VAG Underground Hydrant Water
PN 16
DN 100
Product features
• Industrial use with claw DN 100
• Simple shut-off or double shut-off
• Automatic drainage and protection against loss of supply water
• Maintenance-free stem seal due to O-rings in MS bush
• Pressure test certificate in accordance with EN 12266 (DIN 3230 Part 4)
Materials
• Body, valve body, main valve cone, claw and cover made of cast iron EN – JL
1040 (GG-25)
• Main valve cone seal vulcanized with EPDM (W270)
Corrosion protection
• Inside and outside epoxy powder-coating
Field of application
• Max. operating temperature for liquids: 50°C
• For use outside public water supply networks
Accessories Comment on DIN 3221:
The underground hydrant DN 100 PN 16 cannot be used in public water supply net-
• Operating key works for the public fire-fighting units without a claw reduction to DN 80.
• Street box, cast iron
• EN piece (GGG)
• Claw reduction DN 100/80
• Lid cleaner for underground hydrant
street boxes
For information about installation,
commissioning,operating and
maintenance we kindly refer to our
"Installation and Operating
Instructions - Valves”.
Field of Use Final Inspection Test in acc. with EN 12266
PN Max. operating Max. operating temperature Test pressure in bar
pressure for water with water
in body
bar bar °C in body in seat
16 16 50 24 17.6
We reserve the right to make technical changes and use similar or
higher-quality materials. Drawings are non-binding
VAG Hydrants · KAT 16 43-A www.vag-armaturen.com Edition3 - 08-07
Water VAG Underground Hydrant
Dimensions / weights
Ø 145
Ø 112
27
415
h2
h1
Pipe cover m 1.00 1.25 1.50
Construction height „h1“ mm approx. 680 930 1180
Construction height „h2“ mm approx. 725 975 1225
weight kg approx. 67 75 89
space req. m3 approx. 0.12 0.16 0.20
Turns / stroke 10
We reserve the right to make technical changes and use similar or
higher-quality materials. Drawings are non-binding
www.vag-armaturen.com Edition3 - 08-07 KAT 16 43-A · VAG Hydrants