JT Effect
JT Effect
Gas Turbines
A New Method to
                                                                                          are used for this:
                                                                                          • direct preheating of the intake air
                                                                                            by mixing with:
T
       he output and effectiveness                 - nozzle admission into the air        performing work in the gas turbine
       of gas turbines are greatly de-               stream using binary blast con-       and the steam process.
       pendent on the temperature                    nections (additional air con-
of the process air at the compressor                 sumption)                            Part-load operation
inlet, owing to the use of an axial-               - cascading or film humidification     The intake air quantity through the
flow compressor. The air density                     with water on fitted cooling de-     system is reduced with priority on
and, consequently, the quantity of                   vices (max. 65 to 80% relative       gas turbines for operation at part
air inducted by the axial-flow com-                  humidity)                            load. This is done by actuation of
pressor drop with increasing intake                - direct flow through ice banks.       the fixed blades at the inlet of the
air temperature. The output and the             • indirect cooling of the intake air      axial-flow compressor. This increas-
efficiency of the gas turbine drop in              by waste-heat exchanger, cooled        es the pressure loss at the suction
proportion with this (figure 1).                   with:                                  end and consequently reduces the
   The inducted air quantity, the                  - absorption refrigerating units       efficiency of the gas turbine. In ad-
output and the efficiency can be in-               - adsorption refrigerating units       dition, the air lost as the result of re-
creased again by artificial cooling of             - compression refrigerating units.     duced flow rate is then not available
the intake air in the summertime,               Refrigerating units are costly in-        in the downstream steam process of
and the following methods are al-               vestments and are costly to operate.      a combined gas and steam process,
ready used in practice for this:                Compression refrigerating units re-       thus leading to a reduction in the
• direct adiabatic cooling of the in-           quire expensive electrical power to       parameters in this sub-process as
   take air with water:                         drive them. The drive energy con-         well.
   - nozzle injection into the air              verted to heat and the heat absorbed
     stream using unitary high-pres-            from the intake air stream must be        Secondary cooling circuit
     sure blast connections (can hard-          dissipated to the ambient air. This,      Gas turbines are very effective
     ly be controlled)                          in turn, necessitates large recoolers     drives. Nevertheless, (waste) heat
                                                that also consume water and elec-         that must be dissipated to the en-
                                                tricity.                                  vironment via separate cooling
                                                                                          systems is produced in secondary
                                                Remarkable optimisation                   processes. This includes the (waste)
                                                potential                                 heat of the generator, the waste heat
                                                                                          of the lube oil of the bearings and
                                                Anti-icing                                any gearing mechanisms present
                                                The risk of icing up of the intake        and, depending on make, other
                                                air filter and of the inlet diffuser of   (waste) heat sources. In warmer re-
                                                the axial-flow compressor occurs          gions in particular and also as a con-
                         Dr.-Ing. Frank
                         Triesch, Managing
                                                in cold regions in the wintertime at      sequence of global warming, these
                         Director,              high intake air relative humidities.      coolers frequently pose a problem
                         Airtainer GmbH &       This is counteracted by artificially      in respect of operation of the gas
                         Co. KG, Leipzig/       reducing the relative humidity by air     turbines. The lube oil temperature
                         Germany                preheating. This process is referred      can no longer be stabilised in the
                                                                                  /0
         P/P0
                0,90
                                                                                         0,92
                0,80                                                                     0,90
                                                                                         0,88
                0,70
                                                                                         0,86
                0,60                                                                     0,84
                   –40 –30 –20 –10 0       10 20 30    °C             50                    –40 –30 –20 –10 0       10 20 30    °C                  50
                   –40   –20   0      20    40  60  °F                120                   –40   –20   0      20    40  60  °F                    120
                                Air temperature                                                          Air temperature
9856.1
Figure 1. Example of the dependence of output and efficiency of a gas turbine on ambient temperature
                       summertime and the gas turbine            burning in the form of large droplets,         • recooling of the secondary cooling
                       output must be reduced. In rare cas-      this may cause the dreaded damage                 circuit (lube oil and generator)
                       es, it is also necessary to completely    to the turbine blades, also known as           • fuel preheating
                       discontinue operation temporarily.        flashback.                                     • combustion air conditioning of
                       The lube oil ages more quickly and           Gas turbine manufacturers conse-               the gas turbine:
                       other lube oil grades may need to         quently demand a gas temperature                  - indirect preheating of the intake
                       be used.                                  at the combustion chamber inlet                     air in the event of the risk of sub-
                                                                 that is around 15 K above the hydro-                zero temperatures
                       Fuel preheating                           carbon or water vapour dew point at               - direct humidification of the in-
                       Fuel preheating is required on            every operating point. This combus-                 take air in the case of positive
                       steady-state gas turbines operated        tion gas preheating is performed in                 ambient temperature
                       with natural gas so as to compen-         gas pressure reducing stations in a               - indirect preheating of the intake
                       sate for the Joule-Thomson ef-            separate heating building with a not                air in order to achieve part-load
                       fect when reducing the pressure           insignificant fuel gas consumption                  operation.
                       of the natural gas from pipeline          from the turbine’s own fuel.                   This involves interconnecting the
                       pressure to combustion chamber               Moreover, in power stations,                (waste) heat sources of generator
                       pressure. The temperature reduc-          the fuel gas is heated further, di-            and lube oil etc. with a safety heat
                       tion of the natural gas occurring in      rectly upstream of the gas turbine,            exchanger to be installed in the fuel
                       the isenthalpic restriction process       temporarily up to temperatures                 line and hybrid coolers to be in-
                       may also be so great – depending          as high as approximately 200 °C.               stalled in the intake air by the closed
                       on pressure ratio on regulator and        This preheating is performed with              secondary cooling circuit to form a
                       inlet temperature of the gas from         heat from the combined cycle. This             system of hybrid combustion air
                       the pipeline – that there is a risk of    results in a saving in fuel gas cor-           conditioning (figure 2).
                       the temperature dropping below            responding to the heat equivalent
                       the water vapour dew point and            and an almost proportional in-                 Hybrid cooler
                       consequently, icing up inside and         crease in efficiency of combined               Hybrid coolers have been used for
                       outside the gas pipe.                     cycle.                                         recooling to date. They are operated
                          The effects on gas turbines can                                                       only dry up to outside tempera-
                       be at least just as far-reaching if the   Connection between secondary                   tures of approximately 7 to 18 °C
                       actual temperature drops below the        cooling, fuel preheating, anti-                depending on design. Recooling is
                       carbon dew point in the natural gas.      icing and air humidification                   then performed via a finned tube
                       Propane, butane and other higher                                                         matrix. If the outside temperature
                       hydrocarbons contained in natural         A new system that performs the fol-            is beyond these limits, it is humidi-
                       gas are precipitated to a certain ex-     lowing tasks with few known and                fied externally so that a water film
                       tent in liquid phase at low tempera-      tried-and-tested components has                wets the entire matrix with second-
                       tures and/or low pressures. If this       been developed for conditioning the            ary water. Partial evaporation of the
                       liquid phase enters the gas turbine,      intake air on gas turbines:                    wetting water results in indirect ad-
                                                                                                                        5   Adapter
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                             aaaaaaaaaaaaaaaaa
                                                                                                                        6   Intake silencer
                                                                             aaaaaaaaaaaaaaaaa
                                                                                                                        8   Intake silencer
                                                                             aaaaaaaaaaaaaaaaa
                                                          1 2 3 4   56   7        8              9                      9   Intake duct
   Copper is used as the pipe materi-
al. Fully demineralised water should
be used to wet the hybrid coolers.
Desludging that is then required
far less frequently is controlled as a
function of the measured conductiv-              9856.3
the installation must also be con- Ambient air RH Air RH after HCAC
                                                                                                                                                Relative humidity
turbines at Potsdam South                                 Temperature
CHP station                                                                                                              +74.4%            50
                                                                        20                                                                 40
The German utility Energie und                                                                               19.8 °C
Wasser Potsdam has been operat-                                                                                                            30
ing a combined cycle system as a                                        15                                                                 20
CHP plant using two Siemens SGT-                                                                                        24.5% RH
600 (previously ABB/Alstom GT10B)                                                                                                          10
gas turbines at its southern site since                                 10                                                                  0
1996.                                                                    0:00     4:00           8:00     12:00      16:00       20:00   0:00
   The following operating states                                                                  time (15 min)
were examined in a survey, to deter-                                                                  28 July 2008
mine the cost-effectiveness of retro-
fitting a plant for hybrid combustion            9856.6
Advertisement
                                                                                              24.30
                                  24                                                                           23.66                            the standard output of 22.5 MW by
                                                                                                                            23.30
                                  23                                                          22.79                         22.69
                                                                                                                                                around –2 MW (–9.1%) by means of
                                                                                                               22.49
                                  22                                                                                                            air preheating, or increasing it by
                                                                                                                            21.44
                                  21                                                                                                            approximately +1.2 MW (+5.3%) by
                                       Increase in output and reduction in output = output variability         20.50
                                  20   with hybrid combustion air conditioning                                                                  air humidification (figure 7). Intake
                                  19
                                          Output            Anti-icing                                                                          air humidification increases the ef-
                                        restriction
                                                                                                                                                ficiency of the gas turbine by about
                                  18
                                   –15      –10           –5     0    5       10   15                 20      25       °C           35          0.43% absolute at 25 °C (figure 8). A
                                                                Ambient air temperature                                                         maximum of 1.75 t of completely
                                                                                                                                                demineralised water evaporates per
      9856.7
                                                                                                                                                hour in air humidification.
                                                                                                                                                   Complete replacement of the filter
     Figure 7. Output variability by means of hybrid combustion air conditioning                                                                enclosures with hybrid combustion
     on an SGT-600                                                                                                                              air conditioning and three-stage air
                                                                                                                                                filtration facilitated:
                                                                                                                                                • reliable anti-icing operation
                                                                                                                                                • reduction in intake pressure loss
                                               Without combustion air conditioning       Cold with humidification and heat input                • high output variability
                                               Peak load with 100% humidification        With preheating, dry                                   • no filter flushing requirement
                                  0.345                                                                                                         • considerably longer filter life
                                                                                                                                                • reduction in NOx emissions
                                                                                                                                                • relief of the recooling system in
                                  0.340                             0.3390
                                                                                                                                                   both summer and winter.
                                            0.3380
                                                                    0.3386                      0.3378                                          Alternatively, the combustion air can
                                            0.3372                                              0.3367                                          be conditioned in stackable airtain-
                 Efficiency
                                  0.335                                                                            0.3349
                                                                                                                                                ers, which combine three-stage air
                                                                                                                   0.3328 0.3336
                                                                                                                                                filtration and hybrid combustion air
                                                                                                                            0.3314
                                  0.330
                                              Output            Anti-Icing                                         0.3306                       conditioning within the dimensions
                                            restriction
                                                                                                                                                of a standardised unit. Compared to
                                                                                                                            0.3265              a filter enclosure with two-stage air
                                  0.325                                                                                                         filtration, an airtainer conditioning
                                      –15       –10        –5      0    5       10   15                  20   25        °C          35
                                                                                                                                                system is amortised in less than two
                                                                  Ambient air temperature
                                                                                                                                                years.                               
      9856.8
     humidity > 80% into a non-critical                                            higher part-load combined cycle ef-
     range. The dry cooler fans are now                                            ficiency.
     operated at a lower speed.
                                                                                   Increase in output using adiabatic
     Artificial reduction in output using                                          air humidification
     waste heat                                                                    The possibility exists of operating
     A combined cycle system operating                                             the gas turbine with intake air hu-
     in combined heat and power is pre-                                            midification from approximately
     dominantly heat-led, but is nowa-                                             March to November. The associated
     days also subject to market demands                                           natural cooling of the intake air sta-
     for electrical energy. It is possible to                                      bilises the gas turbine output. In the
     reduce gas turbine output artificially                                        hot months, intake air temperatures
     by preheating air using waste heat.                                           < 20 °C were measured consistently                            triesch@gmx.de
     The elimination of throttling losses                                          at ambient air temperatures of up to
     and the waste heat input produce                                              34 °C (figure 6).                                             www.thermointegral.de