Lecture Notes w8
Lecture Notes w8
Mustafa Bağrıyanık
Prof.Dr.
Istanbul Technical University
Department of Electrical Engineering
Maslak, 34422, TURKEY
• Faults
• Short Circuit
• Symmetrical Components
• Calculation of Short-circuit currents
• Examples
Short-circuit Duration
• Self-extinguishing
– fault too short to cause tripping of protections
– example: bird on a line
• Fugitive
– resolved after tripping of the protections and
reclosing
– example: lightning
• Permanent
– does not disappear after tripping of the protections
– example: breakage of the conductor
• Faults are either temporary or permanent
• A permanent fault is one where permanent
damage is done to the system.
• This includes insulator failures, broken wires,
or failed equipment such as transformers or
capacitors.
• Virtually all faults on underground equipment
are permanent.
• Most equipment fails to a short circuit.
permanent fault
Establishment of Isc :
K
• Relationship between peak current and
2,8 rms current :
2,4
2,0
Isc _ peak K Irms
1,6
1,4
1,2
R
0,8 - p
0,4 where K 2 (1 e X
)
0 R
0,2 0,4 0,6 0,8 1,0 1,2 1,4 X
• Typical values:
– X=0: resistive circuit K 2
– R=0: non-damped system K 2 2
– for MV, R/X ~ 0.1 K 2.5
Fault near a generator
Fault near a generator:
Zsc = generator impedance, variable
during the fault.
Switching angle a :
characterizes the shift between
the initial moment of the fault
and the origin of the voltage
wave
a 0 : Asymmetrical state
Ic maximum
Isc peak maximum
a 0 : Asymmetrical state
Ic maximum
Isc peak maximum
Isc does not go through 0 for
several periods !
• Solution :
– specific protection function
– classical protection function if
using generators designed so
substransient transient steady state that Isc = 3xIn for a few
seconds
Contribution of asynchronous motors
1
Current in neg.-sequence system I 2 ( I1 a 2 I 2 a I 3 )
3
1
Current in zero-sequence system I 0 ( I1 I 2 I 3 )
3
V1 V(1) V(2) V(0) I 1 I (1) I (2) I (0) V(1) E - Z(1) I (1)
V2 a V(1) aV(2) V(0) I 2 a I (1) a I (2) I (0) V(2) - Z(2) I (2)
2 2
V3 aV(1) a V(2) V(0) I 3 a I (1) a I (2) I (0) V(0) - Z(0) I (0)
2 2
V(1)
I(1)
E Z(1)
E V(2)
I(1) I(2)
Z(1) Z(2)
I(2) I(0) 0
V(0)
V(1) V(2) V(0) 0 I(0)
Z(0)
Phase-to-earth fault
Equations
Phase 3
Phase 2
Phase 1
I2 I3 0 Z
3E
V1 ZI1 I1
Z(1) Z(2) Z(0) 3Z
3ZE
• Simplified equation : V1 =
– non-resist. fault Z=0 Z(1) Z(2) Z(0) 3Z
– Z(0) ~ 3ZN >> Z(1) + Z(2)
E
I1
ZN
Phase-to-earth fault
Equivalent single phase layout
V(1)
E I(1)
I(1) I(2) I(0) E Z(1)
Z(1) Z(2) Z(0) 3Z
V(2)
E(Z(2) Z(0) 3Z)
V(1) I(2)
Z(1) Z(2) Z(0) 3Z Z(2)
- Z(2)E
V(2) V(0)
Z(1) Z(2) Z(0) 3Z I(0)
Z(0)
- Z(0)E
V(0)
Z(1) Z(2) Z(0) 3Z 3Z
Phase-to-phase fault
Equations
Phase 3 3E
I2 - j
Phase 2 Z(1) Z(2) Z
Phase 1 3E
I3 j
I1 = 0, I2 - I3 Z Z(1) Z(2) Z
V3 - V2 ZI3 E(2Z(2) Z)
V1
Z(1) Z(2) Z
• Simplified equation :
E(a Z - Z(2))
2
– non-resist. fault Z=0
V2
– In general Z(1) ~ Z(2) Z(1) Z(2) Z
E(aZ - Z(2))
3E V3
I2 - I3 Z(1) Z(2) Z
2Z(1)
Phase-to-phase fault
Equivalent single-phase layout
E
I(1) V(1)
Z(1) Z(2) Z I(1)
E Z(1)
E
I(2) -
Z(1) Z(2) Z V(2) Z
I(2)
I(0) 0 Z(2)
E(Z(2) Z)
V(1) V(0)
Z(1) Z(2) Z
I(0)
EZ(2) Z(0)
V(2)
Z(1) Z(2) Z
V(0) 0
2-phase-to-earth fault
Equations
I3 j
I1 = 0 Z Z(1)Z(2) (Z(1) Z(2))(Z(0) 3Z)
V 2 V 3 Z(I2 I3 )
3Z(2)E(Z(0) 2Z)
V1
Z(1)Z(2) (Z(1) Z(2))(Z(0) 3Z)
3Z(2)ZE
V2 -
Z(1)Z(2) (Z(1) Z(2))(Z(0) 3Z)
V3 V2
2-phase-to-earth fault
Equivalent single-phase layout
V(1)
E(Z(2) Z(0) 3Z) I(1)
I(1) E Z(1)
Z(1)Z(2) (3Z Z(0))(Z(1) Z(2))
V(2)
-E(Z(0) 3Z)
I(2) - Z(2)
I(2)
Z(1)Z(2) (3Z Z(0))(Z(1) Z(2))
- Z(2)E V(0) 3Z
I(0) - I(0)
Z(1)Z(2) (3Z Z(0))(Z(1) Z(2)) Z(0)
Example :
Short-circuit current :
25 kA rms
Thermal withstand :
25 kA rms/1 s
Electrodynamic withstand :
2.5 x 25 = 62.5 kA peak.
• Knowing the short-circuit power of a network
allows us to choose various elements of the
panel so as to be able to withstand
considerable heating and electrodynamic
stresses.
• For example, isolating switches, switchboards
and circuit breakers.
• The breaking and closing capacities required
in circuit breakers are directly dependent on
the short-circuit power value at their terminals
and on the devices that are directly
connected to them.
• The breaking capacity, the maximum
amount of current that a circuit breaker
is capable of breaking on occurance of
a short-circuit under specific standard
conditions, must be greater than or
equal to the rated short time withstand
current that can be set up under these
circumstances.
Short-circuit breaking current Ib
Calculation of the short-circuit breaking current Ib is required only when
the fault is near the generator and protection is ensured by timedelayed
circuit breakers. Note that this current is used to determine the breaking
capacity of these circuit breakers. This current may be calculated with a
fair degree of accuracy using the following equation:
Ib = μ . I"k
where μ = is a factor defined by the minimum time delay tmin and the
I"k / Ir ratio which expresses the influence of the subtransient and
transient reactances, with Ir as the rated current of the generator.
• Closing capacity, the maximum
amount of current that a circuit breaker
is capable of withstanding and of
maintaining on a short circuited
installation, must be greater than or
equal to the peak value of the rated
short time withstand circumstances.
• Calculation of the short-circuit power at
the terminals of a synchronous
generator is very complex since the
internal impedance of the latter varies as
a function of time.
• It increases progressively, with the
current decreasing correspondingly and
passing through three typical stages :
– subtransient
– transient
– steady-state
The transient
stages during
short-circuit
occurred at the
terminals of a
synchronous
generator
Z1
Ze Z1 Z2 Ze
Z2
Z1Z 2
Ze Z 1 Z 2 Ze
Z1 Z 2
Association of impedances
in star and delta layouts
Z2 Z21
Z1 Z32
Z3 Z13
Z 21Z13 Z 2 Z1
Z1 Z 21 Z 2 Z1
Z 21 Z 32 Z13 Z3
Z 32 Z 21 Z3 Z2
Z2 Z 32 Z 3 Z 2
Z 21 Z 32 Z13 Z1
Z13 Z 32 Z1Z 3
Z3 Z13 Z1 Z 3
Z 21 Z 32 Z13 Z2
Diagram reduction
Example
E E E
Source
Rs
Line Xs Ra
R
Rl Xa
Xl
R1 R2 Rb
X
X1 X2 Xb
Cable 1 Cable 2
Diagram reduction example
• Upstream network
– outside power supply source
– positive-sequence voltage symmetric three-phase system
– delivers the rated voltage under all circumstances
3Vn 2 Un 2
Ssc Zsc
Zsc Ssc
• Impedance transformation:
All impedances must be brought to the level of the rated voltage at the
fault point
Up, Ip
Zp 2
Up
Zp Zs Zp k 2 Zs
Us
Up
k , transformation ratio
Zs Us
Us, Is
Transformer characteristics
Typical impedances
Transformer coupling
(detected at R X(1) X(2) X(0)
secondary end)
without neutral
PCu Un 2
Yyn or Zyn, forced flow Zsc Usc X(1) 10 to 15 X(1)
3 In 2 Sn
Dyn or YNyn 4% Usc 20% X(1)
? Zt(0) ?
• There is a path that enables the zero-
sequence current to circulate in the
? ? Zt(0)
transformer windings without circulating
through the system (delta coupling)
Transformer characteristics
Zero sequence layouts: examples
Coupling of Zero-sequence Coupling of Zero-sequence
windings layout windings layout
Zt(0)
Zt(0)
Zt(0)
Zt(0)
Zt(0) Zt(0)
Characteristics of rotating machines
Impedances expressed as %
• For rotating machines, the values of subtransient impedances, X", transient
impedances, X' and synchronous impedances, X, are expressed as
percentages rather than in ohms.
Subtransient 10 to 20 %
Transient << X 15 to 25 % 10 to 20 % 5 to 10 %
at 20 C
63 kV system
PROBLEM:
Ssc = 800 MVA
R/X = 0.1
• Calculate the rms value of the
current circulating at the 6.3 kV
Transformer end during a three-phase non-
63 / 6.3 kV
Sn = 10 MVA resistive short-circuit at 6.3 kV
Usc = 10%
Pcu = 1%
3-phase SC • Draw conclusions concerning
the effect of the circuit
resistance
Calculation of 3-phase Isc, effect of R
ANSWER:
R X
( 6.3 10 )
2 3 2
Uns
Network : Zsc = 0.05
800 10
6
Ssc 0.005 0.05
R = 0.1 X X Zsc
( 6.3 10 )
2 3 2
PCu Uns
Transformer : R = 0.01 0.04
10 10
6
Sn Sn
0.04 0.4
( 6.3 10 )
2 3 2
Usc Uns
Z= 0.1 0.4
10 10
6
Uns Sn
: Z = 0.045 0.45 0.45
2 2
Total 0.045 0.45
6.3 10
3
Uns
Isc = 8083 A
3 Zsc 3 0.45
the resistance R is NEGLIGIBLE
Exercise: Calculation of 3-phase Isc, effect
of MV cables
63 kV system
PROBLEM:
Ssc = 800 MVA
R/X = 0.1
• Calculate the rms value of the
Transformer current circulating at the 6.3 kV
63 / 6.3 kV end during a three-phase non-
Sn = 10 MVA
Usc = 10%
resistive short-circuit 2 km
Pcu = 1% downstream in the cables
3-phase SC
Calculation of 3-phase Isc, effect of MV cables
ANSWER:
Cable : R X
1 1 2000
= mm / m R = = 1.18
2
Network
34 34 50 + trans. 0.045 0.45
x 0.15 / km X 0.15 2 0.3
Cable 1.18 0.3
63 kV system
PROBLEM:
Ssc = 800 MVA
R/X = 0.1
• Establish the equivalent single-
phase layouts according to the
Transformer breakdown of the system into
63 / 6.3 kV
Sn = 10 MVA symmetrical components
Usc = 10%
Pcu = 1%
2-phase SC • Calculate the rms value of the
current circulating at the 6.3 kV
end during an isolated non-
resistive
2-phase short-circuit at 6.3 kV
Calculation of 2-phase Isc
ANSWER:
I(1)
E Zr(1) Zt(1) I1 0 (SC between phases 2 & 3)
I(2) I2 a ² I(1) + a I( 2 ) + I( 0 ) = (a² - a)I(1)
Zr(2) Zt(2)
3 E
I2 - j 3 I(1) =
Zr(0) Zt(0) 2( Zr (1) Zt (1))
with : R 0, Xr(1) = 0.05, Xt(1) = 0.4
E
I(1)
Zr (1) Zr ( 2 ) Zt (1) Zt ( 2 )
6.3 10
3
I( 2 ) I(1),I( 0 ) 0 I2 = -I3 = 7000 A
Zr (1) Zr ( 2 ), Zt (1) Zt ( 2 ) 2 0.45
Exercise: Calculation of phase-to-earth Isc
63 kV system
PROBLEM:
Ssc = 800 MVA
R/X = 0.1
• Establish the equivalent single-
phase layouts according to the
Transformer breakdown of the system into
63 / 6.3 kV
Sn = 10 MVA symmetrical components
Usc = 10%
Pcu = 1%
phase-to-earth SC • Calculate the rms value of the
current circulating at the 6.3 kV
end during a non-resistive
phase-to-earth short-circuit at
6.3 kV
Calculation of phase-to-earth Isc
ANSWER:
I1 = 8394 A
2 0.05 3 0.4
I(1) I( 2 ) I( 0 )
I1_ phase - to - earth > I1_3 - phase
E
I( 0 ) NB : In the case of a transformer with the neutral
Zr (1) Zr ( 2 ) Zt (1) Zt ( 2 ) Zt ( 0 )
earthed by impedance Z, it is necessary to
Zr (1) Zr ( 2 ), Zt (1) Zt ( 2 ) Zt ( 0 ) add 3Z to Zt(0)
(see chapter on earthing systems)
the reactances of the equivalent circuit
• The reactances entered in column 3 are added in the case of series
circuits, while the susceptances in column 4 are added for parallel
configurations.
• Columns 6 to 9 are for calculating the maximum short-circuit current and
the symmetrical breaking current.
• To determine the total reactance of the network at the fault location, one
first adds the reactances of the 220 kV network and of transformer 1.
• The sum 0.1438 % /MVA is in column 3, line 3.
• The reactance of the generator is then connected in parallel to this total.
• This is done by forming the susceptance relating to each reactance and
adding the susceptances (column 4, lines 3 and 4).
• The sum of the susceptances 15.1041 % /MVA is in column 4, line 5.
• Taking the reciprocal gives the corresponding reactance 0.0662 %/MVA,
entered in column 3, line 5.
• To this is added the reactance of transformer 2.
• The sum of 0.9412 %/MVA is in column 3, line 7.
• The reactances of the induction motor and of the induction motor group
must then be connected in parallel to this total reactance.
• Again this is done by finding the susceptances and adding them
together.
• The resultant reactance of the whole network at the site of the fault,
0.7225 %/MVA, is shown in column 3, line 10.
• This value gives
References
• “ABB Switchgear Manual”.
• Schneider Electric, “Calculation of
short-circuit currents”, Cahier
technique.
• “Electrical Installations Handbook”,
Günter G. Seip, John Wiley & Sons.