Steam: Fig. 10.1.1 A Typical Basic Steam Circuit
Steam: Fig. 10.1.1 A Typical Basic Steam Circuit
The steam distribution system is the essential link between the steam generator and the steam user.
This Tutorial will look at methods of carrying steam from a central source to the point of use. The central source might
be a boiler house or the discharge from a co-generation plant. The boilers may burn primary fuel, or be waste heat
boilers using exhaust gases from high temperature processes, engines or even incinerators. Whatever the source, an
efficient steam distribution system is essential if steam of the right quality and pressure is to be supplied, in the right
quantity, to the steam using equipment. Installation and maintenance of the steam system are important issues, and
must be considered at the design stage.
 Top
                                                                                                                     Fig.
                                          10.1.1 A typical basic steam circuit
The steam generated in the boiler must be conveyed through pipework to the point where its heat energy is required.
Initially there will be one or more main pipes, or 'steam mains', which carry steam from the boiler in the general
direction of the steam using plant. Smaller branch pipes can then carry the steam to the individual pieces of
equipment.
When the boiler main isolating valve (commonly called the 'crown' valve) is opened, steam immediately passes from
the boiler into and along the steam mains to the points at lower pressure. The pipework is initially cooler than the
steam, so heat is transferred from the steam to the pipe. The air surrounding the pipes is also cooler than the steam,
so        the        pipework        will     begin        to        transfer       heat        to       the        air.
Steam on contact with the cooler pipes will begin to condense immediately. On start-up of the system, the
condensing rate will be at its maximum, as this is the time where there is maximum temperature difference between
the steam and the pipework. This condensing rate is commonly called the 'starting load'. Once the pipework has
warmed up, the temperature difference between the steam and pipework is minimal, but some condensation will
occur as the pipework still continues to transfer heat to the surrounding air. This condensing rate is commonly called
the                                                     'running                                                 load'.
The resulting condensation (condensate) falls to the bottom of the pipe and is carried along by the steam flow and
assisted by gravity, due to the gradient in the steam main that should be arranged to fall in the direction of steam
flow. The condensate will then have to be drained from various strategic points in the steam main.
When the valve on the steam pipe serving an item of steam using plant is opened, steam flowing from the distribution
system enters the plant and again comes into contact with cooler surfaces. The steam then transfers its energy in
warming up the equipment and product (starting load), and, when up to temperature, continues to transfer heat to the
process                                                (running                                               load).
There is now a continuous supply of steam from the boiler to satisfy the connected load and to maintain this supply
more steam must be generated. In order to do this, more water (and fuel to heat this water) is supplied to the boiler to
make      up    for    that    water     which      has     previously      been      evaporated       into     steam.
The condensate formed in both the steam distribution pipework and in the process equipment is a convenient supply
of useable hot boiler feedwater. Although it is important to remove this condensate from the steam space, it is a
valuable commodity and should not be allowed to run to waste. Returning all condensate to the boiler feedtank closes
the basic steam loop, and should be practised wherever practical. The return of condensate to the boiler is discussed
further in Block 13, 'Condensate Removal', and Block 14,'Condensate Management'.
As steam passes through the distribution pipework, it will inevitably lose pressure due to:
Therefore allowance should be made for this pressure loss when deciding upon the initial distribution pressure.
A kilogram of steam at a higher pressure occupies less volume than at a lower pressure. It follows that, if steam is
generated in the boiler at a high pressure and also distributed at a high pressure, the size of the distribution mains will
be smaller than that for a low-pressure system for the same heat load. Figure 10.1.2 illustrates this point.
        The thermal storage capacity of the boiler is increased, helping it to cope more efficiently with fluctuating
         loads, minimising the risk of producing wet and dirty steam.
        Smaller bore steam mains are required, resulting in lower capital cost, for materials such as pipes, flanges,
         supports, insulation and labour.
        Smaller bore steam mains cost less to insulate.
Having distributed at a high pressure, it will be necessary to reduce the steam pressure to each zone or point of use
in the system in order to correspond with the maximum pressure required by the application. Local pressure reduction
to suit individual plant will also result in drier steam at the point of use. (Tutorial 2.3 provides an explanation of this).
Note: It is sometimes thought that running a steam boiler at a lower pressure than its rated pressure will save fuel.
This logic is based on more fuel being needed to raise steam to a higher pressure.
Whilst there is an element of truth in this logic, it should be remembered that it is the connected load, and not the
boiler output, which determines the rate at which energy is used. The same amount of energy is used by the load
whether the boiler raises steam at 4 bar g, 10 bar g or 100 bar g. Standing losses, flue losses, and running losses are
increased by operating at higher pressures, but these losses are reduced by insulation and proper condensate return
systems. These losses are marginal when compared to the benefits of distributing steam at high pressure.
Pressure reduction
The common method for reducing pressure at the point where steam is to be used is to use a pressure reducing
valve, similar to the one shown in the pressure reducing station Figure 10.1.3.
Plant downstream of the pressure reducing valve is protected by a safety valve. If the pressure reducing valve fails,
the downstream pressure may rise above the maximum allowable working pressure of the steam using equipment.
This, in turn, may permanently damage the equipment, and, more importantly, constitute a danger to personnel.
With a safety valve fitted, any excess pressure is vented through the valve, and will prevent this from happening
(safety            valves              are             discussed              in             Block             9).
        The primary isolating valve - To shut the system down for maintenance.
        The primary pressure gauge - To monitor the integrity of supply.
        The strainer - To keep the system clean.
        The secondary pressure gauge - To set and monitor the downstream pressure.
        The secondary isolating valve - To assist in setting the downstream pressure on no-load conditions.
 Top
Standards and wall thickness
There are a number of piping standards in existence around the world, but arguably the most global are those derived
by the American Petroleum Institute (API), where pipes are categorised in schedule numbers.
These schedule numbers bear a relation to the pressure rating of the piping. There are eleven Schedules ranging
from the lowest at 5 through 10, 20, 30, 40, 60, 80, 100, 120, 140 to schedule No. 160. For nominal size piping 150
mm and smaller, Schedule 40 (sometimes called 'standard weight') is the lightest that would be specified for steam
applications.
Regardless of schedule number, pipes of a particular size all have the same outside diameter (not withstanding
manufacturing tolerances). As the schedule number increases, the wall thickness increases, and the actual bore is
reduced. For example:
          A 100 mm Schedule 40 pipe has an outside diameter of 114.30 mm, a wall thickness of 6.02 mm, giving a
           bore of 102.26 mm.
          A 100 mm Schedule 80 pipe has an outside diameter of 114.30 mm, a wall thickness of 8.56 mm, giving a
           bore of 97.18 mm.
Only Schedules 40 and 80 cover the full range from 15 mm up to 600 mm nominal sizes and are the most commonly
used            schedule              for             steam           pipe            installations.
Tables of schedule numbers can be obtained from BS 1600 which are used as a reference for the nominal pipe size
and wall thickness in millimetres. Table 10.2.1 compares the actual bore sizes of different sized pipes, for different
schedule                                                                                                    numbers.
In mainland Europe, pipe is manufactured to DIN standards, and DIN 2448 pipe is included in Table 10.2.1.
                                                                                                                 Table
                          10.2.1 Comparison of pipe standards and actual bore diameters.
In the United Kingdom, piping to EN 10255, (steel tubes and tubulars suitable for screwing to BS 21 threads) is also
used in applications where the pipe is screwed rather than flanged. They are commonly referred to as 'Blue Band'
and 'Red Band'; this being due to their banded identification marks. The different colours refer to particular grades of
pipe:
          Red Band, being heavy grade, is commonly used for steam pipe applications.
          Blue Band, being medium grade, is commonly used for air distribution systems, although it is sometimes
           used for low-pressure steam systems.
The coloured bands are 50 mm wide, and their positions on the pipe denote its length. Pipes less than 4 metres in
length only have a coloured band at one end, while pipes of 4 to 7 metres in length have a coloured band at either
end.
Pipe material
Pipes for steam systems are commonly manufactured from carbon steel to ASME (ANSI) B 16.9 A106. The same
material may be used for condensate lines, although copper tubing is preferred in some industries.
For high temperature superheated steam mains, additional alloying elements, such as chromium and molybdenum,
are    included   to   improve    tensile strength     and     creep   resistance    at   high   temperatures.
Pipeline sizing
The objective of the steam distribution system is to supply steam at the correct pressure to the point of use. It follows,
therefore, that pressure drop through the distribution system is an important feature.
Liquids
Bernoulli's Theorem (Daniel Bernoulli 1700 - 1782) is discussed in Block 4 - Flowmetering. D'Arcy (D'Arcy Thompson
1860 - 1948) added that for fluid flow to occur, there must be more energy at Point 1 than Point 2 (see Figure 10.2.3).
The difference in energy is used to overcome frictional resistance between the pipe and the flowing fluid.
                                                                                                              Fig. 10.2.3
                                                    Friction in pipes
Bernoulli relates changes in the total energy of a flowing fluid to energy dissipation expressed either in terms of a
head loss hf (m) or specific energy loss g hf (J/kg). This, in itself, is not very useful without being able to predict the
pressure          losses         that          will          occur            in         particular        circumstances.
Here, one of the most important mechanisms of energy dissipation within a flowing fluid is introduced, that is, the loss
in total mechanical energy due to friction at the wall of a uniform pipe carrying a steady flow of fluid.
The loss in the total energy of fluid flowing through a circular pipe must depend on:
L = The length of the pipe (m)
D = The pipe diameter (m)
u = The mean velocity of the fluid flow (m/s)
μ = The dynamic viscosity of the fluid (kg/m s=Pa s)
ρ = The fluid density (kg/m)
ks = The roughness of the pipe wall* (m)
*Since the energy dissipation is associated with shear stress at the pipe wall, the nature of the wall surface will be
influential, as a smooth surface will interact with the fluid in a different way than a rough surface.
All these variables are brought together in the D'Arcy-Weisbach equation (often referred to as the D'Arcy equation),
and shown as Equation 10.2.1. This equation also introduces a dimensionless term referred to as the friction factor,
which relates the absolute pipe roughness to the density, velocity and viscosity of the fluid and the pipe diameter.
The term that relates fluid density, velocity and viscosity and the pipe diameter is called the Reynolds number, named
after Osborne Reynolds (1842-1912, of Owens College, Manchester, United Kingdom), who pioneered this technical
approach          to          energy           losses         in        flowing          fluids       circa       1883.
                                                            Equation 10.2.1
Where                             for                 equation                       10.2.1                       using
SI based units:
                                                           Equation 10.2.2
The reason for the difference is the type of friction factor used. It is essential that the right version of the D'Arcy
equation be used with the selected friction factor. Matching the wrong equation to the wrong friction factor will result
in a 400% error and it is therefore important that the correct combination of equation and friction factor is utilised.
Many textbooks simply do not indicate which friction factors are defined, and a judgement must sometimes be based
on                               the                                magnitudes                                  quoted.
Equation 10.2.2 tends to be used by those who traditionally work in Imperial units, and still tends to be used by
practitioners in the United States and Pacific rim regions even when metric pipe sizes are quoted. Equation 10.2.1
tends to be used by those who traditionally work in SI units and tends more to be used by European practitioners. For
the same Reynolds number and relative roughness, the 'Imperial based friction factor' will be exactly four times larger
than                   the                 'SI                  based                 friction                  factor'.
Friction factors can be determined either from a Moody chart or, for turbulent flows, can be calculated from Equation
10.2.3, a development of the Colebrook - White formula.
                                                                             Equation 10.2.3
Where:
On an SI style Moody chart, the friction factor scale might typically range from 0.002 to 0.02, whereas on an Imperial
style     Moody      chart,       this       scale      might       range      from       0.008     to     0.08.
As a general rule, for turbulent flow with Reynolds numbers between 4000 and 100000, 'SI based' friction factors will
be of the order suggested by Equation 10.2.4, whilst 'Imperial based' friction factors will be of the order suggested by
Equation 10.2.5.
In essence, the friction factor depends on the Reynolds number (Re) of the flowing liquid and the relative roughness
(kS/d) of the inside of the pipe; the former calculated from Equation 10.2.6, and the latter from Equation 10.2.7.
                                                            Equation 10.2.6
Where:
Re = Reynolds number                         
ρ = Density of water                        = 1000 kg/m
u = Velocity of water                       = 0.71 m/s
D = Pipe diameter                           = 0.15 m
μ = Dynamic viscosity of water (at 15°C)    = 1.138 x 10-3 kg/m s (from steam tables)
From Equation 10.2.6:
The pipe roughness or 'ks' value (often quoted as 'e' in some texts) is taken from standard tables, and for 'commercial
steel       pipe'        would          generally          be         taken         as        0.000045          metres.
From this the relative roughness is determined (as this is what the Moody chart requires).
                                                                                      Equation 10.2.7
From Equation 10.2.7:
The friction factor can now be determined from the Moody chart and the friction head loss calculated from the
relevant                                          D'Arcy                                            Equation.
The same friction head loss is obtained by using the different friction factors and relevant D'Arcy equations.
In practice whether for water pipes or steam pipes, a balance is drawn between pipe size and pressure loss.
 Top
Steam
Oversized pipework means:
In a particular example:
            The cost of installing 80 mm steam pipework was found to be 44% higher than the cost of 50 mm pipework,
             which would have had adequate capacity.
            The heat lost by the insulated pipework was some 21% higher from the 80 mm pipeline than it would have
             been from the 50 mm pipework. Any non-insulated parts of the 80 mm pipe would lose 50% more heat than
             the 50 mm pipe, due to the extra heat transfer surface area.
            A lower pressure may only be available at the point of use. This may hinder equipment performance due to
             only lower pressure steam being available.
            There is a risk of steam starvation.
            There is a greater risk of erosion, waterhammer and noise due to the inherent increase in steam velocity.
As previously mentioned, the friction factor (f) can be difficult to determine, and the calculation itself is time
consuming especially for turbulent steam flow. As a result, there are numerous graphs, tables and slide rules
available    for   relating     steam     pipe     sizes      to     flowrates   and    pressure       drops.
One pressure drop sizing method, which has stood the test of time, is the 'pressure factor' method. A table of
pressure factor values is used in Equation 10.2.2 to determine the pressure drop factor for a particular installation.
                                                              Equation 10.2.8
Where:
F    =   Pressure factor
P1   =   Factor at inlet pressure
P2   =   Factor at a distance of L metres
L    =   Equivalent length of pipe (m)
Example 10.2.2
Consider the system shown in Figure 10.2.6, and determine the pipe size required from the boiler to the unit
heater branch line. Unit heater steam load = 270 kg/h.
                                                                                                        Fig. 10.2.6 System
                                            used to illustrate Example 10.2.2
Although the unit heater only requires 270 kg/h, the boiler has to supply more than this due to heat losses from the
pipe.
         If the pipe is less than 50 metres long, add an allowance for fittings of 5%.
         If the pipe is over 100 metres long and is a fairly straight run with few fittings, an allowance for fittings of 10%
          would be made.
         A similar pipe length, but with more fittings, would increase the allowance towards 20%.
From Table 10.2.2 (an extract from the complete pressure factor table, Table 10.2.5, which can be found in the
Appendix at the end of this Tutorial) 'P' can be determined by finding the pressure factors P 1 and P2, and substituting
them into Equation 10.2.8.
                                                                                                                    Table
                                10.2.2 Extract from pressure factor table (Table 10.2.5)
From            the           pressure             factor            table              (see         Table         10.2.2):
Substituting these pressure factors (P1 and P2) into Equation 10.2.8 will determine the value for 'F':
Equation 10.2.8.
Following down the left-hand column of the pipeline capacity and pressure drop factors table (Table 10.2.6 - Extract
shown in Table 10.2.3); the nearest two readings around the requirement of 0.032 are 0.030 and 0.040. The next
lower factor is always selected; in this case, 0.030.
                                                                                                                       Tab
                 le 10.2.3 Extract from pipeline capacity and pressure factor table (Table 10.2.6)
Although values can be interpolated, the table does not conform exactly to a straight-line graph, so interpolation
cannot be absolutely correct. Also, it is bad practice to size any pipe up to the limit of its capacity, and it is important
to    have    some     leeway       to     allow     for    the    inevitable    future      changes      in     design.
From factor 0.030, by following the row of figures to the right it will be seen that:
Since the application requires 286 kg/h, the 50 mm pipe would be selected.
Having sized the pipe using the pressure drop method, the velocity can be checked if required.
Where:
Viewed in isolation, this velocity may seem low in comparison with maximum permitted velocities. However, this
steam main has been sized to limit pressure drop, and the next smaller pipe size would have given a velocity of over
47 m/s, and a final pressure less than the requirement of 6.6 bar g, which is unacceptable.
As can be seen, this procedure is fairly complex and can be simplified by using the nomogram shown in Figure 10.2.9
(in the Appendix of this Tutorial). The method of use is explained in Example 10.2.3.
Example 10.2.3
Using the data from Example 10.2.2, determine the pipe size using the nomogram shown in Figure 10.2.7.
Method
           Select the point on the saturated steam line at 7 bar g, and mark Point A.
           From point A, draw a horizontal line to the steam flowrate of 286 kg/h, and mark Point B.
           From point B, draw a vertical line towards the top of the nomogram (Point C).
           Draw a horizontal line from 0.24 bar/100 m on the pressure loss scale (Line DE).
           The point at which lines DE and BC cross will indicate the pipe size required. In this case, a 40 mm pipe is
            too small, and a 50 mm pipe would be used.
                                                                                                                      Fig.
                                 10.2.7 Steam pipeline sizing chart - Pressure drop
Sizing pipes on velocity
From the knowledge gained at the beginning of this Tutorial, and particularly the notes regarding the D'Arcy equation
(Equation 10.2.1), it is acknowledged that velocity is an important factor in sizing pipes. It follows then, that if a
reasonable velocity could be used for a particular fluid flowing through pipes, then velocity could be used as a
practical sizing factor. As a general rule, a velocity of 25 to 40 m/s is used when saturated steam is the medium.
40 m/s should be considered an extreme limit, as above this, noise and erosion will take place particularly if the
steam                                                 is                                                      wet.
Even these velocities can be high in terms of their effect on pressure drop. In longer supply lines, it is often necessary
to restrict velocities to 15 m/s to avoid high pressure drops. It is recommended that pipelines over 50 m long are
always         checked        for      pressure         drop,      no        matter       what           the       velocity.
By using Table 10.2.4 as a guide, it is possible to select pipe sizes from known data; steam pressure, velocity and
flowrate.
                                                                                                               Table
          10.2.4 Saturated steam pipeline capacities in kg/h for different velocities (Schedule 40 pipe)
Alternatively the pipe size can be calculated arithmetically. The following information is required, and the procedure
used               for            the              calculation              is              outlined            below.
    = Volumetric flowrate (m³/s) = ms x vgFrom this information, the cross sectional area (A) of the pipe can be
      calculated:
Rearranging the formula to give the diameter of the pipe (D) in metres:
Example 10.2.4
A process requires 5 000 kg/h of dry saturated steam at 7 bar g. For the flow velocity not to exceed 25
m/s,                   determine                    the                     pipe                   size.
Where
Therefore, using:
Since the steam velocity must not exceed 25 m/s, the pipe size must be at least 130 mm; the nearest
commercially       available       size,      150        mm,         would        be       selected.
Again, a nomogram has been created to simplify this process, see Figure 10.2.6.
Example 10.2.5
Using the information from Example 10.2.4, use Figure 10.2.6 to determine the minimum acceptable pipe
size
Inlet pressure   =</TD 7 bar g
Steam flowrate   =     5000 kg/h
Maximum velocity =     25 m/s
Method:
       Draw a horizontal line from the saturation temperature line at 7 bar g (Point A) on the pressure scale to the
        steam mass flowrate of 5 000 kg/h (Point B).
       From point B, draw a vertical line to the steam velocity of 25 m/s (Point C). From point C, draw a horizontal
        line across the pipe diameter scale (Point D).
       A pipe with a bore of 130 mm is required; the nearest commercially available size, 150 mm, would be
        selected.
                                                                                                                 Fig.
                                  10.2.8 Steam pipeline sizing chart - Velocity
Sizing pipes for superheated steam duty
Superheated steam can be considered as a dry gas and therefore carries no moisture. Consequently there is no
chance of pipe erosion due to suspended water droplets, and steam velocities can be as high as 50 to 70 m/s if the
pressure drop permits this. The nomograms in Figures 10.2.5 and 10.2.6 can also be used for superheated steam
applications.
Example 10.2.6
Utilising the waste heat from a process, a boiler/superheater generates 30 t/h of superheated steam at 50 bar
g and 450°C for export to a neighbouring power station. If the velocity is not to exceed 50 m/s, determine:
Part 1
        Using Figure 10.2.8, draw a vertical line from 450°C on the temperature axis until it intersects the 50 bar line
         (Point A).
        From point A, project a horizontal line to the left until it intersects the steam 'mass flowrate' scale of 30 000
         kg/h (30 t/h) (Point B).
        From point B, project a line vertically upwards until it intersects 50 m/s on the 'steam velocity' scale (Point
         C).
        From Point C, project a horizontal line to the right until it intersects the 'inside pipe diameter' scale.
The 'inside pipe diameter' scale recommends a pipe with an inside diameter of about 120 mm. From Table 10.2.1 and
assuming that the pipe will be Schedule 80 pipe, the nearest size would be 150 mm, which has a bore of 146.4 mm.
Part 2
        Using Figure 10.2.7, draw a vertical line from 450°C on the temperature axis until it intersects the 50 bar line
         (Point A).
        From point A, project a horizontal line to the right until it intersects the 'steam mass flowrate' scale of 30 000
         kg/h (30 t/h) (Point B).
        From point B, project a line vertically upwards until it intersects the 'inside pipe diameter' scale of
         (approximately) 146 mm (Point C).
        From Point C, project a horizontal line to the left until it intersects the 'pressure loss bar/100 m' scale (Point
         D).
The 'pressure loss bar/100 m' scale reads about 0.9 bar/100 m. The pipe length in the example is 200 m, so the
pressure drop is:
                                                                           Equation 10.2.9.
Where:
P1   =   Upsteam pressure (bar a)
P2   =   Downstream pressure (bar a)
L    =   Length of pipe (m)
s    =   Mass flowrate (kg/h)
D    =   Pipe diameter (mm)
Pressure drop formula 2 (Maximum pipe length: 200 metres)
                                                                    Equation 10.2.10.
ΔP           =   Pressure drop (bar)
L            =   Length of pipe
vg           =   Specific volume of steam (m3/kg)
  </< td>    =   Mass flowrate(kg/h)
D            =   Pipe diameter (mm)
Where:
 Top
Summary
           The selection of piping material and the wall thickness required for a particular installation is stipulated in
            standards such as EN 45510 and ASME 31.1.
           Selecting the appropriate pipe size (nominal bore) for a particular application is based on accurately
            identifying pressure and flowrate. The pipe size may be selected on the basis of:
- Pressure drop (as a general rule, the pressure drop should not normally exceed 0.1 bar/50 m.
Appendix
Table
        10.2.5 Pressure drop factor (F) table
                                                        Tab
le 10.2.6 Pipeline capacity from pressure drop factor
                                                     Fig
10.2.9 Steam pipeline sizing chart - Pressure drop
                                                 Fig
10.2.10 Steam pipeline sizing chart - Velocity
Throughout the length of a hot steam main, an amount of heat will be transferred to the environment, and this will
depend on the parameters identified in Block 2 - 'Steam Engineering and Heat Transfer', and brought together in
Equation 2.5.1.
                                                               Equation 2.5.1
Where:
The effect of insulation is discussed in Tutorial 10.5. This Tutorial will concentrate on disposal of the inevitable
condensate, which, unless removed, will accumulate and lead to problems such as corrosion, erosion, and
waterhammer.
In addition, the steam will become wet as it picks up water droplets, which reduces its heat transfer potential. If water
is allowed to accumulate, the overall effective cross sectional area of the pipe is reduced, and steam velocity can
increase above the recommended limits.
 Top
Piping layout
The subject of drainage from steam lines is covered in the European Standard EN 45510, Section 4.12.
EN 45510 states that, whenever possible, the main should be installed with a fall of not less than 1:100 (1 m fall for
every 100 m run), in the direction of the steam flow. This slope will ensure that gravity, as well as the flow of steam,
will assist in moving the condensate towards drain points where the condensate may be safely and effectively
removed (See Figure 10.3.1).
                                                                                                          Fig. 10.3.1
                                           Typical steam main installation
Drain points
The drain point must ensure that the condensate can reach the steam trap. Careful consideration must therefore be
given        to        the         design       and         location       of        drain        points.
Consideration must also be given to condensate remaining in a steam main at shutdown, when steam flow ceases.
Gravity will ensure that the water (condensate) will run along sloping pipework and collect at low points in the system.
Steam          traps        should       therefore        be        fitted     to        these        low         points.
The amount of condensate formed in a large steam main under start-up conditions is sufficient to require the
provision of drain points at intervals of 30 m to 50 m, as well as natural low points such as at the bottom of rising
pipework.
In normal operation, steam may flow along the main at speeds of up to 145 km/h, dragging condensate along with it.
Figure 10.3.2 shows a 15 mm drain pipe connected directly to the bottom of a main.
A more reliable solution for the removal of condensate is shown in Figure 10.3.3. The trap line should be at least 25
to 30 mm from the bottom of the pocket for steam mains up to 100 mm, and at least 50 mm for larger mains. This
allows a space below for any dirt and scale to settle.
Recommended drain pocket dimensions are shown in Table 10.3.1 and in Figure 10.3.4.
                                                                                                                 Table
                                  10.3.1 Recomended drain pocket dimensions
 Top
        Because the condensate velocity is higher than normal, the dissipation of kinetic energy is higher than would
         normally be expected.
        Water is dense and incompressible, so the 'cushioning' effect experienced when gases encounter
         obstructions is absent.
        The energy in the water is dissipated against the obstructions in the piping system such as valves and
         fittings.
                                                                                                      Fig. 10.3.5
                                        Formation of a ‘solid’ slug of water
Indications   of   waterhammer     include   a    banging    noise,   and    perhaps    movement      of   the    pipe.
In severe cases, waterhammer may fracture pipeline equipment with almost explosive effect, with consequent loss of
live     steam     at    the    fracture,      leading    to      an     extremely       hazardous      situation.
Good engineering design, installation and maintenance will avoid waterhammer; this is far better practice than
attempting   to    contain    it   by     choice    of    materials     and     pressure     ratings    of    equipment.
Commonly, sources of waterhammer occur at the low points in the pipework (See Figure 10.3.6). Such areas are due
to:
                                                                                                             Fig. 10.3.6
                                        Potential sources of waterhammer
       Installing steam lines with a gradual fall in the direction of flow, and with drain points installed at regular
        intervals and at low points.
       Installing check valves after all steam traps which would otherwise allow condensate to run back into the
        steam line or plant during shutdown.
       Opening isolation valves slowly to allow any condensate which may be lying in the system to flow gently
        through the drain traps, before it is picked up by high velocity steam. This is especially important at start-up.
 Top
Branch lines
Table 10.2.4 'Saturated steam pipeline capacities for different velocities' in Tutorial 10.2 will prove useful in this
exercise.
The valve in Figure 10.3.9 (b) should be positioned as near to the off-take as possible to minimise condensate lying in
the branch line, if the plant is likely to be shutdown for any extended periods.
                                                                            Fig. 10.3.9 Steam off-take
Drop leg
Low points will also occur in branch lines. The most common is a drop leg close to an isolating valve or a control
valve (Figure 10.3.10). Condensate can accumulate on the upstream side of the closed valve, and then be propelled
forward with the steam when the valve opens again - consequently a drain point with a steam trap set is good
practice just prior to the strainer and control valve.
                                                                                                            Fig.
                             10.3.10 Diagram of a drop leg supplying a unit heater
 Top
The objective is to prevent the condensate film on the bottom of the pipe increasing in thickness to the point where
droplets can be picked up by the steam flow.
Steam separators
Modern packaged steam boilers have a large evaporating capacity for their size and have limited capacity to cope
with rapidly changing loads. In addition, as discussed in Block 3 'The Boiler House', other circumstances, such as . . .
. . . can cause priming and carryover of boiler water into the steam mains.
Separators, as shown by the cut section in Figure 10.3.12, may be installed to remove this water.
                                                                                          Fig. 10.3.12 Cut section
                                                 through a separator
As a general rule, providing the velocities in the pipework are within reasonable limits, separators will be line sized.
(Separators           are          discussed            in          detail          in         Tutorial            12.5)
A separator will remove both droplets of water from pipe walls and suspended mist entrained in the steam itself. The
presence and effect of waterhammer can be eradicated by fitting a separator in a steam main, and can often be less
expensive        than     increasing      the      pipe       size     and      fabricating     drain      pockets.
A separator is recommended before control valves and flowmeters. It is also wise to fit a separator where a steam
main enters a building from outside. This will ensure that any condensate produced in the external distribution system
is removed and the building always receives dry steam. This is equally important where steam usage in the building
is monitored and charged for.
 Top
Strainers
When new pipework is installed, it is not uncommon for fragments of casting sand, packing, jointing, swarf, welding
rods and even nuts and bolts to be accidentally deposited inside the pipe. In the case of older pipework, there will be
rust, and in hard water districts, a carbonate deposit. Occasionally, pieces will break loose and pass along the
pipework with the steam to rest inside a piece of steam using equipment. This may, for example, prevent a valve from
opening/closing correctly. Steam using equipment may also suffer permanent damage through wiredrawing - the
cutting action of high velocity steam and water passing through a partly open valve. Once wiredrawing has occurred,
the     valve      will    never     give    a     tight   shut-off,    even      if   the     dirt   is     removed.
It is therefore wise to fit a line-size strainer in front of every steam trap, flowmeter, reducing valve and regulating
valve. The illustration shown in Figure 10.3.13 shows a cut section through a typical strainer.
                                                                                         Fig. 10.3.13 Cut section
                                             through a Y-type strainer.
Steam flows from the inlet 'A' through the perforated screen 'B' to the outlet 'C'. While steam and water will pass
readily through the screen, dirt cannot. The cap 'D', can be removed, allowing the screen to be withdrawn and
cleaned at regular intervals. A blowdown valve can also be fitted to cap 'D' to facilitate regular cleaning.
Strainers can however, be a source of wet steam as previously mentioned. To avoid this situation, strainers should
always      be     installed    in     steam      lines     with     their    baskets        to      the      side.
The steam traps selected must suit the system in terms of:
        Pressure rating
        Capacity
        Suitability
Pressure rating
Pressure rating is easily dealt with; the maximum possible working pressure at the steam trap will either be known or
should be established.
Capacity
Capacity, that is, the quantity of condensate to be discharged, which needs to be divided into two categories; warm-
up                         load                        and                      running                         load.
Warm-up load - In the first instance, the pipework needs to be brought up to operating temperature. This can be
determined by calculation, knowing the mass and specific heat of the pipework and fittings. Alternatively, Table 10.3.2
may be used.
       The table shows the amount of condensate generated when bringing 50 m of steam main up to working
        temperature; 50 m being the maximum recommended distance between trapping points.
       The values shown are in kilograms. To determine the average condensing rate, the time taken for the
        process must be considered. For example, if the warm-up process required 50 kg of steam, and was to take
        20 minutes, then the average condensing rate would be:
       When using these capacities to size a steam trap, it is worth remembering that the initial pressure in the
        main will be little more than atmospheric when the warm-up process begins. However, the condensate loads
        will still generally be well within the capacity of a DN15 'low capacity' steam trap. Only in rare applications at
        very high pressures (above 70 bar g), combined with large pipe sizes, will greater trap capacity be needed.
Running load - Once the steam main is up to operating temperature, the rate of condensation is mainly a function of
the    pipe      size      and     the       quality     and      thickness       of     the      insulation.
Alternatively, for quick approximations of running load, Table 10.3.3 can be used which shows typical amounts of
steam condensed each hour per 50 m of insulated steam main at various pressures. For accurate means of
calculating running losses from steam mains, refer to Tutorial 2.12 'Steam consumption of pipes and air heaters'.
                                                                                                                  Table
                10.3.2 Amount of steam condensed to warm-up 50 m of schedule 40 pipe (kg)
Note: Figures are based on an ambient temperature of 20°C, and an insulation efficiency of 80%
                                                                                                                  Table
         10.3.3 Condensing rate of steam in 50 m of schedule 40 pipe - at working temperature (kg/h)
Note: Figures are based on an ambient temperature of 20°C, and an insulation efficiency of 80%
Suitability
A mains drain trap should consider the following constraints:
        Discharge temperature - The steam trap should discharge at, or very close to saturation temperature,
         unless cooling legs are used between the drain point and the trap. This means that the choice is a
         mechanical type trap (such as a float, inverted bucket type, or thermodynamic traps).
        Frost damage - Where the steam main is located outside a building and there is a possibility of sub-zero
         ambient temperature, the thermodynamic steam trap is ideal, as it is not damaged by frost. Even if the
         installation causes water to be left in the trap at shutdown and freezing occurs, the thermodynamic trap may
         be thawed out without suffering damage when brought back into use.
        Waterhammer - In the past, on poorly laid out installations where waterhammer was a common occurrence,
         float traps were not always ideal due to their susceptibility to float damage. Contemporary design and
         manufacturing techniques now produce extremely robust units for mains drainage purposes. Float traps are
         certainly the first choice for proprietary separators as high capacities are readily achieved, and they are able
         to respond quickly to rapid load increases.
Steam traps used to drain condensate from steam mains, are shown in Figure 10.3.14. The thermostatic trap is
included because it is ideal where there is no choice but to discharge condensate into a flooded return pipe.
The subject of steam trapping is dealt with in detail in the Block 11, 'Steam Trapping'.
                                                                                                                  Fig.
                             10.3.14 Steam traps suitable for steam mains drainage
 Top
Steam leaks
Steam leaking from pipework is often ignored. Leaks can be costly in both the economic and environmental sense
and therefore need prompt attention to ensure the steam system is working at its optimum efficiency with a minimum
impact                               on                             the                                environment.
Figure 10.3.15 illustrates the steam loss for various sizes of hole at various pressures. This loss can be readily
translated into a fuel saving based on the annual hours of operation.
Summary
Proper pipe alignment and drainage means observing a few simple rules:
       Steam lines should be arranged to fall in the direction of flow, at not less than 100 mm per 10 metres of pipe
         (1:100). Steam lines rising in the direction of flow should slope at not less than 250 mm per 10 metres of
         pipe (1:40).
       Steam lines should be drained at regular intervals of 30-50 m and at any low points in the system.
       lWhere drainage has to be provided in straight lengths of pipe, then a large bore pocket should be used to
         collect condensate.
       If strainers are to be fitted, then they should be fitted on their sides.
       Branch connections should always be taken from the top of the main from where the driest steam is taken.
       Separators should be considered before any piece of steam using equipment ensuring that dry steam is
         used.
       Traps selected should be robust enough to avoid waterhammer damage and frost damage.
Allowance for expansion
All pipes will be installed at ambient temperature. Pipes carrying hot fluids such as water or steam operate at higher
temperatures.
It follows that they expand, especially in length, with an increase from ambient to working temperatures. This will
create stress upon certain areas within the distribution system, such as pipe joints, which, in the extreme, could
fracture. The amount of the expansion is readily calculated using Equation 10.4.1, or read from an appropriate chart
such as Figure 10.4.1.
                                                                          Equation 10.4.1
Where:
                                                                                                                  Table
                                 10.4.1 Expansion coefficients (a) (mm/m °C x 10-3)
Example 10.4.1
A 30 m length of carbon steel pipe is to be used to transport steam at 4 bar g (152°C). If the pipe is installed at 10°C,
determine the expansion using Equation 10.4.1.
Alternatively, the chart in Figure 10.4.1 can be used for finding the approximate expansion of a variety of steel pipe
lengths - see Example 10.4.2 for explanation of use.
Example 10.4.2
Using Figure 10.4.1. Find the approximate expansion from 15°C, of 100 metres of carbon steel pipework used to
distribute                            steam                            at                              265°C.
Where the diagonal temperature difference line of 250°C cuts the horizontal pipe length line at 100 m, drop a vertical
line down. For this example an approximate expansion of 330 mm is indicated.
                                                                                                                Table
                                      10.4.2 Temperature of saturated steam
 Top
Pipework flexibility
The pipework system must be sufficiently flexible to accommodate the movements of the components as they
expand. In many cases the flexibility of the pipework system, due to the length of the pipe and number of bends and
supports, means that no undue stresses are imposed. In other installations, however, it will be necessary to
incorporate       some            means           of        achieving          this         required       flexibility.
An example on a typical steam system is the discharge of condensate from a steam mains drain trap into the
condensate return line that runs along the steam line (Figure 10.4.2). Here, the difference between the expansions of
the two pipework systems must be taken into account. The steam main will be operating at a higher temperature than
that of the condensate main, and the two connection points will move relative to each other during system warm-up.
                                                                                  Fig. 10.4.2 Flexibility in connection to
                                                 condensate return line
The amount of movement to be taken up by the piping and any device incorporated in it can be reduced by 'cold
draw'. The total amount of expansion is first calculated for each section between fixed anchor points. The pipes are
left short by half of this amount, and stretched cold by pulling up bolts at a flanged joint, so that at ambient
temperature, the system is stressed in one direction. When warmed through half of the total temperature rise, the
piping is unstressed. At working temperature and having fully expanded, the piping is stressed in the opposite
direction. The effect is that instead of being stressed from 0 F to +1 F units of force, the piping is stressed from -½ F
to                 +                  ½                  F                units                   of                force.
In practical terms, the pipework is assembled cold with a spacer piece, of length equal to half the expansion, between
two flanges. When the pipework is fully installed and anchored at both ends, the spacer is removed and the joint
pulled up tight (see Figure 10.4.3).
In practice, pipework expansion and support can be classified into three areas as shown in Figure 10.4.4.
                                                                                                               Fig. 10.4.4
                Diagram of pipeline with fixed point, variable anchor point and expansion fitting
The    fixed   or   'anchor'   points   'A'   provide   a   datum   position   from   which   expansion   takes   place.
The sliding support points 'B' allow free movement for expansion of the pipework, while keeping the pipeline in
alignment.
The expansion device at point 'C' is to accommodate the expansion and contraction of the pipe.
Roller supports (Figure 10.4.5 and 10.4.6) are ideal methods for supporting pipes, at the same time allowing them to
move in two directions. For steel pipework, the rollers should be manufactured from ferrous material. For copper
pipework, they should be manufactured from non-ferrous material. It is good practice for pipework supported on
rollers to be fitted with a pipe saddle bolted to a support bracket at not more than distances of 6 metres to keep the
pipework            in         alignment         during         any         expansion          and         contraction.
Where two pipes are to be supported one below the other, it is poor practice to carry the bottom pipe from the top
pipe using a pipe clip. This will cause extra stress to be added to the top pipe whose thickness has been sized to take
only              the                stress               of              its            working             pressure.
All pipe supports should be specifically designed to suit the outside diameter of the pipe concerned.
 Top
Expansion fittings
The expansion fitting ('C' Figure 10.4.4) is one method of accommodating expansion. These fittings are placed within
a line, and are designed to accommodate the expansion, without the total length of the line changing. They are
commonly called expansion bellows, due to the bellows construction of the expansion sleeve.
Other expansion fittings can be made from the pipework itself. This can be a cheaper way to solve the problem, but
more space is needed to accommodate the pipe.
Full loop
This is simply one complete turn of the pipe and, on steam pipework, should preferably be fitted in a horizontal rather
than     a    vertical position      to   prevent    condensate    accumulating      on     the     upstream      side.
The downstream side passes below the upstream side and great care must be taken that it is not fitted the wrong way
round, as condensate can accumulate in the bottom. When full loops are to be fitted in a confined space, care must
be       taken      to      specify      that      wrong-handed          loops         are       not       supplied.
The full loop does not produce a force in opposition to the expanding pipework as in some other types, but with steam
pressure inside the loop, there is a slight tendency to unwind, which puts an additional stress on the flanges.
If any of these arrangements are fitted with the loop vertically above the pipe then a drain point must be provided on
the upstream side as depicted in Figure 10.4.8.
It can be seen from Figure 10.4.9 that the depth of the loop should be twice the width, and the width is determined
from Figure 10.4.10, knowing the total amount of expansion expected from the pipes either side of the loop.
                                                                                                          Fig. 10.4.10
                                  Expansion loop capacity for carbon steel pipes
Sliding joint
These are sometimes used because they take up little room, but it is essential that the pipeline is rigidly anchored
and guided in strict accordance with the manufacturers' instructions; otherwise steam pressure acting on the cross
sectional area of the sleeve part of the joint tends to blow the joint apart in opposition to the forces produced by the
expanding pipework (see Figure 10.4.11). Misalignment will cause the sliding sleeve to bend, while regular
maintenance of the gland packing may also be needed.
                                                                                          Fig. 10.4.11 Sliding joint
Expansion bellows
An expansion bellows, Figures 10.4.12, has the advantage that it requires no packing (as does the sliding joint type).
But it does have the same disadvantages as the sliding joint in that pressure inside tends to extend the fitting,
consequently, anchors and guides must be able to withstand this force.
Where larger forces are expected, some form of additional mechanical reinforcement should be built into the device,
such           as          hinged           stay           bars           (Figure          10.4.13             (c)).
There is invariably more than one way to accommodate the relative movement between two laterally displaced pipes
depending upon the relative positions of bellows anchors and guides. In terms of preference, axial displacement is
better than angular, which in turn, is better than lateral. Angular and lateral movement should be avoided wherever
possible.
Figure 10.4.13 (a), (b), and (c) give a rough indication of the effects of these movements, but, under all
circumstances, it is highly recommended that expert advice is sought from the bellows' manufacturer regarding any
installation of expansion bellows.
                                                      Fig.
       10.4.13 (a) Axial movement of bellows
                                                        Fig.
10.4.13 (b) Lateral and angular movement of bellows
                                                                                            Fig. 10.4.13 (c) Angular
                                          and axial movement of bellows
 Top
        Pipe supports should be provided at intervals not greater than shown in Table 10.4.3, and run along those
         parts of buildings and structures where appropriate supports may be mounted.
        Where two or more pipes are supported on a common bracket, the spacing between the supports should be
         that for the smallest pipe.
        When an appreciable movement will occur, i.e. where straight pipes are greater than 15 metres in length,
         the supports should be of the roller type as outlined previously.
        Vertical pipes should be adequately supported at the base, to withstand the total weight of the vertical pipe
         and the fluid within it. Branches from vertical pipes must not be used as a means of support for the pipe,
         because this will place undue strain upon the tee joint.
        All pipe supports should be specifically designed to suit the outside diameter of the pipe concerned. The use
         of oversized pipe brackets is not good practice.
Table 10.4.3 can be used as a guide when calculating the distance between pipe supports for steel and copper
pipework.
                                                                                                    Table
                                10.4.3 Recommended support for pipework
The subject of pipe supports is covered comprehensively in the European standard EN 13480, Part3.