30% 3D Model Review Comments Log - Tank Farm Area
Tag No Tag Description 3D Model Snap Action By Remark
Foundation depth design such way that loads are not transfer to existing
1 PENSPEN
lines(FW)
2 Consider possibility to combine the 2 platform PENSPEN
3 All Tag numbers should be as per P&IDs including dummy parts PENSPEN
4 This MOV should be close to main line to reduce dead leg PENSPEN
5 Avoid duplication of MOV Tags 1001-06 in P&ID 1606 & 1614 PENSPEN
6 Check possibility to move this MOV near to filter and common platform PENSPEN
7 Maintain 750mm clear space to be kept for maintenance purpose PENSPEN
8 Add one ladder from platform for access and maintenance for these 2 valves PENSPEN
Page 1 of 4
30% 3D Model Review Comments Log - Tank Farm Area
Tag No Tag Description 3D Model Snap Action By Remark
9 Review location of manual valve for accessible location PENSPEN
10 All actuator handwheel will be maximum 500mm from platform PENSPEN
11 Optimize the platform for crossover to other area PENSPEN
Model Platform and it should not clash with quick opening, Update existing
12 launcher arrangement as per drawings available and update 18" launcher PENSPEN
accordingly
13 Update height of JIB crane as per ADNOC spec & Shell DEP PENSPEN
14 Update Bend radius for these elbow as per pipeline requirement PENSPEN
15 Diesel Tank will be here for pump, check the requirement for separate sheds PENSPEN
16 Move Support to avoid clash with fire water PENSPEN
Page 2 of 4
30% 3D Model Review Comments Log - Tank Farm Area
Tag No Tag Description 3D Model Snap Action By Remark
Goal post Support foundations shall not be hindrance to the existing drain
17 PENSPEN
channel
18 Use 45 degree elbows for 18" lines for crossings PENSPEN
19 Add MOV with Actuator (Typ) PENSPEN
20 Update connection to 48" line with blind flange PENSPEN
21 Update existing facility to ensure that there is not interference to new facility PENSPEN
22 Add 64" line support to check for after demolitions its properly supported PENSPEN
23 Add Support for existing line and check support requirement for new line 4396 PENSPEN
24 Existing Line to be modelled by different color PENSPEN
Page 3 of 4
30% 3D Model Review Comments Log - Tank Farm Area
Tag No Tag Description 3D Model Snap Action By Remark
25 Add TP-115 and add connecting line with blind PENSPEN
Page 4 of 4