Data Sheet
CL80 InRow Cooler
ColdLogik CL80 InRow Coolers are fitted alongside cabinets in
containment, typically being IEC 297 3 and EIA STD 310 compliant. The
coolers ensure efficient thermal and energy performance by removing
the heat generated by the active equipment , preventing hot exhaust
air entering space where it is not permitted.
Ambient air is pulled into the cabinet by the active equipment fans –
the hot air produced by the equipment passes over a heat exchanger
matrix, either by its own velocity or being pulled through via EC
centrifugal fans mounted in the CL80. The heat is rejected to coolant
and chilled air is passed back into the room at a predetermined
ambient temperature.
The InRow coolers can be sited within an existing data centre to work
with existing computer room air-conditioning to provide additional
cooling. They also reduce energy consumption and remove hot spots.
www.usystems.com
August 2020 iss2
CL80 InRow Cooler Technical Specifications
300w 600w
Max Cooling Capacity 68kW 75kW
General
Height 42U (47U, 48U, 52U with blanking plate)
Width 300mm 600mm
Depth 1000mm/1200mm
Weight - Dry 140 200
Weight - Wet 155 212
Volume Capacity 2.82 US gallons / 11 litres
Power Requirement Phase to phase(208v)/phase to neutral(230v)
Fans
Backward curved centrifugal fans, Incorporating EC technology, IP44 rated
Number of 6
Current consumption, each fan 1.25A maximum
Air flow, each fan 839cfm/1,425 m³/hr
Sound pressure, noise per fan 70dBA@1 metre/3.3’
Fan Requirement six fan coolers @ 208V 60Hz /230V 50Hz
Fan Speed %/cfm Power for six fans @ 208V 60Hz Power for six fans @ 230V 50Hz
25%/1255cfm 1.6A/333w 1.5A/302w
30%/1505cfm 1.8A/375w 1.6A/339w
35%/1756cfm 2A/416w 1.8A/376w
40%/2007cfm 2.3A/478w 2.1A/632w
45%/2258cfm 2.6A/541w 2.4A/489w
50%/2509cfm 2.9A/603w 3.7A/545w
60%/3011cfm 3.5A/728w 3.2A/658w
70%/3513cfm 4.3A/895w 3.9A/804w
80%/4015cfm 5.1A/1061w 4.7A/959w
90%/4516cfm 6.1A/1269w 5.5A/1147w
100%/5018cfm 7.1A/1477w 6.4A/1335w