60 - 80 - 100 - 125 - 160 - 200 - 250 - 300 KVA
Three-phase UPS
Performance and reliability
for any kind of critical applications
                           ... we commit
                                  B9000 combines management of THD and power factor, low
                                  cost of ownership and power protection in a highly reliable
                                  solution guaranteed by the most advanced technology
INFORMATION AND COMMUNICATION
                                  Low THDi and power factor                         High efficiency reduces overall
TECHNOLOGY
                                  performance enhance compatibility                 cost of ownership
• Data centers                    with input mains and generators
• Server farms                    The BORRI B9000 UPS uses a new input              The B9000 operates at a high efficiency
• Communication rooms             IGBT rectifier and an advanced PFC (Power         of up to 94%, which reduces utility costs.
• Broadcast                       Factor Control) capable of keeping input          Moreover higher system efficiency reduces
• Networking                      current Total Harmonic Distortion (THDi)          facility air conditioning costs, increasing
                                  at a low level (< 3%), as well as the input       overall reliability. Because of the technology
CRITICAL ELECTRICAL ENGINEERING   power factor very close to unit (0,99).           and topology used, no additional losses
                                  The key benefits are that the UPS is              are generated to get low input harmonics
• Industrial controls             therefore compatible with the upstream            or input/output galvanic isolation.
• Manufacturing machinery         source, the mains or any kind of generator        Additionally, Eco-mode function can be
• Process equipment               and the transfer of power between source          set. In this intelligent mode, the mains line
• Transportation                  and load is more efficient. This results in a     is continuously being monitored in order to
• Building automation             saving in terms of scale of sources, cables       supply with high reliability the load by the
                                  and protective devices.                           same line. If the line is downgraded and
                                                                                    required to be conditioned, the inverter
                                                                                    supports the load in less than 4msec.
                                                                                    Once the load is accessed to properly
                                                                                    operate in this way, in Eco-mode efficiency
                                                                                    is considerably increased, allowing high
                                                                                    energy saving.
                                  Double conversion topology offers                 The most advanced technology
                                  protection for every application
                                  The on-line double conversion topology            If your business application needs an
                                  (VFI, Voltage and Frequency independent)          extremely flexible and reliable UPS
                                  with built-in inverter transformer completely     protection, B9000 delivers advanced
                                  isolates output power from all the input          features     based     on    state-of-the-art
                                  power anomalies and delivers fully                total digital control (Tricore technology
                                  conditioned, pure sine-wave output.               incorporating both DSP and μC).
                                  B9000 is designed to provide excellent            The design ensures that auxiliary
                                  output voltage, suited to very demanding          power supplies and processors are no
                                  applications with either 100% step load,          longer single points of failure that would
                                  unbalanced, non-linear or modern IT loads         compromise high availability of clean power
                                  with a leading power factor up to 0,9.            to the load. In fact, with B9000 distributed
                                                                                    control architecture, there will always be a
                                        F                   F
                                                                                    UPS circuit protecting the load.
                                    3x1L-N
                                                                                    The status of the most critical components
                                        F
                                                                                    is constantly monitored. This allows
                                                                                    predictive maintenance and avoids
                                    3x1L-PE                                1x3L-N
                                                  +B -B
                                                                                    unexpected breakdowns
                                  Accurate Battery Management
                                  Since batteries are electro-chemical              damaging deep discharges.
                                  devices, their performance gradually              An automatic temperature compensation of
                                  decreases over time. B9000 performs               battery charge voltage can be implemented,
                                  Accurate Battery Management according to          properly charging the battery and greatly
                                  the battery manufacturers’ requirements.          extending battery life.
                                  Following a UI characteristic curve, the          By means of the DCM (Dynamic Charging
                                  charger starts at a constant current              Mode) function, very long battery autonomy
                                  appropriate for the battery type used,            times can be achieved without increasing
                                  preventing detrimental excess charging.           total charging time. It is achieved further
                                  In addition to the float voltage level, boost     increasing the maximum battery charge
                                  charge can be set, optimising the recharge        current, without the whole inverter power
                                  time when there may be consecutive power          being drawn by the load.
                                  outages within a short period.                    An integrated periodical battery function
                                  Accurate Battery Management also                  tests and monitors battery health, providing
                                  reduces the residual current ripple, one          advance notification to guide preventive
                                  of the causes of premature battery wear,          maintenance.
                                  as well as protecting the battery from
                Borri B9000                                                                                         3/3
Parallel systems for redundancy or
capacity increasing
The parallel UPS configuration is provided                      Bypass
with control for operation of both redundant                  Mains
and capacity increase.
The parallel control is fully digital and acts
on both active and reactive power on each
output phase, allowing an accurate load
current sharing among the UPSs’, even
during transient conditions.
Parallel control is distributed (not centralised
control, but on each UPS microcontroller)
and communication among units uses CAN
BUS connection loop, providing a highly
reliable system without “single points of
failure”.
Extremely simple parallel control and
                                                                      Load
interconnections make easy installations
and on field upgrading, adding new units
to the system according to the customer’s
needs.
Easy installation, operation and
maintenance
The B9000 can be installed in close
proximity against rear and side walls or
other cabinets. Cooling air is expelled
through top vents. A significant space
saving and a compact design allow a lower
deployment cost in locations where floor
space is in short supply.
Despite the compact design, most of the
components, including the critical ones,
are accessible from the front of the cabinet.
Front panel access facilitates service and
operation, thereby reducing Mean Time to
Repair (MTTR)
User Interface and Accessories                                               Removable blowers
                            User-friendly interface
                                                                                      Front access
                                        Communication
                                                                                          Options
            Monitoring, managing        • RS232 serial port
                                                                                          • Parallel capacity/redundancy
            and shutdown software       • USB port
                                                                                          • Isolation transformer
                                        • EPO
                                                                                          • External bypass
                                                                                          • External battery cabinets
                                        Optional
                                                                                          • Battery switch box
                                        • Web/SNMP
                                                                                          • Battery thermal probe
                                        • ModBus
                                                                                          • Transformers for voltage adaption
                                        • Relays
                                                                                          • Top cable entry
                                        • Modem
                                        • Remote panel
   Printed in Italy 03-2008 - ART & PRINT: DEDALO Printing snc - Bibbiena (Ar)
                                                                                 Rating	                            60 kVA	      80 kVA	 100 kVA	 125 kVA	 160 kVA	            200 kVA	 250 kVA	 300 kVA
                                                                                 Capacity (kVA/kW)	                  60/48	       80/64	  100/80	 125/100	 160/128	            200/160	 250/200	 300/240
                                                                                 Dimensions WxHxD (mm)	                                815x1670x825	                                  1200x1900x860
                                                                                 Weight (kg)	                        580	         600	     630	      662	        720	            870	     1020	     1200
                                                                                 Input/output connection	                                       Hardwired (dual input)
                                                                                 Battery	                                                        External, 300 cells
                                                                                 Input	
                                                                                 Nominal voltage	                                         220/380, 230/400, 240/415 Vac three phase
                                                                                 Voltage range	                                                   -20%, +10% from nominal
                                                                                 Frequency	                                                          50/60 Hz (45–65 Hz)
                                                                                 Power factor	                                                               0,99
                                                                                 Current distortion (THDi)	                                                 < 3%
                                                                                 Output	
                                                                                 Nominal voltage	                                       220/380, 230/400, 240/415 Vac three phase
                                                                                 Frequency	                                                               50/60 Hz
                                                                                 Voltage regulation	                        ±1% static; ± 5% dynamic 100% load change, <20 ms recovery time
                                                                                 PF acceptable without de-rating	                                  Lagging to 0.9 leading
                                                                                 Overload capacity	                             101–125% for 10 min (on-line); 126–150% for 1 min (on-line);
                                                                                 	                                                               1000% for 1 cycle (bypass)
                                                                                 Efficiency	                                                                >93%
                                                                                 (Eco-mode)	                                                                >98%
                                                                                 Options	                                   Parallel capacity/redundancy; isolation transformer; external bypass;
                                                                                 	                                           external battery cabinets, battery switch box; battery thermal probe;
                                                                                 	                                           transformers/autotransformers for voltage adaption; top cable entry
                                                                                 User Interface	
                                                                                 Front panel	                                    Graphical LCD display, mimic with LED’s and keyboard
                                                                                 Standard communication ports	               RS232 serial port, USB port, Remote Emergency Power Off input,
                                                                                 	                                                             battery switch monitoring port
                                                                                 Optional	                                      Web/SNMP, ModBus, relay, modem cards; remote panel;
                                                                                 	                                                     monitoring, managing and shutdown software
                                                                                 Environmental	
                                                                                 Operating temperature	                                                         0°C – +40°C
                                                                                 Storage temperature	                                                          -10°C – +70°C
                                                                                 Altitude	                                                                        <1000 m
                                                                                 Audible noise at 1 meter (dBA)	                                                    <60
                                                                                 Standards and Certification	
                                                                                 Marking	                                                                           CE
                                                                                 Safety	                                                                      IEC EN 62040-1
                                                                                 EMC	                                                                         IEC EN 62040-2
                                                                                 Test and Performance	                                                        IEC EN 62040-3