MRV S: Service Manual (4-6HP)
MRV S: Service Manual (4-6HP)
MRV S (4-6HP)
Service Manual
SYJS-01-2017 REV.A Edition: 2017-01
1.2 Feature.......................................................................................................................................................... 2
2. Specification......................................................................................................................................................... 3
3. Dimension............................................................................................................................................................ 7
4. Piping Diagram.................................................................................................................................................... 8
5. Wiring Diagram.................................................................................................................................................. 10
6. Capacity Calculation Due to Capacity Modification Coefficient.......................................................................... 12
7. Operation Range................................................................................................................................................ 14
8. Sound Level....................................................................................................................................................... 15
AU042FPERA
AU052FPERA
AU062FPERA
AU04IFPERA
AU05IFPERA
AU06IFPERA
1
Downloaded from www.Manualslib.com manuals search engine
1.2 Feature
Round corner
Better outlook & safer
Comfort
6 New aerodynamics fan
550mm super big diameter aerospace helix fan. Lowering sound level 3 dB(A)
7 Enlarged air inlet path and spiral air outlet path
Air flow direction follows the grill direction. Lowering sound level 2-4 dB(A) AVERAGE
EER
8 Automatic sound-lowering program 11%
Night mode set by PCB, 8dB(A) lower
Convenience
2
Downloaded from www.Manualslib.com manuals search engine
2. Specification
Model AU042FPERA AU052FPERA AU062FPERA
Power supply Ph/V/Hz 1Ph,220-230V,50/60Hz
Rated capacity kW 12.60 14.00 15.50
Rated capacity kBtu/h 42.99 47.77 52.89
Capacity (46°C) kW 11.2 12.6 14
Rated power input kW 3.11 3.51 4.31
Cooling Power input (46°C) kW 3.77 4.25 5.22
Max. power input kW 7.20 7.50 7.80
EER 4.05 3.99 3.60
Rated current A 14.73 16.62 20.41
Max. current A 34.09 35.51 36.93
Rated capacity kW 14.20 16.00 18.00
Rated capacity kBtu/h 48.45 54.59 61.42
Rated power input kW 3.18 3.72 4.39
Heating Max. power input kW 6.9 7.2 7.5
COP 4.47 4.30 4.10
Rated current A 15.06 17.61 20.79
Max. current A 32.67 34.09 35.51
Brand MITSUBISHI ELECTRIC
Model MNB42FFAMC-L
Type Rotary Rotary Rotary
Compressor quantity 1 INV 1 INV 1 INV
Capacity W 13780 13780 13780
Power Input W 4130 4130 4130
Compressor
Rated current(RLA) A 15.8 15.8 15.8
Speed rps 75 80 85
Crankcase Heater W 33 33 33
Refrigerant oil brand IDEMITSUKOSAN CO.LTD
Refrigerant oil type FV50S FV50S FV50S
Refrigerant oil charge ml 1100 1100 1100
Brand NIDEC NIDEC NIDEC
Model SIC-88FWJ-F1180-1
Voltage 310V 310V 310V
IP Class IP44 IP44 IP44
Type DC DC DC
Insulation class E E E
Outdoor fan motor
Safe class I I I
Power Input W 180 180 180
Output W 120 120 120
Rated current A 0.4 0.4 0.4
Capacitor μF / / /
Speed rpm 900 900 900
3
Downloaded from www.Manualslib.com manuals search engine
Model AU042FPERA AU052FPERA AU062FPERA
Power supply Ph/V/Hz 1PH,220-230V,50/60Hz
Brand Haier Haier Haier
Model / / /
Outdoor Material Plastic Plastic Plastic
fan Type Axial Axial Axial
Diameter mm 550 550 550
Height mm 200 200 200
Number of rows 2 2 2
Tube pitch(a)x row pitch(b) mm 21*18.186 21*18.186 21*18.186
Fin spacing mm 1.4 1.4 1.4
Fin type (code) Hydrophilic aluminium
Outdoor Fin Coating Type Optional Clear lacquer Clear lacquer Clear lacquer
coil Salt Spray Test Duration Hour 168 168 168
Inner groove tube
Tube outside dia. and type
mm Ф7 Ф7 Ф7
Coil length x height mm 1077*1315 1077*1315 1077*1315
Number of circuits 7 7 7
Coating type Powder coating Powder coating Powder coating
Cabinet Salt Spray Test Duration Hour 72 72 72
coating Sheet Metal Material Hot zinc plate Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 0.8 0.8 0.8
Control panel enclosure IP class Standard IP24 IP24 IP24
Outdoor air flow m3/h 7200 7200 7200
Outdoor sound level(sound pressure level) dB(A) 50 51 53
Outdoor sound level(sound power level) dB(A) 68 69 70
Dimension(W*H*D) mm 950/370/1340 950/370/1340 950/370/1340
Outdoor Packing (W*H*D) mm 1023/471/1420 1023/471/1420 1023/471/1420
unit Net weight kg 115 115 115
Gross weight kg 123 123 123
Type R410A R410A R410A
Refrigerant
Charged volume kg 4 4 4
Throttle type EXV EXV EXV
Design pressure MPa 4.15 4.15 4.15
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Total pipe length m 300 300 300
Refrigerant Max. pipe length
m 175/150 175/150 175/150
piping (Equivalent/ Actual)
50 (Outdoor higher than indoor)
Max. Diff. indoor/outdoor unit m
40 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit m 15 15 15
Connectable indoor unit ratio % 50%~130% 50%~130% 50%~130%
Maximum indoor units Piece 8 10 13
Connection Power wiring mm2 10 10 10
wiring Signal wiring mm2 Shield wire:(0.75-2)*2
Cooling:-15~48
Operation Range °C
Heating:-20~27
Norminal condition: indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating):
20°CDB/14.5°C WB.
Outdoor temperature(cooling): 35°C DB/24°C WB, outdoor temperature(heating): 7°C DB/6°C WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
4
Downloaded from www.Manualslib.com manuals search engine
Model AU04IFPERA AU05IFPERA AU06IFPERA
Power supply Ph/V/Hz 3N,380-400V,50/60Hz
Rated capacity kW 12.60 14.00 15.50
Rated capacity kBtu/h 42.99 47.77 52.89
Capacity (46°C) kW 11.2 12.6 14
Rated power input kW 3.11 3.51 4.31
Cooling Power input (46°C) kW 3.77 4.25 5.22
Max. power input kW 7.20 7.50 7.80
EER 4.05 3.99 3.60
Rated current A 4.92 5.56 6.82
Max. current A 11.40 11.87 12.35
Rated capacity kW 14.20 16.00 18.00
Rated capacity kBtu/h 48.45 54.59 61.42
Rated power input kW 3.18 3.72 4.39
Heating Max. power input kW 6.9 7.2 7.5
COP 4.47 4.30 4.10
Rated current A 5.03 5.89 6.95
Max. current A 10.92 11.40 11.87
Brand MITSUBISHI ELECTRIC
Model MNB42FFDMC-L
Type Rotary Rotary Rotary
Compressor quantity 1 INV 1 INV 1 INV
Capacity W 13780 13780 13780
Power Input W 4060 4060 4060
Compressor
Rated current(RLA) A 12.3 12.3 12.3
Speed rps 75 80 85
Crankcase Heater W 33 33 33
Refrigerant oil brand IDEMITSUKOSAN CO.LTD
Refrigerant oil type FV50S FV50S FV50S
Refrigerant oil charge ml 1400 1400 1400
Brand NIDEC NIDEC NIDEC
Model SIC-88FWJ-F1180-1
Voltage 310V 310V 310V
IP Class IP44 IP44 IP44
Type DC DC DC
Insulation class E E E
Outdoor fan motor
Safe class I I I
Power Input W 180 180 180
Output W 120 120 120
Rated current A 0.4 0.4 0.4
Capacitor μF / / /
Speed rpm 900 900 900
5
Downloaded from www.Manualslib.com manuals search engine
Model AU04IFPERA AU05IFPERA AU06IFPERA
Power supply Ph/V/Hz 3N,380-400V,50/60Hz
Brand Haier Haier Haier
Model / / /
Outdoor Material Plastic Plastic Plastic
fan Type Axial Axial Axial
Diameter mm 550 550 550
Height mm 200 200 200
Number of rows 2 2 2
Tube pitch(a)x row pitch(b) mm 21*18.186 21*18.186 21*18.186
Fin spacing mm 1.4 1.4 1.4
Fin type (code) Hydrophilic aluminium
Outdoor Fin Coating Type Optional Clear lacquer Clear lacquer Clear lacquer
coil Salt Spray Test Duration Hour 168 168 168
Inner groove tube
Tube outside dia. and type
mm Ф7 Ф7 Ф7
Coil length x height mm 1077*1315 1077*1315 1077*1315
Number of circuits 7 7 7
Coating type Powder coating Powder coating Powder coating
Cabinet Salt Spray Test Duration Hour 72 72 72
coating Sheet Metal Material Hot zinc plate Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 0.8 0.8 0.8
Control panel enclosure IP class Standard IP24 IP24 IP24
Outdoor air flow m3/h 7200 7200 7200
Outdoor sound level(sound pressure level) dB(A) 50 51 53
Outdoor sound level(sound power level) dB(A) 68 69 70
Dimension(W*H*D) mm 950/370/1340 950/370/1340 950/370/1340
Outdoor Packing (W*H*D) mm 1023/471/1420 1023/471/1420 1023/471/1420
unit Net weight kg 115 115 115
Gross weight kg 123 123 123
Type R410A R410A R410A
Refrigerant
Charged volume kg 4 4 4
Throttle type EXV EXV EXV
Design pressure MPa 4.15 4.15 4.15
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Total pipe length m 300 300 300
Refrigerant Max. pipe length(Equivalent/
m 175/150 175/150 175/150
piping Actual)
50 (Outdoor higher than indoor)
Max. Diff. indoor/outdoor unit m
40 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit m 15 15 15
Connectable indoor unit ratio % 50%~130% 50%~130% 50%~130%
Maximum indoor units Piece 8 10 13
Connection Power wiring mm2 4 4 4
wiring Signal wiring mm2 Shield wire:(0.75-2)*2
Cooling:-15~48
Operation Range °C
Heating:-20~27
Norminal condition: indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating):
20°CDB/14.5°C WB.
Outdoor temperature(cooling): 35°C DB/24°C WB, outdoor temperature(heating): 7°C DB/6°C WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
6
Downloaded from www.Manualslib.com manuals search engine
3. Dimension
1340
600
950
7
Downloaded from www.Manualslib.com manuals search engine
c
4. Piping Diagram
e
4wv s
Gas pipe stop
valve d Condensor
Oil segregator
Te
HPS
Ps
8
Td
Ts
PMV
Tc1
Tc2
Subcooler
Inverter EEV
compressor
Liquid pipe Gas-liquid segregator
stop valve
Part name Sign Function Date Note
Electronic
EEV In heating, refrigerant flow control Φ3.0
expansion valve
AC220V electrified in
Changing over between cooling and
4-way valve 4WV heating; powered off in
heating cooling or defrosting.
Heater Chi Used to heat oil in inverter compressor 28W, 220V, one
9
Downloaded from www.Manualslib.com manuals search engine
5. Wiring Diagram
AU04/05/062FPERA
0150518287
B R
HPS TD TE(1) TS TA Ps Pd
P
ACL CN13 CN12
6.3A 250VAC ACL AC-N AC-L
ACN FUSE1 CN1 CN2 CN3 CN4CN5 CN6 CN7 CN29 CN28 CN30
ACN PE
CN19 CN21
PTC BM2
CN18
BM1
INV BOARD
ON
ON
12345678
12345678
DK1
LED4 LED2
CN17 W DK2
SV1 CN9 B CN8
V
4WV
CN16 CONTROL CN20
C O MP
W
U
Tfin
JP3
EEV R
HEATER
CN25
BOARD CN8 M CN1
M M
P M V2
CN5
CN7
Tc1 CN31-1
PQ LN
CN8 CN9
10
Downloaded from www.Manualslib.com manuals search engine
AU04/05/06IFPERA
ON
CN9 CN31
12345678
12345678
CN17 DISPLAY
CN30
CN20
4WV CN16
EEV
M
HEATER
CN25
CONTROL BOARD CN8
SW01 SW02
ACFAN2
CN31 Tfin
CN15
SW3 SW1 CN33 CN24 B
W
ACFAN1 W
RY2 CN8 CN7 V COMP
CT
R S T N PQ
R W B BL
<SYMBOL>
Symbol Signification Symbol Signification
<WARNING>
Crankcase High Pressure
Please power off firstly for about 10 HEATER Pd Sensor
Heater
minutes before checking control box, Low Pressure
Unloading Ps Sensor
and make sure the voltage between SV1 Valve
P and N below 20V. EEV Electronic
Four-way Expend Valve
<NOTES> 4WV Valve
Tfin Ipm Temperature
·Please check the power firstly before test , and make DCFAN1,2 DC Fan Motor Sensor
sure the crankcase heater powering on for 12 hours Electronic
ACFAN1,2 AC Fan Motor PMV2
at least to protecting compressor. Expend Valve
High Pressure
·The switch BM1-1 is used for locking the indoor units HPS Switch TC1 Temp Sensor
number, the initial situation is “ OFF”. After power on, TX1
Compressor of Valve Plate
the display board will display 【U**】, “**” indicates Td Vent Sensor
TX2 TC2 Temp Sensor
the number of Indoor units that the outdoor unit can Defrost of Valve Plate
communicate with. If it can match the actual number Te1 Temperature W
Sensor White
of indoor units, please change “OFF” to “ON”, or else
fix the communication problem firstly. Compressor BL Blue
Ts Inhale Sensor
·Forbid connecting the power wire to the “P” and “Q”, B Black
otherwise the control board will be damaged. Ambient
Ta Temperature
·Please make sure the earth wire connecting the grou- Sensor R Red
nding hole on the electric box firmly.
11
Downloaded from www.Manualslib.com manuals search engine
6. Capacity Calculation Due to Capacity Modification Coefficient
(1) Calculation method of refrigerating capacity----cooling capacity to be known=refrigerating
capacity*(A*B*C*D*E)W
A. Capacity compensation value of indoor B. Capacity compensation value of outdoor
air wet-bulb temperature condition air dry-bulb temperature condition
1.2
Capacity modification value
1.1
1.0
1.0
0.9
0.9
0.8 -5 0 5 10 15 20 25 30 35 40 43
15 20 24
Indoor air dry-bulb temperature (°C ) Outdoor air wet-bulb temperature (°C )
C. Capacity modification value under airflow variation D. Capacity compensation suitable for
rate of indoor unit group (only for duct unit) total capability of indoor unit group
120
Capacity modification value
1.1
100
1.0 80
60
0.9
capacity
Standard
80 90 100 110 120 40
E. Capacity compensation value of pipe length, pipe diameter and height drop
Capacity modification value
Notes for E:
Notes
(1) Thefor E: pipe (from outdoor to the first branch pipe) diameter should be enlarged one size
main
when
(1) Thethe single
mian pipeway pipeoutdoor
(from length to
is over 90m.
the first branch pipe) diameter should be enlarged one size
(2) When in cooling mode, outdoor is lower
when the single way pipe length is over 90m. than indoor; or when in heating mode, outdoor is higher than indoor, the
compensation
(2) factor
When in cooling should
mode, be decreased
outdoor the below
is lower than value
indoor; from in
or when figure E. mode, outdoor is higher than indoor, the
heating
compensation factor should
Vertical height drop between be decreased the below value from figure E.
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
indoor and outdoor
Adjustment factor 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.03
12
Downloaded from www.Manualslib.com manuals search engine
(2) Calculation method of refrigerating capacity----heating capacity to be known=refrigerating
capacity*(A*B*C*D*E*F)W
1.1 1.0
0.9
1.0
0.8
0.9
0.7
0.8 0.6
15 20 24
Indoor air dry-bulb temperature (°C) 0.5
-15 -10 -5 0 5 10 15
Outdoor air wet-bulb temperature (°C)
C. Capacity modification value under airflow variation D. Capacity compensation suitable for
rate of indoor unit group (only for duct unit) total capability of indoor unit group
120
Capacity modification value
Capacity modification value
100
1.1
80
1.0 60
40
capacity
Standard
0.9
80 90 100 110 120 20
Notes for E:
(1) The main pipe (from outdoor to the first branch pipe) diameter should be enlarged one size
when the single way pipe length is over 90m.
(2) When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher than indoor, the
compensation factor should be decreased the below value from figure E.
Vertical height drop between
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
indoor and outdoor
Adjustment factor 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.03
13
Downloaded from www.Manualslib.com manuals search engine
7. Operation range
Cooling
50
Heating
45 30
40 25
Outdoor temperature(℃DB)
Consecutive operation
Outdoor temperature(℃DB)
35 20
Consecutive operation
30 15
25 10
20 5
15 0
10 -5
5 -10
0 -15
-5 -20
10 15 20 25 30
-10
Indoor temperature(℃DB)
-15
10 15 20 25 30
Indoor temperature(℃DB)
14
Downloaded from www.Manualslib.com manuals search engine
8. Sound Level
(1) Testing illustration
1.18m
1.18m
1m
1m
2) Testing condition:
a. Unit running in the nominal condition
b. Test in the semi-anechoic chamber
c. Noise level varies from the actual factors such as room structure, etc.
AU042FPERA AU052FPERA
AU04IFPERA AU05IFPERA
70 70
Octave band sound pressure level dB
Octave band sound pressure level dB
NC-60 NC-60
60 60
NC-50 NC-50
50 50
NC-40 H NC-40 H
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 Limit of
20
Limit of
audible audible
continuous continuous
noise noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
AU062FPERA
AU06IFPERA
70
Octave band sound pressure level dB
NC-60
60
NC-50
50
NC-40 H
40
NC-30
30
NC-20
20 Limit of
audible
continuous
noise
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
15
Downloaded from www.Manualslib.com manuals search engine
9. Outdoor Piping Installation
9.1 Safety
• If the air conditioner is transferred to the others, this manual should be transferred together.
• Before installation, please read "Safety precaution" carefully to confirm the correct installation.
• The mentioned precaution includes " WARNING" and " CAUTION". The precaution caused death or heavy
injury for faulty installation will be listed in " WARNING". Even the cautions listed in " CAUTION" also may
cause serious accident. So both of them are related to the safety, and should be executed severely.
• After installation, perform a trial and confirm everything normal, then introduce the operation manual to the user.
Besides, put the manual to the user and ask them to preserve it carefully.
WARNING
• The installation or the maintenance should be performed by the authorized agency. Or the non-specialized
operation will cause water leakage, electric shock or fire etc accidents.
• The installation should be executed as per the manual, or the faulty installation will cause water leakage, electric
shock or fire etc accidents.
• Please install the unit at the space which can bear the weight. Or the unit will drop down to cause the human
injury.
• The installation should defend against the typhoon, and the earthquake etc. Abnormal installation will cause the
unit fall down.
• Use the correct cable and make reliable earthing. Fix the terminal firmly and the loose connection will cause
heating or fire etc accident.
• The wiring should be in shape and can not be raised. Be earthed firmly and can not be clipped by the electric box
cover or the other plate. The incorrect installation will cause heating or fire.
• When setting or transferring the unit, there should not be other air into the refrigerant system except for R410A.
The gas mixture will cause the abnormal high pressure which will cause break or human injury etc accidents.
• When installation, please use the accessories with the unit or the special parts, or it will cause water leakage,
electric shock, fire, refrigerant leakage etc accidents.
• Don't lead the water drainage pipe into the drainage groove with the poisonous gas, such as sulphur. Or the
poisonous gas will enter indoor.
• In installation or after installation, please confirm if there is refrigerant leakage, please take measures for
ventilation. The refrigerant will cause poisonous gas as meeting fire.
• Don't install the unit at the place where there may be flammable gas leakage. In case the gas leaks and gather
around the unit, it will cause fire.
• The drainage pipe should be installed as per the manual to confirm the fluent drainage. Also take measures for
heat insulation against dew drop. Incorrect water pipe installation will cause water leakage even and make the
things wet.
• For the liquid pipe and the gas pipe, take measures for heat insulation too. If there is no heat insulation, the dew
drop will wet the things.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the appliance.
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory
or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with
the appliance. Cleaning and user maintenance shall not be made by children without supervision.
• The appliances are not intended to be operated by means of an external timer or separate remote-control system.
• Keep the appliance and its cord out of reach of children less than 8 years.
16
Downloaded from www.Manualslib.com manuals search engine
CAUTION
• Execute earthing for the unit. But the earthing wire can not be connected to the gas pipe, water pipe, lightening
rod or the telephone earthing wire. Improper earthing will cause electric shock.
• Don't install the unit at the place where leaks the flammable gas. Or it will cause fire.
• Execute the water drainage pipe according to the manual, improper installation will cause water leakage to wet
the family things.
• The outdoor fan can not face to the flower or the other vegetable, or the blowing gas will make the flower dried
up.
• Please ensure the maintenance room, if not, it will cause the maintenance person damaged.
• When installing the unit on the roof or the other high place, to prevent the person falling down, please set the
fixed ladder and the railing at the passage.
• Use the two-end spanner, and fasten the nut at proper torque. Don't fasten the nut excessively against the flared
section broken. Or it will cause refrigerant leakage and lack of oxygen.
• Take measures for heat insulation to the refrigerant pipe, or there will be water leakage or dew drop to wet the
family things.
• After finishing the refrigerant pipe, make leakage test by charging the nitrogen. In case the refrigerant leaks in a
small room and exceeds the limited concentration, it will cause lack of oxygen.
• Don't use the other refrigerant except for R410A. The R410A pressure is 1.6 times higher than R22 pressure. The
refrigerant R410A tank is marked with pink sign.
• Against charging different refrigerant, we changed the stop valve diameter of the R410A unit. To enhance
the compression consistence, we also changed the flared pipe dimension. Prepare the R410A specially tools
according to the below table.
• When charging refrigerant, the refrigerant must be taken out as liquid state from the tank.
17
Downloaded from www.Manualslib.com manuals search engine
9.2 Installation instruction
• If the connected units quantity and the total capacity is in the allowable range?
• If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horizontally or vertically?
• If the additional refrigerant is counted correctly and weighed by the standard balance?
• If there is refrigerant leakage?
• If all the indoor power supplies can be on/off simultaneously?
• If the power voltage is in compliance with the data marked on the rating label?
• If the address of indoors has been set?
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
Outdoor Indoor
Model Combination type Indoor qty Total indoor capacity (100w)
AU04 Single 1~8 63-164
AU05 Single 1~10 70-182
AU06 Single 1~13 78-201
Notice:
Total capacities of indoor units being used ≤ 100% of rated capacities of outdoor unit.
Indoor capacity (100W)
22
28 Total indoor capacity (100W) Branch pipe (optional)
36
40
45 less than 335 FQG-B335A
56
71
Air-conditioner can't be installed in The unit should be installed at the The unit should be installed at
the place with inflammable gas. Or it place with good ventilation. No the strong enough place. Or it will
will cause fire hazard. obstacle at the air inlet/outlet. And cause vibration and noise.
no strong wind blows the unit.
18
Downloaded from www.Manualslib.com manuals search engine
The unit should be installed at the • The place where the water can flow • The unit is better not be installed
place where the cold/hot air or fluently. at the below places, or it will cause
noise will not interfere the neighbours. • The place where no other heat damage.
source will affect the unit. • The place where there is corrosive
• Pay attention to the snow against gas (spa area etc).
clogging the outdoor. • The place blowing salty air (seaside
• In installation, install the anti- etc).
vibration rubber between the unit • Exists the strong coal smoke.
and the bracket. • The place with high humidity.
• The place where there is device
emitting Hertzian waves.
• The place where voltage changes
greatly.
Note:
1. In snowy area, install the unit under the bracket or the snow-proof cover against the accumulative snow on the
unit.
2. Do not install the unit at the place where the flammable gas will leak.
3. Install the unit at the strong enough place.
4. Install the unit at the flat place.
5. When being installed at the place with strong wind, set the air outlet of the unit and the wind direction vertical.
Also fix the unit with the screw.
6. When opening the electric box cover for maintenance, please fix the cover with screw firmly.
(3) Transportation
• In transportation, please don't dismantle the packaging, and move the unit to the installation location as closely
• as possible.
• If the packaging must be dismantled, hang up the unit with rope against damage.
• Don't hang the unit only at two points. When hanging the unit, don't sit on the unit. The unit should be upright.
• When removing the unit with the forklift, put the fork into the special hole at bottom of the unit.
• When being hanged, the rope should be 4 pieces of steel cable with over 6mm diameter.
• Put the cushion at the contact section between steel cable and the unit against the distortion or damage.
19
Downloaded from www.Manualslib.com manuals search engine
Pipe material and specs selection
1. Please select the refrigerant pipe of the below material.
Material: the phosphoric oxidize seamless copper pipe, model: C1220T-1/2H (diameter is over 19.05); C1220T-0
(diameter is below 15.88).
2. Thickness and specs:
Confirm the pipe thickness and specs according to the pipe selection method (the unit is with R410A, if the pipe
over 19.05 is 0-type, the pressure preservation will be bad, thus it must be 1/2H type and over the min. thickness.
3. The branch pipe must be from Haier.
4. When installing the stop valve, refer to the relative operation instruction.
5. The pipe installation should be in the allowable range.
6. The installation of branch pipe and gather pipe should be performed according to the relative manual.
Precautions on installation
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface,
raise the unit in order to provide a free space of more than 5in.(130mm) under the
outdoor unit.
Foundation work
• Check the strength and level of the installation ground so that the unit will not cause
any operating vibration or noise after installation.
• In accordance with the foundation drawing in the figure, fix the unit securely by means
of the foundation bolts.
• It is best to screw in the foundation bolts until their length are 0.8in.(20mm) from the
foundation surface.
˃5in.(130mm)
20
• Fix the outdoor unit to the foundation bolts using nuts with resin washers(1) as shown in the figure.
If the coating on the fastening area is stripped off, the nuts rust easily.
Dimensions (bottom view)(unit of measurement: mm)
A leg pitch1
B leg pitch2
C Front grill (air outlet side)
D Drain hole
E Bottom frame
F Knock-out hole (for piping line)
20
Downloaded from www.Manualslib.com manuals search engine
Selection of installation location of outdoor
(1) Single-unit installation (unit: in.(mm))
The top and two side surfaces must be exposed to open space, and barriers on at least one side of the front and
back shall be lower than the outdoor unit.
The top and two side surfaces must be exposed to open space, and barriers on at least one side of the front and
back shall be lower than the outdoor unit.
• The installation service spaces shown in the illustrations are based on an air intake temperature of 95°F(35°C)(DB)
for COOL operation. In regions where the air intake temperature regularly exceeds 95°F(35°C)(DB), or if the heat
load of outdoor units is expected to regularly exceed the maximum operating capacity, reserve a larger space
than that indicated at the air intake side of units.
• Regarding the required air outlet space, position the units with consideration to the space required for the onsite
refrigerant piping work as well. Consult your dealer if the work conditions do not match those in the drawings.
21
Downloaded from www.Manualslib.com manuals search engine
Drain pipe disposal
• Make sure the drain works properly.
• In regions where buildups of snow can be expected, the accumulation and freezing of snow in the space between
the heat exchanger and external plate may lower operating efficiency.
• After punching the knock-out hole, the application of repair-type paint on the surface around the edge sections is
recommended to prevent rust.
Pipe specification:
b c
a a
b
a a
1. Pipe "a" diameter (between indoor and branch pipe) (depends on indoor pipe)
Note:
1.When the distance from outdoor to the longest indoor is over 30m, the main pipe should be the enlarged
diameter.
2. If pipe b diameter is larger than main pipe c, enlarge main pipe c diameter to be the same as pipe b.
22
Downloaded from www.Manualslib.com manuals search engine
Copper pipe selection:
hardness Softness Half-hardness
Outer diameter (mm) Ø6.35 Ø9.52 Ø12.7 Ø15.88 Ø19.05 Ø22.22 Ø25.24 Ø28.58
Min. thickness (mm) 0.8 0.8 1.0 1.0 1.0 1.1 1.2 1.4
Note: If the copper pipe with outer diameter 19.05 is coil pipe, the thickness should be over 1.1.
A. Outdoor unit
Gas pipe side Liquid pipe side
Model
Diameter (mm) Connecting method Diameter (mm) Connecting method
AU04 Ø15.88 Ø9.52
AU05 Ø15.88 Flared joint Ø9.52 Flared joint
AU06 Ø15.88 Ø9.52
23
Downloaded from www.Manualslib.com manuals search engine
B. Indoor unit
Please refer to the indoor air conditioner manual.
Connecting method: Flared joint
Branch pipe
Outdoor unit type
Branch pipe selection:
Total indoor capacity (100W) Model (optional)
Less than 335 FQG-B335A
Note:
1. When connecting the pipe and the outdoor, please pay attention to the outdoor pipe dimension.
2. When adjusting the diameter among pipes and among the units, please must execute at the branch pipe side.
3. When welding with hard solder, please must blow nitrogen. If not, a number of oxide will be produced and cause
heavy damage. Besides, to prevent water and dust into the pipe, please make the brim as outer roll.
24
Downloaded from www.Manualslib.com manuals search engine
Pipe installation
When doing the piping connection, please do the following:
• Please don't let the pipe and the parts in the unit collide each other.
• When connecting the pipes, close the valves fully.
• Protect the pipe end against and water, impurities (welding after being flatted, or being sealed with adhesive
tape).
• Bend the pipe as large semi-diameter as possible (over 4 times of the pipe diameter).
• The connection between outdoor liquid pipe and the distributing pipe is flared type. Please expand the pipe with
the special tool for R410A after installing the expanding nut. But if the projecting pipe length has been adjusted
with the copper pipe gauge, you can use the original tool to expand the pipe.
• Since the unit is with R410A, the expanding oil is ester oil, not the mineral oil.
• When doing the flare connection, please do the following: When connecting the expanding pipe, fasten the pipes
with double-spanner. The torque refers to the former info.
Projecting length of pipe to be expanded: B(mm)
Expanding pipe: A(mm)
Pipe outer When it is hard pipe
Pipe outer diameter diameter
A Special tool The former
(mm) (mm) for R410A tool
Ø6.35 9.1
Ø6.35
Ø9.52 13.2
Ø9.52
Ø12.7 16.6 0-0.5 1.0-1.5
Ø12.7
Ø15.88 19.7
Ø15.88
• The outdoor gas pipe and the refrigerant distributing pipe, as well the refrigerant distributing pipe and the branch
pipe should be welded with hard solder.
• Weld the pipe at the same time charge the nitrogen. Or it will cause a number of impurity (a film of oxidation) to
clog the capillary and the expansion valve, further cause the deadly failure.
Seal the pipe end with adhesive tape or the stopper to
increase the resistance, fill up the pipe with nitrogen.
Taping <N2>
25
Downloaded from www.Manualslib.com manuals search engine
B. Leakage test
1. The outdoor unit has been executed the leakage test in the factory. After connecting the distributing pipe, execute
the leakage test from the outdoor check valve and the indoor. Besides, while testing, the valves should be close.
2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorine, oxygen,
flammable gas in the leakage test. Apply pressure both on the gas pipe and the liquid pipe.
3. Apply the pressure step by step to the target pressure.
a. Apply the pressure to 0.5MPa for more than 5 minutes, confirm if pressure goes down.
b. Apply the pressure to 1.5MPa for more than 5 minutes, confirm if pressure goes down.
c. Apply the pressure to the target pressure (4.0MPa), record the temp. and the pressure.
d. Leave it at 4.0MPa for over 1 day, if pressure does not go down, the test is passed. Meanwhile, when the
temp. changes for 1degree, pressure will change 0.01MPa as well. Correct the pressure.
e. After confirmation of a~d, if pressure goes down, there is leakage. Check the brazing position, flared position
by laying on the soap. modify the leakage point and take another leakage test.
4. After leakage test, must execute the evacuation.
Check valve
Outdoor
C. Evacuation
Evacuate at the check valve of liquid stop valve and both sides of the gas stop valve.
Operation procedure:
Leakage test passed
Charge refrigerant
Evacuation begins
Evacuation ends
Check vacuum
26
Downloaded from www.Manualslib.com manuals search engine
Tighten torque as the table below:
Tighten torque N.m
Shaft (valve body) Cap (cover) T-shape nut (check joint)
For gas pipe Less than 7 Less than 30 13
For liquid pipe 7.85 (MAX15.7) 29.4 (MAX39.2) 8.8 (MAX14.7)
Note:
• To prevent the different oil into the pipe, please use the special tool for R410A, especially for gauge manifold and
charging hose.
• Mark the refrigerant type in different colour on the tank. R410A is pink.
• Must not use the charging cylinder, because the R410A will change when transferring to the cylinder.
• When charging refrigerant, the refrigerant should be taken out from the tank as liquid state.
• Mark the counted refrigerant volume due to the distributing pipe length on the label.
GWP: 2088
The product contains fluorinated greenhouse gases and its functioning relies upon such gases.
27
Downloaded from www.Manualslib.com manuals search engine
9.3 Trial operation and the performance
Indoor model:
Room No.
e.g. Indoor A, system 1, Floor 2 2F-1A
28
Downloaded from www.Manualslib.com manuals search engine
Trial operation
• Before trial operation:
Before being electrified, measure the resistor between power terminal block (live wire and neutral wire) and the
earthed point with a multimeter, and check if it is over 1MΩ. If not, the unit can not operate.
To protect compressor, electrify the outdoor unit for at least 12 hours before the unit runs. If the crankcase heater
is not electrified for 6 hours, the compressor will not work.
Confirm the compressor bottom getting hot.
Except for the condition that there is only one master unit connected (no slave unit), under the other conditions,
open fully the outdoor operating valves (gas side, liquid side). If operating the unit without opening the valves,
compressor failure will occur.
Confirm all indoor units being electrified. If not, water leakage will occur.
Measure the system pressure with pressure gauge, at the same time, operate the unit.
• Trial operation
In trial operation, refer to the information of performance section. When the unit can not start up at the room
temperature, make trial operation for outdoor.
29
Downloaded from www.Manualslib.com manuals search engine
10. Outdoor Wiring Installation
Communication wiring figure
PQ PQAB C PQAB C
A BC wired
controller
wired wired
controller controller
The outdoor and all indoor units are in parallel through 2 non-polar wires.
Three wiring methods between wired controller and indoor unit:
A. 1 to multi (group control): one wired controller controls 2~16 indoors, as shown in above figure, indoor 1~indoor
2: indoor 2 is wired control master unit, the others are wired control slave units. Wired controller and the master
indoor (directly connected to wired controller) is connected by 3 polar wires; the other indoors and the master
indoors are connected by 2 polar wires.
B. 1 to 1 (one wired controller controls one indoor): as shown in above figure, indoor 3~ indoor 4, indoor and wired
controller are connected by 3 polar wires.
C. 2 to 1 (two wired controller controls one indoor): as shown in above figure, indoor 6. Either of wired controllers
can be set as master wired controller, and the other is slave wired controller. Master/slave wired controller, and
master/indoor are connected by 3 polar wires.
When indoor is controlled by remote controller, refer to the "wired control master unit/wired control slave unit/
remote control unit table". A, B, C on signal terminal block need not wires and not connect the wired controller.
Power wiring figure
Outdoor Outdoor
AU04~06IFPERA AU04~062FPERA
Power source: 3N~, 380-400V, 50/60Hz Power source: 1PH, 220-230V~, 50/60Hz
Power source: 1PH, 220-230V~, 50/60Hz Power source: 1PH, 220-230V~, 50/60Hz Power source: 1PH, 220-230V~, 50/60Hz
Indoor and outdoor use their individual power source. All indoors use one power source. Must install the leakage
breaker and the over current breaker, or electric shock will occur.
30
Downloaded from www.Manualslib.com manuals search engine
Outdoor power source and power cable
31
Downloaded from www.Manualslib.com manuals search engine
11. Outdoor Unit PCB
0151800146J
LED1
LED3
LED2
32
Downloaded from www.Manualslib.com manuals search engine
12. Dip Switch Setting
Note:
Either the indoor unit quantity unlocked or the locked quantity is different with actual connecting number,
the unit cannot running.
33
Downloaded from www.Manualslib.com manuals search engine
BM2 Definition Introduction
Cooling only or heat pump OFF Heat pump (default)
BM2-1 selection ON Cooling only
BM2_2 ON OFF OFF AU04
BM2_3 Outdoor model selection ON OFF ON AU05
BM2_4 ON ON OFF AU06
OFF Single phase
BM2-5 Power supply selection
ON 3-phase
OFF New communication protocol (default)
BM2-6 Communication protocol selection
ON Old communication protocol
BM2-7 BM2-8 Start mode selection
OFF OFF First open priority
OFF ON After opening priority
Cooling priority, any one indoor unit
ON OFF runs in cooling mode, the outdoor unit
BM2-7 will run in cooling mode, the indoor
BM2-8 Start mode selection units running in heating mode will stop
2. bridge instruction
CJ1:
Short it before power ON-- PCB check its function (used for factory production. Short it after power ON-- time short
function, 60 seconds become to 1 second.
CJ2: Reserved
34
Downloaded from www.Manualslib.com manuals search engine
13. Monitor Tools
35
Downloaded from www.Manualslib.com manuals search engine
SW01 SW02 Digital tube display
0 Td discharging temperature (unit: ℃)
1 Ta outdoor ambient temperature (unit: ℃)
2 Ts suction temperature (unit: ℃)
3 Te defrosting temperature (unit: ℃)
4 Toil oil temperature (unit: ℃)
5 Pd high pressure (unit: kg, one decimal)
6 Ps low pressure (unit: kg, one decimal)
Outdoor PMV valve open angle (unit: pls, max. display: 999)
7 (Press start for 5s to enter forced mode, all the indoor units' PMV are full open, flashing
display "480" and press stop for 5s to quit and display outdoor PMV valve open angle)
Valve state
The first position: 4WV (0-OFF; 1-ON)
8
1 The second position: SV1 (0-OFF; 1-ON)
The third position: SV2 (0-OFF; 1-ON)
The first position: high pressure switch (0-OFF; 1-ON)
9 The second position: low pressure switch (0-OFF; 1-ON)
The third position: heater (0-OFF; 1-ON)
A Tfin module temperature (unit: ℃)
B Compressor current (unit: A, one decimal)
C Te defrosting temperature (unit: ℃)
D DC voltage of module (unit: V)
Outdoor CT current (unit: A, one decimal)
E Forced cooling alternate display ”CCC”, (Press start for 5s, all the indoor units are in cooling
state, and press stop for 5s to quit)
Forced heating (Press start for 5s, all the indoor units are in heating state, and press stop for
F
5s to quit) display “ HHH”, otherwise “---”
2 0-F If the communication is normal display indoor program version (one decimal) ,otherwise “---”
3 0-F Indoor type (0,4,5,6,7 ordinary indoor unit; 1-high wall; 2-fresh air; 3-heat recovery)
4 0-F Display indoor failure code, if no failure display “---”
5 0-F Indoor horse power (one decimal)
The first and second position: indoor unit current operation mode (00-OFF, 01-Fan,
6 0-F 02-Cooling, 03-Dehumidify, 04-Heating)
The third position: outdoor unit capacity demand (0-no ; 1-yes)
7 0-F Indoor PMV valve open angle (unit: pls, max. display: 999)
Indoor unit
The first position: float switch (0-OFF; 1-ON)
8 0-F
The second position: pump (0-OFF; 1-ON)
The third position: heater (0-OFF; 1-ON)
9 0-F Indoor Ta ambient temperature (unit: ℃)
A 0-F Indoor TC1 gas temperature (unit: ℃)
B 0-F Indoor TC2 liquid temperature (unit: ℃)
C 0-F Indoor units: fan speed of indoor units(0-OFF, 1-Low, 2-med, 3-high)
Forced cooling (press "start" for 5s for cooling operation of indoor units and press "stop" for
E 0-F
5s to quit) display ”CCC”, otherwise “---“
Forced heating (press "start" for 5s for heating operation of indoor units and press "stop" for
F 0-F
5s to quit) display ”HHH”, otherwise “---“
36
Downloaded from www.Manualslib.com manuals search engine
14. Outdoor Unit Control
Mode Effect priority mode Energy-saving mode Outdoor ambient Pd correction during
(default) temperature running
Target Pd Setting value +3°C Setting value +3°C Ta≥15°C
Target Pd Setting value +2°C Setting value +2°C Ta≥7°C During running:
correct the Pd
Target Pd 48 46 Ta≥-5°C according to the
(set by dip switch) compression ratio
Target Pd Setting value -2°C Setting value -2°C Ta<-5°C
37
Downloaded from www.Manualslib.com manuals search engine
Pd(MPa)
《A area》Pd<1.0 MPa, drop step by step
at the lowest fan speed (fan speed No.1 ) running 1 min , OFF
1.0
《B area》1.0MPa≤Pd<1.5 MPa
Reduce the speed per 1 class /20s until to the lowest
1.5
《C area》1.5MPa≤Pd<2.2 MPa
Keep the current fan speed
2.2
《D area》2.2MPa≤Pd<3.2MPa
Increase the speed per 1 class/20s
3.2
《E area》Pd≥3.2 MPa
Reach the highest speed from the D area speed immediately
《B area》3.5MPa<Pd≤3.8 MPa
Reduce the speed per 1 class /20s until to the lowest
3.5
《C area》3.0MPa<Pd ≤ 3.5MPa
Keep the current fan speed
3.0
《D area》2.4MPa<Pd ≤ 3.0MPa
Increase the speed per 1 class/20s
2.4
《E area》Pd≤2.4 MPa
Reach the highest speed from the D area speed immediately
All the heating start, after the 4-way valve reversing (including defrosting, oil return and 4-way valve is electrified)
the fan motor speed refer to the following:
• Ta≤15°C: highest speed
• 15°C<Ta≤20°C: 3 speed
• Ta>20°C: 1 speed
38
Downloaded from www.Manualslib.com manuals search engine
4. Defrosting control
• & Ta≤20°C
After heating startup 60min
• OR Last defrosting~ heating cumulative operation time is more than 60 minutes
• OR A: Ta≥6°C, Te≤-10°C For 5min continuously
B: -15≤Ta<6°C, Te≤(5Ta-72)/7 For 5min continuously
C: -23≤Ta<-15°C, Te≤(Ta-69)/4 For 5min continuously
D: Tao<-23°C, Te≤-23°C For 5min continuously
X: During the oil return operation meets the following condition, the
cumulative operation time reset
Outdoor Te≥10°C, for 1min continuously
OR
Outdoor Te≥15°C, for 10min continuously
During defrosting, four-way valve power off, outdoor fan stop, indoor fan stop, outdoor PMV open to 470pls.
39
Downloaded from www.Manualslib.com manuals search engine
B: In heating mode When load rate<25%: after 1 hours, 4-way valve
doesn't reversing oil return operation
The master unit compressor cumulative • OR 25%≤load rate<50%: after 2 hours, 4-way valve
• & operation time doesn't reversing oil return operation
Load rate≤30%
• & 50%≤load rate<75%: after 4 hours, 4-way valve
After the outdoor unit startup doesn't reversing oil return operation
• OR
Load rate > 30%
• &
Finish the outdoor unit startup control~after 20min
• &
Finish defrosting~ after 30min
Note: if load rate≥75% and the outdoor unit output rate≥75% for 10 min, oil return time reset
5.2 Oil return control
1) Oil return in cooling mode, the compressor according to the 75% of maximum frequency control, the outdoor
PMV opening angle is 470 pls, the Thermo ON indoor PMV opening angle is 250 pls, the Thermo OFF indoor PMV
opening angle is 125 pls.
2) Oil return in heating mode (4-way valve reversing), the compressor according to the 75% of maximum frequency
control, the outdoor PMV opening angle is 470 pls, the Thermo ON and Thermo OFF indoor PMV opening angle
is 125 pls. When Td > 95 °C ands TdSH > 15 °C, the indoor PMV opening angle increased 10%, max. time is 2;
When Td < 90 °C, return to the usually opening.
3) Oil return in heating mode (4-way valve doesn't reversing), the compressor according to the indoor units load
rate and current running frequency to confirm the oil return enter frequency, the maximum frequency can't exceed
75% of the maximum frequency. the PMV of the outdoor and the Thermo ON indoor unit control automatically,
Thermo OFF indoor PMV opening angle is 250 pls.
1) In cooling mode
After 5min
• OR Td<CT+10°C, for 10s continuously
• OR
• &
Ts-ET<15°C, for 10s continuously
After 1min
2) In heating mode (4-way valve reversing)
After 5min
• OR Td<CT+10°C, for 10s continuously
• OR
• &
Ts-ET<15°C, for 10s continuously
After 2min
After 5min
• OR
40
Downloaded from www.Manualslib.com manuals search engine
15. Failure code
Inverter outdoor unit failure code
Digital tube Indication
indication on wired Failure code
Failure description Remarks
on master controller definition
unit (hex)
AD value is below 11(open circuit) or over 1012(short circuit) for
Defrosting temp. 60seconds, in cooling mode, if the sensor is abnormal, the unit
20 20-0 Resumable
sensor Te failure does not deal with it, besides, in defrosting and within 3 minutes
after defrosting, no alarm
AD value is below 11(open circuit) or over 1012(short circuit) for
Ambient temp.
21 21 60seconds, in defrosting and within 3 minutes after defrosting, no Resumable
sensor Ta failure
alarm
AD value is below 11(open circuit) or over 1012(short circuit) for
Suction temp.
22 22 60seconds, in defrosting and within 3 minutes after defrosting, no Resumable
sensor Ts failure
alarm
After compressor is running for 5 minutes, AD value is below
Discharging temp. 11(open circuit) or over 1012(short circuit) for 60seconds, in
23 23 Resumable
sensor Td failure course of startup, defrosting and within 3 minutes after defrosting,
no alarm
26 26-0 For continuous 200 cycles, can not find connected indoors
Indoor For continuous 300seconds, the searched indoor quantity is less
26-1 26-1
communication than the set quantity. Resumable
failure For continuous 300seconds, the searched indoor quantity is more
26-2 26-2
than the set quantity.
AD value is below 11(open circuit) or
High pressure over 1012(short circuit) for 30seconds,
28 28 Resumable
sensor Pd failure in defrosting and within 3 minutes after
defrosting, no alarm
AD value is below 11(open circuit) or
Low pressure over 1012(short circuit) for 30seconds,
29 1D Resumable
sensor Ps failure in defrosting and within 3 minutes after
defrosting, no alarm
Once
High pressure If disconnect for 50ms continuously, alarm. If alarm 3 times in an
30 30 confirmation,
switch HPS failure hour, confirm the failure
un-resumable
Once
33 33 EEPROM failure EEPROM failure confirmation,
un-resumable
Discharging temp. Td≥239°F(115°C) at interval of 25msec for twice continuously, and Once
34 34 too high protection over the set value, then stop and alarm; 3 minutes later, resume confirmation,
(Td) automatically. If it occurs 3 times in an hour, confirm the failure. un-resumable
After 4-way valve is electrified for 3 minutes, if the below conditions
can be met for continuous 10 seconds, that is conversing
Once
4-way valve successfully:
35 35 confirmation,
reversing failure 1. this outdoor compressor is running normally
un-resumable
2. Pd-Ps≥87PSI(0.6MPa), Otherwise, the system alarms reversing
failure.
After compressor is running (except for residual operation), if
Low pressure in cooling, Ps<0.05Mpa; in heating, Ps<0.03Mpa; in oil return, Once
39-0 39-0 sensor Ps too low Ps<0.03Mpa for continuous 5 minutes, alarm and stop. 2 minutes confirmation,
protection and 50 seconds later, resume automatically, un-resumable
if it occurs 3 times in an hour, confirm the failure.
41
Downloaded from www.Manualslib.com manuals search engine
Digital tube Indication
indication on wired Failure code
Failure description Remarks
on master controller definition
unit (hex)
After compressor is running, compression ratio 8. for
Once
Compression ratio continuous 5 minutes stop and alarm.2 minutes and 50
39-1 39-1 confirmation,
too high protection seconds later, resume automatically, if it occurs 3 times in an
un-resumable
hour, confirm the failure.
In normal operation, compression ratio <1.8 for continuous 5
Once
Compression ratio minutes stop and alarm.2 minutes and 1 seconds later,
39-2 39-2 confirmation,
too low protection resume automatically, if it occurs 3 times in an hour, confirm the
un-resumable
failure.
High pressure In normal operation, Pd>=4.15Mpa for continuous 50ms, alarm Once
40 40 sensor Pd too high and stop. 2 minutes and 50 seconds later, resume confirmation,
protection automatically, if it occurs 3 times in an hour, confirm the failure. un-resumable
In normal operation, if Td<CT+50°F(10 ) for continuous 5
minutes, the unit stops and alarms.2 minutes and 50 seconds
Discharging temp. later, resume automatically. If it occurs 3 times in an hour, Once
43 43 sensor Td too low confirm the failure. After fixed frequency compressor alarms, confirmation, un-
protection inverter compressor will continue to run. If fixed frequency resumable
compressor has been locked for 3 times, the unit will stop and
alarm.
Communication with
46 46 No communication within 30 seconds continuously Resumable
inverter board failure
3 times in an
CT current is too low hour, confirm
53 53 or current sensor 3 minutes after recovery failure; once
fault confirmation, un-
resumable
Cannot receive valve plate module signal in 200 continuous
Valve plate module
54 54 rounds or receive wrong data, recover automatically when Resumable
communication fault
received right data.
Communication
failure between
valve plate Communication failure between valve plate module and host
57 57 Resumable
module and host computer
computer(sending
by valve plate)
Tc1 temp sensor
of valve plate
58 58 Tc1 temp. sensor cannot connect with valve plate module Resumable
error(sending by
valve plate)
Tc2 temp sensor
of valve plate
59 59 Tc2 temp. sensor cannot connect with valve plate module Resumable
error(sending by
valve plate)
Valve plate module
60 60 error(sending by Reserved Resumable
valve plate)
Valve plate module
61 61 error(sending by Reserved Resumable
valve plate)
42
Downloaded from www.Manualslib.com manuals search engine
Digital tube Indication
indication on wired Failure code
Failure description Remarks
on master controller definition
unit (hex)
Valve plate
module
62 62 Reserved Resumable
error(sending by
valve plate)
Once
Valve plate dial
63 63 No valve plate module dial but the valve plate module is detected. confirmation,
setting error
un-resumable
3 times in an
hour, confirm
CT current is too
64 64 CT current exceeds specified value, 3 minutes after recovery failure; once
high
confirmation, un-
resumable
Upper DC motor Running at speed below 20rpm for 30s, or at speed of 70% lower
71-0 71-0 Once
blocked than the target for 2 minutes, 2 minutes and 50 seconds later after
confirmation, un-
Lower DC motor stop, resume automatically. It occurs 3 times in an hour, confirm
71-1 71-1 resumable
blocked the failure.
No pressure drop
In 1 minute after INV compressor starts up, Pd-Ps≤0.1MPa,then Once
between high
75 75-0 stop. 180 seconds later, resume automatically. If it occurs 3 times confirmed,
pressure and low
in an hour, confirm the failure. unresumable
pressure
Too small pressure
If Pd-Ps≤0.2MPa for 5 minutes, the outdoor unit protection stop. Once
drop between high
75-4 75-4 • 3 minutes after stopping protection, restart. If it occurs 3 times in confirmed,
pressure and low
an hour, confirm the failure. unresumable
pressure
Compressor running in cooling mode, Ps<0.2MPa for 30 minutes;
compressor running in heating mode, Tsi - ET>20;
78 78 Lack of refrigerant --
LEV will fully open for 60 minutes, the unit will output lack of
refrigerant alarm, unit will not stop.
3 times in an
IPM modular hour, confirm
81 81 temp. too high IPM modular temp.≥185°F(85°C) failure; once
protection confirmation, un-
resumable
3 times in an
hour, confirm
Compressor Compressor current exceeds specified value, 3 minutes after
82 82 failure; once
current protection recovery
confirmation, un-
resumable
Outdoor model set
83 83 Model and the number of fans do not match Un-resumable
error
3 times in an
Transient over
hour, confirm
current in IPM
108 108 Transient over current in IPM module rectifier side software failure; once
module rectifier
confirmation, un-
side software
resumable
3 times in an
hour, confirm
Current detection
109 109 Current detection circuit abnormality failure; once
circuit abnormality
confirmation, un-
resumable
43
Downloaded from www.Manualslib.com manuals search engine
Digital tube Indication
indication on wired Failure code
Failure description Remarks
on master controller definition
unit (hex)
IPM modular IPM modular over current, in short circuit, over heat, voltage too
110 110
protection (F0) low of control circuit.
Compressor out of In the course of compressor startup or running, the unit can not
111 111
control detect the rotor position, or not connecting compressor.
3 times in an
Radiator of
hour, confirm
112 112 transducer temp. too Radiator temp. too high
failure; once
high
confirmation,
113 113 Transducer overload Output current of transducer is too high un-resumable
Voltage too low of DC
114 114 Voltage of power source is too low
bus line of transducer
Voltage too high
115 115 of DC bus line of Voltage of power source is too high
transducer
Communication
abnormal between
116 116 Communication is disconnected Resumable
transducer and
control PCB
Transducer over Compressor startup fails for 5 times continuously, or compressor
117 117
current (software) is running down till stops caused by over current or over heat
Compressor startup The sensor used for current detecting of transducer is abnormal, 3 times in an
118 118
failure disconnected or incorrectly connection hour, confirm
Detecting circuit of failure; once
Current detection sensor of frequency controller is abnormal or
119 119 transducer current is confirmation,
unconnected or connected wrongly. un-resumable
abnormal
Power supply of
120 120 Power supply of transducer is broken down instantly
transducer abnormal
Power supply of
3 times in an
121 121 inverter board is Power supply of inverter board is broken down instantly
hour, confirm
abnormal
failure; once
Radiator temp.
Resistor of temp. sensor abnormal or temp. sensor confirmation,
122 122 sensor of transducer
disconnected un-resumable
abnormal
3 times in an
Transient over
hour, confirm
current in IPM
123 123 Transient over current in IPM module rectifier side hardware failure; once
module rectifier side
confirmation,
hardware
un-resumable
When there is no failure, if the starting condition can not be met, digital tube on master unit will display stand-by
code:
44
Downloaded from www.Manualslib.com manuals search engine
16. Troubleshooting
[20-23] Temperature sensor failure
If sensor resistor
/characteristic is proper Replace sensor
No
Check if connection between temp. Adjust connection
sensor and inverter board
Yes
No
Measure if temp. sensor resistor is Replace sensor
normal
Yes
45
Downloaded from www.Manualslib.com manuals search engine
[26-0, 26-1, 26-2] Communication circuit between indoor and outdoor
No
If wire of on outdoor No
Modify the port
connecting board is normal
Yes
Yes
Yes
Yes
If indoor quantity is correct Yes Shut off power supply, and outdoor
(check by rotary switch) searches for indoors again
No
No
No
46
Downloaded from www.Manualslib.com manuals search engine
[28, 29] High/low pressure sensor failure
No
If sensor terminal is fixed well Reconnect
Yes
Yes
No
47
Downloaded from www.Manualslib.com manuals search engine
[30] High pressure switch failure
Yes
Yes
If the system is clogged Check the piping system
No
No
48
Downloaded from www.Manualslib.com manuals search engine
[33] Outdoor EEPROM failure
No
If the EEPROM is fixed well Reconnect
Yes
Replace EEPROM
Yes
Yes
No
Replace connecting
board
49
Downloaded from www.Manualslib.com manuals search engine
[35] 4-way valve reversing failure
Yes
Yes
Yes
If compressor running No
Check compressor
current is normal
Yes
No
50
Downloaded from www.Manualslib.com manuals search engine
[39-0, 39-1] Low pressure too low and compression ratio too high
If actual pressure is in No
conformance with the Replace pressure sensor
measured data by sensor
Yes
Yes
No
Check if terminal of
electronic expansion No Re-connect the terminals
valve coil is fixed well
Yes
If actual pressure is in No
conformance with the Replace pressure sensor
measured data by sensor
Yes
Check if compressor No
Check compressor
running current is normal
Yes
Yes
Check if 4-way valve Replace 4-way valve
is interconnected
51
Downloaded from www.Manualslib.com manuals search engine
[40] High pressure too high failure
If characteristic No
of high pressure Replace pressure sensor
sensors are normal
Yes
If stop valve No
Open stop valve
opens fully
Yes
If in cooling No
outdoor fan motor Check fan motor
runs normally
Yes
No
52
Downloaded from www.Manualslib.com manuals search engine
[43] Discharging temp. sensor Td too low protection
Yes
If the terminal of No
Reconnect
sensor is fixed well
Yes
No
Yes
No
Measure if voltage of No
CN28 on connecting board Replace connecting board
changes by multimeter
Yes
Replace module
53
Downloaded from www.Manualslib.com manuals search engine
[53] CT Current too low or current sensor failure
Yes
No
Check if CT wire is conductive Replace wire
Yes
Yes
54
Downloaded from www.Manualslib.com manuals search engine
[64] CT current too high
Yes
No
Check if CT wire is conductive Replace wire
Yes
Yes
If there is air into the system Recharge refrigerant
No
Yes
If there is clogged, motor is bad Fix the system
No
Replace compressor
55
Downloaded from www.Manualslib.com manuals search engine
[71-0,71-1 ] DC motor blocked
No
Yes
Yes
56
Downloaded from www.Manualslib.com manuals search engine
[75-0, 75-4] Pressure difference between high pressure and low pressure is abnormal
Yes
Yes
No
No
Yes
57
Downloaded from www.Manualslib.com manuals search engine
[82] Compressor current protection
[108] Transient over current in IPM module rectifier side software
[110] IPM module hardware over current
[123] Transient over current in IPM module rectifier side hardware
Yes
Yes
If compressor is normal No
(compressor coil resistor Replace compressor
insulation)
Yes
No
If power module is normal Replace power module
Yes
Yes
58
Downloaded from www.Manualslib.com manuals search engine
[111] Compressor out of control
No
Check if voltage of power supply is normal Improve power supply circuit
Yes
Yes
If compressor is normal No
(compressor coil resistor, insulation) Replace the compressor
Yes
[112] Radiator temp. of transducer too high; [81] IPM module temp. too high;
Yes
Yes
Check the radiator is blocked Clean the radiator
Yes
If screw of module is fixed well, and if No Fix it well and daub gel
radiating silica gel is daubed enough
again, clean the radiator
and evenly, if there is no dirt on radiator
Yes
Improve the running
environment of outdoor unit
59
Downloaded from www.Manualslib.com manuals search engine
[113] Protection of overload
No
Check if voltage of power supply is normal Improve power supply circuit
Yes
No
Check if wire of electric box is correct Correct the wiring due to diagram
Yes
If compressor is normal No
Replace compressor
(compressor coil resistor, insulation)
Yes
Yes
Yes
No
Check if wire of electric box Correct the wiring due to diagram
is correct
Yes
No
If AC contactor or relay acts well Adjust or replace relay
Yes
Yes
Check rectifier, reactor, electrolytic
capacitor in inverter main circuit
60
Downloaded from www.Manualslib.com manuals search engine
[115] Voltage too high of DC bus line of transducer
Yes
No
Check if wire of electric box is correct Correct the wiring due to diagram
Yes
[116] Communication abnormal between transducer (inverter module board) and control PCB
Yes
Check if wire between control PCB and Adjust communication wire
inverter board is abnormal
No
No
No
61
Downloaded from www.Manualslib.com manuals search engine
[117] Transducer over current (software protection)
No
Check voltage of power supply is normal Improve power supply circuit
Yes
No
Check if wire of electric box is correct Correct the wiring due to diagram
Yes
If compressor is normal No
(compressor coil resistor, insulation) Replace compressor
Yes
No
If power module is normal Replace power module
Yes
Yes
Yes
62
Downloaded from www.Manualslib.com manuals search engine
[120] Power supply of transducer abnormal
No
Check if voltage of power supply is normal Improve power supply circuit
Yes
No
Check if wire of electric box is correct Correct the wiring due to diagram
Yes
Yes
Yes
Yes
Yes
Yes
If circuit of inverter control board is abnormal Replace power module
No
63
Downloaded from www.Manualslib.com manuals search engine
[122] Radiator temp. sensor of transducer abnormal
Yes
No
Measure if temp. sensor resistor Replace sensor
is normal
Yes
64
Downloaded from www.Manualslib.com manuals search engine
Appendix I: Sensor Resistance Table
65
Downloaded from www.Manualslib.com manuals search engine
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
0 1749.01 1921.99 2094.97 9.00 9.00
1 1651.43 1813.27 1975.10 8.93 8.93
2 1560.17 1711.65 1863.13 8.85 8.85
3 1474.74 1616.59 1758.45 8.78 8.78
4 1394.71 1527.61 1660.51 8.70 8.70
5 1319.68 1444.25 1568.82 8.63 8.63
6 1249.30 1366.10 1482.90 8.55 8.55
7 1183.21 1292.77 1402.34 8.48 8.48
8 1121.12 1223.94 1326.75 8.40 8.40
9 1062.76 1159.27 1255.77 8.33 8.33
10 1007.85 1098.47 1189.10 8.25 8.25
11 956.17 1041.29 1126.42 8.18 8.18
12 907.49 987.48 1067.46 8.10 8.10
13 861.62 936.80 1011.98 8.03 8.03
14 818.37 889.05 959.73 7.95 7.95
15 777.57 844.04 910.51 7.88 7.88
16 739.07 801.59 864.11 7.80 7.80
17 702.71 761.53 820.36 7.73 7.73
18 668.35 723.72 779.08 7.65 7.65
19 635.89 688.00 740.12 7.58 7.58
20 605.19 654.25 703.32 7.50 7.50
21 576.15 622.36 668.57 7.43 7.43
22 548.66 592.19 635.72 7.35 7.35
23 522.65 563.65 604.66 7.28 7.28
24 498.01 536.64 575.28 7.20 7.20
25 474.66 511.08 547.49 7.13 7.13
26 452.54 486.86 521.19 7.05 7.05
27 431.56 463.92 496.28 6.98 6.98
28 411.67 442.18 472.69 6.90 6.90
29 392.80 421.57 450.34 6.83 6.83
30 374.89 402.03 429.17 6.75 6.75
31 357.89 383.49 409.09 6.68 6.68
32 341.75 365.90 390.05 6.60 6.60
33 326.42 349.20 371.99 6.53 6.53
34 311.85 333.35 354.85 6.45 6.45
35 298.00 318.30 338.59 6.38 6.38
36 284.84 304.00 323.15 6.30 6.30
66
Downloaded from www.Manualslib.com manuals search engine
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
37 272.33 290.41 308.49 6.23 6.23
38 260.43 277.49 294.56 6.15 6.15
39 249.10 265.22 281.33 6.08 6.08
40 238.33 253.54 268.75 6.00 6.00
41 228.07 242.44 256.80 5.93 5.93
42 218.31 231.87 245.44 5.85 5.85
43 209.01 221.82 234.63 5.78 5.78
44 200.15 212.25 224.35 5.70 5.70
45 191.72 203.14 214.57 5.63 5.63
46 183.67 194.47 205.26 5.55 5.55
47 176.01 186.20 196.40 5.48 5.48
48 168.70 178.33 187.96 5.40 5.40
49 161.74 170.83 179.93 5.33 5.33
50 155.09 163.68 172.28 5.25 5.25
51 148.75 156.87 164.98 5.18 5.18
52 142.70 150.37 158.04 5.10 5.10
53 136.92 144.17 151.41 5.03 5.03
54 131.41 138.26 145.10 4.95 4.95
55 126.15 132.61 139.08 4.88 4.88
56 121.12 127.23 133.34 4.80 4.80
57 116.32 122.09 127.86 4.73 4.73
58 111.73 117.18 122.63 4.65 4.65
59 107.35 112.49 117.64 4.58 4.58
60 103.16 108.02 112.88 4.50 4.50
61 99.15 103.74 108.33 4.43 4.43
62 95.32 99.65 103.99 4.35 4.35
63 91.66 95.75 99.84 4.28 4.28
64 88.15 92.01 95.88 4.20 4.20
65 84.80 88.44 92.09 4.13 4.13
66 81.58 85.03 88.47 4.05 4.05
67 78.51 81.76 85.01 3.98 3.98
68 75.57 78.64 81.70 3.90 3.90
69 72.75 75.65 78.54 3.83 3.83
70 70.05 72.78 75.51 3.75 3.75
71 67.47 70.04 72.61 3.68 3.68
67
Downloaded from www.Manualslib.com manuals search engine
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
72 64.99 67.42 69.84 3.60 3.60
73 62.61 64.90 67.19 3.53 3.53
74 60.34 62.49 64.65 3.45 3.45
75 58.15 60.19 62.22 3.38 3.38
76 56.06 57.97 59.89 3.30 3.30
77 54.05 55.85 57.65 3.23 3.23
78 52.13 53.82 55.52 3.15 3.15
79 50.28 51.87 53.47 3.08 3.08
80 48.50 50.00 51.50 3.00 3.00
81 46.73 48.21 49.68 3.07 3.07
82 45.03 46.48 47.94 3.13 3.13
83 43.40 44.83 46.27 3.20 3.20
84 41.83 43.25 44.66 3.27 3.27
85 40.33 41.72 43.11 3.33 3.33
86 38.89 40.26 41.63 3.40 3.40
87 37.51 38.86 40.20 3.47 3.47
88 36.18 37.51 38.83 3.53 3.53
89 34.91 36.21 37.51 3.60 3.60
90 33.68 34.96 36.24 3.67 3.67
91 32.50 33.76 35.03 3.73 3.73
92 31.37 32.61 33.85 3.80 3.80
93 30.29 31.50 32.72 3.87 3.87
94 29.24 30.44 31.64 3.93 3.93
95 28.24 29.41 30.59 4.00 4.00
96 27.27 28.43 29.58 4.07 4.07
97 26.34 27.48 28.61 4.13 4.13
98 25.45 26.56 27.68 4.20 4.20
99 24.59 25.69 26.78 4.27 4.27
100 23.76 24.84 25.91 4.33 4.33
101 22.97 24.02 25.08 4.40 4.40
102 22.20 23.24 24.28 4.47 4.47
103 21.46 22.48 23.50 4.53 4.53
104 20.75 21.75 22.75 4.60 4.60
68
Downloaded from www.Manualslib.com manuals search engine
R80=50kΩ±3% B25/80=4450K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
105 20.07 21.05 22.03 4.67 4.67
106 19.41 20.37 21.34 4.73 4.73
107 18.77 19.72 20.67 4.80 4.80
108 18.16 19.09 20.02 4.87 4.87
109 17.57 18.49 19.40 4.93 4.93
110 17.01 17.90 18.80 5.00 5.00
111 16.46 17.34 18.22 5.07 5.07
112 15.93 16.79 17.66 5.13 5.13
113 15.42 16.27 17.11 5.20 5.20
114 14.93 15.76 16.59 5.27 5.27
115 14.46 15.28 16.09 5.33 5.33
116 14.01 14.80 15.60 5.40 5.40
117 13.57 14.35 15.13 5.47 5.47
118 13.14 13.91 14.68 5.53 5.53
119 12.73 13.49 14.24 5.60 5.60
120 12.34 13.08 13.82 5.67 5.67
121 11.96 12.69 13.41 5.73 5.73
122 11.59 12.31 13.02 5.80 5.80
123 11.24 11.94 12.64 5.87 5.87
124 10.90 11.58 12.27 5.93 5.93
125 10.57 11.24 11.92 6.00 6.00
126 10.25 10.91 11.57 6.07 6.07
127 9.94 10.59 11.24 6.13 6.13
128 9.65 10.29 10.92 6.20 6.20
129 9.36 9.99 10.61 6.27 6.27
130 9.09 9.70 10.32 6.33 6.33
131 8.82 9.43 10.03 6.40 6.40
132 8.57 9.16 9.75 6.47 6.47
133 8.32 8.90 9.48 6.53 6.53
134 8.08 8.65 9.22 6.60 6.60
135 7.85 8.41 8.97 6.67 6.67
136 7.63 8.18 8.73 6.73 6.73
137 7.42 7.96 8.50 6.80 6.80
138 7.21 7.74 8.27 6.87 6.87
139 7.01 7.53 8.06 6.93 6.93
140 6.82 7.33 7.85 7.00 7.00
69
Downloaded from www.Manualslib.com manuals search engine
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
-30 145.82 135.02 124.22 7.00 7.00
-29 138.07 129.13 120.18 6.93 6.93
-28 131.79 123.34 114.89 6.85 6.85
-27 125.67 117.68 109.70 6.78 6.78
-26 119.71 112.18 104.65 6.71 6.71
-25 113.93 106.84 99.75 6.64 6.64
-24 108.36 101.69 95.01 6.56 6.56
-23 103.00 96.72 90.44 6.49 6.49
-22 97.85 91.95 86.05 6.42 6.42
-21 92.92 87.37 81.83 6.35 6.35
-20 88.20 82.99 77.79 6.27 6.27
-19 83.70 78.82 73.93 6.20 6.20
-18 79.42 74.83 70.25 6.13 6.13
-17 75.34 71.04 66.74 6.05 6.05
-16 71.47 67.44 63.40 5.98 5.98
-15 67.80 64.02 60.23 5.91 5.91
-14 64.32 60.77 57.22 5.84 5.84
-13 61.02 57.69 54.37 5.76 5.76
-12 57.90 54.78 51.66 5.69 5.69
-11 54.94 52.02 49.10 5.62 5.62
-10 52.15 49.41 46.67 5.55 5.55
-9 49.51 46.94 44.37 5.47 5.47
-8 47.02 44.61 42.20 5.40 5.40
-7 44.66 42.40 40.14 5.33 5.33
-6 42.43 40.32 38.20 5.25 5.25
-5 40.33 38.35 36.36 5.18 5.18
-4 38.35 36.48 34.62 5.11 5.11
-3 36.47 34.72 32.97 5.04 5.04
-2 34.70 33.06 31.42 4.96 4.96
-1 33.03 31.49 29.95 4.89 4.89
0 31.45 30.00 28.56 4.82 4.82
1 29.95 28.59 27.24 4.75 4.75
2 28.54 27.26 25.99 4.67 4.67
3 27.20 26.01 24.81 4.60 4.60
4 25.94 24.82 23.69 4.53 4.53
70
Downloaded from www.Manualslib.com manuals search engine
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
5 24.74 23.69 22.63 4.45 4.45
6 23.61 22.62 21.63 4.38 4.38
7 22.54 21.61 20.68 4.31 4.31
8 21.52 20.65 19.77 4.24 4.24
9 20.56 19.74 18.92 4.16 4.16
10 19.65 18.87 18.10 4.09 4.09
11 18.78 18.05 17.33 4.02 4.02
12 17.96 17.28 16.59 3.95 3.95
13 17.18 16.54 15.90 3.87 3.87
14 16.44 15.83 15.23 3.80 3.80
15 15.73 15.17 14.60 3.73 3.73
16 15.06 14.53 14.00 3.65 3.65
17 14.42 13.93 13.43 3.58 3.58
18 13.82 13.35 12.88 3.51 3.51
19 13.24 12.80 12.36 3.44 3.44
20 12.69 12.28 11.86 3.36 3.36
21 12.17 11.78 11.39 3.29 3.29
22 11.67 11.30 10.94 3.22 3.22
23 11.19 10.85 10.51 3.15 3.15
24 10.73 10.41 10.09 3.07 3.07
25 10.30 10.00 9.70 3.00 3.00
26 9.90 9.60 9.31 3.06 3.06
27 9.51 9.23 8.94 3.13 3.13
28 9.15 8.86 8.58 3.19 3.19
29 8.80 8.52 8.24 3.25 3.25
30 8.46 8.19 7.92 3.31 3.31
31 8.14 7.87 7.61 3.38 3.38
32 7.83 7.57 7.31 3.44 3.44
33 7.53 7.28 7.02 3.50 3.50
34 7.25 7.00 6.75 3.56 3.56
35 6.98 6.73 6.49 3.63 3.63
36 6.72 6.48 6.24 3.69 3.69
37 6.47 6.23 6.00 3.75 3.75
38 6.23 6.00 5.77 3.81 3.81
39 6.00 5.77 5.55 3.88 3.88
40 5.78 5.56 5.34 3.94 3.94
41 5.56 5.35 5.14 4.00 4.00
71
Downloaded from www.Manualslib.com manuals search engine
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
42 5.36 5.15 4.94 4.06 4.06
43 5.17 4.96 4.76 4.13 4.13
44 4.98 4.78 4.58 4.19 4.19
45 4.80 4.60 4.41 4.25 4.25
46 4.63 4.43 4.24 4.31 4.31
47 4.46 4.27 4.09 4.38 4.38
48 4.30 4.12 3.94 4.44 4.44
49 4.15 3.97 3.79 4.50 4.50
50 4.00 3.83 3.65 4.56 4.56
51 3.86 3.69 3.52 4.63 4.63
52 3.72 3.56 3.39 4.69 4.69
53 3.59 3.43 3.27 4.75 4.75
54 3.47 3.31 3.15 4.81 4.81
55 3.35 3.19 3.04 4.88 4.88
56 3.23 3.08 2.93 4.94 4.94
57 3.12 2.97 2.83 5.00 5.00
58 3.02 2.87 2.73 5.06 5.06
59 2.91 2.77 2.63 5.13 5.13
60 2.82 2.68 2.54 5.19 5.19
61 2.72 2.59 2.45 5.25 5.25
62 2.63 2.50 2.36 5.31 5.31
63 2.54 2.41 2.28 5.38 5.38
64 2.46 2.33 2.21 5.44 5.44
65 2.38 2.26 2.13 5.50 5.50
66 2.30 2.18 2.06 5.56 5.56
67 2.23 2.11 1.99 5.63 5.63
68 2.16 2.04 1.92 5.69 5.69
69 2.09 1.97 1.86 5.75 5.75
70 2.02 1.91 1.80 5.81 5.81
71 1.96 1.85 1.74 5.88 5.88
72 1.90 1.79 1.69 5.94 5.94
73 1.84 1.74 1.63 6.00 6.00
74 1.78 1.68 1.58 6.06 6.06
75 1.73 1.63 1.53 6.13 6.13
72
Downloaded from www.Manualslib.com manuals search engine
R25=10kΩ±3% B25/50=3700K±3%
Temp Resistance (kΩ) % (Resist. Tol)
(°C) Rmax R (t) Normal Rmin MAX (+) MIN (-)
76 1.68 1.58 1.48 6.19 6.19
77 1.63 1.53 1.43 6.25 6.25
78 1.58 1.48 1.39 6.31 6.31
79 1.53 1.44 1.35 6.38 6.38
80 1.49 1.40 1.31 6.44 6.44
81 1.44 1.36 1.27 6.50 6.50
82 1.40 1.32 1.23 6.56 6.56
83 1.36 1.28 1.19 6.63 6.63
84 1.32 1.24 1.16 6.69 6.69
85 1.29 1.20 1.12 6.75 6.75
86 1.25 1.17 1.09 6.81 6.81
87 1.21 1.14 1.06 6.88 6.88
88 1.18 1.10 1.03 6.94 6.94
89 1.15 1.07 1.00 7.00 7.00
90 1.12 1.04 0.97 7.06 7.06
91 1.09 1.01 0.94 7.13 7.13
92 1.06 0.99 0.91 7.19 7.19
93 1.03 0.96 0.89 7.25 7.25
94 1.00 0.93 0.86 7.31 7.31
95 0.97 0.90 0.84 7.38 7.38
96 0.94 0.88 0.81 7.44 7.44
97 0.92 0.85 0.79 7.50 7.50
98 0.89 0.83 0.77 7.56 7.56
99 0.87 0.81 0.75 7.63 7.63
100 0.84 0.78 0.72 7.69 7.69
101 0.82 0.76 0.70 7.75 7.75
102 0.80 0.74 0.68 7.81 7.81
103 0.77 0.72 0.66 7.88 7.88
104 0.75 0.69 0.64 7.94 7.94
105 0.73 0.67 0.62 8.00 8.00
73
Downloaded from www.Manualslib.com manuals search engine
Appendix II: Enthalpy-Humidity Chart
0 102xPa 5 10 15 20 25 30 35 40 45 50 55 60
0mmHg 5 10 15 20 25 30 35 40 45
Humidity d. g/kg dry air
0 5 10 15 20 25 30 35 40
60
55
55
50
50
45
45
40
40
40
35
35
0
13
33
30 30
32
0
12
0
31
10
30
25 25
25
29
11
90
24
28
70
20
23
27
20
22
18
80
26
60
21
17
15 15 20
16
40
19
15
50
10
14
11
10
13
10
30
0
12
5 1000
9
5
8
20
0 k∫ /kg
7
0
6
10
00
kcal /kg
5
50
-5
4
g干空气
0
g干空气
2500
00
3
15 0
40
/k
-10
200
/k
k∫
00
2
al
kc
1
焓
-15
00
10
3000
0
-20
Heat-humidity ratio
-1
0
-1
0
-25
-2
-2
-3
-30 500
-4
1000
-6
1013.25mbar (10Pa)
Atmosphetic ptessute
-7
760mmHg
i
d
0
10
-50
-10 00
=1.01t+0.001d(2500+1.84t)k∫/kg dtyait
-15 00
00
-25
0
00
=1.24t+0.001d(597.3+0.44t)kcal/kg dtyait
0
-10
-20 00
00
-30 00
-40
00
-500
-10000
74
Downloaded from www.Manualslib.com manuals search engine
Haier Commercial Air Condition
Web: Http://www.haier.com
Haier reserves the right to make change without any notice.