February, March and April 2018
Julie Sievers
Iowa DNR Field Office 3
Available on the IRWA website
Go to www.iowaruralwater.org/
Then Resources
Then Downloads
You will find the presentation there
Introductions
Chlorine Chemistry, Ammonia Sources and Impact
Nitrification – The Good, the Bad, and the Ugly
Testing, Indicators, and Specific Examples
Flint Lead Event
Roundtable Discussion
Monochloramine, NH2Cl
Dichloramine, NHCl2 Combined Chlorine
Trichloramine, NCl3
Free Chlorine, OCl- (hypochlorite) or HOCl
(hypochlorous acid) – dependent on pH
Free Chlorine = Free Available Chlorine
Total Chlorine = Free + Combined
Chlorine Residual = Dose - Demand
Do you know which are present in your system?
Ammonia, NH3 or Ammonium ion, NH4
◦ In neutral or acidic natural waters, ammonia is
present as ammonium ion
Nitrite, NO2
Nitrate, NO3
Kjeldahl Nitrogen, TKN
◦ TKN = Organic nitrogen + ammonia
For systems adding ammonia
◦ Ammonium sulfate (LAS), ammonium hydroxide, or
others
Naturally occurring in Iowa
When the nitrogen present in the well is ammonia
it is not from surface source
◦ Surface source is converted to nitrate before reaches
aquifer = nitrate in well, not ammonia
Ammonia is from the mineralization of organic
material present from when aquifer was formed
◦ Mineralization of organic matter to ammonium by
microorganisms in presence of organic carbon sources in
an anaerobic (without oxygen) environment
◦ Most of Iowa was shallow seas
Found in all aquifers
Levels of 1 to 5 mg/L common
◦ DNR/UHL study
◦ GSB data
◦ USGS data
◦ Ambient water quality data
Ammonia Molecule
◦ DNR 2013 study 3 hydrogen and 1
◦ Raw water monitoring nitrogen atoms
Levels as high as 11 mg/L
Ammonia is NOT regulated in Iowa in drinking water
Ammonia has a huge chlorine demand (10 – 12 mg/L of
chlorine per 1 mg/L of ammonia)
Need to know what form of disinfectant you are using
◦ Must meet minimum levels to protect public health
Taste and odor issues
Nitrification
Disinfection byproducts violations or issues
◦ TTHM/HAA5 for free chlorine; Nitrosamines for chloramines
Water quality impacts
Do you know the ammonia level in your system?
From Bob Spon, OpFlow Article, June 2008
Chlorine typically added as gas chlorine or
sodium hypochlorite (liquid chlorine)
Disassociates based on pH (and temperature)
Chlorine Hypochlorous Acid Hypochlorite Ion
If you add ammonia or have it present in the raw water, these
reactions occur:
Formation is
dependent
on the pH
and chlorine
to ammonia
ratio
Monochloramine Dichloramine Trichloramine
AKA Nitrogen trichloride
There are competing reactions
NaOCl + H2O → HOCl + NaOH Liquid chlorine
Cl2 + H2O → HOCl + Cl- + H+ Gas chlorine
NH3 + HOCl → NH2Cl + H2O Monochloramine
NH2Cl + HOCl → NHCl2 + H2O Dichloramine
Trichloramine
NHCl2 + HOCl → NCl3 + H2O
For typical, traditional chloramination, the system
adds chlorine and ammonia
◦ The system can control both chlorine feed rate and
ammonia feed rate
◦ Typically, chlorine is added first, then ammonia
In systems with naturally occurring ammonia,
chloraminating due to ammonia in source water
◦ System can control chlorine feed rate BUT have no to
limited ability to change or control ammonia level
Do you have ammonia in your raw water?
Do you add ammonia?
Ammonia reacts with chlorine to form monochloramine,
dichloramine, and trichloramine
Formation is dependent on the pH and chlorine to
ammonia ratio
Monochloramine, dichloramine, and trichloramine are
measured as a part of the total chlorine residual and are
weak disinfectants
Trichloramine = Nitrogen trichloride
Monochloramine and dichloramine exist together at pH
of 6.5 to 7.5
◦ Chlorine to ammonia ratio determine which is formed
Dichloramine and trichloramine cause taste and odor
problems
Small amounts of trichloramine (nitrogen trichloride)
may exist past the breakpoint and may also cause taste
and odor problems
From Bob Spon, OpFlow Article, June 2008
Ammonia results from a certified lab are for total
ammonia
Free ammonia testing must be done immediately and
is done on-site
◦ Free ammonia and monochloramine are measured as a two
step test
Total chlorine = free + combined
Combined chlorine = monochloramine +
dichloramine + trichloramine
Free chlorine in the presence of chloramines is “false”
free
Minimum levels dependent on where you are at on
the curve
◦ Levels throughout the distribution system
Minimum of 0.3 mg/L free chlorine residual if on
the breakpoint side of the curve
Minimum of 1.5 mg/L total chlorine residual if
chloraminating
Maximum of 4.0 mg/L total chlorine
◦ Based on Running Annual Average (RAA) = MRDL
Minimum = 1.5 mg/L total chlorine Min = 0.3 mg/L free
From Bob Spon, OpFlow Article, June 2008
Determine where you are at on the curve
Measure free chlorine immediately and at 30
second intervals to 2 minutes after adding reagent
◦ Are the readings stable or do the readings increase?
◦ If the free residual increases more than 0.1 mg/L, you
are on the chloramine side of the curve & do NOT have
free chlorine.
This is often referred to as “false” free
Measure total chlorine residual
◦ Rule of thumb is if the free residual is stable and about
80% of total, you are on the breakpoint side and have
“true” free residual
“False” Free Chlorine Residuals
All in mg/L
The rate of
interference is
dependent upon:
• the
concentration
of the
chloramine
Zero Immediately = 0.08 30 seconds = 0.20 • the chloramine
compound
present
• and the
sample
temperature
60 seconds = 0.36 90 seconds = 0.52 120 seconds = 0.76
Where are You on the BP Curve?
Test Results = 3.0 mg/L total chlorine
Courtesy of Hach disinfection series
http://www.hach.com/DisinfectionSeries06
What else do you need to know?
From Bob Spon, OpFlow Article, June 2008
What do we need to measure?
Where is the best spot to test for it?
What results are we looking for?
What do we do if we don’t get them?
All Systems:
Free chlorine residual
◦ Determine if true or false free
Total chlorine residual
Chlorine dosage
Total ammonia
◦ In systems with naturally-occurring ammonia, to measure raw
water fluctuations
◦ Seasonal changes
◦ Water levels
◦ Usage, pumping rates
◦ Well rotation
If no total ammonia but indications, test TKN
Chloraminating Systems:
Free Ammonia
◦ To determine location on the curve
Monochloramine
◦ This is the target disinfectant for chloraminating systems
◦ Total residual = Monochloramine
◦ In systems that add ammonia, you can achieve this
Nitrite and nitrate
◦ Important to determine if nitrification is occurring
◦ Measure nitrite and nitrate separately
◦ More on this later, including locations where to measure
For systems adding ammonia, measure free chlorine prior
to ammonia addition to determine how much ammonia to
add
Testing Along the Curve
Assume a 1 mg/L ammonia-N dose
Courtesy of Hach disinfection series
http://www.hach.com/DisinfectionSeries06
Dependent on system and location of chlorine addition
Always measure at the SEP
Always measure in the distribution system
◦ Important to know residuals and levels at different water age
locations
May need to measure at specific treatment processes
◦ More on this later
For chloraminating systems:
The key is the chlorine to ammonia ratio
◦ In systems that add ammonia, chlorine typically is added first,
then ammonia
Free chlorine residual (not dose)
Ammonia dose
◦ In systems with natural ammonia, minimizing free ammonia as
much as possible
◦ Chlorine dose – target is monochloramine
Other factors
◦ pH
◦ Temperature
Minimum total residual of 1.5 mg/L
◦ If can show consistent treatment, may not be required to
measure free chlorine (false) – discuss with DNR FO
Systems that add ammonia can control the dosage of
chlorine and ammonia
Measure Free Chlorine before ammonia addition
◦ Target Monochloramine (NH2Cl) level
After ammonia addition:
Free Ammonia 0.04 – 0.1 mg/L
Monochloramine (NH2Cl) at the target
Total Chlorine = Monochloramine (NH2Cl)
Know your raw water ammonia levels
◦ If you blend or rotate wells, do this is a way to get the most
consistent ammonia levels possible OR
◦ May need to have different chlorine dosages for different
wells or combination of wells
Goal is to either chloraminate or use free chlorine –
NO yo-yoing back and forth
Determine target chlorine residuals based on your
system and work to meet them
Consistent chlorine residuals throughout the
distribution system
For free chlorine systems:
The key is to always stay on the free
chlorine side of the curve (past breakpoint)
Free chlorine residuals are stable
Free chlorine residuals within 80% of the
total residuals throughout the system
Minimum free residual of 0.3 mg/L
throughout the distribution system
I Am Here!
NH2Cl = TC NH2Cl < TC NH2Cl = 0
F NH3N > 0 F NH3N = 0 F NH3N = 0
FC = stable
FC=80% TC
Courtesy of Hach disinfection series TC = Total Chlorine
http://www.hach.com/DisinfectionSeries06 F NH3N = Free Ammonia
Chloramination Free Chlorine
Monochloramine is equal to No remaining ammonia
Total Chlorine True free chlorine
residual (reading does
Free Ammonia of 0.04 to 0.10
not increase)
mg/L
Free chlorine is at least
Minimum of 1.5 mg/L total
80% of total
chlorine residual throughout the
◦ Optimal is > 85%
distribution system Minimum of 0.3 mg/L
free chlorine residual
throughout the
distribution system
Factors to consider:
Change in chlorine levels
◦ What are the two reasons why chlorine residuals change?
Remember: Residual = Dose - Demand
Factors to consider: Dose
Calculate the chlorine dose, has it changed, if so, why?
Chlorine Gas Dosage, mg/L = Chlorine Used, lbs/day__
(Flow, MGD) (8.34 lbs/gal)
Liquid Chlorine Dosage, mg/L = (lbs of chlorine) (% available chlorine as decimal)
(Flow, MGD) (8.34 lbs/gal)
OR
Liquid Chlorine Dosage, mg/L = (gallons of chlorine) (% available chlorine as decimal)
(MGD)
Factors to consider: Demand
Change in ammonia levels
◦ Have the ammonia levels changed?
Changes in chlorine residuals after regeneration of softeners
◦ Often see residuals change due to formation of chloramines rather
than free chlorine
Decrease in the chlorine residuals or areas where the
minimum levels cannot be maintained
◦ Nitrification or the bacterial conversion of ammonia to nitrite to
nitrate
◦ Chloramine decay in distribution, especially in low use and dead
end areas
Others
Changes in other chlorine demand
Free Chlorine Demand
Water Quality Parameter Multiplier x (Factor)
Iron 0.64 mg/L
Manganese 1.3
Hydrogen Sulfide 0.2 - 2.5
Nitrite (as N) 5
Ammonia (as N) 10 to 12
Organic Nitrogen 1
TOC 0.1
Example of changes in chlorine demand due to ammonia
Free Chlorine
Water Quality Demand Multiplier Input Water Demand per Input Water Demand per
Parameter x (Factor) Quality Parameter Quality Parameter
Iron 0.64 mg/L 1.2 0.768 1.2 0.768
Manganese 1.3 0.24 0.312 0.24 0.312
Hydrogen Sulfide 0.2 0 0 0 0
Nitrite (as N) 5 0 0 0 0
Ammonia (as N) 10 to 12 2 24 2.5 30
Organic Nitrogen 1 0 0 0 0
TOC 0.1 0 0 0 0
TOTAL Chlorine Demand 25.08 31.08
Example of changes in chlorine demand due to iron &manganese
Free Chlorine
Water Quality Demand Multiplier Input Water Demand per Input Water Demand per
Parameter x (Factor) Quality Parameter Quality Parameter
Iron 0.64 mg/L 1.2 0.768 1.8 1.152
Manganese 1.3 0.24 0.312 0.34 0.442
Hydrogen Sulfide 0.2 0 0 0 0
Nitrite (as N) 5 0 0 0 0
Ammonia (as N) 10 to 12 2 24 2 24
Organic Nitrogen 1 0 0 0 0
TOC 0.1 0 0 0 0
TOTAL Chlorine Demand 25.08 25.594
Free chlorine residuals are higher than total residuals
False free
Reaction not complete
◦ Consider chemical feed location to sample tap location
Using same sample vials
◦ Dedicated sample vial for free chlorine
◦ Another dedicated sample vial for total chlorine
◦ Zero each before analysis
Alkalinity and pH interference
◦ According to Hach: After adding the DPD reagent, the sample pH
should measure 6.3 Samples with pH of 7.6 or above and alkalinity of
250 or above may not have pH of 6.3 after adding the reagent, causing
small bubbles to form which increases the reading. After 1 minute the
free residual will decrease as the bubbles dissipate.
• NH2Cl too high • FAA too high
• Reduce NH3 • Reduce NH3
• Reduce Cl2 • Increase Cl2
IT’S A BALANCING ACT
• TC dropped after • TC > NH2Cl
NH3 addition • Reduce Cl2
• Increase NH3
• Reduce Cl2
From Bob Spon, OpFlow Article, June 2008
Drop in total chlorine residuals in storage
and distribution
Free ammonia can convert to nitrite and
nitrate
Taste and odor issues if form di or
trichloramines
Hypochlorous Acid 20 mg/L
Monochloramine 5 mg/L
Dichloramine 0.8 mg/L
Trichloramine 0.02 mg/L
Typically “swimming pool” or other “chemical” or
“chlorine” type smell
“Burning” of eyes, particularly in shower or other hot
water uses
Break Time…
Then on to nitrification…
Ammonia, NH3
Ammonium ion, NH4
◦ In neutral or acidic natural waters,
ammonia is present as ammonium ion
Nitrite, NO2
Nitrate, NO3
Kjeldahl Nitrogen, TKN
◦ TKN = Organic nitrogen + ammonia
Pidwirny, M. (2006). "The Nitrogen Cycle". Fundamentals of Physical Geography, 2nd Edition.
Ammonia Treatment Storage and
in Well Plant Distribution
Ammonia, Ammonia,
Nitrite or Nitrite or Nitrate
Nitrate depending on
depending on conditions
conditions
Nitrosomas and Nitrobacter
Can be a result of surface activities or
contamination
◦ When you find nitrite or nitrate in raw water samples
(directly from well) indicates it is a result of surface
activity
Can be a result of bacterial nitrification of
ammonia within the water system
◦ Often find ammonia, nitrite and nitrate present in the
same SEP or system sample if nitrification is
incomplete
Result of contamination from surface activities
◦ When found in raw water samples (directly from well) indicates
close source of contamination or recent contamination
Result of bacterial nitrification of free ammonia
◦ Conversion within transmission line, treatment plant, storage or
distribution system
◦ Up to one nitrite formed for each ammonia
1 mg/L of ammonia can form 1 mg/L of nitrite
MCL in drinking water of 1.0 mg/L - ACUTE health
concern
SDWA requirement is “one time only” sampling at SEP
Iowa DNR protocol implementation includes SEP and
distribution system monitoring – more on these later
Result of contamination from surface activity
◦ Find nitrate in raw water samples
Result of bacterial nitrification of nitrite
MCL of 10 mg/L - ACUTE health concern
Often find present with ammonia and nitrite if
nitrification is incomplete
Up to one nitrate can be formed from each nitrite
Sampling at SEP:
◦ 1/year
◦ 1/quarter if >5.0 mg/L <10
◦ 1/month if > 10
Health concerns the same for each but at different
levels, both are ACUTE contaminants
◦ Nitrite = 1.0 mg/L
◦ Nitrate = 10 mg/L
Blue baby syndrome
◦ Difficult to identify
Failure to thrive
Many times appears to be formula intolerance
◦ Change to premade formula and symptoms disappear
Some links to bladder and other cancers
Nitrosomonas convert ammonia to nitrite
Nitrobacter convert nitrite to nitrate
Present in treatment plants
◦ Aerators, detention tanks, filters
Present in transmission lines, storage and
distribution systems
◦ Biofilm
Common in soil and environment
Not detected as part of total coliform test
Not always detected as part of HPC
(heterotrophic or other total plate count)
Nitrosomonas
◦ Convert ammonia to nitrite
◦ Resistant to chloramines
◦ Less sensitive to chlorine
◦ If established, can protect themselves in presence of high
chlorine residuals
Nitrobacter
◦ Very sensitive to ammonia
Any ammonia not consumed by Nitrosomonas will inhibit
Nitrobacter
◦ Very sensitive to chlorine and chloramines
Will be dormant (hibernate) in presence of chlorine or
chloramines, usually will not be killed except at high levels
◦ Thrive in narrow pH range – 7.6 to 7.8
Ammonia can convert to nitrite at 1:1 ratio
Nitrite can convert to nitrate at 1:1 ratio
IF no limiting factors present
Highest risk during low water use and warm water
temperatures
◦ Spring and fall when warm water due to time in tower/storage and
low use
◦ Last few years in the summer: issues with nitrification in systems
that had not had previous problems due to low water use and
warm temperatures
Same bacterial action as in wastewater systems –
conversion of ammonia to nitrate
Factor Nitrosomonas Nitrobacter
pH 5.8 – 9.5 5.7 – 10.2
Optimum pH 7.5 – 8.0 7.6 – 7.8
Temperature 5 – 30 C 5 – 40 C
Optimum Temp 30 C 28 C
Chlorine Less sensitive Very sensitive
Ammonia Consume Very sensitive
Amount of Microbial community
dissolved oxygen composition
(DO) Alkalinity
Chlorine residuals Phosphate level
Temperature Carbon or TOC levels
Detention/retention Type of filter media
time
Backwash water –
Amount of free
ammonia present chlorinated or
nonchlorinated
pH
Light Others
For complete nitrification (conversion of ammonia to nitrate),
4.57 mg/L of oxygen is consumed per each 1 mg/L of
ammonia
◦ This is in addition to the oxygen needed for oxidation of iron and other
contaminants
◦ Often this is the limiting factor – conversion stops at nitrite leading to
nitrite MCL violations
For complete nitrification, 7.1 mg/L (as CaCO3) of alkalinity is
needed for each 1 mg/L of ammonia
◦ Used to build cell walls by nitrifying bacteria
Drop in total chlorine residuals or no chlorine
residual in ends or portions of the distribution
system
◦ May also be in the middle of a loop (water moving from both
directions with oldest water in the middle of the loop and
little water movement)
Fluctuations in chlorine residuals with no apparent
cause or reason such as changes wells or high
service pumps
Decrease (drop) in pH and/or alkalinity in areas of
distribution system
Changes in nitrogen compounds through system
◦ No nitrite or nitrate in raw water but nitrite or nitrate at SEP, in or after
storage, or in portions of distribution system
◦ Look at historical data
Taste and odor complaints
Dirty water complaints
Changes in chlorine residuals (demand) after change of filter
media or shock chlorination of filter media, particularly in iron
removal plants
Disinfection depletion (drop in residuals)
Nitrite/nitrate formation
Dissolved oxygen (DO) depletion
Reduction in pH
Reduction in alkalinity
DBP formation changes
“Dirty water” complaints
Corrosion issues, commonly seen as lead and
copper exceedances
On to control options…
1. Ammonia removal
Running filters in “bio” mode, also called
biological ammonia removal treatment
2. Breakpoint chlorination
No ammonia to nitrify
3. Combination of oxidants
4. Chloramination with operational control
Biological removal of ammonia through nitrification
Ammonia to nitrite to nitrate
◦ No ammonia or nitrite in finished water
◦ Free chlorine residuals – past breakpoint on curve
Typically occurs in filters but may occur in aeration,
detention – before SEP
No chlorination prior to filters
Care must be taken during establishing to protect
nitrifying bacteria
◦ Backwash rate
◦ Backwash water – chlorinated or not chlorinated
Typically takes 8 – 12 or more weeks to establish
Limiting factor!
Dissolved oxygen
◦ If ammonia is greater than ~2 mg/L, there will not be enough oxygen
for complete nitrification
◦ About 4.5 mg/L of oxygen is needed to completely nitrify 1 mg/L of
ammonia
◦ Conversion stops at nitrite if not enough oxygen
◦ Often have nitrite MCL violations at SEP as not enough oxygen to get
from nitrite to nitrate
Systems with higher ammonia levels now operating with air
injection to get ammonia removal in contactors (new
treatment step)
Destroys all ammonia so no “food” for the nitrifying
bacteria
◦ Ammonia to nitrogen gas
Disinfection by free chlorine – past breakpoint on
free side of curve
Requires large dose of chlorine
◦ In practice, 10 to 12 mg/L (or more) of chlorine per 1
mg/L of ammonia is common
TTHM/HAA5 concerns
◦ Many systems with raw water ammonia have high raw water
TOC levels
Free chlorination may not be possible
◦ Often cannot add enough chlorine to meet demand
May not be enough reaction time
◦ Reaction time dependent on pH and temperature
◦ Must go through all reactions to get to free chlorine
(past breakpoint)
◦ If reaction not complete, unstable water entering the
system
Taste and odor complaints
Dirty water and corrosion issues common
Combination of oxidants
◦ Consider use of multiple oxidants
◦ Permanganate, chlorine, others
Other oxidants
◦ MIOX (Mixed oxidants) is in use in some systems
◦ Uses a salt mixture and DC cell to form oxidants,
including ozone, hydrogen peroxide, chlorine, chlorine
dioxide, etc.
Not common practice to control as has many
operational challenges
Addition of sodium chlorite
◦ Very specific monitoring requirements
◦ Must do pilot and show operational control
Minimize free ammonia as much as possible
◦ For systems adding ammonia, target 0.04 – 0.1 mg/L free
ammonia
◦ For systems with natural ammonia, target consistent
ammonia levels and maximum chlorine to ammonia ratio
Target disinfectant
◦ Monochloramine = Total Chlorine
Increase residuals to control nitrifying bacteria
◦ Necessary levels vary by system – typically 2 mg/L or
higher (total chlorine residual)
◦ May need to go to breakpoint for a few weeks each
spring and/or fall to kill biofilm and then maintain
higher chloramine residuals to inhibit growth
Notify customers and DNR FO if change disinfection
practice
May still have free ammonia present so may have
nitrite formation in low use areas, dead-ends, and
storage facilities
◦ Reversion to ammonia (breakdown of chloramines)
Other changes in operation to control
depending on where nitrification is taking
place, such as
◦ Changes to backwash
◦ Increased flushing program
◦ Addition of booster chlorine/ammonia feed
◦ Loop deadends
◦ Periodic forcing of water to move one direction
through looped areas
◦ Changing to free chlorine periodically
Frequency and duration varies
Nitrosamine formation
◦ Nitrosamines are DBPs in chloraminating systems
◦ N-nitrosodimethylamine (NDMA) is most common
◦ Much on-going research
◦ Formation from reaction of natural organic matter (NOM),
use of quaternary amine-based coagulants and anion
exchange resins, or wastewater-impaired source waters
EPA is currently reviewing the existing microbial
and disinfection byproducts regulations as part of
the six year review process (SY3)
Very specific to each system
No magic fix that will work for all
systems
Must know what disinfection practice
you are using and where you are on the
curve!
Many factors impact decision on how to
control ammonia
Work with your engineer and/or technical
service provider
Need to weigh all of the options and
consequences – many unintended
consequences such as nitrification, L/C
corrosion, chlorine residuals, etc.
Communicate with DNR
Minimum = 1.5 mg/L total Minimum = 0.3 mg/L free
From Bob Spon, OpFlow Article, June 2008
On to DNR protocols, testing and system specific examples…
Systems have naturally occurring ammonia in their
groundwater (source water)
Systems adding ammonia to form chloramines
Significant potential exists for conversion of ammonia to
nitrite and nitrite to nitrate
◦ MCL nitrite 1.0 mg/L
◦ MCL nitrate 10 mg/L
Nitrite levels at SEP and/or distribution found ranging from
ND (no detection) to 3.5 mg/L
A number of systems have not been meeting minimum
disinfection residuals
Protocols for use:
◦ During sanitary surveys
◦ Investigations of nitrite MCL violations
◦ Complaint investigations
◦ System not meeting minimum residual requirements
Training of all DNR staff in Nov. 2015
Protocols are being implemented
Systems are encouraged to sample each well or
source if ammonia levels are not known
To determine if there is a need to sample
Assignment of monitoring determined classification:
◦ Systems with complete nitrification at SEP and/or using free chlorine
for disinfection
◦ Systems with the potential for nitrite formation
◦ Systems with nitrite MCL exceedances
◦ Systems adding ammonia
◦ Consecutive systems using chloramines or not meeting minimum
chlorine residuals
Interpretation of results
Any required monitoring will be included in a WS operation
permit
Systems with Complete Nitrification at SEP and/or using
Free Chlorine for Disinfection
◦ Free and total chlorine residuals
◦ SEP ammonia 1/year for systems with ammonia >0.7 mg/L in
combined raw water
Systems with the Potential for Nitrite Formation
◦ Ammonia >0.7 mg/L in combined raw water and chloraminating or
nitrification occurring at any site
◦ Free and total residual - total only with FO approval
◦ SEP ammonia, SEP and distribution nitrite
◦ Self-monitoring for nitrite at SEP and distribution system
◦ Frequency dependent on if nitrification has occurred
Systems with Nitrite MCL Exceedances
◦ For systems with current or historical nitrite MCL exceedances
◦ Free and total residual - total only with FO approval
◦ Quarterly SEP ammonia, monthly SEP and distribution nitrite
◦ Weekly self-monitoring for ammonia and nitrite at SEP and
distribution system
Systems Adding Ammonia
◦ For systems adding ammonia for chloramination
◦ Total chlorine residual, monochloramine, free ammonia, pH
◦ Distribution system nitrite
◦ Self-monitoring for nitrite
◦ Monitoring Plan with Alert and Action Levels
Consecutive Systems Using Chloramines
Systems purchasing water containing chloramines
If the producing system has naturally occurring ammonia:
◦ Free and total residual - total only with FO approval
◦ Distribution system nitrite
◦ Self-monitoring for nitrite
If the producing system adds ammonia to chloraminate:
◦ Total chlorine residual, monochloramine, free ammonia, pH
◦ Distribution system nitrite
◦ Self-monitoring for nitrite
Required for systems with monthly or quarterly distribution
system monitoring
No template as system specific
Select location(s) with highest risk of nitrification
Often deadend or low use areas
◦ May be in the middle of a loop
Use chlorine residuals, monochloramine, free ammonia, and
pH levels; temperature; and taste and odor complaints as
guide
Select locations with the highest potential for nitrification
◦ Lowest total chlorine residual
◦ Largest separation between total chlorine and monochloramine
◦ Highest free ammonia levels
◦ Lowest pH (drop in pH indicates nitrification)
Submit to FO and use this location(s) for certified lab
sampling
◦ Remember to test this sample as part of self-monitoring (paired
samples)
Several options depending on:
Colorimeter/spectrophotometer model
Needed range of the system
Be aware of disposal requirements
◦ Nessler reagent for ammonia contains mercury
Samples for nitrite need to be at room temperature for
accurate results
Protocols require “paired” samples
◦ Self-monitoring testing and certified lab testing of the same sample
◦ Results should be comparable, if not need to determine why
◦ Use self-monitoring to indicate when something has changed so
results must be accurate and representative
Guidelines for systems changing from Chloramine to Free
Chlorine or vise versa
◦ Pre-Transition
◦ Water Plant Activities
◦ Distribution Activities
Customer Notification Samples
Post Transition Strategy
On to System Specific Examples…
Curve is specific for each system
First example is from a system that Dale and Joe worked with
to develop the curve for the system
Chlorine was added (dosed) after all treatment
Treatment = aeration, detention, filtration, ion exchange
Water dosed:
Iron 0.02, Manganese 0.044, Ammonia 0.39 (all mg/L)
Dose (mg/L) Free Chlorine Total Chlorine Monochloramine Free Ammonia Total Ammonia
0.00 0.00 0.00 0.00 0.00 0.39
0.25 0.00 0.05 0.00 0.38 0.40
0.50 0.00 0.29 0.22 0.37 0.40
0.75 0.00 0.46 0.40 0.35 0.41
1.00 0.00 0.62 0.58 0.33 0.41
1.25 0.00 0.74 0.66 0.30 0.41
1.50 0.00 0.85 0.74 0.26 0.40
1.75 0.00 0.98 0.85 0.23 0.40
2.00 0.00 1.11 0.95 0.19 0.39
2.25 0.00 1.24 1.07 0.20 0.39
2.50 0.00 1.37 1.18 0.21 0.39
2.75 0.00 1.48 1.29 0.16 0.38
3.00 0.00 1.58 1.39 0.11 0.38
3.25 0.00 1.61 1.40 0.08 0.39
3.50 0.00 1.63 1.41 0.06 0.38
3.75 0.00 1.66 1.41 0.03 0.37
4.00 0.00 1.68 1.42 0.00 0.27
4.25 0.00 1.65 1.32 0.00 0.25
4.50 0.00 1.62 1.22 0.00 0.24
4.75 0.00 1.58 1.11 0.00 0.22
Dose (mg/L) Free Chlorine Total Chlorine Monochloramine Free Ammonia Total Ammonia
5.00 0.00 1.55 1.01 0.00 0.20
5.25 0.00 1.44 0.90 0.00 0.18
5.50 0.00 1.34 0.80 0.00 0.16
5.75 0.00 1.23 0.69 0.00 0.13
6.00 0.00 1.12 0.58 0.00 0.11
6.25 0.00 1.05 0.51 0.00 0.10
6.50 0.00 0.97 0.43 0.00 0.09
6.75 0.00 0.90 0.36 0.00 0.08
7.00 0.00 0.82 0.28 0.00 0.07
7.25 0.00 0.90 0.25 0.00 0.07
7.50 0.00 0.98 0.21 0.00 0.07
7.75 0.00 1.06 0.18 0.00 0.06
8.00 0.00 1.14 0.14 0.00 0.06
8.25 0.00 1.21 0.12 0.00 0.03
8.50 0.91 1.28 0.09 0.00 0.00
8.75 1.05 1.34 0.05 0.00 0.00
9.00 1.18 1.40 0.00 0.00 0.00
9.25 1.51 1.74 0.00 0.00 0.00
9.50 1.84 2.08 0.00 0.00 0.00
9.75 2.17 2.42 0.00 0.00 0.00
10.00 2.50 2.76 0.00 0.00 0.00
Chloraminating or Breakpoint
mg/l SEP Mid-point End
Initial – 1 Initial – 1 Initial – 1
Free Cl2 minute minute minute
1.16 – 1.35 0.47 – 0.47 0.19 – 0.20
Total Cl2 1.39 0.62 0.26
Mono-
1.37 ND ND
chloramine
Free Ammonia ND ND ND
Total Ammonia 0.23 ND ND
0.005 (0.004
Nitrite ND ND
min)
Determination of
Chlorine Curve –
System A
Courtesy of Mikael Brown, Bartlett and West, Inc.
Raw water ammonia
= 1.69 mg/L
pH = 7.6
Cl2 dose = 23.9
mg/L
Fe/Mn demand =
1.2 mg/L
Plant A
Courtesy of Mikael Brown, Bartlett and West, Inc. Raw Water NH3 = 1.69
Plant A
• Chlorine demand
measured over time
• At pH of 7.6, reaction
90% complete in 20
minutes
• At pH of 10.5,
reaction 90%
complete in 600
minutes (10 hours)
Courtesy of Mikael Brown, Bartlett
and West, Inc.
Plant B
Raw water ammonia
= 0.36 mg/L
Iron = 6.96 mg/L
Mn = 0.41 mg/L
Free Chlorine Demand
Water Quality Parameter Multiplier x (Factor)
Iron 0.64 mg/L
Manganese 1.3
Hydrogen Sulfide 0.2
Nitrite (as N) 5
Ammonia (as N) 10 to 12
Organic Nitrogen 1
TOC 0.1
Courtesy of Mikael Brown, Bartlett and West, Inc.
Plant B
Courtesy of Mikael Brown, Bartlett and West, Inc.
Plant B
Courtesy of Mikael Brown, Bartlett and West, Inc.
3 Dakota Aquifer Wells
Wells are within about 2 blocks of each other
◦ Common to see variation in ammonia levels in wells in same aquifer
Lime softening
Nitrification occurring in filters and distribution system
Plant 1 – Natural Ammonia
3 Dakota Aeration
Wells
NH3 = 1.2 - 2.2 Lime Softening
NO2 = <0.02 NH3 = 1.1
NO3 = <0.1 NO2 = <0.02
NO3 = <0.1
Bottom of Filters Top of Filters
NH3 = 0.7 - 0.9 NH3 = 1.1
NO2 = 0.26 - 0.46 NO2 = <0.02-0.12
NO3 = <0.1 NO3 = <0.1
S/EP High Usage
NH3 = 0.4 Area in
NO2 = <0.02 - 0.24 Distribution
NO3 = 0.27
System
NH3 = 0.4
NO2 = 0.32
NO3 = 0.26
Dead End
NH3 = 0.1
NO2 = 0.19
NO3 = 0.72
Data - Plant 1
Location Ammonia Nitrite Nitrate
Raw 1.2 <0.02 <0.1
After lime 1.1 <0.02 <0.1
softening
Top of Filters 1.1 – 1.2 <0.02 – 0.12 <0.1
Bottom of 0.7 – 0.9 0.26 – 0.46 <0.1
Filters
S/EP 0.4 <0.02 – 0.24 0.27
End of System 0.4 0.32 0.26
High Usage
Deadend 0.1 0.19 0.72
All results in mg/L
Initially using raw water to backwash
Now using chlorinated water to backwash filters
Flushing system regularly
Frequent monitoring (self-monitoring) to determine
nitrite levels
Nitrite levels now typically <0.1 mg/L
◦ During low use, warm temps 0.1 to 0.3 mg/L
Total chlorine ~2.2 – 3.0 in system
“False” free chlorine
Disinfection = chloramination
Jordan Wells
Treatment = Aeration, filtration, zeolite softening,
chlorination, caustic soda addition
Saw significant decrease in chlorine levels when
filter media was changed
◦ No free, low total residual
Nitrifying bacteria re-established and conversion
to nitrite to nitrate in filters
Total chlorine ~0.8 - 1.2 in system
Free chlorine ~ 0.6 - 1.1 in system
Disinfection = Free chlorine
Location Ammonia Nitrite Nitrate
Well 7 2.1 <0.1 <0.5
Well 8 2.1 <0.1 <0.5
Well 9 2.2 <0.1 <0.5
Well 10 1.9 <0.1 <0.5
S/EP <0.05 <0.1 1.62
Testing indicated no ammonia
No nitrite or nitrate in wells
Nitrate in SEP result
Nitrification occurring in the filters
Disinfectant = Free chlorine
Location Ammonia TKN Nitrite Nitrate
Well 3 <0.2 2.0 <0.1 <0.5
Well 4 <0.2 1.8 <0.1 <0.5
Filter <0.2 Not tested <0.1 1.6
Effluent
S/EP <0.2 Not tested <0.1 1.6
All results in mg/L
2 Dakota wells
◦ Naturally occurring ammonia
Iron removal
◦ Aeration, detention, gravity filtration
2 Dakota Aeration
Wells NH3 = 3.5
NO2 = <0.02
NH3 = 3.4 - 3.8 NO3 = <0.1 Detention
NO2 = <0.02 NH3 = 3.6
NO3 = <0.1 NO2 = <0.02
NO3 = <0.1
S/EP
NH3 = 2.5 After Filters
NO2 = 0.29
NO3 = 0.55 NH3 = 2.5 - 2.9
Free chlorine = 0.3 NO2 = 0.66 - 0.85
Total chlorine = 2.6 NO3 = <0.1 - 0.10
Dist System -
After Tower
NH3 = 2.1
Near Tower
NO2 = 0.41 NH3 = 2.0
NO3 = 0.72 NO2 = 0.70
Free chlorine = 0.1 NO3 = 0.59
Total chlorine = 1.2 Free chlorine = 0.2
Total chlorine = 1.4
Dist System - Dist System -
Dead-end Looped Line
NH3 = 0.51 - 1.1 NH3 = 2.2
NO2 = 1.1 - 2.1 NO2 = 0.44
NO3 = 0.54 - 0.59 NO3 = 0.67
Free chlorine = 0.1 Free chlorine = 0.2
Total chlorine = ND – 0.4 Total chlorine = 1.4
Tower with 2½ average day capacity
Tried breakpoint chlorination to control - could not
feed enough chlorine to reach breakpoint, could not
get reaction to be complete in plant/clearwell
Used MIOX to eliminate ammonia until unit failed
Exceeded lead and copper action levels
Now injecting air into contactors for biological
ammonia removal
Complete nitrification in the plant
Free chlorine for disinfection
Treatment is an in-line air stone (atomerator), liquid chlorine
addition, and pressure sand filtration
The water flows to the tower with splash aeration in the tower,
then to the distribution system
Line to Tower
2 Buried NH3 = 3.4
Sand & NO2 = <0.02
NO3 = <0.1
Gravel Wells Total Chlorine = 2.7
NH3 = 3.3 - 3.6
NO2 = <0.02
NO3 = <0.1
S/EP
NH3 = 3.0
NO2 = <0.02
NO3 = <0.1
Total Chlorine = 2.0
Dist System - Average
NH3 = 2.1
NO2 = 0.59
NO3 = <1.0
Total chlorine = 1.7
Dist System - Dead-end
NH3 = 1.8
NO2 = 1.2
NO3 = <1.0
Total chlorine = 0.64
Tried breakpoint chlorination to control - could not feed
enough chlorine to reach breakpoint with the time they have
for the reaction
Too high of ammonia to get ammonia removal through
nitrification in the plant
◦ Did not have enough oxygen present in the filters to be able to sustain
complete nitrification
Aggressive flushing program to control nitrite formation
Surface Water
Surface Water Plant
Clearwell Plant SEP
Free NH3 = 0.43
Prior to NH3 Add Monochloramine =
Free Chlorine = 3.00
0.8 – 1.0
Pump Station 1
Consecutive System
Total NH3 = <1.0
NO2 = 1.0
NO3 = 0.9
Total Chlorine = 2.7
Dist System - Downstream
Total NH3 = 0.34
Free NH3 = 0.28
NO2 = >0.69
Total chlorine = 0.63
Monochloramine = 0.21
Dist System - Dead-end
Total NH3 = 0.17
Free NH3 = 0.10
NO2 = >0.69
Total chlorine = 0.17
Monochloramine = <0.12
Tried flushing – could not get velocity to strip biofilm and did
not increase chlorine residuals
Switched to breakpoint chlorination to control nitrification
◦ Stopped feeding ammonia, increased chlorine feed
After 8 weeks, started adding ammonia
◦ Targets:
◦ Free ammonia <0.1
◦ Monochloramine = total chlorine
◦ All total chlorine residuals >1.5
Very specific to each system
No magic fix that will work for all
systems
Must know what disinfection
practice you are using and where
you are on the curve!
Minimum = 1.5 mg/L total Min = 0.3 mg/L free
From Bob Spon, OpFlow Article, June 2008
Julie Sievers
712-262-4177
Julie.sievers@dnr.iowa.gov
Class Number: 23884
Sponsor: IRWA
Title: Ammonia & Disinfection in
Drinking Water - Flint Crisis & Lead in
Iowa
Date: February 28, 2018
Location: Ventura
CEU Hours: 6