‘Manual No. 165-56380
BAYLOR
INSTRUCTION OPERATION
AND SERVICE MANUAL
FOR MODEL. 56380
« BATTERY CHARGER AND
SWITCHOVER UNIT
EQUIPMENT FURNISHED
BY
BAYLOR COMPANY
500 INDUSTRIAL BLVD.
SUGAR LAND, TEXAS 77478-2898
PHONE (281) 240-6111
FAX (281) 274-0426
6/98 REVISEDBAYLOR
NOTICE
This document is and contains confidential and trade secret
information of the Baylor Company. This Document is loaned
for limited purposes only, and remains the property of the
Baylor Company. It is to be returned upon request and in all
events upon completion of the purpose of the loan. Neither it nor
the information it contains may be reproduced, used, or
disclosed to persons not having a need to know consistent with
the purpose of the loan, without written consent of Baylor
Company.
ADDRESS COMMENTS TO:
BAYLOR COMPANY
500 INDUSTRIAL BLVD.
SUGAR LAND, TEXAS 77478-2898
TELEPHONE: (281) 240-6111
FAX: (281) 274-0426
PRINTED INU.S.A.SECTION 1
INTRODUCTION AND DESCRIPTION
SCOPE OF MANUAL
GENERAL DESCRIPTION
SECTION 2
PRESCRIPTION OF OPERATION
MAJOR COMPONENTS
2.1.1 BATTERY SWITCHOVER PANEL - P/N 56406
2.1.2 BATTERY CHARGER PANEL (P/N 56032)
2.1.2.1 ALARM CIRCUITS
2.1.2.2 CHARGING PROCEDURE
2.1.2.3 BATTERY CHECKS
2.1.3 DRILL FLOOR EMERGENCY STOP STATION
(P/N 53564)
SECTION 3
SPECIFICATIONS
GENERAL
BATTERY CHARGER AND SWITCHOVER UNIT
DRILL FLOOR EMERGENCY STOP STATION
GENERAL
BATTERY CHARGER AND SWITCHOVER UNIT4.3
4.2.1 MAIN POWER FREQUENCY SELECTION
DRILL FLOOR EMERGENCY STOP STATION
SECTION 5.
OPERATING INSTRUCTIONS
OPERATING PROCEDURE
5.1.1 Reset Procedures
SECTION 6
MAINTENANCE
BATTERY SWITCHOVER PANEL
BATTERY CHARGER PANEL
6.2.1 | CURRENT LIMIT CHECK
6.2.2 FLOAT VOLTAGE CHECK
6.2.3 EQUALIZE VOLTAGE CHECK
6.2.4 ALARM CHECKS
6.2.4.1 FIRING BOARD POWER ALARM CHECK
6.2.4.2 HIGH, LOW AND RECTIFIER FAILURE
ALARM CHECK
6.2.4.3 GROUND DETECTION ALARM CHECK
SECTION 7
PARTS AND SERVICE
GENERAL
PARTS AND SERVICE
RECOMMENDED SPARE PARTS - BATTERY SWITCHOVER PANEL
RECOMMENDED SPARE PARTS - BATTERY CHARGER PANEL
RECOMMENDED SPARE PARTS - EMERGENCY STOP STATION
ii
6-2
6-2
6-2
6-3
6-4
6-4BAYLOR
1.2
SECTION 1.
INTRODUCTION AND DESCRIPTION
SCOPE OF MANUAL
This manual provides information regarding the
installation, operation, troubleshooting and maintenance of
the BAYLOR Model 56360 Battery Charger and Switchover Unit.
This manual is divided into sections giving a narrative
description of the theory of operation, function of
controls, operating instructions, maintenance and service,
a parts and supplies list, applicable schematics, flow
diagrams, and major assembly drawings.
Operators are requested to read and thoroughly familiarize
themselves with this manual before attempting to operate
the equipment.
GENERAL DESCRIPTION
The Baylor Battery Switchover Unit provides a simple and
safe method of interfacing a Brake Control System with a
bank of rechargeable batteries and a battery charger used
as a source of backup DC power to the Eddy Current Brake.
The 56032 Battery Charger is designed to charge the battery
bank used for emergency backup power supply to an Eddy
Current Brake. The charger consists of a main power
transformer, an SCR bridge, a firing board, alarm circuits,
and a display panel integrated together in a steel
enclosure manufactured to NEMA 12 standards.
The system is designed to operate on 50/60 Hz single phase
120/240 Volts AC. Two power ranges are available on the
transformer output. Low power range is for charging
battery banks of 240 Volts DC or less. The high power
1-1BAYLOR
1.2
GENERAL DESCRIPTION (Cont! d)
range is for charging battery banks of 240 to 325 Volts DC.
In all cases voltage output is controlled by the firing
board. In addition, the firing board also limits the
output current to 5 amps.
The alarm circuits installed in the Battery Charger detect
high voltage output, low voltage output, SCR failure,
firing board loss of power, and DC power output grounded.
The Battery Charger contains a second transformer which
provides control voltage to the firing board, alarm
circuits, and indicator lights on the display panel. An
indicator light is provided on the display panel for each
of the above mentioned alarm conditions. In addition, the
display panel contains voltage = output'_— control
potentiometers for float and equalizing operations, as well
as panel meters for displaying the voltage and current
output of the Battery Charger. A circuit breaker is also
mounted in the display panel to provide short circuit
protection to the AC input circuits of the Battery Charger.
It also functions as the on/off switch.
The battery disconnect switch is a heavy duty, two pole,
circuit breaker used to manually disconnect the battery
bank from the battery transfer unit. The fuse in the
battery circuit is sized to protect the battery cables and
limit available battery fault current.
The disconnect switch is rated for 250 volts DC at 125
amperes.
An auxiliary switch is installed to be connected to the
battery transfer logic circuitry.
1-2BAYLOR
GENERAL DESCRIPTION (Cont! d)
If the switchover panel (DWG 56406) is revision “C” or
higher, the following applies. A shunt trip is installed in
the battery disconnect, which can be remotely shunt tripped
using a contact closure that is rated for 120 vac. It is
only used for emergency total shutdown condition. Also
included is a timed shunt trip, which senses the battery
supply monitor relay (CR1)and the de-energization of C1. When
CR1 is energized and C1 is de-energized, the timer (TDR2)
starts timing out. The timer has a range that can be adjusted
up to 10 minutes. Once timed at the timer’s set point, it
shunt trips the battery disconnect. This will prevent the
batteries from draining down to a nonrecoverable recharging
condition. The recommended set point on the timer is 5
minutes, which should provide adequate time to bring the
drawworks load to a stop and set the drill pipe into the
slips. As soon as conditions permit, the system can be
reset using the reset procedure in Section 5.1.1.BAYLOR
SECTION 2
DESCRIPTION OF OPERATION
MAJOR COMPONENTS AND THEIR THEORY OF OPERATION
BATTERY SWITCHOVER PANEL
The 56406 Battery Switchover Panel has been designed to
give a maximum of trouble-free operation in the rugged
drilling rig environment with a minimum of maintenance
required.
A magnetic DC contactor is used to connect a bank of
rechargeable batteries to the Eddy Current Brake when
either one of the following occu:
1. Loss of AC power to the primary Brake Control unit.
2. Upon energizing the Drill Floor Emergency Stop
Button, by the Driller.
Input AC power to the primary Brake Control unit is
monitored by providing an input at fuses F3, F4 and FS from
the Brake Control unit 186/240 volt AC power input. Loss
of power is sensed by relays MR1, MR2 and MR3. Upon loss
of power MR1, MR2 or MR3 is de-energized which allows its
contacts 1 and 7 to open, in turn de-energizing normally
closed contactor Cl. When contactor Cl closes full battery
voltage is applied to the brake and the "BACK UP IN USE"
lamps are illuminated on the Unit’s front door and on the
Drill Floor Emergency Stop Station. Depressing the
Emergency Stop Pushbutton at the Driller's position on the
rig floor accomplishes the same function by breaking the
path of coil voltage to the contactor C1.BAYLOR
2.1.2
BATTERY SWITCHOVER PANEL (Cont'd)
The reader will note, upon examination of the logic and
wiring diagrams, that the positive output of the primary
SCR unit and the positive terminal of the battery bank are
always connected to the positive brake terminal thru
steering diodes which isolate the primary Brake Control
unit from the battery bank. Upon closure of the DC
contactor Cl, the battery bank is effectively in parallel
with the primary Brake Control. Therefore regardless of
the output voltage level of the primary Brake Control unit
the highest voltage present at the point of connection of
the steering diode cathode terminals will be present at the
brake after the DC contactor closes.
After an operation of the transfer unit the system is reset
by opening the battery disconnect switch. Disconnecting
battery voltage from the unit is sensed by Battery Supply
Monitor Relay CR-1, When battery voltage is removed, CR-1
is de-energized which starts the time delay relay TDRI
cycle. TDR1 should be set to provide a time delay while
the brake field is collapsed thru the free wheeling diode
and contactor Cl which is still in the closed position.
Upon completion of the time delay, contactor ci is
energized (opened) and the "CLOSE DISCONNECT" lamp will be
illuminated. Upon closure of the battery disconnect
switch, Ri-1 will be energized, which in turn extinguishes
the "CLOSE DISCONNECT" lamp and illuminates the "SYSTEM
READY" lamp. The system is now ready for use.
An isolation transformer is provided in the battery
transfer unit to accept a the customer furnished, stable,
source of 120/240 VAC power to operate system logic. Be
sure and select the correct voltage during installation as
an improper voltage setting may damage components.
2-2BAYLOR
2.1.2
BATTERY CHARGER PANEL - P/N 56032
The 56032 Battery Charger provides a means for charging the
battery bank used as emergency backup power for a Baylor Eddy
Current Brake. The voltage output of the Battery Charger is
adjustable to match the voltage requirements for charging the
battery bank. The voltage level is adjusted by moving the
float or equalizing voltage controls on the display panel.
Float voltage is defined as the voltage level required to
maintain the charge of the battery bank. Equalizing voltage
is defined as the voltage level necessary to recharge all of
the cells in a battery bank to the same volts per cell. A
battery bank that has been discharged to a level of 60% to 708
of the rated voltage per cell can be recharged in the equalize
mode for 6 hours maximum. This will insure the full charging
of all cells in the battery bank. The Battery Bank must be
maintained on float charge and should be fully recharged
within 24 hours after any discharge. output current is
limited to 5 Amps. in either the float or equalize operation.
Do not attempt to recharge a battery with an
open circuit voltage less than 1.0 volt per
cell. Hydration shorts may be present, causing
the battery to be non-recoverable.
2.1.2.1 ALARM CIRCUITS
Alarm circuits are integrated into the Battery Charger. These
alarm circuits detect high voltage output, low voltage output,
SCR failure, firing board power failure, and DC output
grounded. Alarm conditions are indicated by lights on the
display panel. In addition, a dry set of contacts are
available for interfacing the general alarm into a customer
supplied alarm annunciation system or brake monitor.
2-3BAYLOR
2.1.2.2
CHARGING PROCEDURE
If the battery bank has been engaged to power the Eddy Current
Brake, or a new battery bank is being charged for the first
time, the following charging procedure should be followed:
1)
2)
3)
Carry out the reset procedure for the battery switchover
system. Make sure that the battery bank is disconnected
from the Eddy Current Brake.
With the float/equalize timer switch in the float
position read the current and voltage as displayed on the
ammeter and voltmeter mounted on the display panel.
If the Battery Charger voltage is near the float voltage
setting ( Reference SECTION 6 "MAINTENANCE") and the
current is less than 2 Amp., leave the Float/Equalize
timer switch on the "Float" position.
If the ammeter on the display panel indicates that the
current is greater than 2 Amp., turn the Float/Equalize
timer knob for 6 hour equalize charge. The voltage level
indicated by the voltmeter on the display panel should
rise and the current, as indicated on the ammeter mounted
on the display panel, should increase. If the battery
charger is current limited there will not be any increase
in voltage or current. After the 6 hour charge time the
battery charger voltage will switch back to the "Float"
WARNING !
The “Equalize” setting of the Battery Charger
is not intended for long term use. If the
Battery Charger is left in the “Equalize”
setting for a period of time greater than 6
hours, damage to the cells of the battery
bank could result.
_——————
2-4
condition.BAYLOR
2.1.2.2 CHARGING PROCEDURE (Cont’d)
4)
If the battery bank is not quite fully charged, the
Battery Charger will continue to trickle charge the
battery bank on the "Float" setting.
2.1.2.3 BATTERY CHECKS
Periodic checks of the ammeter and voltmeter on the
display panel of the Battery Charger should be performed
to insure that the unit is functioning properly. Most
battery manufacturers recommend periodic checks of the
"Float" voltage of a battery bank on a volts per cell
basis. If one battery in the battery bank exhibits
“Bloat" voltage readings that are low, it may be
necessary to charge the bank at “Equalize" voltage for a
period of time to insure that all cells are fully charge.
When performing this operation, be sure and follow the
battery manufacturers recommendations. (See SECTION 9.)
DRILL FLOOR EMERGENCY STOP STATION P/N 53564
The Drill Floor Emergency Stop Station provides the Driller
with a means of manually activating the Model 56380 Battery
Switchover Unit in emergency situations or for test
purposes.
The Drill Floor Emergency Stop Station consists of a
mushroom head pushbutton and a red lamp installed in an
enclosure certified for use in a Class 1, Division 1, Group
c & D hazardous area.
2-5DRILL FLOOR EMERGENCY STOP STATION (Cont/d)
When the Driller firmly depresses the large mushroom
operator on the pushbutton, the battery switchover unit is
activated connecting full battery potential to the Eddy
Current Brake Magnet Coils.
The red "BACKUP IN USE" is illuminated when the battery
switchover unit is activated.GENERAL
The Model 56380 is designed and manufactured to meet the
special requirements of land and offshore drilling rig
service.
BATTERY CHARGER AND SHITCHOVER UNIT
Battery Bank Voltage (Max.). . . .
Battery Rating . 2...
sos ss +. 288 volt De
see es 40 amp, at 20 min.
to 1.75 V.P.c.
Brake Control Voltage Sense . ... . . 186/240 volt AC,
3 phase,
50/60 Hz
Customer Furnished Supply Feeder . . . 120/240 volt ac,
(Battery Charge Panel 20A/10A) 1 phase,
(Battery Switchover Panel 10A/5A) 50/60 Hz
DC Contactor Rating»... ..... 2... 110 amp DC
DC Contactor Coil Volts .......... . 120 volt AC
Max. Charger Current ...............5 amp
Battery Charger Float Voltage .... . . . 270-272.4 vde
Battery Charger Equalize Voltage . . . . . 280-282.4 vde
Enclosure Type... 2... 2. ....... . NEMA12
Cable Entry... ......... 2... Top or Bottom
DRILL FLOOR EMERGENCY STOP STATION
Emergency Stop Pushbutton . . .. 1N.0., 1 N.C. Contact
rated at 6 amp, 120
volt AC
"BACKUP IN USE" Lamp... . ... . . 120 volt AC, RED
Enclosure... 2... 2... Cast aluminum
3-1SECTION 4
INSTALLATION
GENERAL
The Battery Charger and Switchover system has two
components that require installation:
* Battery Charger and Switchover unit
* Drill Floor Emergency Stop Station
Baylor Drawings 56409, and 56008 detail SCHEMATICS for the
system. Also, see SECTION 8 for customer cable detail
connections.
BATTERY CHARGER AND SWITCHOVER UNIT
The Battery Charger and Switchover Unit should be installed
in an upright position against a wall or bulkhead using the
two mounting channels provided. There should not be any
restriction to air flow at the top or bottom and the
cabinet should be mounted as far away as possible from any
heat producing sources. The cabinet should be installed in
@ clean, dry, non-hazardous atmosphere such as the air
conditioned SCR house or switchboard room.
THE BATTERY CHARGER AND SWITCHOVER UNIT
SHOULD NOT BE INSTALLED IN A HAZARDOUS
AREA SUCH AS THE DRILL FLOOR
Provisions are made for top or bottom cable entry into the
enclosure.
4-1BAYLOR
4.2.1
MAIN POWER FREQUENCY SELECTION
If the AC power to the Battery Charger is 50 Hz, insure
that the jumper at JU8 is in the 50 Hz position on the
firing board. This is accomplished by installing a jumper
between points 1 and 2 of JU8. For 60 Hz power the jumper
at JU8 should be in the 60 Hz position of the firing board.
This is accomplished by installing a jumper between points
2 and 3 of gus.
DRILL FLOOR EMERGENCY STOP STATION
The Drill Floor Hmergency Stop Station should be installed
on the Drill Floor within easy sight and reach of the
Driller. Two mounting ears for 1/4 inch bolts are provided
at the rear of the enclosure. Mount the enclosure to allow
cable entry from the bottom. Always use cable glands or
fittings appropriate for hazardous area.
4-2W ka FP
SECTION 5
OPERATING INSTRUCTIONS
OPERATING PROCEDURE
The Baylor Model 56380 Battery Charger and Switchover Unit
provides a means of interfacing a bank of rechargeable
batteries, that are used to backup the primary Brake
Control System, in the event of an AC power loss or in an
emergency.
In normal operations the Eddy Current Auxiliary Drawworks
Brake is powered by the primary Brake Control unit. The
"SYSTEM READY" lamp on the Battery Charger and Switchover
Unit front door should be illuminated and the Battery
Disconnect Switch should be closed. The battery bank
should be charged and ready for use.
In the event of a loss of power to the primary Brake
Control unit, contactor Cl in the Battery Charger and
Switchover Unit will close automatically, connecting the
Battery Bank voltage to the Eddy Current Brake magnet
coils. At this time the "BACKUP IN USE" lamps, located on
the Battery Charger and Switchover Unit front door and on
the Emergency Stop Station, will be illuminated.
On BRAKE MONITOR SYSTEMS only (Models 1025, 1040, 2025, or
2040) there is a throttle mismatch relay (R3 or K3) if an
error is detected, it will open a set of contacts on R3
that breaks the circuit to the coil of Contactor (C1).
Contactor (Cl), on the battery switchover panel will de-
energized. This connects the battery bank potential to the
Eddy Current Brake. Also, at this time the “BACKUP IN USE”
lamps, located on the Battery Charger/Switchover Unit and
Emergency Stop Station, will be illuminated.: BAYLOR :
5.1
5.1.1
OPERATING PROCEDURE (Cont/d)
After the drawworks load has been brought to a stop and the
drill pipe is set in the slips, the following reset
procedure should be accomplished:
RESET PROCEDURE
1. Return AC power to the primary Brake Control unit.
2. Open the battery disconnect switch.
3. After approximately one minute the "CLOSE DISCONNECT"
lamp, on the Battery Charger and Switchover Unit, will
be illuminated.
4. Close the battery disconnect switch and note that the
“SYSTEM READY" lamp has been illuminated.
5. The system is now ready for use.
|THE SYSTEM SHOULD BE RESET AS SOON AS SAFE.
In the event of a drill floor emergency, the Battery
Charger and Switchover Unit can be operated, upon demand,
by depressing the emergency stop push-button, located on
the drill floor emergency stop station. As soon as
conditions permit the system can be reset following the
above reset procedure.
5-2BAYLOR
6.1
SECTION 6
MAINTENANCE
BATTERY SWITCHOVER PANEL
The Battery Switchover Unit should not require any
maintenance other than a periodic inspection for loose
terminals and broken or damaged wires.
ANY INSPECTION OTHER THAN OPERATIONAL |
CHECKS SHOULD BE PERFORMED WITH POWER]
REMOVED.
On a routine basis the entire system should be tested, to
assure correct operation, using the following procedure.
1. Remove AC Power from the primary Brake Control Unit by
opening the circuit breaker on the transformer
primary.
2. Note that system transfers to battery power.
3. Reset system following procedure in Section 5.1.
4. Operate Emergency Stop Pushbutton on the Drill Floor
Emergency Stop Station.
5. Note that system transfers to battery power.
6. Reset system following procedure in Section 5.1.BAYLOR
ABOVE TEST SHOULD BE PERFORMED DURING LOGGING OR
OTHER OPERATIONS NOT REQUIRING USE OF THE EDDY
CURRENT BRAKE, AS ESTING WILL PARTIALLY
DISCHARGE BATTERY BANK. ALWAYS NOTIFY DRILLER
THAT TESTING IS IN PROGRESS.
6.2 BATTERY CHARGER PANEL
The 56032 Battery Charger is simple in design and does not
require regular maintenance. It is recommended that the
current limit and alarm settings be checked every six months.
6.2.1 CURRENT LIMIT CHECK
Step 1 Make sure that the battery bank and AC input power are
properly connected to the battery charger.
Step 2 The current limit can only be set if the battery
it charger is delivering its maximum rate of charge.
Adjust potentiometer R11 (counter clockwise lowers the
current limit)on the VRCLIP-1 board to limit the
maximum current to 5 Amp.
6.2.2 FLOAT VOLTAGE CHECK
The float voltage setting can be checked by placing
the Float/Equalize timer switch in the "Float"
position and reading the voltage from the voltmeter
mounted on the display panel. Since most Baylor
Brakes utilize either a 240 Volt DC or a 325 Volt DC
battery banks, "Float" voltage settings, for these two
common battery bank voltage levels, are listed below:
BATTERY BANK | FLOAT VOLTAGE
VOLTS Dc VOLTS DC @ 75°
325 365
240 272
6-2BAYLOR
6.2.2
6.2.3
FLOAT VOLTAGE CHECK (Cont'd)
If the ambient temperature is not 75°F consult the Battery’s
Field Service Manual for recommended float voltage setting,
See DWG. #BTD-177.
If the "Float" voltage setting is not correct, adjust the
"Float" potentiometer mounted on the display panel until
the correct voltage is displayed on the voltmeter mounted
on the display panel.
EQUALIZE VOLTAGE CHECK
The "Equalize" voltage setting can be checked by moving the
Float/Equalize timer switch off of the "Float" position.
This will switch to the "Equalize" position. Read the
voltage from the voltmeter mounted on the display panel.
Since most Baylor Brakes utilize either a 240 volt DC or a
325 volt DC battery banks, "Equalize" voltage settings for
these two common battery bank voltage levels are listed
below:
-—— eae
BATTERY BANK | EQUALIZE VOLTAGE
voLTs pc VOLTS DC @ 75°F
If the “Equalize" voltage setting is not correct, adjust
the "Equalize" potentiometer mounted on the display panel
until the correct voltage is displayed on the voltmeter
mounted on the display panel.
6-3The following alarm checks, must be performed with the
DC output to the battery charger disconnected from the
battery bank. This can be accomplished by removing the
two knife switch blocks that are located on the rear
wall on the center right side. Caution must be taken
because there is still 200 to 290 Volt DC level on both
sides of the knife switch blocks while performing these
checkouts.
6.2.4.1 Firing Board Power Alarm Check
Place Circuit Breaker (CB1) in the “OFF” Position and remove
fuse F2. After the fuse has been removed from the fuse
holder, turn Circuit Breaker (CB1) to the “on” position.
The firing board alarm light should activate, as well as the
low voltage, general alarm and rectifier failure alarm
lights. Place Circuit Breaker (CB1) in the “OFF” position
and replace fuse F2. Turn Circuit Breaker (CB1) on. The
firing board alarm light should not activate.
6.2.4.2 High, Low, and Rectifier Failure Alarm Check
Insure that the Float/Equalize timer on the display panel is
in the “Float” position. Use the “Float” potentiometer to
adjust the output voltage of the Battery Charger to the
levels listed below. For accurate readout of the Battery
Charger output voltage, it is recommended that a voltmeter
be connected to the output of the Battery Charger. This can
be accomplished by inserting the red voltmeter lead in the
red positive test point on the display panel and the black
voltmeter lead into the black negative test point on the
display panel. The various alarms should activate at the
alarm “ON” voltage and deactivate at the “OFF” voltage for
6-4BAYLOR
6.2.4.2 High, Low, and Rectifier Failure Alarm Check (Cont! d)
each alarm listed below. If incorrect operation is
observed, adjust the appropriate potentiometer on the 56038
alarm board as listed below.
CAUTION
Use care in making adjustments since surrounding
components are at a high voltage and can cause
electrical shock.
Settings are listed for 240 and 325 Volt DC battery banks.
240 VOLT BATTERY BANK
(ALL READINGS ARE VOLTS DC)
ALARM ALARM ON ALARM OFF ADJUST POT ON
VOLTAGE VOLTAGE PCBH56038
HIGH DC VoLTS 288 286 Re
LOW Dc VOLTS 235 237 RO
RECTIFIER FAIL 215 217 R1O
325 VOLT BATTERY BANK
(ALL READINGS ARE VOLTS DC)
ALARM ALARM ON ALARM OFF ADJUST POT ON
VOLTAGE VOLTAGE PCBH56038
HIGH DC VOLTS 382 380 RE
LOW DC VOLTS 295 297 RO
RECTIFIER FAIL 275 277 R10BAYLOFfrF
6.2.4.2 HIGH,LOW,AND RECTIFIER FAILURE ALARM CHECK (Cont'd)
To test the rectifier failure alarm, adjust the "Floats
poténtiometer to drop the voltage below the “Low pc
volte" alarm set point, The "Low DC Volte" alarm will
come on at the "Low DC Volts" alarm set point reading.
The "Low DC Volts" alarm will stay "ON" until the "Float"
potentiometer is adjusted to a point that raises the
Battery Charger output voltage above the "Low DC Volts"
alarm "OFF" voltage setting. The activation of any alarm
will cause the general alarm to activate.
Before continuing, readjust the "Float" potentiometer on
the display panel so that the output of the Battery
Charger is at the correct "Float" voltage per SECTION
6.2.2.
6.2.4.3 GROUND DETECTION ALARM
Attach a jumper between groumd and TB9-2, the negative
side of the Battery Charger output. The ground alarm and
the general alarm should activate. If the ground alarm
does not activate, adjust potentiometer R19 on the 56036
ground detection board until an alarm is given.
CAUTION
Use care in making adjustments since
surrounding components are at a high voltage
and can cause electrical shock.
Remove the grounding jumper and the ground alarm should
go away. No grounding alarm should be given. It may be
necessary to fine tune the ground detection point by
adjusting potentiometer R19 on the 56036 ground detection
board to insure that the ground alarm activates and
deactivates as it should.
6-6BAYLOR
6.2.4.3 GROUND DETECTION ALARM (Cont‘d)
Repeat the procedure for the positive side of the Battery
Charger output using TB9-1 as the grounding point and
potentiometer R14 on the ground detection board for
adjustment. It should take approximately one minute to
activate the positive ground alarm.
Use care in making adjustments since surrounding
components are at a high voltage and can cause
electrical shock.
DaSECTION 7
RARIS AND SERVICE
7.1 GENERAL
The recommended spare parts and supplies for the Control
System are provided in the following tables.
7.2 PARTS AND SERVICE
Parts and service are available from the factory:
BAYLOR COMPANY
500 Industrial Blvd.
Sugar Land, Texas 77478-2898
Telephone: (281) 240-6111
Fax: (281) 274-0426
Or from the following Baylor Service Centers:
BAYLOR COMPANY LTD. ABB SERVICES AS
Unit 13 Robert Leonard ctr. Torneroseveien 4,
Howemoss Drive, Kirkhill P.O. Box 173
Industrial Estate N-4033 FORUS
Dyce, Aberdeen Norway
Scotland
Telephon 44 1224 773555 Telephone: 47 51 678022
Telefax: 44 1224 773445 Telefax: 47 51 678683
WATT & AKKERMANS PTE. LTD.
No.2, Pioneer Sector 3,
Jurong, Singapore 2262
Telephone: 65 861 4444
Telefax: 65 861 2054
71: BAYLOR
7.3 RECOMMENDED SPARE PARTS - BATTERY SWITCHOVER PANEL
QUANTITY
OR HOHE He hee
PART NUMBER
6525~40-0056
6525~42-0022
6425-70-0038
6425-05-0007
6425~-05-0016
6500~18-0001
6525-25-0152
6525~-25-0134
6525~25-0129
6425-05-0096
6450-95-0088
6450-75-0181
DESCRIPTION
Contactor, 2 Pole (C1)
Auxiliary Contact Kit (C1)
Time Delay Relay (TDR1)
Relay, 3 PDT, (MR1, MR2, MR3)
Relay, 4PDT, (RL1)
Diode (Di, thru D7)
Fuse, 125 amp (F-B)
Fuse, 2amp 250 volt (F1)
Fuse, lamp 250 volt (F2, F3,
Relay, DPDT (CRI)
Resistor, 12K 5W (R1)
Resistor, 1.2K (RA,RB, RC)
7.4 RECOMMENDED SPARE PARTS ~ BATTERY CHARGER PANEL
QUANTITY
10
10
1
1
i
10
1
7.5 RECOMMENDED SPARE PARTS - EMERGENCY
QUANTITY
1
1
PART NUMBER
6525-25-0134
6525-25-0064
6725-12-0009
56038
56036
6375-10-0053
6500~33-0049
PART NUMBER
6525-67-0015
6375~29-0008
7-2
DESCRIPTION
Fuse, 2A
Fuse, 5A, 600V
Firing Board
Alarm Board
Ground Board
Lamp, Display
Module, Dual SCR
STOP STATION
DESCRIPTION
Pushbutton, Explosion Proof
Lamp, Red, Explosion ProofDESCRIPTION
Outline and Dimensions ... .
Cable Diagram Model 48999 Brake
Customer Connect Diagram . . .
Cable Diagram, 2025A .....
Cable Diagram, PWM... 1.
Cable Diagram, 1025......
Interconnect System Diagram, Brake Controller
Wiring Diagram, Customer Interconnections
Assembly, Brake Power Backup/Switchover .
Bill of Material... .
Assembly, Panel Battery Switcho'
Bill of Material... . .
Wiring Diagram, Battery Backup/Switchover
Logic Diagram, Battery Backup/Switchover
Assembly, Panel Battery Charger System
Bill of Material... .
ver
8-1
54968
56954
56955
55789
56435,
56496
56484
56404
56380
56380
56406
56406
56408
56409
56032
56032BAYLOR
DESCRIPTION DRAWING NUMBER
Assembly, Status Panel Unitzed system... ........ 56318
Bill of Material... 2.1... ........ B/W 56318
Wiring Diagram, Status Panel United System... . 2... 56377
Assembly, Heat Sink... . 6... eee 86084
Schematic, Battery Charger... 1... ........ . 56008
Wiring Diagram, Battery Charger Panel fee ee ee ww . 56006
ASSEMBLY AND SCHEMATIC, GROUND DETECTION PCB tote ew we . 56036
ASSEMBLY AND SCHEMATIC, ALARM CONDITION PCB . soe ee ee - 56038
Assembly, Emergency Stop Control ............ . 53564
Bill of Material»... 2... LL... Bs 53564
8-2\ DRL FLOOR.
\ OrALERS coNTRAL
SAEE AREA ' SOR BRAKE CONTROL we, 70
| sees 9
aac 1 es
490/240 VOL, TOR, SP, 59/6082 {
'
BATTERY TRANSFER
unt
i soe se
ASST 156320, | EMERGENCY STOP
AL DUNGEONS AE OMS WSS Ong SonED
oae/oup seoouren tie i a
ee paar anes i FE S| SEVERE
Sean wena meee ure tear
Seaman eeacnemesremanefale alee ge
/
=
<2 & =|
[
| snpee
| == oe
= sreeSAFE AREA DRILL FL005
AC INPUT POWER ‘SCR ASSEMBLY
sees wa sm 9 72 le
i : =
s— dea oO
ae
ORMLERS CONTROL
“ASSEMBLY
ogy aes
‘Sn
POWER SELECTOR
SWITCH ASSEMBLY
i
LODY CURRENT BRAKE
NOTE: aa _ “ee
O- wo re eS fe
@ = IrewuLy MRED aie rf
eects a
:
| reaper 3 =z
exeree eet amraneemem remem
| [ees
1 Savas,
gg ate ane
Fastouh ave Pha
sil 6 |”
a3
doors ThalaPART No.
DRUL FLOOR
4 CONDUCTOR No.4. ANG FOR
7838. & 7040 BRAKES
2040/10 Aue
2AOVRC/S A
NOTE: AL SYSTENS 50/60 Hz1 : ial beieedetscaidenchessuuneussers 77
Totnes aa
[Le 1S,
| eee
‘mv cxf oma ¢ J ee
J
4 —sun:
ens 9 me ce mw as
Ine Poe BE sar Re ove ee, "Wont Co
ey ee oe
reoncjuamae ‘eome/zaoac 186YAG/2AOAC I
10/5 AMPS: 20/10 AMPS je
BATTERY SWITCHOVER BATTERY CHARGER VOLIAGE SENSING
CONTROL PANEL INPUT POWER
tam raw famat
om Be fo cu I392 ‘one
wR0d 183%
sze09saue
dou isa
g005s*
66/66/66 00/00/00 NK 4 3 00°F 000° sss go NoTawutaino0a soNausage spawasay
56/66/66 £6/61/2 NK GWG 000°T ooo'r == T Loowntw A0ods Wr i5au "H00KG 000~s3-0089
86/66/66 e6/6t/t NA WS 00°F ooo°r «=» 6}_—S sD SKS BENEWHD GUI ‘SOVLOSE ss095
auwa 30 9S WA wxoWa XTaWASSW “ON AY 4 Norzaraosaa WaGHAN neve
auatosao aTiogisa aouaazaza go uinvasa aa Uark Bae KIO WELT O
saa a
66/e0/e :0oa ESV Jo Siva
sejeye
‘qWiia ON. 093
Garazsswioua — tanows 3d09 Ss¥I9
areregs 7 aswa1ae #1300H
b 7g anaaw TWNTS “jneaw SKS NSDNWHO LING TaNWa ‘ASSW 1ASH 0 1gG00d0 e095
‘Sif8
z Se “mH “ema razo37a © 900e —_gaoD SsWIy
tis bg ; SENENOSHOO_"¥03
66/e0/8 40 sw
ieriaiw 20 77a sees "one ‘ant
ANWGHOD BOIRYE SWEVLVGH' Z'007'IT
aot 10N awa86/86/65 £6/12/1 o 0 00's o00'ze © sy © oatvyt~o2 woxoannoo ‘zayoos stoo-es-s219
6766/68 €6/te/1 seo 8 ‘48 SNTMNE ura ¥ ona "woDaNROD ous0=t0-S219
86/66/55 £6/02/1 se 0 13 98 © oMWoe-or mzaet Sata “uORDENNOD SevO-T0-Sc59
66/66/65 86/t2/t ec'te 09 [238 F DeAgOs NOs Sata ‘WozoENHOD OSt0-10-S459
Screc/ee ce/te/t wo 8 "yyy oT suraur'nra'a ona ‘woIDaNnoo set0-T0-s219
56/66/66 £6/80/T TAoH 98 aeeeHeeteetees ‘SHUD99 AON “BOLSTEVA St00-0.-0s99
86/66/66 £6/80/T o 8 "23 FT aaN Gow/t x D18/s ey /UaDvES 9250-89-s219
56/66/66 £73071 oO cy 0¥ «WE BSU/H Guvod ONTUTA God. Asse Sooo-es-sez9
56/66/66 96/40/ ware 8 "3 6e taoos ox Sode: wan “yG0TE e000~20-9419,
Se/eeree 86/0077 Tete 6 eG EG outs Soap huss Gore ecoodoe-sit9
66/66/66 €6/80/T OTe. oO o v ae ¥ dS 9t/tT sode Weas. ‘xOOTE £200-02~-92T9
een
se/ce/ss es/eo/t ‘erez’es © 0 “© ek as 91/6 sods Muay ‘yo0Te s200-02-9219
sereesee £6/90/3 38 8 "8 © F ona oansost canon? “WorroWeND Stro-or-sers
Seree/ee 86/8027 o 8 i} £6} Wouswaeo WOrNqNETAD. ‘aNeTD y000=2e-0089
86766/66,66/204 wre 8 oT 8 Sanve2°aNoHD Mana’ -“Weax, evoo-de-0099
S6re6/eg e6/8078 we 8 + te vt “aoee oveveet i ‘F¥oo-gs-0099
85/66/66 00/00/00 ° 8 me teecee tettit 2£00-40-069t
Sereeres 96/90/9 o 8 reteset SE00-01-0691
55/66/66 96/50/9 ° 8 sar 28 eb00-vo-oeat
86766766 00/00/00 ° 8 ve $ ss. se INT 'aauswiniogT £200-1r-069t
8766766 00/00/00 2 6 pee Ss az~Dungt-0/e NaH “EON e100-82-025T
86766766 00/00/00 o 8 oe ee ‘$5 aNQ¢e~O XH, LAN S200-82-008t
86/66/68 09/00/00 o 8 rn ‘$8 ohnze-9 aH /EnN eeoo-se-ozet
86/66/66 00/00/00 o 8 eat ss a/e x te-orw /SHid 000-909-2452
Seresree Se/40/9 o 8 ort sSv/ier'x tecag ‘Shi o¥00-90-6082
56/66/66 00/00/00 ° 8 “at ss 2/t x 26-88 ‘Sqn ‘o0o-s0-t192
56/66/66 66/80/8 ° 6 fe cetees tet my woz 48 401 “WoLsTsaE ¥050-S6-0599
56/86/66 00/00/00 o 6 i Se t/e x ee-99 shite 3000-30-co¥2
e6resree ee/eore 8 Poo 8 Stes som oa’ “agora S800-0r-0089
&6766/66 00/00/00 m2 0 seat re te str/oez nose Tost “aMax Vro0-08-0059
86/66/65 00/00/00 5 6 + oF @o Suits Svait ‘assy
6/66/66 00/00/00 of ‘8 GT cue norsraNoo MEeIY cod 'LE5Y
s67e6/s6 00/00/00 0 8 } 8 «ST Gavoe Notiparad aus god ‘xsse
86/66/66 00/00/00 ao oO 7 “£ oO WIId M@/T &T N6¥9 ‘YOLSISas
66/66/88 00/00/00 to 8 foot 0 wang. Be/t at Ne ‘uousrsaa
6676/66 36/2079 veo 0 ooo + 'iviga anti ooo vo" 'gend Sero-se~sea9
6766/66 00/00/00 wre 8 coo'e t yoo asna ana "Nori9as $ooe-t2-s.19
86/66/66 00/00/00 © carza9 8 ooo'z 3 waTa ‘Tene soaN ose ve. asna veromeznses3
86/66/68 09/00/00 eta 8 ooo'e + yse avis e1g/M asn3 "yoo eooe-0e=s239
86/66/66 00/00/00 © 0 00°F HK W¥a coor ooo"? «= T «= aE HaSSAS WaOEWIO AUGLIVE “TONNE ye093,
SING gLNG_MOIWNOTSq 04S LAS KLTINND JO 2S Nn HIOWa AIGHSSEY “ON AU a
‘SuSI0Seo ATsOaaaa SONTEEESE 330 Uinvasa eg agarA 83a X10 WRIT
skva a
norsareosaa aEHON LIKE
66/e0/@ :ooa isw1 40 3va
és jaye ‘aunoa ‘ow 053
O77 spears 1g00H
Loss GE waaw TN “BPRS ITY "yaaae ss wsouvio save tava ‘assy taga 9 !aa00a0 26088
Gag FE aa SUNNOAMOD TWOTHIOSTA 900 __sadOD SSID
Vie if . ‘asTgisswionN — +endw ¥00D SSVID
66/t0/8 30 SY
aeeeseeneewenene sage tclppe anal)
cso t0N BoWa TWIUSLYN 20 TITS emwmuen aanvun S685, 08,, 008 20dgliii igiis @
a8,Lae an Hy
Fstasietelstst
iow
@OESSO |_° 2
ee = . o
@®@
@229@-
Sow we65/66/66 00/00/00 70 0 = 000"% ~—NK_d ¥E_000"F 000"e ts / + on/om wouno (ta) xnw ‘towLNoo 7 —zzo0-z0-szs9
86/66/66 00/00/00 G0 900°eF NK 4 YE 0007s o00'st «= oP» «=~ TdG¥D ¥/T BAS TSH /UHSWANDOT
86/66/66 00/00/00 0 © 000°8T NK a WE 000°T ooo'st = ge~ oT da 0/T NIWId "BaHSeM
66/66/66 00/00/00 2 © 000'8F NK a WE G00'T Oooo §=be~ Ta_¥o @/$ X 02-#/T *SOHH
66/66/66 00/00/00 9 6 o00'T NK WWE 000s ooo"r ze t
86/66/68 96/tT/€ Ta 0 0 G00" ~—N @ WS OG0'T o00'T. se r 0zT0-30-S2¥9
86/66/66 00/00/00 FadL © 0 © 000° ~—RK_d_WS O00'T 000'T se t se00-04-s749
66/66/66 00/00/00 0 0 OkE'Z NK S353 000't oee'z ge z 8000~90-022T
86/66/66 00/00/00 9 0 o€€:< RK A ZI OGO'T OE'z oe t Teo0-s0-0zct
86/66/66 00/00/00 9 9 00076 RK a WS 00°F 00's. ze t 9000-st-sezt
86/66/66 $6/t0/2 0G o00'e = RK a WS O00'T Caos te o fETO~89-SLT9
86/66/66 00/00/00 0 9 «Gou'z = NK a Wa O00'T 000-2 oc r 2000-26-94T9
56/66/66 00/00/00 © 9 oo0'et NAG NI 000"t ooO'zt gz { ourunnow 3078 Hus can Tooo-Te-9219
86/66/66 00/00/00 Ty@L 0-9 o00r9z NK Ga VE 000'F o00"sz a 0 aWaIS WOS AOD WYSE ‘YOOTE 1900-02-94t9
86/66/66 00/00/00 ¥a’Ed’Zd 0 9 «000"E ~=—NA. d WE 000°E OO0'E 4e ¥ waig Tend J9GW AoSz Wt ‘asnz 62T0~S2~S259
66/66/66 00/00/00 JE0 0 000" NK @ YB 000° 000"F 9e ¥ WTS Tend LOH nos? Wz ‘asna sETO~$2-S289
65/66/66 00/00/00 © 9 000° NA WB 00°F 00's. ve 9 B10a F W009 agaTON BSn3 ‘wDOTE es00-re-sz59
85/56/66 00/00/00 REO 9 000°F ~—NK_ od ¥S 000° Q00"T ez r AM MS 83 Net ‘YousTSaE 2800-36-0599
86/86/68 S6/t0/¢ = Da’aa’WH 0 © 000"E ~=—NX_d Wa 000°T O00'E 1 ¥ MM MOT SHHO Ne"T Yaa ‘HOLSTSTE , — teto-sz-0s¥9
88/86/66 00/00/00 Wo 6 000" NK Sa ¥E 00°F 000'T OF FON BTOd 2 WOT ‘uoro¥LNoD f/ — 9s00-08-sz59
66/66/66 06/00/00 @ 9 © 000'9 «NK gS 000"T 00's ~— gt t ‘Id GvO + X ve-94 ‘SHE 8000~-so~6097
66/66/66 00/00/00 0 «(000° = NK YE 000°T OO'e BT t ‘id avo @/€ X ZE-9H ‘SHHE e000-so-s0¥e
66/66/66 $6/30/2 © 9 o00°F NX AVE 000'F ooo'T «= ctv BOLSISHY ONIENNON ‘SIVId ssz9s
ean
86/66/66 00/00/00 © tUN' TEN 0 ©9000" ~—NA dW 000'T O00'E or 1 BaKL aM Sale tt AvigE ‘ZENDOS vooo-ze~sut9
can
86/86/66 00/00/00 ZEN TEH 0 ©0000" += NR d WE 000°T ovo'e ~— gt ¥ TioD ownOTT vor Lage ‘xwrgy
66/66/66 00/00/00 9 0 000°. NR 3 Wa 000'T oo0'F vw t Id GWO ote NiWid ‘SaHSYM
86/66/66 00/00/00 © 0 007% NA 4 Wa 00°F coo"e «er 3 Wa avo tw INT ‘usHSWHIDOT
66/66/66 00/00/00 © 0 000°% NK 3 WB 000" 000" ay v Ta Qed 2/t x Ze-OTw ‘SHHE ¥O00-S0-2T97
66/66/66 00/00/00 Tadd 0 0000'S = NK Oa VE 000'T 000"F =H. t S¥T/0EZ AUSS TOST “wWaK ¥E00-0€-0099
66/66/66 00/00/00 2 0 000°T NE BW Wa oGG's ooa'T, ot oat SEN WOLND ¥ SdoTa ‘aLvId T2788
66/66/66 90/00/00 2 9 00072 Ng Wa ¢0"r ooo"? 6 + 4D ONNOZ-¥/7 XBH, ‘LON 9000-s2-0z85
86/66/66 00/00/00 © 9 000" = NK WS O00'T coo'z 8 Fo Wd avo $/T-T X 02-4/7 ‘ssus 0t00-30-st9e
86/66/66 00/00/00 0G c00'e «= RK od YE OOO'T D0" =k, t */ X O@-¥/T GHL TIY ‘ants 2000-10099
86/66/66 00/00/00 0 0 000°2 NK ¥ 000"F oo0'z 3 3 ago ¥/t-r X T dqUS “HOLWINSNT 6000-to-szet
86/66/66 00/00/00 @ 0 ov0'st NK J WH 000't ooo-st —g r ‘Ta avo ¥/e Xx ze-oTW ’SHHE 9000-so-2t8z
56/66/66 00/00/00 “a-ta. 9-9 000") NK a WE OOO'T ODO'e = r otstrdao# ONzsusagY ‘saoTG Fo00-es-o0s9
86/66/66 00/00/00 © 9 90075 = Kd WS 000"T OOO" & r Ta Geo 2/t X Bt-9T/s ‘soHH ¥000-so-Lt6e
85/66/66 00/00/00 S40 9 0007T NA - WE 000°T O00'r zt t nooe ws27t ‘asng zsto-s2-ses9
86/66/66 00/00/00 @ 9 000"T = NK WH Wa o00"T 000" t @ F WSAOHOIMS LYE ONTINOOK ‘TaNWa saves
BING HOLWNDISEG OFS 13S ALIENWNO 30 DS Wn BLOW ATAWESSY “ON AU a NorsaTuosaa waeHAN cava
suatoseo argosaen “Sonauasae 240 Lanvagza 49 QISIK B3d ALD WELT
siva a
Bboy
86/12/01 tooa IswI do 3uva
‘SHNDS TON O53
sree aseay we Stato
Bb )e¢701 “qaagy Tenta TaNVa WAAOHOLINS Ugve ‘xSSwW = 3 tATH 0 +Bq0040 9099s
,
: suxmonies nonwsoe1s coo +3009 ss¥o
Fr son aove cert x30, foam00°F NK $3 Ya 000'T oo0't = cor So onrtavo ‘ovra sepos
66/66/88 00/00/00 o 0
66/66/65 00/00/00 © 9 000°F NK S3-¥3 000°r 00's zor oNrTEvo Maa ‘owza cezss
66/66/66 00/00/00 & 8 000° NK S4¥a co0"T 000°F = tor NOTL9gNNOD ‘ovra ezers
66/66/66 00/00/00 © © 00075 NK S3.¥H O00"r o'r got NorZoanNooEauNT ‘ByTa yotss
86/66/66 00/00/00 ® 8 000: NK @ WE 000°5 ooo'z ee x 998 AINA TENNVHD ‘ anw1> zo00-ze~9219
56/66/66 00/00/00 2 9 00078 KK NT 000'F 00's =e. F SNTUNNON YOOTE KUSE “TaNNYHD Fo00-re-g2r9,
86/66/66 16/12/3, © 9 00078 NK 3 WR 000"T coos sy 5 SS O/T x OF-¥H ‘SHH 20-90-5087
88/66/66 36/t2/5 2 9 o00'T RRS WE QOD" CO's a. 5 yiooTa aSna aNa ‘NozE9as ¥000-T2-92F9,
86/66/66 T6/¥5/5, 820 9 000'5 NK @ WR O00"T 00's =a. + Wea8 Twng 290M nose ws ‘gsna BS00-s2-s759
86/66/66 36/43/5, 2 0 00:2 NX ava 00°F ooo? Le rise Qe1a B1a/H gsna ‘xo07E E000-08-sz19,
86/66/66 16/40/2 © 9 90072 = RA EWE QOD"F OO"? 9 0 SOWIE STEVAONTY HOLINS ‘OOTE To00-ee-s7s9
66/86/65 06/82/6 ® 9 00077 KK a ¥S D00"T ao0's =~ ee T "97 8/t x Wid @/F dod ‘ISATe 9000-st-sezt
66/86/66 06/87/6 © 9 00076 ©~—NA 38 VE 00°F COD"E LE. $ wwinans A009 vos wEaE “ote 600-02-9219,
66/85/66 00/00/00 © 9 000° NK HVE 000°F 000°t be % SO¥LION HOTH wSDNYG “ovzaHEN z-99T6e
66/66/55 06/e0/9 @ 0 000°
¥or0-0e-0699,
86/66/65 66/t0/2T 2 0 000703 NK @ va 000's o00'09 oy z 88 Dunoe-8/% XgH ‘LAN 9400-s2-oz¥t
86/66/66 00/00/00 9 © 90070 NK ag Wa 000°% oo0'oF ~—T. ¥ 88 G2~DNNOT~G/e XBH ‘ENN ‘8200-sz-oz9t
66/66/66 ¥6/92/5 2 0 000°f NK 3a WE 000°T ogo'e gt ¥ Wos A009 Wie WEBL ON ‘NorEgS 6t00-re-9219
86/66/66 00/00/00 9 9 00073 NK “WIS 000'T 000's Sew NOTINOTATINGGT ‘SOWE
86/66/66 00/00/00 2 © 000703 mK gd YE O00"t OOD'U9 ey T $8 9/5 aS THN “YSHSHHNDOT
86/66/66 00/00/00 D9 ‘000°0T NK ¥ 00°F ooo'os EF T __ ($8 8/6 Was TSH “ESHSVINIDOT
86/66/66 00/00/00 © 9 000708 Ax J YB 000°F 000'09—Z 1 SS 9T/tx9t/sxo/e NIWIa “ESHSY
86/66/66 00/00/00 © 0 000707 NK a ¥E 000°T ooo'or yr F “aov/e Ss eve NrWTa ‘waHowH 8600-t0-0695
66/66/66 00/00/00 ® 9 000708 Nk @ ¥a 000"T oo0"0s or r 88 9/6 X 0-8/1 ‘SOHH 9000-s0-s56¢
86/68/66 86/20/27 © 9 000708 Nx @ WE 000°t o00'02 8g 0 an yove sive LnSEsINn “saNNeHD seoes
86/66/66 t6/z0/2 8 9 000° RX aE O00"T oo's T MGISKS “DRO xuSLIVG ‘SLWIGaHN 65985
66/66/66 86/eo/er 9 0 00-0 NX GWE O00'T OOD-os 3 0 GUY HOZON/M LauzsTNn “TaNNeH 88s
66/66/86 00/00/00 9 © o0070% NA Sa ¥E O00'T O 5 t WATOIWS GwaT ‘ANsLIVE 4000-24-0089
86/65/65 00/00/00 © 0 00's Nag Wa O00'F OF ¥ 3 Nadosst anoe/y 2 isnwuxg. ‘Nu £200-s2-s229
66/66/65 00/00/00 9 0 000"F = NA_ XW O00'F £ 0 sks wgpuvHo sive Tanya /xSSv zeoss
66/66/66 00/00/00 9 0 000°T KX WE O00'F 0 Z 30 TaN SSAOHDLINS Love ‘xss¥ 30895
66/66/65 00/00/00 2 8 000°F NX KW 000'r opD'F ~=6 st Ss} eas IWE/ING “ZUNSOTONG ro0ss
BERG qr Gawd, NOUWNDISG OaS Igs XLTLNEND 3D 98 Hn BIDVA XTENGSSY “ON AB a nozaaraosaa si
Susiosdo ATZOagg3 SONSHEaSe ago Linvaaa aa OUaTA BSE AL WELT 0
Sawa a
66/10/25 +008 ast 40 3140
Gsjelzr ‘outing ‘on 033
Saree asverse Wha’ "tacon
anagy ents "OY “Teee — oeno/ava ez4tnn avo save @ tnau 0 +sa0040 ovees
be pty, WHE, lage av oauo/avE azuzNn av awa ‘Asse
ao eva SHaNoaios seaa 000 _+g009 sso
Wa : py TPL aaratssvionn —¥" tanoup gd09 $S¥19
86/t0/2T 30 sw
wor tom goa ‘TWTaaLYA JO TIE
~ Yona :norungzuisra
6665 * 230 ‘osm
AnWaHOD WOIAVE SVEVIVGH"2 ‘002/174 —L. 2° + 2 1
q Se
yy witha .
Cpa me ss 3.3 (4
ee
Ps Po)
00) ws
3 69. o bg
mus (3)-—2F itn mar2eo—2t By
b a I, J
ese. x
oman ey
ie a (0
fee
Sh 8
i we Date
a
‘OS mnt) it maoo
“Lg —men i
fom GAS
«eo
a |
sw a
EE Se 8)
is NOTES:
cs Meee
fi
a|
seceoaee
nvwowsa
s8/s6/68 00/00/00 “DHTHIM 0 © 000" a Wa 000"T 000" ss GO noravaataansoa sonsugas4 sonmusase
aoreeeee Ae a 0 000°F NA W Wa 000°T G00°T at wo ‘UnaLNo AwaLINE “d°E ‘OWL we azess |
sereores certiver 9 9 000:¢ AK wa 000s coos © oe Ss t/t x ce-oe, ‘Sai so00-0-1102
g87e67e6 cesit/on © 0 doors Mk Wea Go0'r co's © Se se7a ONEEKNOM “Tne 12698
gerssrss e5rst/ 8° 9 090°? RR S¥ao00't Gonz? bz na ava e/e 20-94 ‘SHE £000-g0-6082
y ot emma © «8 no't | MA_Z Wa G00T ooo'E © Ee Sana WN aavae 9t AWIgy “Is9008 Ytoomeenset9
Se7serse cerviser — FuEEL 9 gga"? NA Fava Gog'r Goo'T GEE Yon owAGEY ws gy /AWISE oero-s0-s209
8786766 99700700 THES 0 Goo"r MA ad Wa Og0'r Ooo Fe BYOKO HD ROE ‘WENT 2eo0-ee-ses9
6768766 00700700, 8 8 Goes | Mk da oo0"r go's) oe $8 2/t x Ge-w “sit Sooocso-1ts2 |
66768786 90/00/00 pau 0 8 Go0't MK Wa Gor oor BE Sbvie isa Sour Stoorve-sets |
86766766 00/00/00, Soa 80° G00"t NK @ wa O00" ogo? «= at age sau ‘your He
i 66/66/86 00/00/00 . “ een eae
seresc Fad 0 0 000'F_= NK WRB O00'T OOOTS «LT + oNTENNOW aD, ‘TeNDeEE seces jf
| BASIS Sreovos HEE Segre ME eR coars cease FF ae aohbah MoE ramy SS eseocto'sees
gezsares es/port —oxneat 3-8 oavoy kG va Ooo'y anova SE Suiatoae ownoet “ake es00-0F-sce9
fearee oo/oerbo Skint 8 Qou'or ak 4 Wa ovo-t goo'oy Py F macnn yeas oyu Mota viowinoo —Eg0u-veeta9 |
gevesves 00700700, ore 149 Gou'ok Hx Wa Goo'r ouo-ay Gr © E aghm'asas /0°N JOT "soWanOD Sooomte-se59
Sevesves Sersort” Suita © 8 Goovay mM dv Qoo's oogvor tt F S/a/a Wit aus af Ua “OnTBnOH Tooo-ze-sces
i 88766768 99/00/00 e108 oot) Mk Wa G00°t Coos) TE 0 TMOe LTH cuvameas. “sxe cboo-so-sces
se7ee7es 99/00/00 oft 09 Goo" RA @ Wa Oba"t Goo'T ok TAD Maan catvaNWES ‘S17 ftoo-so-sces
6/66 EE/OO/T on BE 0 900"T NK d WS 000°T 000°t 6 ' too" NITYD GUVONWIS /SNIT STOOnSP eye
66/66/66 £6/90/T 6141-21 0 0 a00"e ‘Nk @ W2 000'F ooo‘ 8 r ‘TuO# GFE GEWONWLS ‘SNST ares seer
i 86/66/66 E6/2t/2 yalea o oO o00"2 NK d W3 000'E 000°? ‘L YOOT LaVHS?/t ASSW ‘LANYOOT ae rose eere
Se/ee/6e e6/z0/ wales0 9 000°t WX 2 WA 000'T OOD'e t SRENEOS Me HOE. oe SON gon0~ss-075
6/86/66 E6/TT/0E FY 0 9 -«:000"F NA Gd WR OOO'T GOO" = Fwra .2/t-1 ogemy “SHEE DAD ¥200-0-S259
86/66/66 00/00/00 2G 0 0 000'T NA Wa 000"F OOD'T = «=O aAOSe/A¥-UT~O Od ANY /HBLON s9T0-ES-5429
feres/es t0/a0/t wed 0 00" Mi a Wa Bo0'y ooo't Tod oa A00s~0 10n /ga0aK ss00-eo-s09
55/66/66 86/90/5 WOO 0 000°F NK ¥a 00°F O00's, «= Zw tS HBOUWHD IVE SNEWS “TANS sreos
86766766 00/00/00 © 0 do"t «Mk Ges OGo'y Ooo
have auvd” ouenorsaa S35” 2a3 AUTTHGAO JO 53 nn wxovs xzenassw "ON aH
auaioseo arioasaa “Soummassu a0 Linvaad 43 Gian Gad AsO WaT 0
sxva a
s/to/os ‘008 S50 40 aus
ona 108 02
Leflore *1g00H
Cree ei 5 theo e985
Caleay APES ET GES ayy yet 948 sazsimn ta snuwss ‘xe8e 9 SARE 0 “0000 é
. * iNGNOaWOD TwOTULOTIS coor #3009 SS¥19
IT wo £0/ i —< , SaNGNOGHOgraroSwioNN —¥ ‘ano 3009 SSVID |
18/10/01 40 $¥
atecrestenensse paeebtasot ane
ao AAWaHOD WOTKYE SWAWIVGH'2/002/TT
\errt0N aoRa
YONA :NOruAaTUisTCOPPER BUS BAR - 1/8" X
F TONG
(6500-50-0038 [HEAT SNK - 4.72" LONG
'2412-06-0003_| BAS, 10-32UNF_X 3/8" SS
NUMEERS W ( ) OESGAATE OUANTY -]i
|
i
| Faneese
[a= 18,3 3}
(BERR
T
TTju) ena‘ALL DIMENSIONS ARE IN RICHES UNLESS CTHERWSE SPECIED —__8/M 53564
HL frees Oss: .
Ne HU cia a Oeanar
eleea| 11/32 DA. MIG
Eee
| —312—e| [Pe [us "ASSEWBLY- & OUTUINE
ee ie site EMERGENCY STOP CONTROL
i | Sor wo
| ‘uel 172 1B 53564 at ot [O
| en een eee rate care
REDRAWN TO CAD | Reeiatnanracractartta tua een emurarRE roeFRI, JUN ZU, 199/ Bib UF marRKuAL PAGE NO: teet
AS OF 6/20/87
CLASS CODE GROUP: + UNCIASSTFrED
GLASS CODE: 3030 DT-ELECTRICAL COMPONENTS Daw foo ux. LDS chol97
53564 OPCODE: 1 REV: C —ASSY, EMERGENCY STOP STATION ABPVL, OL? | eat nppuL. L464,
toate Sethe” ¢, SRM Ae loch
ECO NO? ECN#C ene
DATE OF LAST ECO: 5/01/97 ;
R pays
© a7eM gry PeR yrexD EP DEFAULT OFF REFERENCE EFFECTIV OBSOLETE
TTY SET SEQ DESIGNATOR DATE DATE,
1120-08-0082 ENCE, ELEC 3.62 X 12.62 X 5.62 4 4 4,000 1,000 EAP mM = 1,000 0 90/00/00 98/33/99
6525-57-0035 2/8,‘ MUSHROOM HEAD RED 1NO/NC 1 2 1,000 1,000 EAP uy 21000 0 oo 90700700 99/99/93
6375-23-0008, EiGitt, PILOT RED 110 EXP 1 3 1,000 1/000 EAP HIN 1.000 9 00/00/00 99/99/99,
~ §3506-1 HAMEPEATE, BACKUP IN USE a % £1000 1000 EA P YN © 1.000 0 oo. 90/00/00 99/99/99
53506-2 MAMBPLATS, EMER STOP 1 5 1000 L100 EAP YN 000 00 00/00/00 99/99/99ION _9
veh INFORMATION
9.1 Enerpro Firing Circuit Pip
9.2 Batteries
9-1Single Phase Four SCR
Firing/Regulator
Circuit Board
Part Number FCRO4100
Features
‘Syrimatrical Digital Gate Delay Generator for balanced phase
control.
‘Custom CMOS LSI gate array for lower parts count, higher
reliably.
“Soft Start & Soft Stop circuit.
“Feedback Error Amplifier for current or voltage regulation
‘Regulator Circuit intertace for optional “piggy-back" voltage
regulation/current limit board.
‘New larger capacity on-board transformer with primary vottage:
available up to 600 Vac.
‘Bipolar gating for 4-quadrant applications,
‘Auxiliary (slave) Fring Board output for gating parallel and 4-
‘quadrant SCR ciruits,
Fully connectorized for easy maintenance.
Applications “Heavy-duty two-sided .093 inch circult board with solder mask
The FCRO4100 firing circuit/regulator supplies hard firing “picket
% «Polyurethane conformal coating.
ence" gate pulses for single phase AC/AC controller and AC/DC
‘converters. Common SCR phase control circuit configurations “Fully tested at rated voltage in customer's SCR circuit
include: configuration.
Single Way Converter 3
2-SCR with center-
Soe transforme’) Gate Delay Angle Transfer Function
‘The gate delay angle in the open loop mode varies in negative
Proportion to the contral signal input voltage as shown below.
‘The minimum and maximum delay angles, amin and amax ,
+2-Quadrant Bridge Converter are determined by the values of two resistors.
Typical limits are 5° and 175°,
max,
“AC Controller (2 ant-parallel SCRs) Fin
*4-Quadrant Bridge Converter (requires
FCOAUX60 auxiliary firing board) 3
DELAY ANGLE,
a
ere
23 4 5
‘CONTROL VOLTAGE (Vdc)Phase Delay Generator
The variable gate delay angle cis produced it a phase-locked
Joop (PLL) consisting of an XOR phase detector, low pass fier,
‘summing junction, volage-contriled oscWitor (VCO) and digi
countdown chain, The VCO, countdtvin chaln, and phase
detectors, as well as addtional bank select and inhibit circuitry,
are contained in a custom 22-pin DIP CMOS gate array IC,
Input Control Signal
‘The input control command signal is 0 to 5.0 Vac with an input
impedance of 10.0 k©. An optional input shunt resistor can be
installed to permit operation with a miliamp type control signal,
2.9.4 to 20 mAdc.
Current and Voltage Regulation
‘The included error amplifier provides the option of either current
Or voltage regulation. Current transformer feedback or an
attenuated 0 to 1.0 Vée voltage feedback must he supplied. The
FCRO4100 may also be used in the open-loop mode with no.
feedback.
AA regulator board interface connector is included for mounting
Special purpose “piggy-back’ regulator circuits. Two such plug
in boards now availabie.are the models. VRCL1P-1 and PTIR.
‘The VACLIP-1 provides vottage regulation with current
‘The PTIR-1 provides vottage and current regulation in addi
a “polarity transition inhibit" circult foruse with 4-quadrant
converters,
Power-On Reset
Circuitry is provided to inhibit gating until the on-board power
‘Supply voltage has stabilized. This circuit also inhibits SCR
Gating during line voltage dropouts,
Soft-Start & Soft-Stop
‘The Soft-Start circuit over-rides the gate delay angle command.
‘The Soft-Start circuit is activated by a contact opening. Gating
‘commences at the maximum delay angle limit. The delay angle
‘amps down to the commanded angle,
‘The Soft-Stop circuits activated by a contact closure. The delay
‘angle ramps up from the commanded delay angle to the
‘maximum delay angle limit before gating is inhibited. The soft-
‘start and soft-stop ramp rates are separately settable with timing
resistors.
Instantaneous Inhibit
‘A second inhibit function is provided which instantly enables or
inhibits SCR gating. This function is actuated by a contact
closure,
Board Mounted Power Supply
‘A 24,VA transformer with a center-tapped 120/240 Vac or
240/480 Vac primary winding is standard. Other voltages are
also avalable. The transformer output is rectified and filtered and
sed otrectly for gate drive +30 V power and is also applied to a
+12 V regulator for operation ofthe control electronics circuitry,
‘The 24 Vac output ofthe transformer is also used as the phase
Felerence for the gate delay circuit,
SCR Gate Drive Circuits
Four isolated and 180° spaced hard-fring gate pulse outputs are
Provided. Gate drive outputs are pulse transformer coupled,
Gate Pulse Specification
Burst width: 180-a
Pulse width: 32.6 ps
Pulse risetime: = § Ain 6 us
Short circuit current: 2.0 A initial pulse
BAsustaining pulses
Open circuit voltage: 15
These voltage and current levels are nominal because they are
‘derived trom unregulated 24 Vac,
Gate Delay Angle Specifications
Frequency response: 3 6B atten, at 67 Hz
45° phase shift at 57 Hz
Frequency sensitivity 2.6°el/Hz
Temp. sensitivity: 32° el. for 0 °C