PowerIT Power Factor Controller RVT
The ultimate Power Factor Controller
RVT : The Ultimate Power Factor Controller
Measurements and Easy commissioning Communication:
Monitoring: with automatic setting of: Modbus (RS485)
Active power (kW) Phase shift (for special connections) Printer connection
Apparent power (kVA) C/k (starting current) Input: day/night cos ϕ
Reactive power (kvar) Number of outputs Input: external alarm
Reactive power (kvar) to reach the target cos ϕ Switching sequence Output: alarm relay
Voltage (V) Output: fan relay
Current (A)
Temperatures (°C or °F)
Total Harmonic Distortion on Voltage : THD V (%) Indicates a demand for switching
Locking icon Active outputs on/off a capacitor step
Total Harmonic Distortion on Current : THD I (%)
Frequency (Hz)
Measurements:
Cos ϕ
Voltage Harmonics : U2 up to U49 (%-spectrum)
Current Harmonics : I2 up to I49 (%-spectrum)
Number of steps needed to reach the target cos ϕ
Number of switching per output
Programmable parameters:
Target cos ϕ (day/night)
Target cos ϕ in regenerative mode
Phase shift (for special C.T. connections)
C/k (starting current)
Switching sequence (customizable)
Number of active outputs
Switching delay times (on/off/reset)
Switching strategy (linear or circular
- normal or integral - direct or progressive)
Alarm thresholds
Single phase or three phase connection
Help button Keypad Alarm
Overtemperature
Full
(fan relay)
graphics
display
with
backlighting
Voltage harmonics spectrum Voltage monitoring Help message
2 ABB
Powerful features
Full graphics display Guided navigation and programming
With its large dimensions and the clear positioning of Information and warning messages guide you all the
information, prompts and icons, the RVT graphics way in the menu navigation and RVT programming.
display offers a high level of readability and an
unprecedented level of viewing comfort. Fully automatic set-up
C/k, active outputs, switching sequence and phase shift
Menu navigation may be automatically set-up.
The clever organization of menus and items makes the
navigation easy and intuitive. Easy commissioning
The fully automatic set-up of the RVT makes the
Communication commissioning quick and easy.
The RVT-Modbus can be linked to a supervision system
through its Modbus adapter (RS485). All parameters Programmable protection thresholds
settings and measurements are accessible remotely (see Programmable thresholds allow you to protect the
page 6). capacitor bank against such event as over and
undervoltage, overtemperature and excessive harmonic
HELP button distortion.
The Help button gives you an instant access to a
comprehensive description of all RVT's features and Backlighting
functionality. The backlighting allows ease of operation under any
ambient lighting conditions. The backlighting is always
ON as long as the RVT is energised.
Network information and capacitor bank monitoring High ambient temperature rating
The RVT computes and displays network and capacitor The RVT is suitable for hot environments thanks to its
bank information such as voltage, current, harmonics maximum ambient temperature rating of 70°C.
spectra and much more.
Multi-voltage and multi-frequency
Multi-language support The RVT may be connected to voltages in the range
The RVT allows you to choose its working language 100-440Vac, 50 or 60Hz.
between English, French, German and Spanish.
Works with 5A and 1A CT’s
Protective transparent door Both 5A and 1A CT’s may be connected to the RVT.
The keypad and display are protected by a transparent
door.
ABB 3
Powerful features
Customizable measurements overview
The RVT allows you to sort your preferred data in such a way that they are viewed first on the graphics display.
Day – night target cos ϕ
The RVT allows the programming of two different target cos ϕ values.
Locking switch
Unauthorised use may be blocked by a switch at the back of the RVT.
Alarm logging
The last five alarm messages are recorded and may be consulted at any time.
Event logging
For selected measured parameters and according to the threshold set, the RVT records:
- the maximum value logged between two resets.
- the total duration during which the measured value has exceeded the threshold.
Example: event logging of Total Harmonic Distortion on Voltage
maximum recorded
%
threshold
t1 t2 t3
time
total duration = t1 + t2 + t3
Menu navigation
4 ABB
Easy Commissioning
A dedicated menu allows the commissioning of the RVT in only a few simple steps.
Select “Automatic” in the commissioning menu
Validate automatic setting
Enter the Current Transformer scaling
Parameters are automatically set
Enter the target cos ϕ
ABB 5
Optional accessories
Modbus adapter
All RVT controllers are Modbus communication enabled. The Modbus adapter is
an optional item which allows communication with a monitoring system.
All RVT parameters are available (including harmonic spectrum and tables)
through an RS485 Modbus adapter.
All RVT parameters are accessible and locking parameters allows to limit their
access through the Modbus communication only.
External probes for temperature measurements
Two temperature probes may be connected to the RVT.
The RVT will close the fan relay if a temperature threshold is exceeded.
Information on temperature may be recorded with the event logging function.
Printer connection
The RVT can be connected to a printer through the isolated RS-232 serial port.
ABB printer cable is needed.
IP54
The RVT front plate offers an IP43 protection degree in standard version.
The gasket accessory enhances the standard RVT protection degree to IP54.
6 ABB
Wiring diagram
PL2, PL3 : power supply A, A : output relays’ common source
ML2, ML3 : measurement 1-12 : outputs
OPTO1 : day/night input F1, F2 : output relay FAN
k, l : current transformer M1, M2 : output relay ALARM
OPTO2 : external alarm input
MODBUS ADAPTER :
T1, T2 : temperature probe inputs A, B : Modbus (RS485)
H, L : CAN : extension module GND : Ground
Dimensions
(Front plate)
(Overall)
With Modbus Without Modbus
adapter adapter
ABB 7
Technical Specifications
Measuring system: Step configuration:
Micro-processor-based system for balanced three-phase networks or Automatic, fixed, disabled.
single-phase networks. Full graphics display with backlighting:
Supply voltage: 64 x 132 pixels with extra symbols.
From 100Vac up to 440Vac. Number of outputs:
Consumption: RVT 6: programmable up to 6 outputs.
15 VA max. RVT 12: programmable up to 12 outputs.
Connection type for measuring circuit and power supply: Switching time between steps:
Phase-phase or phase-neutral Programmable from 1s to 18h.
Voltage tolerance: Saving-function:
+/- 10% on indicated supply voltages. All programmed parameters and modes are saved in a non-volatile
memory.
Voltage measurement:
The IndustrialIT wordmark and all above-mentioned product names in the form PowerIT are registered or pending trademarks of ABB.
Up to 690Vac or higher with voltage transformer. Power outage release:
Accuracy : 1% full scale. Automatic disconnection of all capacitors in case of a power outage
longer than 20ms.
Frequency range:
50 or 60 Hz +/- 5% (automatic adjustment to network frequency). Automatic adaptation to the phase-rotation of the network and
the CT-terminals.
Current input:
5A or 1A (RMS) (class1 C.T.). Not affected by the harmonics.
Current input impedance: Working with passive and regenerative loads (four-quadrant
<0.1 Ohm. operation).
Output contact rating: LCD contrast automatically compensated with temperature.
-Max. continuous current: 1.5A (ac) – 0.3A (110V dc). Operating temperature:
-Max. peak current: 8A. -20° C to 70° C.
-Max. voltage: 440 Vac.
-Terminal A-A are rated for a continuous current of 18A (9A/terminal). Storage temperature:
- 30° C to 85° C.
Alarm contact rating (voltage free contact):
- Normally closed contact. Mounting position:
- Max. continuous current: 1.5A. Vertical panel mounting.
- Rated voltage: 250Vac (max. breaking voltage: 440Vac). Dimensions:
Fan contact rating (voltage free contact): Front plate : 144 x 144 mm (h x w).
- Normally open contact. Overall : 144 x 211 x 67 mm (h x w x d).
- Max. continuous current: 1.5A. Weight:
- Rated voltage: 250Vac (max. breaking voltage: 440Vac). 1.0 kg (unpacked).
Power factor setting: Connector:
From 0.7 inductive to 0.7 capacitive. Cage clamp type (2.5mm2 single core cable).
Starting current setting (C/k): Front plate protection:
- 0.01 to 5A. IP 43 (IP54: on request).
- automatic measurement of C/k.
Relative humidity:
Switching sequences: Maximum 95%, non-condensing.
1:1:1:1:1:….:1 - 1:2:2:2:2:…..:2 - 1:2:4:4:4:…..:4 - 1:2:4:8:8:….:8
1:1:2:2:2:….:2 - 1:1:2:4:4:…..:4 - 1:1:2:4:8:…..:8 - 1:2:3:3:3:….:3 CE Marked.
1:2:3:6:6:….:6 - 1:1:2:3:3…...:3 - 1:1:2:3:6…...:6 UL Recognized (file n° NKCR2.E163424).
and any other customer programmable sequence.
CSA certified for use in 120Vac system voltage.
Modbus baud rate:
110 - 300 - 600 - 1200 - 2400 - 4800 - 6900 - 19200 - 38400 - 57600 Article number for ordering:
RVT-6 2GCA289004A0050
RVT-12 2GCA289005A0050
June 2007
This product has been tested and certified by ABB Group as IndustrialIT Enabled™ . All product information
is supplied in consistent electronic format, based on ABB Aspect Object™ technology. Plug and Produce™
installation and integration with other Industrial IT certified products is available through the ABB Aspect Integrator™
2GCS302016A0050
Platform.
While all care has been taken to ensure that the information contained in this publication is correct, no responsibility
can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at
any time in the light of technical or other developments. Technical specifications are valid under normal operating
conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for
www.abb.com/lowvoltage indirect or consequential damages.