SWITCHGEARS
ISO 9001
400 A POLE Pole Mounted Fuse Switch Disconnector for
MOUNTED L.V.System is specially designed as an on-load
protective switch and offers a reliable medium for
FUSE SWITCH disconnection and protection of fully insulated open wire
DISCONNECTOR network section.
The unique modular design offers flexibility to connect
switches for single, double, triple and quadruple
phases. Series of such combinations can be linked
together.
Features
Electrical and Mechanical fuse indicators.
4
Minimum number of moving parts.
4
Designed for switching on full load with DIN Type
4
fuse links upto a rated current of 400A.
Arc quenching chambers to allow for On-Load
4
switching.
Change of fuse possible by using the Insulated
4
operating rod.
Lower flap can be withdrawn by the Insulated
4
operating rod.
Flexibility of linking a series of flaps for
4
simultaneous operation.
The contacts are rigidly mounted in the housing,
4
independent of the terminal bolts.
Bolted or Moving blades linked neutral.
4
Host of termination available on request to suit
4
individual requirements.
Construction
The switch is versatile and ideally suited for top
mounting directly to poles, transformers and cross
arms.
The fuse switch disconnector is fully insulated made
from corrosion proof, impact resistant, weather and UV
resilient glass fibre reinforced polyamide compound
with high glass content.
This high quality of material, together with robust
construction guarantees consistent performance even
under adverse climatic conditions.
The upper housing of the switch is hinged to the lower
body and houses the conductors, terminals and
contacts. The operation of the switch is simple and safe
with the help of an insulated operating rod.
The fuse contacts are fully shrouded and terminals are
made of ETP grade high conductivity copper. They are
duly tin plated which ensures minimum contact
resistance besides offering flexibility to use copper or
aluminum cables.
The switch can take conductor size of 50 to 240 sq. mm.
Tested Power...Trusted Solution
400 A POLE MOUNTED
SWITCHGEARS Type Testing
FUSE SWITCH DISCONNECTOR
351
The fuse switch has been extensively type tested according
to IEC 60947 part 1 & 3 for:
Test Sequence - 1: General Performance Characteristics.
Test Sequence - 2: Electrical and Mechanical Endurance.
Test Sequence - 3: Short Circuit Performance Capability
at 10 kA rms for 0.5 s.
Test Sequence - 4: Conditional Short Circuit at 17 kA
195
peak.
Test Sequence-5: Overload Performances, Degree of
Protection and Impulse Test at 9.8 kV
peak.
Dimensions
83 323 163 403
80(TYP.)
260
200
Technical Details
CATALOGUE REFERENCE ADPM-1/400A
BODY MATERIAL Polyamide
RATED OPERATIONAL CURRENT In 400 Amps
RATED OPERATING VOLTAGE Ue 440 Volts, 50 Hz
RATED INSULATION VOLTAGE Ui 1000 Volts
RATED SHORT TIME CURRENT Icw 10 kA rms for 0.5 s with 17 kA peak
CABLE SIZE upto 240 sq. mm.
FUSE LINK NH Type Size 1 & 2
DIMENSIONS 270 X 142 X 218 mm (Approx.)
WEIGHT 2.5 Kgs (Not Binding, Without Fuse)
Note : The company follows a policy of continuous development and improvement of its products and hence products
PACE
supplied may differ from those described & illustrated in this catalogue.
Design & Produce By
5egistered Office:
Axis House, Plot No. 104C, Govt. Industrial Estate, Kandivali (West), Mumbai, India
Tel.: +91-22-28696636 Fax: +91-22-28678491
ISO 9001 E-mail: info@axis-india.com MKT-C-01/07
Visit us at:
www.axis-india.com Tested Power...Trusted Solution