Reactive Power Control For Distributed Generation Power Plants To Comply With Voltage Limits During Grid Faults
Reactive Power Control For Distributed Generation Power Plants To Comply With Voltage Limits During Grid Faults
fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
             Abstract—Grid faults are one of the most severe problems for                     alleviate the adverse effects of grid faults, grid codes from the
          network operation. Distributed generation power plants can help                     network system operators dictate the behaviour of DG plants.
          to mitigate the adverse effects of these perturbations by injecting                 The evolution of these codes for DG during grid faults started
          reactive power during the sag and the post-fault operation. Thus,
          the risk of cascade disconnection and voltage collapse can be                       with low-voltage ride-through, which demands withstanding
          reduced. The proposed reactive power control is intended to                         voltage sags. As the penetration level of DG sources was
          regulate the maximum and minimum phase voltages at the point                        increased, reactive power injection was included in grid codes
          of common coupling within the limits established in grid codes                      to support the grid voltage and to reduce the possibility of
          for continuous operation. In balanced three-phase voltage sags,                     voltage collapse [5]. The next generation of grid codes could
          the control increases the voltage in each phase above the lower
          regulated limit by injecting positive sequence reactive power. In                   require negative sequence current injection [6] and voltage
          unbalanced voltage sags, positive and negative sequence reactive                    support control [7]–[9] in steady-state and transient. The aim
          powers are combined to flexibly raise and equalize the phase                        is to regulate the point of common coupling (PCC) voltage
          voltages; maximum phase voltage is regulated below the upper                        to a safety range, preventing damage in the equipment while
          limit and the minimum phase voltage just above the lower limit.                     improving voltage support services.
          The proposed control strategy is tested by considering a distant
          grid fault and a large grid impedance. Selected experimental                           In a real distribution power system, the capacity of voltage
          results are reported in order to validate the behavior of the                       restoration is obviously limited by the power rating and the
          control scheme.                                                                     grid stiffness. Grid codes are demanding more reactive power
            Index Terms—Reactive power control, grid fault, voltage sag,                      capacity to improve the contingency against faults [8], [10].
          voltage support, positive and negative sequence control.                            The use of these extra resources can be adapted to implement
                                                                                              smart voltage support services during distant grid faults. A
                                                                                              smart voltage support service, as proposed below, should
                                      I. I NTRODUCTION                                        regulate the phase voltages within the limits established in grid
                                                                                              codes for continuous operation [11]. The safety limit strategy
          T     HE high penetration level of renewable energy sources
                and distributed generation (DG) plants faces new
          challenges in the operation of transmission and distribution
                                                                                              depends on particular grid codes, and each code provides
                                                                                              its own specification for continuous operation, although most
          networks [1]–[3]. The growing installed power from DG plants                        of them state the maximum voltage limit at 1.10 per unit
          has led to a change in the requirements for ancillary services,                     (p.u.), and the minimum at 0.85 p.u. In type I voltage sags
          particularly during grid faults. Among these new services,                          (one dropped phase) or type II (two dropped phases), the
          voltage control in wind plants, photovoltaic parks and other                        reactive power strategy should be different than the strategy
          large-scale power plants is gaining increasing attention due to                     for type III (three dropped phases) sags [12]. Balanced type
          its capability to improve grid efficiency, safety and reliability                   III sags only require positive sequence reactive power to raise
          in a distributed manner.                                                            the phase voltages above the lower limit, since this type of
             A voltage sag is a perturbation in the grid voltages                             grid fault lacks negative sequence voltage. On the other hand,
          characterized by a short-time reduction in the magnitude of                         unbalanced type I and II sags require a flexible combination of
          one or several phases. The effects of such disturbances are                         positive and negative sequence reactive power to avoid under-
          important in terms of economic losses, malfunction of devices                       voltage in the faulted phase(s) and over-voltage in the non-
          connected to the grid and in extreme cases, black-outs [4]. To                      faulted phase(s) [13].
                                                                                                 Advanced control algorithms to ride through different
            This work was supported by the Spanish Ministry of Economy and                    types of voltage sags are mainly based on symmetric
          Competitiveness under Grant ENE2012-37667-C02-02.
            A. Camacho, M. Castilla and J. Miret are with the Department of Electronic        sequences [13]–[29]. Some of these studies have been
          Engineering, Technical University of Catalonia, 08800 Vilanova i la Geltrú,        proposed to achieve particular control objectives related to
          Spain (e-mail: antonio.camacho.santiago@upc.edu; miquel.castilla@upc.edu;           power oscillations, total harmonic distortion, power factor, dc-
          jmiret@eel.upc.edu)
            R. Guzman is with the Department of Signal Theory and Communications,             link ripple, or peak current limitation during balanced and
          Technical University of Catalonia, 08800 Vilanova i la Geltrú, Spain (e-mail:      unbalanced grid faults [16]–[23]. However, little work has
          guzman@tsc.upc.edu)                                                                 been developed for voltage support control during unbalanced
            A. Borrell is with the Department of Electrical Engineering, Escola
          Universitària Salesiana de Sarrià, Autonomous University of Barcelona, 08017      voltage sags [24]–[29], and they are based on voltage sequence
          Barcelona, Spain (e-mail: aborrell@euss.es)                                         amplitudes as voltage targets. Hence, to further improve
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                              V
                              V
                            Vc
                                     Va
Vb
          voltage support services, phase voltage regulation instead of                       continuous operation are defined as
          voltage sequence regulation is developed in this work, since
                                                                                                                             V := 1.10 p.u.                                (1)
          this is the main concern to remain connected in some grid
          codes during grid faults [30].                                                                                     V := 0.85 p.u.                                (2)
             In contrast, the reactive power control proposed in this work                    where V is the upper safety limit and V is the lower one, which
          tries to solve the aforementioned problem and extends the                           correspond to the most stringent limits provided in some grid
          contribution of [31] for any type of voltage sag. In [31], only                     codes to remain connected during grid faults [6]. However,
          symmetric sags were considered. However, voltage sags are                           these limits depend on national grid codes and can take
          very complex phenomena [4], [12], [32]. As shown in that                            different values for different regulations [11]. These voltage
          works, some of the recorded sags are asymmetric and time-                           thresholds define the safety region in which the three-phase
          varying. To achieve all these features, a detailed mathematical                     voltage amplitudes must reside regardless of the fault type.
          formulation is developed to set the voltage targets, and a                          Beyond these limits, the system should disconnect because of
          simplified impedance model is used to compute the reactive                          over-voltage or under-voltage, according to the functionalities
          power references.                                                                   of the power equipment and the trip times established in grid
             The paper is organized as follows. Section II formulates the                     codes [11]. The trip times are needed to avoid unnecessary
          problem. Section III introduces the DG plant and the control                        disconnection by short time transient voltages.
          scheme during grid faults. Section IV develops the voltage                             To meet these limits, a combination of positive Q+ and
          support concept. Section V focuses on the proposed solution.                        negative Q− sequence reactive power [34] can be injected into
          Section VI presents a saturation technique to protect against                       an inductive grid to support the grid voltage. Positive sequence
          inverter overcurrent. Section VII shows the experimental                            reactive power is related to the amplitude of the current 90◦
          results. Finally, section VIII presents the conclusions.                            leading from the positive sequence voltage (i.e. the reactive
                                                                                              current injected via positive sequence). The same applies for
                              II. P ROBLEM F ORMULATION                                       negative sequence reactive power, although it is shifted from
                                                                                              the negative sequence voltage.
             This study is intended to support the grid voltage in medium                        To understand the proposed reactive power control, Fig. 1
          or high rated DG power plants, as for example wind farms or                         presents different strategies of reactive power injection [13]
          photovoltaic parks, which are interfaced to the grid by means                       during a voltage sag. The figure shows the three-phase voltages
          of power electronic converters. These plants are subject to                         Va , Vb and Vc . The dashed line highlights the safety limits V
          very stringent requirements during grid faults depending on                         and V. The dotted line indicates the nominal voltage. The
          the rated power, and the grid operators require huge amounts                        figure is divided in four parts. On the left, Fig. 1(a), the phase
          of reactive power, both steady-state and dynamic to support                         voltages at the PCC without voltage support are shown. If
          the grid voltage [8]. Typically the most stringent requirements                     the reactive power is injected via positive sequence Q+ > 0,
          in grid codes apply for power plants rated above 30MW [33].                         Q− = 0, then the voltage in each phase raises equally as
             Whenever a sag occurs close to a DG power plant,                                 shown in Fig. 1(b). The phase voltages should raise until the
          the circuit breakers isolate the system to prevent damage.                          minimum phase voltage achieves the lowest voltage limit to
          However, if the sag occurs far away, low-voltage ride-through                       comply with grid codes. The problem with this strategy is that
          is mandatory, and grid codes demand reactive current injection                      the highest phase voltage Va suffers over-voltage. However,
          to avoid cascade disconnection and reduce the risk of black-                        when the reactive power is injected via negative sequence
          out. For distant grid faults, if the grid impedance and the                         Q+ = 0, Q− > 0, the phase voltages tend to be equalized
          plant rated current are large enough, then the voltage can be                       as presented in Fig. 1(c). The problem is that two phase
          supported by an appropriate reactive power strategy. As stated                      voltages, Vb and Vc , suffer under-voltage. From these two
          previously, the main objective in voltage support control is                        figures, it can be concluded that some flexible combination
          the avoidance of over-voltage and under-voltage at the PCC                          of both positive and negative sequence reactive power can
          whenever possible.                                                                  regulate the maximum phase voltage to the safety upper limit
             Throughout this paper, the safety voltage limits for                             V and the minimum phase voltage to the lower one V. This
                                  0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                          http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                                                                                                                inverter
          strategy is adopted in this work and can be clearly understood
          from Fig. 1(d).                                                                         power
                                                                                                  source
             It is worth mentioning that there exist more stringent targets,                                                                 PCC                      grid
          such as the maximization and minimization of the voltage                                                                                    Lg
          sequences or the regulation of the three phase voltages at                          STATCOM
          the nominal pre-fault values (i.e. Va = Vb = Vc ≈ 1 p.u.).                                                                                   i
                                                                                                                                               v              vg
          However, these strategies require higher currents.                                    Switched                       transformer
             A particular case can occur for low unbalanced sags, i.e.                           caps.
          when the difference between the maximum and minimum
          phase voltages is less than the difference between upper
          and lower safety limits. In this case, negative sequence
                                                                                              Fig. 2.   Simplified scheme of a DG power plant.
          voltage is either zero or quite low. In this situation, the best
          strategy in terms of reducing the injected current, is to only                      power facilities are made up of the following VAr devices
          supply positive sequence reactive power. Then, the three-phase                      [7]
          voltages will raise equally until the lowest one achieves the
          lower safety limit.                                                                    •   power inverters
             The problem in complying with voltage limits during grid                            •   STATCOMs
          faults can be formulated as:                                                           •   switched capacitors
                                                                                              Power inverters can be controlled to supply both active and
                                    find    Q+ , Q−                                           reactive power. Moreover, full-scale power converters are
                            such that: max{Va ,Vb ,Vc } ≤ V                           (3)     becoming the preferred choice in wind turbine technology
                                       min {Va ,Vb ,Vc } ≥ V.                                 because of their flexibility [40]. STATCOMs provide some
                                                                                              dynamic reactive power required by grid codes. Steady-state
          The solution to the problem consists in finding which are the                       VAr compensation is mainly operated by switched capacitors
          values for the positive and negative sequence reactive power                        since they present lower investment cost. All these elements
          references, Q+ , Q− , such that the maximum amplitude of the                        allow the power plant to behave as an equivalent power system
          phase voltages Va , Vb , Vc is kept below the safety upper limit                    that exchanges active and reactive power at the PCC [10].
          V, and the minimum above the lower voltage limit V.                                 For proper operation, a communication infrastructure with
             Some assumptions are needed in order to simplify the                             networked control schemes is shared among the elements of
          theoretical study:                                                                  the plant; the dependency among the inner elements of the
             • the grid impedance is mainly inductive,                                        power plant (P and Q dispatchers) are out of the scope of
             • the grid impedance is approximately known,                                     this work. For an in deep analysis of fault operation modes,
             • only reactive power is injected during the fault.                              see [7]. Under this consideration, Fig. 2 shows a simplified
          The first assumption holds in transmission and distribution                         configuration of a grid-connected DG power plant which
          networks with high X/R ratio. The second assumption                                 behaves as an active and reactive power source from a system
          indicates that the grid impedance can be estimated even if                          operator point of view.
          it changes. To do so, a well known grid model or a proper                              The complete system is composed of power sources, dc-
          grid impedance estimator [35]–[39] is required. The third                           link capacitors, inverters, filters, and step-up transformer. The
          assumption is required in some grid codes for deep voltage                          plant is connected to the grid at the PCC. The inductance Lg
          sags because the reactive power capacity can be strongly                            is used to model the grid impedance. The grid voltage vg
          increased. In shallow voltage sags, active and reactive power                       represents the fault produced somewhere in the transmission
          should be simultaneously injected to support and feed the grid.                     or distribution network.
          However, for the sake of clear demonstration, in this work
          active power is set to zero during the sag.
                                                                                              B. Voltage Sag Identification
                   III. DG P OWER P LANT U NDER G RID FAULTS                                    For a proper control under grid fault, the voltage v at
            This section develops three basic aspects to control DG                           the PCC is of interest. The instantaneous phase voltages
          power plants during grid faults. First, the basic architecture                      need to be processed in order to identify the characteristics
          of the plant is presented. Second, the voltage sag is analyzed                      of the voltage sag based on symmetric sequences. Using
          based on symmetric sequences. Finally, the control scheme is                        Clarke transformation in a three-wire system, the instantaneous
          assessed.                                                                           voltages can be expressed in the stationary reference frame
                                                                                              (SRF) as
          A. DG Power Plant Architecture                                                                           
                                                                                                                                          
                                                                                                                                         va
                                                                                                                                                 
            DG power plants are considered a key element to improve                                       vα      1 2 √     −1 −1   √
                                                                                                                =                          vb  .        (4)
          the grid operation. Wind farms and photovoltaic parks are the                                   vβ      3 0         3 − 3
                                                                                                                                             vc
          most widely extended example of DG plants with flexible
          operation during grid faults. These medium to high rated                               The SRF voltages can be separated into positive and
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
          where vα+ and vβ+ are the instantaneous positive sequence                             where each channel has a positive and a negative sequence
          voltage in the SRF and vα− and vβ− are the negative ones.                             term.
             Positive and negative sequence voltages as a function of                              The last stages in Fig. 3 correspond to the current loop,
          time can be represented as                                                            where the references are compared with the measured currents.
                                                                                                The current control loop provides the duty cycles dα and dβ
                                   vα+ = V + cos(ωt + ϕ+ )                                (7)   that are processed by the space vector pulse width modulator
                                                      π                                         (SVM) to drive the switches u1 , u2 , . . . u6 .
                                   vβ+ = V + cos(ωt − + ϕ+ )                              (8)
                                                      2
                                   vα− = V − cos(ωt − ϕ− )                                (9)                  IV. VOLTAGE S UPPORT C ONCEPT
                                                      π
                                   vβ− = V − cos(ωt + − ϕ− )                             (10)     Inside the voltage support block in Fig. 3, the mathematical
                                                      2                                         computation of the reactive power references is obtained.
          where V + , V − are the amplitudes of the positive and negative                       These references are computed on-line so as to achieve the
          sequences respectively, ω is the grid frequency and ϕ+ , ϕ−                           objective in (3). The voltage support service at the PCC (see
          are the initial phase angles of positive and negative sequences.                      Fig. 2) can be expressed as a function of the grid voltage and
            From (7)-(10), the amplitudes V + and V − are obtained as                           the injected current as
                                     q
                              V + = (vα+ )2 + (vβ+ )2                 (11)                                                            diα
                                                                                                                          vα = vgα + Lg                    (17)
                                     q                                                                                                 dt
                              V − = (vα− )2 + (vβ− )2                 (12)                                                            diβ
                                                                                                                      vβ = vgβ + Lg                        (18)
                                                                                                                                       dt
          and the angle ϕ = ϕ+ − ϕ− between the positive and negative                           where vgα and vgβ are the grid voltages in the SRF, and vα ,
          sequence is obtained from                                                             vβ represent the local measures at the PCC. The magnitude of
                                                 vα+ vα− − vβ+ vβ−                              the voltage sag is derived by inserting (5)-(10), (15) and (16)
                                     cos(ϕ) =                                            (13)   in (17) and (18)
                                                     V +V −
                                                 vα vβ + vβ+ vα−
                                                  + −
                                     sin(ϕ) =                                .           (14)
                                                           V +V −                                                        Vg+ = V + − ωLg I +                             (19)
                                                                                                                         Vg−   =V   −
                                                                                                                                        + ωLg I   −
                                                                                                                                                                         (20)
          C. Control Scheme
                                                                                                where
             The behavior of the power plant is determined by the
          injected current at the PCC. Thus, a proper current-mode                                                             2 Q+
                                                                                                                               I+ =                       (21)
          control, capable of riding through voltage sags is required. Fig.                                                    3V+
          3 shows a control block diagram for voltage support during                                                           2 Q−
                                                                                                                         I− =        .                    (22)
          grid faults. The inputs of the controller are local measured                                                         3V−
          voltages v and currents i and the dc-link voltage vdc . Voltages                      From (19)-(22), it can be shown that the magnitude of the sag
          v and currents i are transformed into SRF values. Voltages                            Vg+ , Vg− can be estimated based on measured PCC voltages
          vα and vβ are split into their symmetric components vα+ ,                             V + , V − and injected power Q+ , Q− . Also, the voltage
          vβ+ , vα− and vβ− by using a sequence extractor [41]–[46]. The                        support concept can be explicitly described from (19)-(22).
          voltage support block detects the voltage sag and provides                            By injecting positive sequence reactive power, the positive
          the reactive power references Q+ and Q− to the reference                              sequence voltage at the PCC raises with respect to that of
          generator. The dc-link voltage regulator controls the active                          the grid. Furthermore, by injecting negative sequence reactive
                                    0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                            http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                                                     Vg −
                                  ω                                                           reactive power references are derived based on the grid voltage
                             +          −
                                                                                              estimation.
                                                                     ϕ−
                                                 −
                                                 V
                                                            ωL
                                 gI −
                                                             g
                                                             I
                                            I−
                                                                 +
                                                                                              A. Amplitude of the Phase Voltages
                                                     I
                                                      +
                               ωL
                                                                     V
                                                                                                  Va = (V + )2 + (V − )2 + 2V + V − cos(ϕ)             (23)
                                                                         +
                                                                                                        p
                                                                                                             +  2         2      +
                                                                                                  Vb = (V ) + (V ) + 2V V cos(ϕ − /3)
                                                                                                                        −            −        2π       (24)
          Fig. 4.   Phasor representation of the reactive power control.                                p
                                                                                                             +  2         2      +
                                                                                                  Vc = (V ) + (V ) + 2V V cos(ϕ + /3). (25)
                                                                                                                        −            −        2π
          power, the negative sequence voltage is lower in the PCC than                       The expressions (23)-(25) link positive and negative sequence
          in the grid.                                                                        voltages with the phase amplitudes for a given voltage sag
             The voltage support concept can be graphically explained                         angle. In fact, only two of the three expressions are of interest:
          as in Fig.4. The grid voltage is characterized by the amplitude                     max{Va ,Vb ,Vc } and min{Va ,Vb ,Vc }. By defining
          of the positive Vg+ and negative sequence voltages Vg− .
          According to the symmetric sequences theory, the two phasors                               x = max{cos(ϕ), cos(ϕ − 2π/3), cos(ϕ + 2π/3)}                       (26)
          rotate in opposite directions. Then, Vg+ represents the positive                           y = min {cos(ϕ), cos(ϕ − 2π/3), cos(ϕ + 2π/3)}                      (27)
          sequence grid voltage phasor rotating counter-clockwise at ω
          rad/s. The initial phase angle is ϕ+ . Similarly, the negative                      then
          sequence grid voltage Vg− rotates clockwise. In this case, the                           max{Va ,Vb ,Vc } =
                                                                                                                     p
                                                                                                                      (V + )2 + (V − )2 + 2V + V − x                     (28)
          initial angle is ϕ− . In nominal grid conditions, the amplitude                                            p
          of Vg+ ≈ 1 p.u. and Vg− ≈ 0 p.u. However, during the                                     min{Va ,Vb ,Vc } = (V + )2 + (V − )2 + 2V + V − y.                    (29)
          sag these phasors experience sudden changes in amplitude
                                                                                                 The above expressions can be used to regulate the phase
          and phase jump. The objective of the voltage support is to
                                                                                              amplitudes to the desired values. Henceforth, these voltage
          increase the amplitude of the positive sequence voltage V +
                                                                                              targets will be denoted with a super-index “∗” in order to
          at the PCC compared with the grid sequence voltage Vg+ ;
                                                                                              differentiate them from the measured values
          and to reduce the negative sequence voltage V − compared                                                  q
          with the grid one Vg− . If this is accomplished, then the phase                                                      2           2
                                                                                               max{Va∗ ,Vb∗ ,Vc∗ } = [(V + )∗ ] +[(V − )∗ ] +2(V + )∗ (V − )∗ x
          voltages are increased and the voltage imbalance reduced.
                                                                                                                                                           (30)
          Reactive current injection is the key for this voltage support                                            q
          objective. To inject positive sequence reactive power Q+ , a 90◦                                                     2           2
                                                                                               min{Va∗ ,Vb∗ ,Vc∗ } = [(V + )∗ ] +[(V − )∗ ] +2(V + )∗ (V − )∗ y.
          current leading from the positive sequence voltage is needed                                                                                     (31)
          as obtained from the definition in (15) and (16). On the other
          hand, to inject negative sequence reactive power Q− , a 90◦                         This means that if the injection of reactive power can help the
          current shifted from the negative sequence voltage must be                          measured positive or negative sequence voltages V + , V − to
          injected. When the positive and negative reactive power flow                        achieve the desired objectives (V + )∗ , (V − )∗ , then the phase
          through an inductor, it produces a voltage variation which is                       voltages Va , Vb and Vc will be regulated to the desired values
          proportional to ωLg . In the case of positive sequence reactive                     Va∗ , Vb∗ , Vc∗ . Normally voltage sags exhibit asymmetrical and
          power, the voltage difference is positive, as a result the positive                 time-varying profiles. Thus, in a real scenario, the max and
          sequence voltage at the PCC increases by ωLg I + volts. In the                      min expressions derived in (30) and (31) are also time-varying
          case of the negative sequence reactive power, the voltage drops                     functions.
          by ωLg I − , which helps to reduce the imbalance at the PCC.
          By flexibly combining the amounts of positive and negative
          reactive power, the desired voltage support strategy at the PCC                     B. Targets for Positive and Negative Sequence Voltage
          can be reached, thus regulating the phase voltages according                          As previously stated in section II, the goal is to keep phase
          to (3).                                                                             voltages within the limits established in grid codes. Therefore,
                                                                                              an appropriate phase voltage target should be
                                 V. P ROPOSED S OLUTION                                                                max{Va∗ ,Vb∗ ,Vc∗ } = V                           (32)
            This section develops the mathematical procedure to solve                                                   min{Va∗ ,Vb∗ ,Vc∗ }    = V.                      (33)
          the problem stated in (3). To begin with, the amplitude
          of phase voltages is obtained from the sag identification.                            Replacing the phase voltages in (30) and (31) with the
          Then, the relationship between the phase voltages and voltage                       desired objectives (32) and (33), and solving the voltage
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                Sag detector                                                                     The step by step procedure of this reactive power control is
                                                                                              shown in Fig. 5, from the detection of the sag to the synthesis
              Seq. extract. [41]                vα+ ,vβ+ ,vα− ,vβ− = f (va ,vb ,vc )          of the power references and the current reference generator.
            Sag param. (11)-(14)               V + ,V − ,ϕ = f (vα+ ,vβ+ ,vα− ,vβ− )          Once the sag has been detected and the symmetric sequences
                                                                                              obtained, it should be characterized and identified. Then, to
             Grid seq. (19),(22)           Vg+ ,Vg− = f (V + ,V − ,Q+ ,Q− ,ω,Lg )             implement the proposed control, Vg+ and Vg− need to be
                                                                                              computed based on previous power references Q+ and Q−
            Target seq. (32),(36)                (V + )∗ ,(V − )∗ = f (V,V,ϕ)
                                                                                              and PCC measurements V + and V − according to (19) and
            Power ref. (38),(39)        Q+ ,Q− = f (Vg+ ,Vg− ,(V + )∗ ,(V − )∗ ,ω,Lg )        (20). Then the targets (V + )∗ and (V − )∗ are obtained based
                                                                                              on the desired safety values V and V for a given sequence
            Saturation (43),(44)                Q+ , Q− := f (I + , I − , Imax )              angle ϕ by applying (32)-(36). The new positive and negative
           Current ref. (15),(16)            i∗α ,i∗β = f (vα+ ,vβ+ ,vα− ,vβ− ,Q+ ,Q− )       reactive power references are derived from (38) and (39). Due
                                                                                              to the dynamic behaviour of sequence extractors, the settling
          Fig. 5.   Flow diagram of the proposed control scheme.                              time in perturbed situations last one grid cycle approximately
                                                                                              [42]. For this reason, the power reference block is triggered
          sequence targets, the following expressions are obtained                            once per grid cycle to compute the new values of Q+ and
                    v
                    u                 r                                                      Q− , which remain constant in the flow diagram until the new
                                                     2  2           2
                    u xV − yV 2 +
                    u 2
                                         yV
                                            2
                                              − xV 2
                                                         −  V   − V 2                         update. Once the reactive power references are obtained, a
          (V + )∗ =
                    t                                                                         current saturation strategy ensures that the injected currents
                                          2(x − y)                                            will be safely limited to the maximum rated current of the
                                                                     (34)                     inverter Imax . The procedure to saturate the current injection
                    v
                    u                 r                                                      is developed in the next section.
                                                      2             2
                    u xV − yV 2 −           2                 2
                    u 2                            2                2
                    t                    yV   − xV       −  V   − V
          (V − )∗ =                                                      .                                         VI. C URRENT S ATURATION
                                          2(x − y)
                                                                     (35)                        This section is intended for the case of stiff grids where
                                                                                              the voltage limits strategy proposed in (3) could not be
          Equations (34) and (35) are the basis for the proposed voltage
                                                                                              achieved. Voltage support in stiff grids require higher reactive
          support control because they relate phase voltage targets to
                                                                                              currents. Thus, the required reactive currents can overpass the
          sequence voltage targets. Furthermore, the above equations
                                                                                              safety limits of the inverter. To overcome this issue, a current
          allow us to obtain the targets for any sag, whether symmetric
                                                                                              saturation strategy is developed. To achieve this objective, the
          or asymmetric.
                                                                                              injected currents are mathematically derived and a correction
             For the particular case presented in section II in which the
                                                                                              factor is included to limit the maximum injected current to the
          sag has low imbalance (i.e. max{Va ,Vb ,Vc }−min{Va ,Vb ,Vc } <
                                                                                              safety limit Imax .
          V − V ), the limits in (32) and (33) need to be modified to
                                                                                                 Similarly to (23)-(25), the amplitude of the phase currents
          acomplish the aforementioned objective as
                                                                                              are
            max{Va∗ ,Vb∗ ,Vc∗ } = V + max{Va ,Vb ,Vc } − min{Va ,Vb ,Vc }                                 p
                                                                                                   Ia = (I + )2 + (I − )2 + 2I + I − cos(ϕI )             (40)
                                                                      (36)                                p
                                                                                                              +   2        2     +
                                                                                                    Ib = (I ) + (I ) + 2I I cos(ϕI − /3)
                                                                                                                        −           −           2π        (41)
            min{Va∗ ,Vb∗ ,Vc∗ } = V                                   (37)                                p
                                                                                                              +   2        2     +
                                                                                                    Ic = (I ) + (I ) + 2I I cos(ϕI + /3)
                                                                                                                        −           −           2π        (42)
          C. Reactive Power References                                                        where ϕI = π − ϕ. Note that from (40)-(42), the maximum
                                                                                              phase current can be identified since the reactive power
            Once the desired targets for positive and negative sequence
                                                                                              references and the voltage sequences are all known.
          voltage have been established, the formulation for the reactive
                                                                                                 Once the theoretical injected currents are characterized,
          power references can be easily obtained. The proposed voltage
                                                                                              the limitation process can be started. If the required power
          support control to comply with the voltage limits is obtained
                                                                                              references from (38) and (39) induce a current higher than the
          by rearranging (19)-(22) with the target values
                                                                                            maximum allowable current of the inverter max{Ia , Ib , Ic } >
                           +    3 (V + )∗ (V + )∗ − Vg+                                       Imax , then these references should be modified in order to
                        Q =                                          (38)                     protect the inverter from overcurrents. A method for doing
                                2          ωLg
                                                                                            so is to modify the power references as
                                3 (V − )∗ Vg− − (V − )∗
                        Q− =                              .          (39)                                                           Imax
                                2          ωLg                                                                      Q+       +
                                                                                                                     sat = Q                                             (43)
                                                                                                                                max{Ia , Ib , Ic }
            By injecting these amounts of positive and negative                                                                     Imax
          sequence reactive power, the positive and negative sequence                                               Q−
                                                                                                                     sat   = Q−                                          (44)
                                                                                                                                max{Ia , Ib , Ic }
          voltage targets will be achieved. These targets have been
          computed to keep the maximum and minimum phase voltages                             and the effective value for positive sequence reactive
          within the safety region.                                                           power in the reference generator (15) and (16) should be
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                                                                                                                        −200
                                            TABLE I
                                                                                                                                                                                                              V
          selected as min{Q+ , Q+  sat }, and for the negative sequence as
                                                                                                                                   0.5                                                                         a
                                                                                                                                                                                                              Vb
          min{Q− , Q−  sat }                                                                                                                                                                                  V
                                                                                                                                                                                                               c
             It is worth mentioning that if the current saturation strategy                                                          0
          is activated, then the resulting reactive power is lower than                                                                  0      0.05   0.1    0.15     0.2   0.25   0.3   0.35   0.4   0.45        0.5
                                                                                                                                                                             t(s)
          necessary to meet (3). In this case, even if the voltage support                                                                                           (b) Rms voltage.
          targets expressed in (32) and (33) cannot be accomplished, the
          overcurrent is properly controlled.                                                  Fig. 6.                                       Test1: voltages without voltage support control.
                                                                                                                        −200
          after the sag, 750 W of active power feed the grid; this
          operating point corresponds to an arbitrary wind or solar power
                                                                                                                                   0.5                                                                        V
                                                                                                                                                                                                               a
          production (0.37 p.u.). During the fault, the proposed voltage                                                                                                                                      Vb
          support control is activated. The sequence extractor presented                                                                                                                                      V
                                                                                                                                                                                                               c
          in [41] has been employed to obtain symmetric sequences at                                                                 0
          run-time. For the current loop, a proportional-resonant current                                                                0      0.05   0.1    0.15     0.2   0.25   0.3   0.35   0.4   0.45        0.5
                                                                                                                                                                             t(s)
          controller has been used.                                                                                                                                  (b) Rms voltage.
             Based on [12], three tests have been programmed in order
          to show the dynamic behavior of the proposed reactive power                          Fig. 7.                                       Test1: voltages with voltage support control.
          control:
             • test 1 is a single-phase-to-ground (type II) voltage sag,
                                                                                                  The waveforms of the injected currents are presented in
             • test 2 is a balanced three-phase (type III) voltage sag,
                                                                                               Fig. 8. Note that before and after the sag, the inverter
             • test 3 is a phase-to-phase (type I) sag with slow recovery.
                                                                                               injects balanced active currents, the current amplitudes in this
                                                                                               situation are around 0.37 p.u. However, during the sag, the
          A. Test 1                                                                            currents increase up to 0.9 p.u. It is worth mentioning that
            Test 1 is an unbalanced single-phase-to-ground voltage                             deeper voltage sags or smaller grid inductances will require
          sag which could be caused by a short circuit or lightning                            higher reactive currents to regulate the phase voltages. Also,
          somewhere in the transmission or distribution network. The                           it should be pointed out that during the sag, there exists an
          sag is time-varying to mimic real behavior of grid faults.                           inherent current imbalance due to the injection of both positive
            The PCC voltage waveforms and rms values without voltage                           and negative sequence reactive currents.
          support are presented in Fig. 6(a) and 6(b). These figures                              Fig. 9 clearly shows the proposed solution to the stated
          show the dynamic evolution of the voltage sag when no                                problem. This figure presents the positive and negative reactive
          reactive power is injected. The next two figures, 7(a) and                           power references. These references are computed on-line
          7(b), illustrate the measurements when the proposed voltage                          according to the flow diagram in section V-C. Fig. 9 also
          support control is activated. As can be shown, the voltage at                        shows the instantaneous reactive power q, plotted in the thinner
          the PCC is regulated to the selected voltage limits V = 1.10                         line. As expected, a significant oscillation at twice the grid
          p.u., V = 0.85 p.u. which is the main objective of the proposed                      frequency can be observed during the sag due to the imbalance
          reactive power control.                                                              in the system.
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
−10
                                                                                                                                                                                                1
           phase currents (A)
                                                                 0
                                                                                                                                                                                      0.5                                                                                V
                                                                                                                                                                                                                                                                             a
                                                                 5                                                                                                                                                                                                       V
                                                                                                                                                                                                                                                                             b
                                                                                                                                                                                                                                                                         Vc
                                                             10                                                                                                                                 0
                                                                                                                                                                                                    0     0.05   0.1   0.15   0.2    0.25   0.3      0.35   0.4   0.45           0.5
          Fig. 8.                                                        Test 1: inverter current waveforms (50 ms/div).                                                                                                             t(s)
                                                                 3                                                                                       Fig. 11.                                       Test 2: rms voltages without voltage support.
                                                                                                                                           Q+
                                         Reactive power (kVAr)
                                                                                                                                               −
                                                                 2                                                                         Q
                                                                                                                                           q                                                    1
                                                 150                                                                                                                                            3
                                                                                                                                                                                                                                                                         Q+
                                                                 0                                                                                                                              0
                                                                     0      0.05   0.1   0.15   0.2    0.25   0.3   0.35      0.4   0.45           0.5
                                                                                                                                                                                                    0     0.05   0.1   0.15   0.2    0.25   0.3      0.35   0.4   0.45           0.5
                                                                                                       t(s)
                                                                                                                                                                                                                                     t(s)
          Fig. 10.                                                        Test 1: positive and negative sequence amplitude.                              Fig. 13.    Test 2: Positive and negative reactive power references, and
                                                                                                                                                         instantaneous total reactive power.
          B. Test 2
                                                                                                                                                                                                1
                                                                                                                                                          rms voltage (p.u.)
                                                                                     0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                                                                             http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
          sag is cleared and the system suffers a slow voltage recovery                        [8] J. A. Diaz de Leon, B. Kehrli, and A. Zalay, “How the Lake Bonney
          as a type III (t > 0.3 s).                                                               wind farm met ESCOSA’s, NEMMCO’s and ElectraNet’s rigorous
                                                                                                   interconnecting requirements,” in IEEE Power and Energy Society
             The rms voltages at the PCC when the voltage support is                               General Meeting, 2008, pp. 1 –7.
          activated are shown in Fig. 15. The results show that the                            [9] S. Martin-Martinez, E. Gomez-Lazaro, A. Molina-Garcia, A. Vigueras-
          reactive power control is able to keep the voltages within                               Rodriguez, M. Milligan, and E. Muljadi, “Participation of wind power
                                                                                                   plants in the spanish power system during events,” in 2012 IEEE Power
          the safety limits, which corroborates that the proposed control                          and Energy Society General Meeting, 2012, pp. 1–8.
          strategy can comply with the voltage requirements even in                           [10] F. Blaabjerg, M. Liserre, and K. Ma, “Power electronics converters for
          complex situations.                                                                      wind turbine systems,” IEEE Trans. Ind. Appl., vol. 48, no. 2, pp. 708
                                                                                                   –719, Mar. 2012.
                                                                                              [11] M. Altin, O. Goksu, R. Teodorescu, P. Rodriguez, B.-B. Jensen, and
                                    VIII. C ONCLUSIONS                                             L. Helle, “Overview of recent grid codes for wind power integration,” in
                                                                                                   12th Int. Conf. on Optimization of Electrical and Electronic Equipment,
             This paper presents a reactive power control scheme for                               May 2010, pp. 1152–1160.
                                                                                              [12] M. Bollen, M. Stephens, S. Djokic, K. Stockman, B. Brumsickle,
          three-phase grid-connected inverters operating under voltage                             J. Milanovic, J. R. Gordn, R. Neumann, G. Ethier, F. Corcoles,
          sags. The control objective is to regulate the maximum and                               A. Ferguson, P. Goossens, P. Ligot, A. Lopes Leiria, P. Marteyn,
          minimum phase voltages within the limits established in grid                             A. McEachern, J. Mentzer, I. McMichael, U. Minnaar, K. van Reusel,
                                                                                                   and F. Zavoda, “Voltage dip immunity of equipment and installations,”
          codes for continuous operation. Therefore, DG power plants                               CIGRE/CIRED/UIE Joint Working Group C4.110, pp. 1–279, Apr. 2010.
          can avoid disconnection while helping to mitigate the adverse                       [13] A. Camacho, M. Castilla, J. Miret, J. Vasquez, and E. Alarcón-Gallo,
          effects of grid faults.                                                                  “Flexible voltage support control for three phase distributed generation
                                                                                                   inverters under grid fault,” IEEE Trans. Ind. Electron., vol. 60, no. 4,
             The problem can be divided into two aspects: i) setting the                           pp. 1429–1441, 2013.
          positive and negative sequence targets based on the desired                         [14] X. Guo, X. Zhang, B. Wang, W. Wu, and J. Guerrero, “Asymmetrical
          phase voltages, and ii) setting the positive and negative                                grid fault ride-through strategy of three-phase grid-connected inverter
                                                                                                   considering network impedance impact in low voltage grid,” IEEE Trans.
          reactive power references based on an equivalent impedance                               Power Electron., In press.
          grid model. The control scheme solves these two issues and                          [15] A. Vidal, F. Freijedo, A. Yepes, P. Fernandez-Comesana, J. Malvar,
          presents a step by step realization of the proposal.                                     O. Lopez, and J. Doval-Gandoy, “Assessment and optimization of
                                                                                                   the transient response of proportional-resonant current controllers for
             The proposed reactive power control shows good dynamic                                distributed power generation systems,” IEEE Trans. Ind. Electron.,
          behavior as can be seen from the experimental results. The                               vol. 60, no. 4, pp. 1367–1383, 2013.
          control proposal is able to set the voltage references in any                       [16] J. Yao, H. Li, Z. Chen, X. Xia, and X. Chen, “Enhanced control
                                                                                                   of a DFIG-based wind-power generation system with series grid-side
          type of balanced or unbalanced voltage sag. Moreover, the                                converter under unbalanced grid voltage conditions,” IEEE Trans. Power
          set of experiments prove that the control proposal can even                              Electron., vol. 28, no. 7, pp. 3167–3181, Jul. 2013.
          support time-varying grid faults.                                                   [17] S. Alepuz, S. Busquets-Monge, J. Bordonau, J. Martinez-Velasco,
                                                                                                   C. Silva, J. Pont, and J. Rodriguez, “Control strategies based on
             Future work will focus on the behavior of the control                                 symmetrical components for grid-connected converters under voltage
          scheme in more complex networks, and the selection of                                    dips,” IEEE Trans. Ind. Electron., vol. 56, no. 6, pp. 2162–2173, Jun.
          different control objectives to improve the overall system                               2009.
                                                                                              [18] M. Castilla, J. Miret, J. Sosa, J. Matas, and L. Garcı́a de Vicuna,
          performance. In addition, the constraints and communication                              “Grid-fault control scheme for three-phase photovoltaic inverters with
          requirements for a proper power plant design should be                                   adjustable power quality characteristics,” IEEE Trans. Power Electron.,
          analyzed.                                                                                vol. 25, no. 12, pp. 2930–2940, Dec. 2010.
                                                                                              [19] F. Wang, J. L. Duarte, and M. A. M. Hendrix, “Pliant active and reactive
                                                                                                   power control for grid-interactive converters under unbalanced voltage
                                         R EFERENCES                                               dips,” IEEE Trans. Power Electron., vol. 26, no. 5, pp. 1511–1521, May
                                                                                                   2011.
           [1] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. Timbus, “Overview              [20] M. Reyes, P. Rodriguez, S. Vazquez, A. Luna, R. Teodorescu, and
               of control and grid synchronization for distributed power generation                J. Carrasco, “Enhanced decoupled double synchronous reference frame
               systems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409,                current controller for unbalanced grid-voltage conditions,” IEEE Trans.
               Oct. 2006.                                                                          Power Electron., vol. 27, no. 9, pp. 3934 –3943, Sep. 2012.
           [2] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power        [21] C. Liu, D. Xu, N. Zhu, F. Blaabjerg, and M. Chen, “Dc-voltage
               converters in ac microgrids,” IEEE Trans. on Power Electron., vol. 27,              fluctuation elimination through a dc-capacitor current control for DFIG
               no. 11, pp. 4734–4749, 2012.                                                        converters under unbalanced grid voltage conditions,” IEEE Trans.
           [3] S.-F. Chou, C.-T. Lee, H.-C. Ko, and P.-T. Cheng, “A low-voltage                    Power Electron., vol. 28, no. 7, pp. 3206–3218, Jul. 2013.
               ride-through method with transformer flux compensation capability of           [22] P. Rodriguez, G. Medeiros, A. Luna, M. Cavalcanti, and R. Teodorescu,
               renewable power grid-side converters,” IEEE Trans. Power Electron.,                 “Safe current injection strategies for a statcom under asymmetrical grid
               vol. 29, no. 4, pp. 1710–1719, 2014.                                                faults,” in IEEE Energy Conversion Congr. and Expo. (ECCE), Sep.
           [4] V. Ignatova, P. Granjon, S. Bacha, and F. Dumas, “Classification                    2010, pp. 3929 –3935.
               and characterization of three phase voltage dips by space vector               [23] P. Rodriguez, A. Luna, J. Hermoso, I. Etxeberria-Otadui, R. Teodorescu,
               methodology,” in Int. Conf. on Future Power Systems, Nov. 2005.                     and F. Blaabjerg, “Current control method for distributed generation
           [5] B. Kirby and E. Hirst, “Ancillary-service details: Voltage control,”                power generation plants under grid fault conditions,” in 37th Ann. Conf.
               ORNL/CON-453, Oak Ridge National Laboratory, Oak Ridge TN, Rep.                     on IEEE Ind. Electron. Society (IECON), Nov. 2011, pp. 1262 –1269.
               Dec., 1997.                                                                    [24] Y. Mohamed and E. El-Saadany, “A control scheme for PWM voltage-
           [6] Offprint of the Operation Procedure O.P. 12.2: Technical requirements               source distributed-generation inverters for fast load-voltage regulation
               for wind power and photovoltaic installations and any generating                    and effective mitigation of unbalanced voltage disturbances,” IEEE
               facilities whose technology does not consist on a synchronous generator             Trans. Ind. Electron., vol. 55, no. 5, pp. 2072 –2084, May 2008.
               directly connected to the grid., Asociación Empresarial Eólica, Oct.         [25] H.-S. Song and K. Nam, “Dual current control scheme for PWM
               2008, [Online]. Available: www.aeeolica.org.                                        converter under unbalanced input voltage conditions,” IEEE Trans. Ind.
           [7] J. Martinez and P. Kjaer, “Fast voltage control in wind power plants,”              Electron., vol. 46, no. 5, pp. 953 –959, Oct. 1999.
               in IEEE Power and Energy Society General Meeting, Jul. 2011, pp. 1             [26] M. Castilla, J. Miret, A. Camacho, J. Matas, E. Alarcón-Gallo, and
               –7.                                                                                 L. Garcı́a de Vicuna, “Coordinated reactive power control for static
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
                                                        10.1109/TPEL.2014.2301463, IEEE Transactions on Power Electronics
                 synchronous compensators under unbalanced voltage sags,” in IEEE Int.                                  Antonio Camacho received the B.S. degree in
                 Symp. on Industrial Electronics (ISIE), May 2012, pp. 987 –992.                                        chemical engineering in 2000 and the M.S. degree
          [27]   M. Castilla, J. Miret, A. Camacho, J. Matas, and L. de Vicuna, “Voltage                                in automation and industrial electronics in 2009,
                 support control strategies for static synchronous compensators under                                   both from the Technical University of Catalonia,
                 unbalanced voltage sags,” IEEE Trans. Ind. Electron., In press.                                        Barcelona, Spain. Currently, he is pursuing the Ph.D.
          [28]   T. Lee, S. Hu, and Y. Chan, “D-STATCOM with positive-sequence                                          degree in electronic engineering also at the Technical
                 admittance and negative-sequence conductance to mitigate voltage                                       University of Catalonia. His research interests
                 fluctuations in high-level penetration of distributed generation systems,”                             include networked and embedded control systems,
                 IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1417–1428, Apr. 2013.                                  industrial informatics, and power electronics.
          [29]   S. Chaudhary, R. Teodorescu, P. Rodriguez, P. Kjaer, and A. Gole,
                 “Negative sequence current control in wind power plants with VSC-
                 HVDC connection,” IEEE Trans. Sustainable Energy, vol. 3, no. 3, pp.
                 535 –544, Jul. 2012.
          [30]   “Resolution-P.O.12.3-Response requirements against voltage dips in
                 wind installations,” Red Electrica (REE), Operat. Proced., Oct. 2006.
          [31]   J. Miret, A. Camacho, M. Castilla, L. Garcı́a de Vicuna, and                                           Miguel Castilla received the B.S., M.S. and Ph.D.
                 J. Matas, “Control scheme with voltage support capability for distributed                              degrees in telecommunication engineering from the
                 generation inverters under voltage sags,” IEEE Trans. Power Electron.,                                 Technical University of Catalonia, Barcelona, Spain,
                 vol. 28, no. 11, pp. 5252–5262, Nov. 2013.                                                             in 1988, 1995, and 1998, respectively.
          [32]   J. Mora, J. Melndez, D. Llanos, J. Colomer, and X. Snchez J., Corbella,                                   Since 2002, he has been an Associate Professor in
                 “Classification of sags measured in a distribution substation using a                                  the Department of Electronic Engineering, Technical
                 fuzzy tool,” in ICREPQ Int. Conf. on Renewable Energy and Power                                        University of Catalonia, where he teaches courses on
                 Quality, 2003, pp. 1–7.                                                                                analog circuits and power electronics. His research
          [33]   Procedimiento de operación 7.4: Servicio complementario de control                                    interests are in the areas of power electronics,
                 de tensión de la red de transporte, Red Eléctrica de España, Oct. 2000,                             nonlinear control, and renewable energy systems.
                 [Online]. Available: www.ree.es.
          [34]   “IEEE standard definitions for the measurement of electric power
                 quantities under sinusoidal, nonsinusoidal, balanced, or unbalanced
                 conditions,” IEEE Std 1459-2010, pp. 1–40, Mar. 2010.
          [35]   L. Asiminoaei, R. Teodorescu, F. Blaabjerg, and U. Borup,
                 “Implementation and test of an online embedded grid impedance
                 estimation technique for PV inverters,” IEEE Trans. Ind. Electron.,                                    Jaume Miret (M01) received the B.S. degree in
                 vol. 52, no. 4, pp. 1136 – 1144, Aug. 2005.                                                            telecommunications and the M.S. and Ph.D. degrees
          [36]   A. Moallem, D. Yazdani, A. Bakhshai, and P. Jain, “Frequency domain                                    in electronics from the Technical University of
                 identification of the utility grid parameters for distributed power                                    Catalonia, Barcelona, Spain, in 1992, 1999, and
                 generation systems,” in 26th Ann. IEEE Applied Power Electronics Conf.                                 2005, respectively.
                 and Expo. (APEC), Mar. 2011, pp. 965 –969.                                                                He is currently an Associate Professor with the
          [37]   A. Timbus, R. Teodorescu, and P. Rodriguez, “Grid impedance                                            Department of Electronic Engineering, Technical
                 identification based on active power variations and grid voltage control,”                             University of Catalonia, Vilanova i la Geltrú, Spain,
                 in 42nd Ann. Meeting. Conf. Record of the 2007 IEEE Industry                                           where he teaches courses on digital design and
                 Applications Conference (IAS), Sep. 2007, pp. 949 –954.                                                circuit theory. His research interests include dc–ac
          [38]   S. Cobreces, E. Bueno, D. Pizarro, F. Rodriguez, and F. Huerta,                                        converters, active power filters, and digital control.
                 “Grid impedance monitoring system for distributed power generation
                 electronic interfaces,” IEEE Trans. Instrum. Meas., vol. 58, no. 9, pp.
                 3112 –3121, Sep. 2009.
          [39]   N. Hoffmann and F. W. Fuchs, “Minimal invasive equivalent grid
                 impedance estimation in inductive-resistive power-networks using
                 extended kalman-filter,” IEEE Trans. Power Electron., In press.                                        Ramon Guzman received the B.S. and M.S. degrees
          [40]   K. Ma and F. Blaabjerg, “Thermal optimised modulation methods of                                       in telecomunications engineering from the Technical
                 three-level neutral-point-clamped inverter for 10 MW wind turbines                                     University of Catalonia, Barcelona, Spain in 1999
                 under low-voltage ride through,” IET Power Electron., vol. 5, no. 6,                                   and 2004, respectively. He is currently working
                 pp. 920 –927, Jul. 2012.                                                                               toward the Ph.D. degree in the Power and Control
          [41]   F. Rodriguez, E. Bueno, M. Aredes, L. Rolim, F. Neves, and                                             Electronics Systems (SEPIC) group.
                 M. Cavalcanti, “Discrete-time implementation of second order                                              Since 2001, he is an Associate Professor of the
                 generalized integrators for grid converters,” in 34th Annu. Conf. of IEEE                              Comunications and Signal Theory Department at the
                 Ind. Electron., Nov. 2008, pp. 176–181.                                                                Technical University of Catalonia, Barcelona, Spain.
          [42]   J. Matas, M. Castilla, J. Miret, L. Garcia de Vicuna, and R. Guzman,                                   His current research interests are in the area of
                 “An adaptive prefiltering method to improve the speed/accuracy tradeoff                                nonlinear and adaptive control for three phase power
                 of voltage sequence detection methods under adverse grid conditions,”        converters.
                 IEEE Trans. Ind. Electron., vol. 61, no. 5, pp. 2139–2151, 2014.
          [43]   F. Neves, H. Souza, E. Bueno, M. Rizo, F. Bradaschia, and
                 M. Cavalcanti, “A space-vector discrete fourier transform for detecting
                 harmonic sequence components of three-phase signals,” in 35th Annu.
                 Conf. of IEEE Ind. Electron., Nov. 2009, pp. 3631–3636.
          [44]   P. Rodriguez, A. Luna, R. Muñoz Aguilar, I. Etxeberria-Otadui,                                        Angel Borrell received the B.S. degree in
                 R. Teodorescu, and F. Blaabjerg, “A stationary reference frame grid                                    electrical engineering, M.S. degree in automation
                 synchronization system for three-phase grid-connected power converters                                 and industrial electronics engineering and PhD
                 under adverse grid conditions,” IEEE Trans. Power Electron., vol. 27,                                  in electronics engineering from the Technical
                 no. 1, pp. 99–112, 2012.                                                                               University of Catalonia, Barcelona, Spain, in 1993,
          [45]   P. Rodriguez, A. Luna, I. Candela, R. Mujal, R. Teodorescu,                                            2006 and 2012 respectively.
                 and F. Blaabjerg, “Multiresonant frequency-locked loop for grid                                           Since 1994, he has been an Associate Professor
                 synchronization of power converters under distorted grid conditions,”                                  in the Department of Electrical Engineering, Escola
                 IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 127–138, Jan. 2011.                                    Universitària Salesiana de Sarrià, where he teaches
          [46]   P. Roncero-Sánchez, X. del Toro Garcı́a, A. Parreno Torres, and                                       courses on electrical machines and automation.
                 V. Feliu, “Fundamental positive- and negative-sequence estimator for                                   His research interest are in the areas of power
                 grid synchronization under highly disturbed operating conditions,” IEEE      electronics, electric motor drives and renewable energy systems.
                 Trans. Power Electron., vol. 28, no. 8, pp. 3733–3746, Aug. 2013.
                                 0885-8993 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
                                         http://www.ieee.org/publications_standards/publications/rights/index.html for more information.