0% found this document useful (0 votes)
60 views4 pages

Review Comment Log - Tank Farm

The document is a log of 24 comments on a 3D model review of a tank farm area. The comments note issues like foundation depths transferring loads to existing lines, combining platforms, tag numbers matching P&IDs, valve locations, clearance spaces, ladder access, actuator locations, platform optimizations, crane heights, bend radii, support locations, line crossings, blind flanges, interferences, line supports, and modeling existing lines in a different color. All comments are marked as actions for "PENSPEN" to address.

Uploaded by

srini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views4 pages

Review Comment Log - Tank Farm

The document is a log of 24 comments on a 3D model review of a tank farm area. The comments note issues like foundation depths transferring loads to existing lines, combining platforms, tag numbers matching P&IDs, valve locations, clearance spaces, ladder access, actuator locations, platform optimizations, crane heights, bend radii, support locations, line crossings, blind flanges, interferences, line supports, and modeling existing lines in a different color. All comments are marked as actions for "PENSPEN" to address.

Uploaded by

srini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

30% 3D Model Review Comments Log - Tank Farm Area

Tag No Tag Description 3D Model Snap Action By Remark

Foundation depth design such way that loads are not transfer to existing
1 PENSPEN
lines(FW)

2 Consider possibility to combine the 2 platform PENSPEN

3 All Tag numbers should be as per P&IDs including dummy parts PENSPEN

4 This MOV should be close to main line to reduce dead leg PENSPEN

5 Avoid duplication of MOV Tags 1001-06 in P&ID 1606 & 1614 PENSPEN

6 Check possibility to move this MOV near to filter and common platform PENSPEN

7 Maintain 750mm clear space to be kept for maintenance purpose PENSPEN

8 Add one ladder from platform for access and maintenance for these 2 valves PENSPEN

Page 1 of 4
30% 3D Model Review Comments Log - Tank Farm Area

Tag No Tag Description 3D Model Snap Action By Remark

9 Review location of manual valve for accessible location PENSPEN

10 All actuator handwheel will be maximum 500mm from platform PENSPEN

11 Optimize the platform for crossover to other area PENSPEN

Model Platform and it should not clash with quick opening, Update existing
12 launcher arrangement as per drawings available and update 18" launcher PENSPEN
accordingly

13 Update height of JIB crane as per ADNOC spec & Shell DEP PENSPEN

14 Update Bend radius for these elbow as per pipeline requirement PENSPEN

15 Diesel Tank will be here for pump, check the requirement for separate sheds PENSPEN

16 Move Support to avoid clash with fire water PENSPEN

Page 2 of 4
30% 3D Model Review Comments Log - Tank Farm Area

Tag No Tag Description 3D Model Snap Action By Remark

Goal post Support foundations shall not be hindrance to the existing drain
17 PENSPEN
channel

18 Use 45 degree elbows for 18" lines for crossings PENSPEN

19 Add MOV with Actuator (Typ) PENSPEN

20 Update connection to 48" line with blind flange PENSPEN

21 Update existing facility to ensure that there is not interference to new facility PENSPEN

22 Add 64" line support to check for after demolitions its properly supported PENSPEN

23 Add Support for existing line and check support requirement for new line 4396 PENSPEN

24 Existing Line to be modelled by different color PENSPEN

Page 3 of 4
30% 3D Model Review Comments Log - Tank Farm Area

Tag No Tag Description 3D Model Snap Action By Remark

25 Add TP-115 and add connecting line with blind PENSPEN

Page 4 of 4