induction: Naturally Aspirated
Frequency: 50 Hz 60 Hz
Engine Speed: 1500 RPM 1800 RPM
Gross Engine Power: kW (hp) 18.0 (24.0) 21.5 (29.0)
BMEP: kPa (psi) 649.0 (94.2) 647.0 (93.8)
Piston Speed: m/sec (ft/sec) 5.0 (16.4) 6.0 (19.7)
Fuel Tank Capacity: litres (US gal) 45 (11.9) 45 (11.9)
Fuel Consump, Prime l/hr (USg/hr) 4.4 (1.2) 5.2 (1.4)
Fuel Consump, Standby l/hr (USg/hr) 4.8 (1.3) 5.7 (1.5)
Heat Rejected to
Exhaust System: kW (Btu/min) 11.6 (660) 12.8 (728)
Heat Rejected to
Water & Lube Oil: kW (Btu/min) 15.2 (864) 17.2 (978)
Heat Radiation to Room: kW (Btu/min) 3.1 (176) 3.2 (182)
Exhaust Gas Temperature: °C (°F) 394 (740) 434 (812)
Radiator Cooling
Air Flow: m³/min (cfm) 33.0 (1165) 41.4 (1462)

Combustion Air Flow: m³/min (cfm) 1.5 (51) 1.7 (61)


Exhaust Gas Flow: m³/min (cfm) 3.7 (131) 4.0 (141)

Dimensions and Weights


Length: mm (in) Width: mm (in) Height: mm (in) Dry: kg (lb) Wet: kg (lb)
1320 (52.0) 552 (21.7) 1179 (46.4) 447 (985) 454 (1001)
Dry = With Lube Oil Wet = With Lube Oil and coolant

Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.

P18-4
Generating set pictured may include optional accessories.

FG Wilson has manufacturing facilities in the following


locations:
Northern Ireland · Brazil · China · India · USA
With headquarters in Northern Ireland, FG Wilson operates through a Global
Dealer Network. To contact your local Sales Office please visit the FG Wilson
website at www.FGWilson.com

In line with our policy of continuous product development, we reserve the right to change specification without notice
P18-4/1PP/0908/GB

You might also like