6062 - Multi-Purpose Timer: Overview
6062 - Multi-Purpose Timer: Overview
Overview:
Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications,
Siren/Bell Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed
Release, Delayed Operate, Delayed Pulse and Pulser/Flasher. A new feature has been added which provides a momentary relay acti-
vation at the end of a desired timing cycle. This feature eliminates the need for having to use two (2) timers to achieve this function.
Specifications:
• 12VDC or 24VDC operation is selectable. • One (1) second momentary relay activation at the end of
• Quick and extremely accurate time range adjustment from the timing cycle (eliminates the need to use two (2) timers
1 sec. to 60 min. for this function).
• LED indicates relay is energized. • Built-in reset feature which cancels timing cycle.
• Form “C” relay contacts are 8 amp at 120VAC/28VDC. • Repeat (pulser/flasher) mode.
• Current Draw: Stand-by 3mA, Relay Energized 40mA. • Snap Track compatible (order Altronix model #ST3)
• Triggers via positive DC (+) voltage, dry contact closure, • DIN Rail Mount version available
or removal of contact closure. (order Altronix model #DTMR1).
• Selectable relay activation at the start or end of the Board dimensions: 3”L x 2.5”W x .75”H (approximate)
timing cycle.
Installation Instructions:
1. Mount 6062 in desired location/enclosure.
2. Set proper DC Input Voltage Dip Switch 3: 12VDC ON, 24VDC OFF.
3. Refer to Dip Switch Selection and Jumper Selection Tables for desired functions (e.g.: Timing, Trigger, Pulse)
4. Measure DC input voltage before powering device to ensure proper operation.
5. Refer to Terminal Identification Table and Typical Applications fig. 1 thru fig. 8. for desired wiring connections.
Note: When triggering via a N.O. (normally open), momentary or maintained trigger, connect the dry contact trigger to Pos (+)
and TRG terminals. When triggering via a N.C. (normally closed), momentary or maintained trigger, connect the trigger to Neg. (-)
and TRG terminals and install a resistor [for 12VDC - 2K (2,000 ohm) or for 24VDC - 4.7K (4,700 ohm)]
between the Pos (+) and TRG terminals (Fig. 8).
6. Enable the reset features:
- Cut J3 when power is removed the timer will reset and not re-trigger when power is restored unless a new trigger is applied.
Note: The closed trigger and delayed pulse options will not operate if the reset feature is desired.
Terminal Identification:
Terminal
Function/Description
Legend
Applying a positive voltage will activate timing cycle.
TRG
Trigger voltage range: 7-12VDC at 12 volt setting, 15-24VDC at 24 volt setting.
--- , + Connect 12 or 24VDC filtered and regulated voltage. Refer to Dip Switch Selection Table for voltage setting.
N.O., C, N.C. Dry form “C” relay contacts are rated 8 amp at 120VAC/28VDC.
6062 Typical Applications:
Fig. 1 - Timed Door Annunciator: Fig. 5 - Timed Door Strike:
NC
NC
OFF
OFF
4 3 2 1 4 3 2 1
+ +
CHIME Pos (+) and Neg (--)
C
ON ON
ON
ON
--- terminals constant
4
3
2
1
4
3
2
1
+ --- 12VDC or 24VDC
RELAY CONTROL
RELAY CONTROL
NO
NO
TRIG CONTROL
TRIG CONTROL
---
SEC. / MIN.
SEC. / MIN.
CUT J3 FOR RESET
12V / 24V
J2
J2
J3
J3
ON POWER-UP
ON POWER-UP
Door Strike
CUT J2 FOR DELAY PULSE
J1
+
Pos (+) and Neg (--)
+
CUT J1 FOR REPEAT
60
---
1
1
--
--
TRG
TRG
15
15
45
45
Normally Open Normally Open
Door Contacts Door Contacts
For this application Switch #1 and Switch #4 For this application Switch #1 should be in the OFF
should be in the OFF position. position and Switch #4 should be in the ON position.
Fig. 2 - Guard Tour Supervisory Timer: Fig. 6 - Timed Shunt for a Door: Use to bypass alarm contacts.
NC
NC
OFF
OFF
DIALER OR
4 3 2 1 4 3 2 1
TRANSMITTER
C
C
ON ON
Door Contacts
ON
ON
Protective
4
3
2
1
4
3
2
1
Circuit
RELAY CONTROL
RELAY CONTROL
NO
NO
TRIG CONTROL
TRIG CONTROL
SEC. / MIN.
SEC. / MIN.
CUT J3 FOR RESET
12V / 24V
J2
J2
J3
J3
ON POWER-UP
ON POWER-UP
CUT J2 FOR DELAY PULSE
J1
+ +
Pos (+) and Neg (--) Pos (+) and Neg (--)
+
+
CUT J1 FOR REPEAT
60
--- ---
1
1
--
--
TRG
TRG
15
15
45
45
Normally Open Normally Open
Switch Contacts Switch Contacts
For this application Switch #1 and Switch #4 For this application Switch #1 should be in the OFF
should be in the OFF position. position and Switch #4 should be in the ON position.
+
NC
NC
Closed Bell
OFF
OFF
4 3 2 1
Circuit
4 3 2 1
or
Siren
Zone on
C
C
ON ON
---
ON
Control Panel
ON
4
3
2
1
4
3
2
1
RELAY CONTROL
RELAY CONTROL
NO
NO
TRIG CONTROL
TRIG CONTROL
SEC. / MIN.
SEC. / MIN.
CUT J3 FOR RESET
12V / 24V
J2
J3
J3
ON POWER-UP
ON POWER-UP
CUT J2 FOR DELAY PULSE
J1
+
Pos (+) and Neg (--)
+
+
CUT J1 FOR REPEAT
terminals constant
Bell
12VDC or 24VDC
60
60
--- Output
1
--
--
TRG
15
45
45
For this application Switch #1 should be in the OFF position For this application Switch #1 should be in the ON position and
and Switch #4 should be in the ON position. Switch #4 is not used in this application.
Fig. 4 - Delay Timer: Use for Door Ajar Alarm, Delayed Fig. 8 - Closed Circuit Trigger Option:
Activation of Digital Dialer, Defrost Cycle Timer, etc...
+ Power
NC
OFF
--- Supply
4 3 2 1
+
Resistor
ON
ON
Normally Open
4
3
2
1
Triggering Device
RELAY CONTROL
NO
TRIG CONTROL
SEC. / MIN.
J3
--
ON POWER-UP
CUT J2 FOR DELAY PULSE
J1
+
Pos (+) and Neg (--) Closed
+
CUT J1 FOR REPEAT
terminals constant
Circuit
TRG
12VDC or 24VDC
60
---
Contact
1
--
TRG
15
45
For this application Switch #1 should be in the ON position For this application a resistor [for 12VDC - 2K (2,000 ohm)
and Switch #4 is not used in this application. or for 24VDC - 4.7K (4,700 ohm)] must be installed as shown
(resistor not supplied).