Accurate Impedance Based Fault Location Algorithm Using Communication Between Protective Relays
Accurate Impedance Based Fault Location Algorithm Using Communication Between Protective Relays
Abstract— The reactance method with fault resistance the faulty loop’s reactance, which is linearly proportional to
separation has been developed in order to determine as precisely the distance to the fault.
as possible the impedance of a fault loop in a transmission or
distribution power system line. This method has commonly been
used for impedance calculation in case of a single phase-to-earth
fault in diverse power system protection applications. New
developments in this area have shown that the extension of the
method to multi-phase faults is not only possible but also of
practical relevance. This research consists in an improvement of
this calculation method using data from both the own and the
remote line end. This approach uses communication between two Figure 1. Fault with transition resistance in a double side supplied line
measurement units e.g. protection relays, which have the
advantage of not requiring a precise synchronization with each
A faulty doubly in-fed line is first considered in the form of a
other. The additional time invariant parameters of the power
system, acquired by each device and transferred to the remote single-phase system (Fig. 1). For the short circuit, a purely
end, allow an exact computation of the fault reactance and fault resistive fault is adopted. If the faulty loop includes a fault
resistance. In this paper, the derivation of this novel approach as resistance RF, it is not possible to calculate the exact reactance
well as experimental results in a fault location application are value using only the measurements from one side A or B.
presented. Indeed, the unknown fault current IF is necessary for the
calculation. Applying Kirchhoff’s Voltage Law (KVL) to the
Keywords— Fault Location, Impedance Measurement, Power system from the point of view of side A results in (1), which is
System Protection, Transmission / Distribution Line the base to extract the fault reactance and resistance:
The compensation quantity and extension factor can further be ZA,0 mZL,0 (1-m)ZL,0 ZB,0
used to determine the fault’s resistance RF. Replacing the fault zero seq.
X Fault j
Im[e I A,1 I
*
A , Cmp
*
A, B ] (13)
RF (14)
Im[ I A,Cmp A,B e j I A,1 ]
*
A, B , 2 (12)
I F , Ph1 I F , Ph 2 I F I A, Cmp , 2 I A,Cmp ,0
A, B , 0 Figure 5. Meshed power system with fault on the line between busbars A and
B a) network during fault; b) sequence network; c) reduced sequence network
Since in case of a phase-to-phase fault, the zero sequence
current is zero, the formulation from (12) is still valid. The line data used in the computation of the compensation
For three phase faults, the positive sequence current and factors is available in the relay device. However, the source
voltage are used: impedances are not parameterized in common protection
devices. These network parameters can be computed using the
measurements made by the protection relays during the fault
transient. Considering the equivalent circuits in symmetrical Data exchange makes it possible to determine the system’s
components, it can be concluded that based on the measured state. Moreover, the parameter m (fault location) can be
voltages and currents, in case of the fault on the line, the real calculated using an iterative procedure. Equation (5) is divided
source impedance can be simply calculated: by the reactance per unit length x’, which is a constant
parameter of the line, in order to obtain the fault location.
U A, 0 U A, 2 Introducing Gauss’ method, (20) is obtained:
Z A,0 , Z A, 2 ,
I A, 0 I A, 2
sin Im[U A, Ph I A, Cmp A, B ( mn )]
* *
U A,1 (15) mn 1 ,
Z A,1 x ' Im[e j I A, Ph I A,Cmp A, B ( mn )]
* *
(16)
I A,1
m mn 1 if mn 1 mn
This method can also be used in meshed networks however in
that case, the calculated impedances do not reflect the real
source impedances. As a proof, the power system from Fig. 5a where is a condition for the last iteration step. With this
can be used. Each meshed system can be replaced by the condition, if iterations do not contribute to any improvement
system given in Fig. 5a, so that this network can be considered of the result, the fault location m is adopted. Considering (16),
as an equivalent for any meshed power system. Taking this it can be noted that after some reformulations, a quadratic
network into account in a symmetrical or superimposed form for almost all fault types can be derived as well. An
component representation, each sequence network can be analytic equation of the third order only appears in the case of
considered separately like shown in Fig 5b. As presented in a phase-to-phase fault with earth. The analytical solution of
Fig. 2-5 the connection type of the sequence network depends such an equation is much more complex than the iterative
on the fault type only. The meshed system can be reduced to approach. As a result, the iteration approach was chosen as
the system from Fig. 5c. with two busbars using the general solution for the implementation of each fault type.
commonly known wye-delta transform. During the reduction After a successful estimation of the fault location, the fault
process, a fictive parallel line without mutual coupling appears resistance as minor product is computed.
between busbar A and B. In order to prove that this parallel IV. EXPERIMENTAL RESULTS
line does not impact the calculation procedure for the
compensation factors and compensation quantities, the wye- After implementing the algorithm in protection devices,
delta transform can be used. It can be noted that the calculated tests were performed for different network structures and fault
impedances applied to compute the compensation factors types represented by simulation models. The parameters used
depend on the fault location. This does not limit the approach for the network model are typical for high voltage overhead
lines. The test environment, shown in Fig. 6, is made of two
presented in this paper. However, using the estimated source
test devices to which three phase currents and voltages are
impedances presumes that the fault occurs on the line between provided by current and voltage amplifiers [8], [9]. A
busbars A and B. communication interface without synchronization was
implemented between the two devices, enabling the data
III. ACCURACY IMPROVEMENT exchange. The fault locator function was triggered after the
pick up of the protection function [10], [11], for which
The compensation quantity introduced in section A-C distance protection was used.
corresponds to the fault current seen from side A and is
deduced from the measured values on this side (ZA,0, ZA,1 or
ZA,2). However, the compensation factor depends on the Device 1: m=59.9%
network homogeneity degree as well as on the fault location
m. Therefore, the compensation factors require an equivalent Device 2: m=39.7%
of source impedance from side B in symmetrical components
(ZB,0, ZB,1 or ZB,2), and the fault location m. The impedance
parameters are a priori unknown because they depend on the Current-Voltage Amplifier
short circuit power of the remote side and on the network
configuration, which are not available to the relay. However,
they can easily be obtained by implementing data exchange Voltage Amplifier
between both devices. This data exchange procedure offers
several advantages:
It makes network states available to each relay in
order to calculate the fault current. Figure 6. Test environment
It only requires the exchange of a limited number of
parameters. The behavior of the fault locator algorithm for various fault
It does not require synchronization of the exchanged locations has been tested for each fault type. As an example,
data, as opposed to other two-side based algorithms. the calculated fault location for a phase-to-earth, phase-to-
phase (without and with earth) and a three-phase fault are
plotted in Fig. 7 for locations every 5% of the fault line. The as the impedances calculated with the measurements from the
fault resistance is equal to 5Ω. The representation focuses on protection relays gave an equivalent of the meshed network.
several points, which present the greatest observed deviance.
8
As shown in Fig. 7, the maximum error attained is of 0.8%, Fault L1L2
Fault L2L3
although the simulated system contains significant load flow 6 Fault L3L1
(different short circuit power and phase shift between both
4
voltage sources from Fig. 1) and inhomogeneous network.
2
Error in %
0
-2
-4
-6
-8
0 20 40 60 80 100
Exact Fault Location (% of line length)
2.5
Fault L1E
2 Fault L2E
Fault L3E
1.5
0.5
Error in %
-0.5
-1
-1.5
-2
-2.5
0 20 40 60 80 100
Exact Fault Location (% of line length)
15
Fault L1L2
Fault L2L3
10 Fault L3L1
5
Figure 7. Calculated fault location determined with protection devices as a
Error in %
function of the exact fault location for each fault type L1E, L1L2, L1L2E and
L1L2L3 respectively 0
0
developed algorithm efficiently calculates the faulty loop’s
impedance in fault location applications. Successful
-1 experimental results were obtained, also when considering
-2 typical influent factors such as load flow, fault resistance and
-3
system homogeneity degree. A significant improvement in
precision of fault location is therefore achieved. The
-4 advantage of the algorithm is an elimination of the numerous
-5
0 20 40 60 80 100
aspects regarding synchronization accuracy and availability of
Exact Fault Location (% of line length) the stable communication interface between devices. The
weakness of the method is its dependency on the line
Figure 11. Calculated fault location determined with protection devices as a parameters, which can show through the residual factor k0 or
function of the exact fault location for each phase-to-earth fault – transposed the mutual coupling of the parallel line kM. The line geometry
line distirbuted parameters
and transposition schema can also influence the results of the
fault location. Moreover, the faulty loop must be provided to
For the transmission of power on long distances, transposed fault location algorithm in order to calculate the correct fault
lines are used. Depending on the voltage level and on the line location and fault resistance. Nevertheless, this method can be
length, different transposition schemas can be applied. In successful used in combination with other fault location
order to further investigate this method, a single line from the algorithms and in a lot of cases guarantees a very good
Mexican power system (from the transmission system operator accuracy.
CFE) was considered. This line has three main sections that
are transposed to each other. The line is fed in from both sides
with a heavy load. Different fault types with fault resistances
References
were simulated and tested, using a protection device as shown [1] T. Takagi, Y. Yamakoshi, M. Yamaura, R. Kondow and T. Matsushima,
in Fig. 6. The investigation results are presented in Fig. 8-9. "Development of a New Type Fault Locator Using The One-Terminal
Voltage and Current Data," IEEE Trans. Power Apparatus and Systems,
The line was modeled with concentrated parameters. As vol. 101, pp. 2892-2897, Aug. 1982.
shown in Fig. 8-9, the iterative algorithm (16) converges to the [2] L. Eriksson, M. M. Saha and G. D. Rockefeller, "An Accurate Fault
stable fault location value. Due to transposition of the lines, an Locator with Compensation for Apparent Reactance in the Fault
error on the fault location appears. It depends on the fault Resistance Resulting from Remote-End Infeed," IEEE Trans. Power
position, faulted phases and also on the fault type. This error Apparatus and Systems, vol. 104, pp. 424-436, Feb. 1985.
[3] M. M. Saha, J. Izykowski, E. Rosolowski, Fault Location on Power
results from line geometry. In case of a phase-to-phase fault,
Networks, London: Springer, 2010.
errors up to 8% were measured. For phase-to-earth faults, the [4] J. Izykowski, Fault Location on Power Transmission Lines, Wroclaw
observed errors were below 2.5%. The fault location errors Poland: Wydawnictwo Politechniki Wroclawskiej, 2008.
(relative values) are decreasing with an increasing fault [5] J. Izykowski, E. Rosolowski and M. M. Saha, "Locating Faults in
location. The reason for these errors is a parasitic effect, which Parallel Transmission Lines under Availability of Complete
results from the line’s asymmetry caused by the fault. This Measurements at One End," IEE Proc.-Gener. Transm. Distrib. vol. 151,
pp. 268-273, March. 2004.
leads to two unwanted effects: a) the fault model given in Fig. [6] C. Dzienis, Y. Yelgin, G. Steynberg and M. Claus, "Novel Impedance
2-4 in symmetrical components is only an approximation of Determination Method for Phase-to-Phase Loops," in Proc. 2014 Power
the fault because of the magnetic coupling between sequence Systems Computation Conf., pp. 1-7.
networks; b) the calculation of the source impedance with the [7] J. Blumschein, C. Dzienis, Y. Yelgin, "New design of distance
measured values not exact. An improvement of the result in protection for smart grid applications, " in Proc. 2015 XII Simposio
Iberoamericano Sobre Proteccion de Sistemas Electricos de Potencia.,
this case can only be achieved if the transposition schema and pp 1-7.
full coupling matrix is available in the protection relay. For [8] IEEE Guide for Protective Relay Application to Distribution Lines,
long lines, the influence of the capacitive currents and the fact IEEE Std. C37.230-2007, Feb. 2008.
that the line parameters are distributed must also be [9] Siemens, SIPROTEC Line Differential Protection with Distance
considered. The results of these tests are presented in Fig. 10- Protection 7SD5 – Manual, Siemens AG, Feb. 2011.
[10] G. Ziegler, Numerical Differential Protection – Principles and
11. It was assumed that the line is transposed. In this case,
Applications, Erlangen Germany: Siemens AG, 2012.
only a low deviation of the results is observed, compared to [11] G. Ziegler, Numerical Distance Protection – Principles and Applications,
the results obtained with the model with concentrated Erlangen Germany: Siemens AG, 2006.