ELEC 423
Distribution of Power System
              Power Distribution Protection
Adel Gastli
                                              Adel Gastli
              CONTENTS
                   •Objective of Distribution System Protection
               1
                   •Overcurrent Protection Devices
Adel Gastli
                                                                                 Adel Gastli
               2
                   •Coordination of Protective Devices
               3
                                  ELEC432: Electric Power Distribution Systems     2
Adel Gastli
Adel Gastli
              Five components of protection systems
               Current and voltage transformer to step down the high voltages and currents of the
                electrical power system to convenient levels for the relays to deal with,
Adel Gastli
                                                                                                      Adel Gastli
               Protective relays to sense the fault and initiate a trip, or disconnection,
               Circuit breakers to open/close the system based on relay and autorecloser commands;
               Batteries to provide power in case of power disconnection in the system,
               Communication channels to allow analysis of current and voltage at remote terminals
                of a line and to allow remote tripping of equipment.
                 Transducer
              • Sensor & transformer
              • Current transformer (CT)
Adel Gastli
                                                Adel Gastli
                       &
               Potential transformer (VT, PT)
Adel Gastli
Adel Gastli
              POWER SYSTEM PROTECTION
                          Main idea is to remove faults as quickly as possible
                           while leaving as much of the system intact as possible
                          Fault sequence of events
                           1. Fault occurs somewhere on the system, changing the system
Adel Gastli
                                                                                              Adel Gastli
                              currents and voltages
                           2. Current transformers (CTs) and potential transformers (PTs)
                              sensors detect the change in currents/voltages
                           3. Relays use sensor input to determine whether a fault has
                              occurred
                           4. If fault occurs relays open circuit breakers to isolate fault
              The protections are often classified according to the object that they
              protect. An example is shown in following figure. If a failure occurs
              within an indicated area in figure, this area should be isolated from
              the rest of the network.
Adel Gastli
                                                                                       Adel Gastli
                             Protective relays
              A protective relay is a device designed to trip a circuit breaker when a
              fault is detected. The first protective relays were electromagnetic
              devices, relying on coils operating on moving parts to provide detection
              of abnormal operating conditions such as over-current, over-voltage,
              reverse power flow, over- and under- frequency.
Adel Gastli
                                                                                         Adel Gastli
Adel Gastli
Adel Gastli
              COORDINATION OF PROTECTIVE DEVICES
               What is coordination?
                 Overcurrent protective devices can be coordinated selective or
                  nonselective.
                 Selective coordination: localization of overcurrent condition to restrict
                  outages to the circuit or equipment affected, accomplished by choice of
Adel Gastli
                                                                                              Adel Gastli
                  overcurrent protective devices and their ratings or settings (i2t).
                 Nonselective coordination: occurs when a fault on a branch circuit
                  opens not only the branch-circuit overcurrent device but also the feeder
                  overcurrent device.
                  • Nonselective systems are installed unknowingly
                  • Causes needless power outage in portions of the electrical system
                    that should not be affected.
                                              ELEC432: Electric Power Distribution Systems    11
              COORDINATION OF PROTECTIVE DEVICES
               The fault on the branch-circuit
                may trips both the branch-circuit                  CBM                             CBB
                breaker and the feeder circuit                     100A                            20A
                breaker if the curves are set as                                         CBB CBM
                shown in this figure.
Adel Gastli
                                                                                                                        Adel Gastli
               In this case the protection is not
                fully coordinated.
                                                                             Time
                                                                                                         Overlap
               As a result, power to the panel is                                                       zone
                cut off, and circuits that should                          0.9s
                                                                           0.5s
                not be affected are now off.
                                                                                           3kA     5kA
                                                                                                              Current
                                          ELEC432: Electric Power Distribution Systems                                  12
              COORDINATION OF PROTECTIVE DEVICES
               In general, when the protective device
                characteristics do not intersect, the
                system is fully coordinated.                                      100A                      20A
               If they touch in the bottom or anywhere
                (overlap zone), then they are not fully
                coordinated.
Adel Gastli
                                                                                                                               Adel Gastli
                                                                                                      20A     100A
               As rule of thumb, if the branch fuses are
                rated not more than half of the main
                                                                                               Time
                feeder fuse, then in most of the cases we
                have a fully coordinated system. So the
                main protective device should be rated
                twice the largest branch protective device.
                                                                                                                     Current
                                                ELEC432: Electric Power Distribution Systems                                   13
              COORDINATION OF PROTECTIVE DEVICES
               Circuit breaker coordination:
                 The ground fault pickup time delay
                   feature is useful for circuit breaker
                   coordination. In the following scheme,
                   upstream breaker “A” has been set to
Adel Gastli
                                                                                             Adel Gastli
                   .2s and downstream breakers “B” and
                   “C” have been set to .1s.
                 A ground fault occurring in the circuit
                   supplied by “B” will trip the “B” breaker
                   without disturbing “A” or “C”..
                                              ELEC432: Electric Power Distribution Systems   14
              COORDINATION OF PROTECTIVE DEVICES
              IMPORTANT NOTE:
               We must be careful when large motors are part                                       33kA
                of the distribution system to be protected.
               During short-circuit, large motors will behave as
Adel Gastli
                                                                                                              Adel Gastli
                generators for a short time period until they stop
                                                                                              3kA
                completely (regenerative breaking) and will                                            36kA
                contribute to further increase of the short circuit
                current in the point of fault.                                            M
                                           ELEC432: Electric Power Distribution Systems                       15
              CIRCUIT BREAKERS
               This figure shows one line diagram
                that has three molded case circuit
                breakers in series: from the main
                1200A to the 100A branch circuit
                with the 400A feeder in between.
               The other circuit breakers on the
Adel Gastli
                                                                                            Adel Gastli
                one-line diagram supply other
                circuits and loads.
               The fault current path from the
                power source is depicted by the red
                arrows/lines superseded on the
                one-line diagram.
                                             ELEC432: Electric Power Distribution Systems   16
              CIRCUIT BREAKERS
               These curves illustrate the time current
                characteristics for the 1200A, 400A, and 100A
                circuit breakers.
               The instantaneous trip (IPU) settings for each of
                these three molded case circuit breakers are
                provided on the one-line diagram.
               The 100A circuit breaker has a non-adjustable
Adel Gastli
                                                                                                   Adel Gastli
                instantaneous trip setting and the curve is as
                depicted.
               The 400A circuit breaker has an instantaneous
                trip set at 10 times its amp rating (10X) which is
                10 times 400A or 4000A.
               The 1200A circuit breaker has an instantaneous
                trip set at six times its amp rating (6X) which is
                six times 1200A rating or 7200A..
                                                    ELEC432: Electric Power Distribution Systems   17
              CIRCUIT BREAKERS
               Remember that when the curves of two circuit
                breakers cross over in their instantaneous trip
                region, then the drawing indicates that the two
                circuit breakers do not coordinate for fault
                currents greater than this cross over point.
               For instance, interpreting the coordination
                curves for the 100A circuit breaker and the
                400A circuit breaker: their curves intersect in
Adel Gastli
                                                                                                   Adel Gastli
                the instantaneous region starting at
                approximately 3600A.
               That means for a fault current greater than
                3600A on the load side of the 100A circuit
                breaker, the 400A circuit breaker will open as
                well as the 100A circuit breaker.
               This demonstrates a lack of coordination and
                results in a "cascading effect" that will cause a
                partial blackout.
                                                    ELEC432: Electric Power Distribution Systems   18
              CIRCUIT BREAKERS
               This curve also shows that for any fault
                greater than approximately 6500 amps
                on the load side of the 100A circuit
                breaker, the 400A and 1200A circuit
                breakers will open as well as the 100A
                circuit breaker.
Adel Gastli
                                                                                              Adel Gastli
               The reason: for a fault of or greater than
                6500A, all three of these circuit breakers
                are in their instantaneous trip region.
               Both the 400A and 1200A circuit
                breakers can unlatch before the 100A
                circuit breaker clears the fault current.
                                               ELEC432: Electric Power Distribution Systems   19
              CIRCUIT BREAKERS
               How does this affect the electrical system?
               Look at the one-line diagram next.
               For any fault current greater than
                approximately 6500A on the load side of the
                100A circuit breaker, the 1200A and 400A
                circuit breakers open as well as the 100A
                circuit breaker.
Adel Gastli
                                                                                                  Adel Gastli
               The yellow shading indicates that all three
                circuit breakers opened - 100A branch circuit,
                400A feeder and the 1200A main.
               In addition, all the loads fed by the other
                circuit breakers, denoted by the hash shading,
                are blacked out unnecessarily.
               This is due to the lack of coordination between
                the 100A, 400A and 1200A circuit breakers.
                                                   ELEC432: Electric Power Distribution Systems   20