Rotary Vane Air Compressors
Operation
   And Maintenance
       Manual
       For Models
         750
       ____________________
        1000
  Mattei Compressors
  9635 Liberty Road
Randallstown, MD 21133
 (410) 521-7020 phone
   (410) 521-7024 fax
                                1
                      TABLE OF CONTENTS
                                          PAGE
INTRODUCTION                               3
PRINCIPLES OF OPERATION                    4
TECHNICAL SPECIFICATIONS                   5-6
INSTRUMENT PANEL                           7-8
CONTROLS                                   9-10
COMPRESSOR OPERATION                       11-13
LUBRICATION SYSTEM                         14
INSTALLATION                               15-16
START UP and CALIBRATION                   17-18
MAINTENANCE                                19-23
FAULT FINDING GUIDE                        24-27
OVERAL DIMENSIONS
RECOMMENDED SPARE PARTS                    28-32
WIRING DIAGRAMS (provided separately)
                                                   2
INTRODUCTION
Mattei Compressors are oil-sealed, rotary sliding vane compressors directly driven by an electric motor.
This manual contains only operating and maintenance instructions and is not intended as an overhaul
manual. Anyone installing, operating and maintaining the compressor should familiarize themselves with
the contents of this manual.
Mattei Compressors have been designed and manufactured to the highest standards and regular
maintenance will ensure long and reliable operation.
If you require additional information not contained in this manual, please contact your Mattei distributor or
the Mattei Service Department (410)-521-7020.
Fig.1 WARNING DECALS ON COMPRESSOR
                                                 CAUTION
    This operating manual contains information that is vital to the safe operation of the compressor.
    Read the manual carefully before attempting any operation, and closely follow all instructions.
    Failure to do so may result in injury.
                                                WARNING
    The compressor oil temperature may be checked by filling the hole on the oil filler plug with oil and
    then inserting a thermometer. The oil temperature should never exceed 212°F.
                                                                                                            3
PRINCIPLES OF OPERATION
Atmospheric air is drawn through the inlet air filter (1) and intake valve (2) into the compression chambers
formed by sliding vanes (3). The vanes slide in rotor slots cut in the rotor (4), which in turn is
eccentrically-mounted within the stator (5). As the rotor turns, the vanes slide in and out of the slots and
are kept in contact with the stator wall by centrifugal force. The air is compressed through the contraction
in volume of the chambers formed by the vanes, rotor, and stator wall.
Throughout the compression cycle, the oil carries out the four vital functions of lubricant, sealant, control
fluid and coolant. However, after compression, it is necessary to remove the oil that has been previously
injected (6).
The air/oil mixture passes from the compression chamber into the oil chamber, where most of the oil is
separated from the air via a labyrinth (7). The rest of the air/oil mixture passes into the final separation
stage (8) and the oil is returned to the intake through the oil return valves (9). Only clean air is delivered to
the point of usage (10).
Fig.2 OPERATING PRINCIPLE OF ROTARY VANE COMPRESSOR
                                                                                                                4
5
6
INSTRUMENT PANEL (Refer to Figure 3 next page)
All compressor models are equipped with a sophisticated solid state control system. A comprehensive
control panel is mounted on the front of the unit and includes the following:
    •   Button-OFF/STOP
            o This stops the machine manually. The green off light lights when the unit is stopped
                 manually: in this condition it acts as “main on” (electrical power on to the compressors)
                 warning light. It is switched off when the unit is started
    •   Button-MANUAL/START
            o This starts the machine manually. The yellow light is on during manual operation and is
                 switched off when the machine is not running.
    •   Button-AUTOMATIC/START
            o This starts the machine for automatic operation. During this phase the yellow light is on.
    •   Button-RESET
            o This returns the compressor to normal operation after it has been stopped by one of the
                 safety switches.
            o The red light is on as well as the other alarm warning lights: to switch them off, press the
                 RESET button when normal working conditions are restored.
    •   Yellow light-STOPPING
            o The yellow warning light switches on when the automatic stop procedure commences.
                 The light switches off when line pressure decreases sufficiently or when the compressor
                 is stopped
    •   Yellow light-OFF LOAD
            o The yellow warning light is always on during off-load running. During automatic
                 operation it switches off when the compressor comes on load or when the units is
                 automatically stopped.
    •   Red light-AIR INTAKE FILTER BLOCKED (optional)
            o The red warning light switches on when the filter is clogged but will not stop the
                 machine. The intake filter must be cleaned or replaced. To switch off the light, push the
                 RESET button.
    •   Red light-OIL SEPARATOR BLOCKED (optional)
            o The red warning light switches on when the compressed air pressure drops through the
                 separator filters and reaches the maximum allowed value (set at 14/5 psi/1Bar pressure
                 differential), but will not stop the machine. The filters must be replaced. To switch off
                 the light, push the RESET button.
    •   Red light-LOW OIL LEVEL (For EMS 500/600/750/1000 only) (This is a two stage alarm)
            o The red warning light switches on when the oil level reaches the first alarm point; in this
                 condition the machine is not stopped. When the second alarm point is reached, the oil
                 level is dangerously low and the machine will stop with the red light still on. In both
                 cases, it is necessary to top off the oil level then push the RESET button.
            o NOTE
                            The compressor must be stopped immediately and the fault corrected when this
                            light comes on.
                            Daily check of the oil is still the primary compressor protection
                            Compressor failure due to low oil level is not a warrantable failure
    •   Red light-HIGH TEMPERATURE
            o The red light switches on when the oil temperature inside the compressor exceeds 212°F
                 and the machine stops. Check for cause of over temperature and correct, then wait until
                 the oil temperature falls to its normal level and push the RESET button. (For models
                 500/600/750/1000, there is also an RSU air outlet temperature shutdown at 212°F).
    •   Red light-MAIN MOTOR OVERLOAD
            o The red light switches on when, due to overload, the motor temperature exceeds the
                 maximum permitted value and the compressor will stop. This is thermistor controlled.
                                                                                                         7
                  Check for cause of overload and correct, then wait until the motor temperature falls to its
                  normal value and press the RESET button.
             o If motor protection is by means of a thermal relay, the red light will switch on when
                  current drawn by the motor is excessive. Check for cause of overload and correct. The
                  lamp switches off when the thermal relay (inside the starter) is reset manually and the
                  RESET button is pressed.
    •    Red light-FAN MOTOR OVERLOAD (for EMS models only)
             o The red light switches on when, due to overload, the safety overload inside the electrical
                  control box trips. Check for cause of overload and correct. The safety overload must be
                  reset manually and then the RESET button must be pressed.
WARNING: In order to avoid some false signals occasionally caused by sudden variation of operating
conditions when starting the unit, certain alarms have been delayed and are activated 20 seconds after start
up.      They are:         -Intake Filter Blocked              -Low Oil Level
                           -Oil Separator Blocked              -High Temperature
Fig. 3 INSTRUMENT PANEL
                                                                                                            8
CONTROLS
EMERGENCY STOP BUTTON
In case of emergency, stop the compressor immediately by pushing the Emergency Stop button and
electrically isolate the compressor. Correct the fault that caused you to push the button. To release the
emergency stop button, rotate in the direction of the arrow and push the red RESET button.
REMOTE CONTROLS
The electronic card/printed circuit board allows the compressor to be connected to a centralized control unit
or a remote control board by means of terminals marked “H”. The electronic car (see Fig. 4) can also
supply remote “machine on” and “machine failure” signals. Contact the Mattei Service Department for
further details.
CONTROLS
The electronic card (PC board) incorporates a series of timers and is connected to several pressure switches
and solenoid valves, which monitor and control the compressor running mode depending on air demand.
         Timer settings (see Fig. 4) (Not all machines use all features on the PC board)
         A=start delay timer                        about       8 seconds
         B=Star Delta timer                         about       2.5 seconds
         C=stop timer (T1)                          about       2 minutes
         D=stop timer (T2)                          about       15 minutes
         E=solenoid valve closing delay timer       about       1 second
         F=stop delay timer                         about       3 seconds
         G=timer for delayed activation
            Of safety devices when starting         about       20 seconds
         H=connection for remote operation and indication
         I=terminal strip
Fig. 4 PC Board
                                                                                                            9
CONTROL SWITCHES and SOLENOID VALVES
  •   High temperature switch.
          o Stops the motor when the oil temperature reaches 212°F.
  •   Off-load solenoid valve.
          o Delivers pressure to the minimum pressure valve in order to off-load compressor.
  •   Blow-down solenoid valve.
          o Allows a quick exhaust of the inside pressure before starting the motor.
  •   Pressure switch PS1.
          o Provides upper limit for automatic operating, allows full load operation of the compressor
               and controls the stop timer
  •   Pressure switch PS2.
          o Provides lower limit for automatic operating and re-starts the compressor.
  •   Blocked air intake filter switch. (Optional)
          o Operated the blocked intake filter light should the intake filter be blocked.
  •   Blocked separator differential pressure switch. (Optional)
          o Operates the blocked separator element light if the separator element becomes blocked.
  •   Low oil level gauge/switch. (Optional on EMS 500/600/750/1000)
          o Monitors oil level in the chamber and operates in two stages
                        Stage 1: Low oil level light illuminated
                        Stage 2: Compressor stops
  Fig. 5 Pressure Switches and Solenoid Valves
                                                                                                   10
    COMPRESSOR OPERATION
    Compressor can be set for manual or automatic operation.
    The selection must be made when starting the unit by depressing the proper button. In both cases
    stopping is by means of the “stop” button.
    When pressing the start button, compressor will start after about 8 seconds. When pressing the stop
    button compressor will stop after a 3 second delay. This delay allows the solenoid valve to unload the
    compressor.
         1) MANUAL OPERATION
               a. In “manual” operation the air flow is regulated by the servovalve/intake valve
                  system. The compressor runs continuously and pressure switches PS1 and PS2 are
                  overridden.
         2) AUTOMATIC OPERATION
               a. In “automatic” operation compressor cycling is controlled by PS1 and PS2 pressure
                  switches. When line air pressure falls to PS2 setting, the Minimum Pressure Valve
                  opens, increasing air flow. When line pressure rises to PS1 setting, the Minimum
                  Pressure Valve shuts, stopping air flow.
               b. During “automatic” operation, when air consumption is greatly reduced or stopped,
                  the compressor will “auto-idle” and if this continues, the compressor will
                  automatically stop. When air demand returns, the compressor will re-start
                  automatically.
DESCRIPTION OF AUTOMATIC OPERATION
         1) No air demand
                a. If through lack of air demand, the line pressure rises to the value of PS2 max, the off-
                    load solenoid valve is de-energized and the minimum pressure valve closes: in this
                    way the compressor runs off-load. At the same time the stop timer and the stop
                    delay timer start counting times T1 and T2 respectively.
                b. Any air demand will cause a fall in line pressure; if this pressure reaches the value of
                    PS1 minimum before the time T1, then the T1 timer is cancelled, the compressor
                    does not stop and continues running off-load until pressure falls to the value of PS2
                    min.
                c. At this stage the T2 timer is also cancelled, the off-load solenoid valve is energized,
                    the minimum pressure valve is released and compressor comes on-load to meet the
                    air demand.
                d. The T2 timer stops the compressor in case the air consumption stops completely after
                    the T1 timer has been cancelled.
                e. If the line pressure remains over the value of PS1 minimum for the time T1, then the
                    compressor stops and inside pressure exhausts gradually to atmospheric pressure.
         2) Air demand increases after the compressor shuts down
                a. When the line pressure reaches the value of PS2 minimum, the compressor starts
                    after an 8 second delay, during which time the blow down solenoid valve is
                    energized to allow quick venting of the residual inside pressure.
Note: If there is a continuous air loss or usage the unit will never shut down completely in automatic since
the line pressure will drop below PS2 within the set 15 minutes. In this case there is no advantage to
running the unit in automatic and it should be switched to manual mode.
OFF LOAD RUNNING WITH AUTO IDLE (Auto idle no applicable to all models.)
When the pressure causes the contacts of PS1 to open, compressors fitted with the auto-idle mechanism
will vent the internal pressure down to 2.3 bar, thus reducing power consumption.
                                                                                                         11
Fig. 6 shows the schematic flow of the line pressure, both during manual and
automatic operation.
                                                                               12
Fig 7. Automatic Operation by Means of 2 Pressure Switches
                                                             13
LUBRICATION SYSTEM
The lubricant in the Mattei Rotary Vane Compressor provides four vital functions:
    1) Lubrication
           a. Utilizing a differential pressure, the lubrication system eliminates the requirement for a
                separate oil pump. Air pressure acting on oil in the chamber forces oil through drilled
                passageways to critical wearing surfaces (i.e., main bearings).
    2) Seals
           a. Oil injected into the rotor stator unit creates a seal between the sliding vane tip and the
                stator wall to lubricate and seal individual compression chambers.
    3) Cools
           a. Oil injected into the rotor stator unit dissipates the heat of compression and allows
                efficient operation.
    4) Controls
           a. Pressurized oil in the chamber acts on servo/unloader valves to control air intake. Air
                flow is matched to air demand providing efficient off-load operation.
To meet all four design criteria, Mattei has developed a special Mattei lubricant, 8000F2, for use in rotary
compressors
Warning: It is important that the compressor oil be of the recommended type, and
that this oil, as well as the air filter, oil filter and air/oil separator elements, be
inspected and replaced as stated in this manual.
Mattei’s extended Limited Warranty requires the use of Mattei oil (currently 8000F2).
Please note that all Mattei compressors are factory tested and supplied with oil, which
must be changed after 500 hours of operation.
                                                                                                           14
INSTALLATION
  1) Locating the compressor
        a. Place the compressor in a well-ventilated environment away from any
           sources of heat. The unit is designed to operate in ambient temperatures
           up to 100°F. For temperatures greater than this, consult your authorized
           distributor.
DANGER: Hot oil under pressure can cause injury, death or property damage.
Ascertain that the compressor is shut down, disconnected from the main electrical
supply, and relieved of all pressure before starting any work on the compressor
           b. The compressor oil temperature may be checked by filling the hole on the
               oil filler plug with oil and then inserting a thermometer. The oil
               temperature should never exceed 212°F.
  2)   To ensure effective cooling-DO NOT
           a. Position the compressor so that the air-cooled radiator is within 7 feet of a
               wall or large obstruction.
           b. Place compressor in a confined area such that the hot air will not be
               allowed to disperse.
  3)   Always place the compressor in a position that allows easy access to perform
       standard maintenance procedures. Avoid all inclines and ascertain that the
       compressor is level in both directions
  4)   All Mattei compressor packages are equipped with air-cooled after-coolers and
       separator drains. Separate installation of air dryers and filters is recommended to
       help protect downstream equipment and devices.
  5)   All installation wiring should be handled by a licensed electrician who is familiar
       with such procedures. Always refer to the wiring diagram.
  6)   Electrical Connections
           a. Ascertain that wire sizes, power supply, and disconnects are suitable to
               operate compressor.
           b. Check for the correct voltage supply
  WARNING: All compressors must be wired such that they rotate
  clockwise when viewed from the motor end. Operation of the compressor
  in the wrong direction for more than 10 seconds may cause serious
  damage. To change direction or rotation, reverse two of the three main
  cables on the terminal board.
                                                                                         15
      DISCHARGE AIR LINES
      If the Mattei compressor is operating in conjunction with other compressors, especially
      reciprocating, a check valve should be fitted between the two to isolate the Mattei
      compressor. Always size the pipe properly to minimize the pressure drop. Piping
      should also be kept as straight and as short as possible to minimize potential leakage
      spots. (See tables below)
      All main air piping should slope away from the compressor to properly drain condensate.
      When vertical piping is used, a drip leg should be installed.
      A flexible hose with an air gun should be fitted near the compressor to assist in periodic
      cleaning of both the oil cooler and the air cooler.
      Pipes for delivery of air to individual stations should always be branched off from the
      upper side of the main air supply.
          PIPING REQUIREMENTS FOR AIR DISTRIBUTION SYSTEMS
Pipe size used should be large enough to keep the pressure drop
between the tank and the point of use to a minimum. All piping
should slope to an accessible moisture drain point.
The main airline should not be smaller than the compressor outlet
size. For long lines, sizes shown at right are recommended.
Outlets should be taken from the top of the mainline (tees facing
up) to keep moisture out.
Check all piping and fittings regularly to avoid leaks in the
system. Filters, regulators, and other accessories should
also be properly maintained.
                                                                                                16
STARTUP AND CALIBRATION
   1) Starting
          a. Confirm that the supply voltage coincides with that on the compressor
              nameplate.
NOTE: Never remove or loosen the oil fill plug until all pressure has been released from
the compressor. Then open safety valve before removing the plug to release any residual
air.
           b. Check oil level. Ensure that it is filled to overflowing.
 CAUTION: Before starting the compressor, be sure this manual has been
 completely read and understood with particular attention paid to ALL warnings.
           c. Press the MANUAL or AUTOMATIC button to start the compressor. All
              models have a delayed start of about 8 seconds to ensure unloaded
              starting.
           d. On the first start up, check that rotation is in the direction of the arrow on
              the motor case, i.e. clockwise when viewed from the motor end. If this is
              not the case, stop the compressor immediately and reverse 2 of the main
              electrical supply leads.
 Note: Continued rotation of the compressor in the wrong direction for more than 10
 seconds will seriously damage the unit.
   2) Stopping
         a. Press the “off” button whether in Manual or Automatic operation. The
             compressor will stop with a 3 second delay period to ensure an off-load
             condition.
NOTE: The emergency stop button should not be used to stop the compressor
during standard operation.
   3) Calibration
         a. Manual Mode
                  i. To adjust the operating pressure in the manual mode requires
                     adjustment of the servovalve only. (In manual, the pressure
                     switches and timers are cut out of the circuit)
                 ii. To adjust the servovalve located on the side of the oil chamber
                     under the oil filter, (Note: Location may vary. Check the
                     applicable arrangement drawing for your compressor.), loosen the
                     locking nut and turn the adjusting screw. Turn the screw
                     clockwise to increase pressure; counterclockwise to decrease
                                                                                          17
                    pressure. With the air discharge closed (compressor off-load), a
                    pressure gauge setting of 105-11- PSI is recommended.
               iii. When pressure is properly adjusted, retighten locking nut.
          b. Automatic Mode
                 i. The pressure switches should be calibrated as follows:
                        1. PS1: this pressure switch should be set 1.5-3 PSI lower
                            than the compressor servovalve setting.
                        2. PS2: this pressure switch should be set 17-20 PSI lower
                            than the PS1 maximum value
                        3. The pressure differential should be 5.7-7.1 PSI for both
                            pressure switches.
                ii. To adjust the pressure switches, loosen the lock screws (2) and, for
                    PS2, remove the safety plate (4). The settings can now be adjusted
                    by turning screws (1) and (3) as appropriate. The values set can be
                    read from the scales on the front of the pressure switches.
Fig 8A. Pressure Switch PS1                        Fig 8b. Pressure Switch PS2
                                                                                     18
MAINTENANCE
WARNING: Before performing any maintenance work on the compressor, be sure
all pressure is relieved from compressor and system and the unit is disconnected
from the power source.
The following table is a summary of the routine maintenance operations necessary to guarantee the long
life and safe operation of the compressor.
NOTES:
  • Break in oil must be changed after first 500 operating hours.
  • Oil filter requires cleaning after first 500 operating hours.
  • Oil return valves require cleaning after first 500 operating hours.
  • Time periods are based on normal operating conditions. When the unit is
     operating in an adverse environment, maintenance should be performed more
     frequently. When in doubt, contact Mattei Service Department.
    * More frequent changes may be necessary depending on operating conditions.
    ** When approved petroleum based oil is used
    *** Only when Mattei (currently 8000F2) oil is used.
                                                                                                         19
   The following are brief instructions on how to perform the above
   simple maintenance operations.
   WARNING: Before performing any maintenance work on the compressor, ascertain
   that the unit is not under pressure. Wait until the air pressure gauge reads zero, and
   then lift the safety valve lever to discharge all pressure.
   Also, the main electric disconnect switch must be open and red-tagged to remain open
   while maintenance is being performed.
    Failure to follow above instructions may result in serious bodily injury
    or death.
   1. CONDENSATE SEPARATOR (see fig. 9)
        a. A condensate separator and drain is fitted on the aftercooler of each unit.
           During compressor operation the solenoid valve opens approximately
           every two minutes (or four minutes in some models) and remains open
           until all water is discharged. Two internal electrodes detect the lack of
           water and close the valve instantaneously. The presence of oil or dirt may
           interrupt the conductivity between these two electrodes and hence even
           though the solenoid will continue to open every 2 (or 4) minutes, it will
           not remain open long enough to drain sufficient water. If this is the case:
                i. Undo lock nut (2) and remove solenoid valve.
               ii. Remove and clean or replace filter (3).
              iii. Clean electrodes (1).
              iv. Reassemble, taking care not to cross the solenoid valve and lock
                    nut.
Fig. 9 Drain Solenoid Valve Maintenance
                                                                                       20
   2. AIR INTAKE FILTER (see fig. 10)
         a. Remove nut (1) from filter cover.
         b. Remove cover (2).
         c. Remove nut (3) and plate (4) holding filter (5).
         d. Remove and clean or replace filter element (5).
         e. Refit filter (5), plate (4), and nut (3).
         f. Lock assembly in place with
            nut.
   3. RADIATOR/COOLERS
         a. On a Mattei rotary vane compressor both oil and air are cooled in air blast
             external radiators. In order to maintain effective cooling, the radiator
             and piping must be kept clean. The radiators can easily be cleaned with a
             jet of clean dry compressed air.
   4. OIL CHANGE (see Fig. 11) (Location of oil drain plug and filter may vary by
      model.)
CAUTION: Do not loosen or remove any plugs until all pressure is relieved from the
system and the pressure gauge reads zero. Raise safety valve lever to ensure all
pressure has been relieved.
       a. Unscrew and remove oil filler plug (1).
       b. Remove oil drain plug (2) from underside of the oil chamber.
       c. Drain oil.
       d. Fit with new seal (3) to oil drain plug, replace and tighten
       e. Fill compressor with oil until overflowing
       f. Fit new seal (4) to oil fill plug, replace and tighten
       g. Let compressor operate for about 10 seconds to allow oil to circulate.
       h. Stop the compressor and relieve all pressure.
       i. Check oil level and top off to overflowing.
    5. OIL FILTER (see Fig 11.) NOTE: When the compressor is first installed the oil
       filter must be cleaned after first 500 hours.
            a. Drain oil as per OIL CHANGE instructions.
            b. Remove caphead screws (5) and filter cover (6).
                                                                                     21
       c.   Extract oil filter element (8).
       d.   Clean the element with appropriate solvent.
       e.   Clean filter housing with clean cloth.
       f.   Refit element into housing.
       g.   Fit new O-rings (7) to filter and refit.
       h.   Fill with oil as per OIL CHANGE instructions.
       i.   Check that there are no leaks.
6. OIL RETURN VALVES (see Fig. 12.) NOTE: When the compressor is first
   installed the oil return valves should be cleaned after first 500 hours.
       a. Remove circlip (1), sight window (2) and seal ring (3) from the seat.
       b. Remove valve (4) and gasket (5) using appropriate socket wrenches.
       c. Examine ORV’s and, if blocked, replace. NOTE ORDER OF
           DISASSEMBLY.
       d. Refit valve and gasket into housing.
       e. Refit new seal ring (3), sight window (2), and circlip (1) if necessary.
                                                                                     22
7. ELECTRIC MOTOR
     a. The bearings of the electric motors on the EM(S)400-1000 compressors
        should be greased as indicated in the table below.
                               User’s Notes
                                                                               23
  MATTEI ROTARY VANE COMPRESSORS
                        FAULT FINDING GUIDE
WARNING: Never attempt any remedy without first ensuring that all internal
pressure has been released and compressor is isolated from the main electrical
supply.
Failure to comply with this warning may cause injury.
                                                                                 24
25
26
27
28
   OVERALL DIMENSIONS
RECOMMENDED SPARE PARTS
                          29
30
31
32
33