Cuprion
Cuprion
Appendices
Bio-fouling problems associated with sea water system are well known and if allowed
unchecked can cause complete blockage of pipes necessitating expensive repairs.
Barnacles, limpets, mussels and tubeworms can colonize pipe work rapidly once they
settle during bloom periods. To ensure plant efficiency settlement of bio-fouling must be
prevented.
Seawater is treated by the release of controlled quantities of copper ions into the intake
flow. This is achieved by passing a low d.c. current from the control panel, between the
anodes and cathode frame. The required dosage of copper ions to deter settlement is
extremely small and measured in micrograms per litre of seawater. Therefore, relatively
small quantities of copper are required to provide protection dependent upon the flow rate
and life required.
The function of the aluminium anodes is to produce a floc of aluminium hydroxide. This
floc assists with transporting the copper ions. Additionally the aluminium hydroxide is
carried through the system to repair areas where the protective coating has been
damaged and provide corrosion protection.
Each of the 4 No. seawater intakes are fitted with an electrolytic anti-fouling electrode
screen, and dosing is provided to each unit at pre-determined levels to suit operational
conditions from it’s control panel. Drawing P12504-08 details the system arrangement.
The dosing levels are a function of the anode current applied to the electrode. The
current levels are used to set-up the system to meet the criteria. Table 5.1 shows the
current settings.
Output Voltage: 0 to 6 V / 0 to 12 V
2.6.1 Electrode
The electrode screen is factory wired with a 10 metre cable tail for direct connection into
the junction box provided.
This cabling system is to be provided by the installer/other and must be selected and
protected to suit the environmental constraints and electrode circuit current requirements.
The maximum permissible volt drop is limited to 1 V to enable the electrode current to be
achieved on the 0 to 12 V output setting.
Note
When installing a 3 core cable, the cathode (-ve) conductor will carry the summation of the
copper and aluminium circuit currents.
Each electrode is supplied with high purity copper and aluminium anodes incorporated
into a zinc coated mild steel cathode framework encapsulated into end caps. The end
sections of the electrode unit are protected with a two part high build isocyanate cured
coal tar/epoxy resin based coating.
The control panel has regulated d.c. outputs to suit the specific electrode operating criteria
housed within the panel enclosure.
The panel rectifies the a.c. supply providing a controlled d.c. output for connection to the
electrolytic anti-fouling electrode assembly. One positive output is connected to the
copper anode and the other positive output is connected to the aluminium anode. The
negative return of the unit is commoned from the steel structure supporting the copper
and aluminium anodes.
The flow of d.c. current from each anode in an electrolytic anti-fouling system is required
to be constant for a given rate of flow of water. This requirement dictates that the d.c.
supply operates in a constant current mode and each d.c. supply is capable of being set
to any value of current within the maximum stated rating of the d.c. output. Each output
control system incorporates a current limit facility to prevent the maximum design current
being exceeded. It should be noted that the maximum output will be reduced should the
d.c. driving voltage to achieve the maximum current be greater than the 8 V d.c. available
from the unit.
The level of current to flow is different for each anode. The current to the copper anode
always a higher value than the aluminium anode.
Pump Run
Hours Counter
Voltmeter
Ammeter
4mm Jack
Plugs
Set Low
Cu/Al Selector Current
Switch
Low Current
Alarm
Set High
Current
Fig 1
The incoming a.c. supply is connected to the primary of the main transformers (fig 2 & 3)
via the door interlocked isolator and the miniature circuit breaker as applicable to the
respective electrode system (fig 4).
fig 2 fig 3
fig 4
fig 5 fig 6
Control of output d.c. is achieved by controlling phase firing angle pulses derived from
control module pcbs (fig 7). The firing angle is controlled by multi-turn potentiometers
fitted to the control facia and identified as ‘set low current’ and ‘set high current’ for each.
fig 7
fig 8
The output d.c. voltage to the copper and aluminium anodes is monitored with voltmeters
mounted on the inner door and protected by 250mA fuses (fig 9).
fig 9
The ‘SET HIGH CURRENT’ and ‘SET LOW CURRENT’ potentiometers set the dosing
levels and are user adjustable to meet with the design criteria.
A push button is provided to set the pump run condition dosing level without the pump
being required to run.
Low current dosing indication is provided and repeater volt free signals are provided for
remote monitoring/alarm purposes as standard.
All external connections are made to rail type terminals appropriately sized to suit
specified cables.
Each electrode unit complete with cable, an attachment unit, a junction box and a single
control panel. Schematic drawing No. P12504-08 shows the general arrangement and
principle items of the system.
The cable tail from the electrode unit has three cores numbered 1, 2, & 3. Cable
connection is as follows:
Core
Copper Anode (positive) 1
Aluminium Anode (positive) 2
Steel Frame Cathode (negative) 3
1. Using suitable lifting equipment to take the weight remove the electrode unit from
its packing case using all four of the lifting lugs, as shown in fig.
3. Lower the electrode unit into the intake using all four of the lifting lugs as shown in
figure 10.
4. Whilst the electrode unit is lowered into the intake, the cable tail must be unwound,
avoiding kinks and secured.
fig 10
See schematic diagram and T-R unit rating plate for connections
Installation Procedure
1. The T-R units are designed to be mounted on a concrete plinth using the fixing holes
provided. See general arrangement drawing for detail. The tank should be positioned to
ensure all doors, covers and the sunshade are clear of obstruction.
2. When the T-R unit is located inside, ensure adequate ventilation for dissipation of heat
generated by the T-R unit. See Equipment specification max ambient operating
temperature.
3. The tank must be bonded to the AC supply system earth utilising the earth stud
provided at the bottom of the tank and at the AC supply terminals.
The output negative is isolated and is not to be earthed to the supply system.
4. Normal cable insulation checks are not to be carried out using megger equipment
without first disconnecting the T-R unit. Damage to semi conductors and PCB’s will
result if test voltages in excess of 1000V are applied.
2. Prove that anode and structure cables are connected correctly by checking polarity.
4. Check the oil level is visible on the sight gauge and is above the redline.
Important: The copper and aluminium anodes are connected to the positive output of the
control panel whilst the steel framework of the electrode unit is connected to the negative
terminal of the control panel and becomes the cathode. See drawing P12504-04 for
control panel terminations.
For the safe operation of the system it is essential that the above polarity be
adhered to.
1. Prior to energising panel ensure that all potentiometers are turned fully anti-
clockwise.
2. The panel should be energised via the door-interlocked isolator and the
corresponding miniature circuit breaker (MCB).
ON 63.2 A
Copper
OFF 3.15 A
Cooling Pumps
ON 26.6 A
Aluminium
OFF 1.30 A
VR1
VR2
There is only 1 user adjustable potentiometer on the PCB. These have the following
functions:
VR1
VR 2
This is the current limit setting potentiometer and may be used to set the maximum
current allowable from the unit regardless of the position of the main current adjustment
from the transformer rectifier. This is a 10-turn device and fully clockwise allows for the
maximum current output. Turning the adjuster in an anticlockwise direction progressively
limits the maximum current
Adjustable multi-turn potentiometers are provided for limit settings and relays provide a
changeover contact for remote signalling and control purposes outside of these settings.
The module also has provision for powering alarm LED indicators on the control fascia.
Relays are only fitted for the alarm mode(s) specified
VR1 VR2
There are two user adjustable multi-turn potentiometers, VR1 & VR2, fitted to PCB 031
and the following procedures should be adopted to effect satisfactory set-up and
operation.
VR1
Note
VR2
2. Keep the T-R unit clean and ensure all doors and covers are closed, sealed and locked
when unattended.
3. Check the tightness of all connections every 6 months. Ensure the unit is switched off
at the site supply before check.
6. Check the anti-condensation heater and thermostat control function correctly annually if
fitted.
7. Maintain oil level. Ensure oil level between black and red line when cold. Note only fill
with transformer insulating oil approved by CPCL.
WARNING
THE FRAME IS HEAVY AND COULD CAUSE SERIOUS INJURY IF DROPPED.
TAKE THE APPROPRIATE PRECAUTIONS AND DO NOT STAND UNDER OR NEAR
RAISED CARRIAGE.
3. If still no d.c. output check potentiometer is not fully anti-clockwise. Turn clockwise
to increase output
1. Check supply on
2. Check voltmeter terminals, if voltage there but no reading then replace voltmeter
No change over from pump off to pump running when pump is energised:
In all correspondence please quote reference number P12504, and anti-fouling unit and
control panel serial numbers.
CABLE DATASHEET
Physical Details:
Overall diameter 29.8 mm
Laid up diameter 20.8 mm
Radial thickness of bedding 1.6 mm
Weight in air 1,640 kg/km
Electrical Characteristics
Maximum conductor resistance 0.727 ohms/km
Spark test voltage 6 kV
Working voltage 1000 volts
Insulation resistance core to core >500 Megohms
Standard
BS 6883
TEST CERTIFICATES
SECTION
‘CUPRION’ ANTI FOULING
5.0 CONTENTS
5.0 ‘Cuprion’ Anti Fouling
Datasheet 5.0 7/8/08 09:59 Page 1
REVISION 1
Cathodic Protection Co. Limited have manufactured and supplied the electrolytic 'Cuprion'™ anti-fouling system since the
early 1970's to protect pumped sea water systems against marine growth. Today, the system is used by many of the
major oil and gas offshore operators to protect vertical sea water and fire water pumps on platforms. Other
applications include jetty fire pumps and sea water intake systems.
• Environmentally acceptable
System Description
The method is based upon the use of impressed current on
copper and aluminium anodes which are themselves contained
within an insulated steel frame which forms the cathode. The
anode/cathode electrode unit is suspended from the pump
motor base within the confines of the caisson so that all the
water entering the pump must pass the electrode unit.
Venture Way, Grantham, Lincs NG31 7XS UK. Tel: +44 (0)1476 590666 Fax: +44 (0)1476 570605 DATASHEET
Email: cpc@cathodic.co.uk Website: www.cathodic.co.uk 5.0
Registered Office: Minalloy House, Regent Street, Sheffield S1 3NJ, UK VAT No. 116 8408 71, Reg’d in England No. 478098
Datasheet 5.0 7/8/08 09:59 Page 2
REVISION 1
• Jockey Pumps
For some applications traditional method of pump / electrode configuration may not be suitable. As an alternative we
offer the deck mounted system.
With the deck mounted 'Cuprion'™ anti-fouling system the anodes are located inside an tank through which sea water is
fed from the main sea water system. As the water passes through the tank the carefully controlled anode currents
ensure that the correct dosing level is applied for the particular application. The treated water is then piped down
directly to the pump suction. In this way several pumps can be protected against fouling from a single treatment
source. The Deck Mounted 'Cuprion'™ System is ideally suited for retro-fitting where the pump / electrode configuration
may not be possible.
DATASHEET Venture Way, Grantham, Lincs NG31 7XS UK. Tel: +44 (0)1476 590666 Fax: +44 (0)1476 570605
5.0 Email: cpc@cathodic.co.uk Website: www.cathodic.co.uk
Registered Office: Minalloy House, Regent Street, Sheffield S1 3NJ, UK VAT No. 116 8408 71, Reg’d in England No. 478098
Marine Growth Anti-Fouling Systems
Cuprion™
SHIPS & MARINE VESSELS
Bio-Fouling of seawater intakes on Ships & Marine Vessels can be a major problem, causing expensive
equipment damage and pipework blockages, leading to shut down of vital seawater supplies.
Cathodic Protection Co. Limited has developed a range Cuprion™ anti-fouling systems to protect submerged
pumps, seawater intakes and associated pipework against marine growth. Originally the Cuprion™ system was
developed and utilised for application on Platforms in North Sea during the Early 1970’s.
Developing the system for use on Ships and Marine Vessels involved changes to hardware and installation
methods, Design requirements remained unchanged as Cuprion™ operates on proven electrolytic principles,
Marine Growth Anti-Fouling Systems
Cuprion™
FIREWATER PUMP FOULING PREVENTION
Marine Growth Prevention is achieved by employing a small dc current flow (generally less than 0.5 Kw). This
current flow energises copper and aluminium anodes to produce a fully effective, anti-foulant dosing solution.
Selected dosing levels vary slightly to suit location and application, however maximum dosing limits utilised for
design purposes are 25 µg/litre and 4 µg/litre for copper and aluminium respectively.
Where space or weight restrictions are design considerations, CPCL have developed systems that can be
mounted above or below deck. These systems utilise an electrolysis tank or Dosing Spool.
The Cuprion™ anodes are simply mounted in the electrolysis tank or Candu™ dosing spool and energised to
produce anti-foulant solution, which is delivered via suitably rated pipes or hoses. Several seawater intake
systems can be Marine Growth Protected from a single source,
Electrolysis tanks are generally mounted on a steel plinth along with the dc
power unit, making the complete system integral, ideal for maintenance
operations.
Cuprion™ systems have been installed on all types of Ships & Marine Vessels indicative list below.
Cuprion™
FIREWATER PUMP FOULING PREVENTION
CPCL have developed a standard range to suit National Fire Protection Association directives in NFPA 20 –
Standard for the Installation of Stationary Pumps for Fire Protection. The selector chart overleaf indicates the
range of Cuprion™ systems available to suit NFPA 20.
NOTES.
Items 2, 3,6,7,8 &10 provided by CPCL, remainder by others. CPCL can provide Items 4,9,11 & 12 upon request
and receipt of relevant information.
Standard TR Control Unit utilises M/Steel coated IP45 enclosure suitable for indoor installation, other specifica-
tions available upon request.
Electrode Unit cable tail employs multi-stranded, tinned copper conductor, CSA to suit current output.
System available in 12-14 weeks (Ex-Works) from Approved Documents/Purchase Order depending on client
requirements,
Marine Growth Anti-Fouling Systems
Cuprion™
FIREWATER PUMP FOULING PREVENTION
Usgpm L/min
25 95 10 45 NFPA - 0025 - 10
50 189 10 45 NFPA - 0050 - 10
100 379 10 45 NFPA - 0100 - 10
150 568 5 45 NFPA - 0150 - 05
200 757 5 45 NFPA - 0200 - 05
250 946 5 45 NFPA - 0250 - 05
300 1,136 5 45 NFPA - 0300 - 05
400 1,514 5 60 NFPA - 0400 - 05
450 1,703 5 60 NFPA - 0450 - 05
500 1,892 5 60 NFPA - 0500 - 05
750 2,839 5 80 NFPA - 0750 - 05
1,000 3,785 5 90 NFPA - 1000 - 05
1,250 4,731 5 110 NFPA - 1250 - 05
1,500 5,677 5 145 NFPA - 1500 - 05
2,000 7,570 5 145 NFPA - 2000 - 05
2,500 9,462 5 170 NFPA - 2500 - 05
3,000 11,355 5 200 NFPA - 3000 - 05
3,500 13,247 5 245 NFPA - 3500 - 05
4,000 15,140 5 260 NFPA - 4000 - 05
4,500 17,032 5 310 NFPA - 4500 - 05
5,000 18,925 5 390 NFPA - 5000 - 05
Electrode unit weight may vary, sizing based on maximum practical weight, shorter electrode life can be
accommodated to suit project specific requirements.
CPCL shall provide a formal quotation for a standard NFPA 20 Cuprion™ within 2 working days from receipt
of a formal enquiry, email sales@cathodic.co.uk. For further visit our website at www.cathodic.co.uk.
.
Marine
MarineGrowth
GrowthAnti-Fouling
Anti-FoulingSystems
Systems
Cuprion™
Cuprion™
OFFSHORE
OFFSHOREPLATFORMS
PLATFORMS
Bio-Fouling of water intake pumps and pipework on Offshore Platforms can be a major problem, causing
expensive equipment damage and pipework blockages, leading to shut down of vital seawater supplies.
In the case of fire water systems Crewe Safety and Structure Integrity
must be considered. In addition, repairs to damaged pumps and pipe
work are both costly and time consuming.
Cathodic Protection Co. Limited has developed a range Cuprion™ anti-fouling systems to protect submerged
pumps, seawater intakes and associated pipework against marine growth. Originally the Cuprion™ system was
developed and utilised for North Sea application during the Early 1970’s. Today the system is specified for use
on Offshore Platforms worldwide by many of the major Oil & Gas offshore operators.
Cuprion™ operates on electrolytic principles, employing a small dc current flow (generally less than 1 Kw). This
current flow energises copper and aluminium anodes to produce a fully effective, anti-foulant dosing solution.
Selected dosing levels vary slightly to suit location and application, however maximum dosing limits utilised for
design purposes are 25 µg/litre and 4 µg/litre for copper and aluminium respectively.
The Cuprion™ system has been successfully applied on all types of seawater intakes from submerged pumps
to open intake sea chests. The design of the electrode units can be adapted to suit all application
requirements, but are usually flange mounted on submerged pumps or bolted to the wall of a sea chest.
The Cuprion™ anodes are simply mounted in the tank and energised to produce
anti-foulant solution, which is delivered to the intake area via suitably rated pipes
or hoses.
Marine Growth Anti-Fouling Systems
Cuprion™
OFFSHORE PLATFORMS
The electrolysis tank is generally mounted on a steel plinth adjacent to the dc power unit, making the complete
system integral, ideal for maintenance operations. Anti-Fouling electrodes take around 30 minutes to replace.
Cuprion™ systems have been installed on all types of offshore structures worldwide, indicative list below.
To obtain additional technical or product data sheets on our Anti-Fouling products please contact us on email
sales@cathodic.co.uk. For further information on CPCL visit our website at www.cathodic.co.uk.
Datasheet 5.0 7/8/08 09:59 Page 1
REVISION 1
Cathodic Protection Co. Limited have manufactured and supplied the electrolytic 'Cuprion'™ anti-fouling system since the
early 1970's to protect pumped sea water systems against marine growth. Today, the system is used by many of the
major oil and gas offshore operators to protect vertical sea water and fire water pumps on platforms. Other
applications include jetty fire pumps and sea water intake systems.
• Environmentally acceptable
System Description
The method is based upon the use of impressed current on
copper and aluminium anodes which are themselves contained
within an insulated steel frame which forms the cathode. The
anode/cathode electrode unit is suspended from the pump
motor base within the confines of the caisson so that all the
water entering the pump must pass the electrode unit.
Venture Way, Grantham, Lincs NG31 7XS UK. Tel: +44 (0)1476 590666 Fax: +44 (0)1476 570605 DATASHEET
Email: cpc@cathodic.co.uk Website: www.cathodic.co.uk 5.0
Registered Office: Minalloy House, Regent Street, Sheffield S1 3NJ, UK VAT No. 116 8408 71, Reg’d in England No. 478098
Datasheet 5.0 7/8/08 09:59 Page 2
REVISION 1
• Jockey Pumps
For some applications traditional method of pump / electrode configuration may not be suitable. As an alternative we
offer the deck mounted system.
With the deck mounted 'Cuprion'™ anti-fouling system the anodes are located inside an tank through which sea water is
fed from the main sea water system. As the water passes through the tank the carefully controlled anode currents
ensure that the correct dosing level is applied for the particular application. The treated water is then piped down
directly to the pump suction. In this way several pumps can be protected against fouling from a single treatment
source. The Deck Mounted 'Cuprion'™ System is ideally suited for retro-fitting where the pump / electrode configuration
may not be possible.
DATASHEET Venture Way, Grantham, Lincs NG31 7XS UK. Tel: +44 (0)1476 590666 Fax: +44 (0)1476 570605
5.0 Email: cpc@cathodic.co.uk Website: www.cathodic.co.uk
Registered Office: Minalloy House, Regent Street, Sheffield S1 3NJ, UK VAT No. 116 8408 71, Reg’d in England No. 478098
CUPRION ELECTROLYTIC
TM
ANTI FOULING
AN OVERVIEW
THE PROBLEM
Hard fouling is the generic name given to the accumulation of the hydroid classification of
invertebrate. Examples include Barnacles, Limpets, Mussels and Tubeworms. A typical example
can be seen in the photograph which shows mussel colonisation of a marine pump.
Mussels in particular are prolific breeders which attach themselves to almost any submerged
surface (rocks, boats, piers, pipes and to each other) by secreting horny sticky threads. Egg
fertilisation and production occurs within hours of the water temperature rising above 12°C. After
hatching and as long as the water temperature stays between 14°C and 24°C the free swimming
larvae will appear in plankton and be dispersed by water currents. Spores can settle out if the
circulation velocities are low enough – under 1-1.5m/sec. Once the shell grows too heavy it will
attach itself to a suitable substrate by means of its threads. By the end of the first growing season
the female mussel can produce 30,000 to 40,000 eggs. Population growth is therefore rapid and
will spread quickly through a seawater system where the flow of water ensures a good food supply.
Marine Growth is therefore a problem in most oceans of the world, including colder environments
such as the North Sea. The consequences are of particular concern for submerged pumps and
water intakes. Initially resulting in reduced flows and pressure, untreated marine growth can lead to
complete blockage of pumps and pipe work. Fire pumps are particularly at risk due to their
infrequent operation
1
CUPRION ELECTROLYTIC ANTI FOULING
TM
THE SOLUTION
The effectiveness of copper as a deterrent for marine growth has been well known for centuries.
Hulls of wooden sailing ships were clad in copper sheeting to maintain them free from growth.
Copper is a naturally occurring element in sea water and one which is necessary for marine life.
However by locally increasing the concentration of copper, an environment is created which
discourages marine growth. This environment is not toxic to marine life, but does prevent
settlement of the larvae and colonisation.
The Cuprion™ system uses an automatic control system to produce the copper ions from a solid
anode. Passing a low voltage DC current between the copper ‘anode’ and steel ‘cathode’ results in
the release of copper ions from the anode. By regulating the current, the level of copper dosing is
tailored accurately to each application.
A typical Cuprion™ installation for a submerged sea water pump is shown below
2
CUPRION ELECTROLYTIC ANTI FOULING
TM
The Cuprion™ electrode is mounted on the pump intake using a custom designed attachment unit.
Water being drawn into the pump passes over the Cuprion™ unit and ‘collects’ copper ions which
are being produced by the anode assembly. The treated water is then carried through the pump
and pipe work, preventing marine growth throughout the system.
The system automatically adjusts the output of copper ions to suit pump running conditions so that
the pump is constantly protected, even in standby mode.
Electrode life is usually matched to pump overhaul intervals, typically 5 years.
To assist with the distribution of the copper ions, the Cuprion™ system also features aluminium
anodes. A second electrical circuit is used to produce aluminium ions and these react with the sea
water to form hydrated aluminium oxide. This in turn combines with the copper ions to produce a
‘floc’ of aluminium hydroxide. The floc maintains the copper ions in suspension so that they are
carried with the water as it is pumped through the system. Data from Cuprion™ installations show
that this technology allows copper ions to be carried over many kilometres of pipe work, so
protecting it from fouling.
3
CUPRION ELECTROLYTIC ANTI FOULING
TM
Pump mounted Cuprion™ electrodes can be provided to suit the majority of marine pump
configurations. An alternative system has been developed for customers to suit multiple pump
applications, or where there is insufficient space to fit a conventional electrode to the pump intake.
The Cuprion™ tank system has electrodes which are contained in a remote tank through which a
constant flow of water is passed, and then fed to the pump intake. The water becomes treated with
copper/aluminium ions in the tank, and the discharge of this treated water gives anti fouling
protection to the pump(s).
The CuprionTM tank system was developed with the maintenance engineer in mind and contains
design features to ensure reliability and a low maintenance burden:
• Constant water flow through tank
• No motorised control valves
• System output is electronically regulated by varying anode currents
• No moving parts for single pump system
• Simple solenoid valves for flow control in multiple pump applications
• Simple anode replacement (~30 mins)
• Self contained package – all equipment on skid
4
CUPRION ELECTROLYTIC ANTI FOULING
TM
Chlorine based systems are the traditional method used for marine growth control. Chlorine is a
highly effective anti fouling agent, but has high toxicity and is corrosive to marine equipment when
dosing is not accurately controlled. Manual dosing with chlorine based products is notoriously
unreliable due to the human factors involved, and storage and shipping of chemicals are
problematic and costly. These issues mean that overdosing and corrosion problems are
commonplace. Periodic ‘shock dosing’ with chlorine may also result in the release of marine growth
that has accumulated between treatments, causing downstream filters and equipment to become
blocked or contaminated.
More sophisticated chlorine based systems generate chlorine (hyperchlorite) from sea water. This
equipment is contained in a ‘package’ or ‘skid’ which is mounted on the deck of the platform. These
systems feature high power consumption and a high level of mechanical complexity, with pumps,
motorised valves, mixers etc. It eliminates the hazards of transporting and storing chemicals. These
systems generate the anti fouling agent and then mix it with water which is then piped to the pump
intake.
5
Cathodic 6pp - Single Pages 3/3/08 10:18 Page 6
HEAD OFFICE
Cathodic Protection Co. Limited
Venture Way
Grantham
Lincolnshire
NG31 7XS
United Kingdom
Tel: + 44 (0)1476 590666
Fax: + 44 (0)1476 570605
Email: cpc@cathodic.co.uk
UK BRANCH OFFICE
accreditations
www.cathodic.co.uk
Marine Growth Anti-Fouling Systems
Cuprion™
FIREWATER PUMP FOULING PREVENTION
CPCL have developed a standard range to suit National Fire Protection Association directives in NFPA 20 –
Standard for the Installation of Stationary Pumps for Fire Protection. The selector chart overleaf indicates the
range of Cuprion™ systems available to suit NFPA 20.
NOTES.
Items 2, 3,6,7,8 &10 provided by CPCL, remainder by others. CPCL can provide Items 4,9,11 & 12 upon request
and receipt of relevant information.
Standard TR Control Unit utilises M/Steel coated IP45 enclosure suitable for indoor installation, other specifica-
tions available upon request.
Electrode Unit cable tail employs multi-stranded, tinned copper conductor, CSA to suit current output.
System available in 12-14 weeks (Ex-Works) from Approved Documents/Purchase Order depending on client
requirements,
Marine Growth Anti-Fouling Systems
Cuprion™
FIREWATER PUMP FOULING PREVENTION
Usgpm L/min
25 95 10 45 NFPA - 0025 - 10
50 189 10 45 NFPA - 0050 - 10
100 379 10 45 NFPA - 0100 - 10
150 568 5 45 NFPA - 0150 - 05
200 757 5 45 NFPA - 0200 - 05
250 946 5 45 NFPA - 0250 - 05
300 1,136 5 45 NFPA - 0300 - 05
400 1,514 5 60 NFPA - 0400 - 05
450 1,703 5 60 NFPA - 0450 - 05
500 1,892 5 60 NFPA - 0500 - 05
750 2,839 5 80 NFPA - 0750 - 05
1,000 3,785 5 90 NFPA - 1000 - 05
1,250 4,731 5 110 NFPA - 1250 - 05
1,500 5,677 5 145 NFPA - 1500 - 05
2,000 7,570 5 145 NFPA - 2000 - 05
2,500 9,462 5 170 NFPA - 2500 - 05
3,000 11,355 5 200 NFPA - 3000 - 05
3,500 13,247 5 245 NFPA - 3500 - 05
4,000 15,140 5 260 NFPA - 4000 - 05
4,500 17,032 5 310 NFPA - 4500 - 05
5,000 18,925 5 390 NFPA - 5000 - 05
Electrode unit weight may vary, sizing based on maximum practical weight, shorter electrode life can be
accommodated to suit project specific requirements.
CPCL shall provide a formal quotation for a standard NFPA 20 Cuprion™ within 2 working days from receipt
of a formal enquiry, email sales@cathodic.co.uk. For further visit our website at www.cathodic.co.uk.