HVAC and Refrigeration System
HVAC and Refrigeration System
4.1 Introduction
The Heating, Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products, or building environment. Energy in form
of electricity or heat is used to power mechanical equipment designed to transfer heat
from a colder, low-energy level to a warmer, high-energy level.
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant.
There are several heat transfer loops in refrigeration system as described below:
In the Figure 4.1, thermal energy moves from left to right as it is extracted from the space
and expelled into the outdoors through five loops of heat transfer:
− Indoor air loop. In the leftmost loop, indoor air is driven by the supply air fan
through a cooling coil, where it transfers its heat to chilled water. The cool air then
cools the building space.
− Chilled water loop. Driven by the chilled water pump, water returns from the cooling
coil to the chiller’s evaporator to be re-cooled.
− Condenser water loop. Water absorbs heat from the chiller’s condenser, and the
condenser water pump sends it to the cooling tower.
− Cooling tower loop. The cooling tower’s fan drives air across an open flow of the hot
condenser water, transferring the heat to the outdoors.
Air-Conditioning Systems
Depending on applications, there are several options / combinations, which are available
for use as given below:
Air Conditioning (for comfort / machine)
Split air conditioners
Fan coil units in a larger system
Air handling units in a larger system
Refrigeration Systems (for processes)
A large industry may have a bank of such units, often with common chilled water pumps,
condenser water pumps, cooling towers, as an off site utility.
The same industry may also have two or three levels of refrigeration & air conditioning
such as:
Heat flows naturally from a hot to a colder body. In refrigeration system the opposite
must occur i.e. heat flows from a cold to a hotter body. This is achieved by using a
substance called a refrigerant, which absorbs heat and hence boils or evaporates at a low
pressure to form a gas. This gas is then compressed to a higher pressure, such that it
transfers the heat it has gained to ambient air or water and turns back (condenses) into a
liquid. In this way heat is absorbed, or removed, from a low temperature source and
transferred to a higher temperature source.
The refrigeration cycle can be broken down into the following stages (see Figure 4.2):
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its surroundings,
usually air, water or some other process liquid. During this process it changes its state
from a liquid to a gas, and at the evaporator exit is slightly superheated.
2 - 3 The superheated vapour enters the compressor where its pressure is raised. There
will also be a big increase in temperature, because a proportion of the energy put into the
compression process is transferred to the refrigerant.
3 - 4 The high pressure superheated gas passes from the compressor into the condenser.
The initial part of the cooling process (3 - 3a) desuperheats the gas before it is then turned
back into liquid (3a - 3b). The cooling for this process is usually achieved by using air or
water. A further reduction in temperature happens in the pipe work and liquid receiver (3b
- 4), so that the refrigerant liquid is sub-cooled as it enters the expansion device.
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device, which
both reduces its pressure and controls the flow into the evaporator.
It can be seen that the condenser has to be capable of rejecting the combined heat inputs
of the evaporator and the compressor; i.e. (1 - 2) + (2 - 3) has to be the same as (3 - 4).
There is no heat loss or gain through the expansion device.
The use of CFCs is now beginning to be phased out due to their damaging impact on the
protective tropospheric ozone layer around the earth. The Montreal Protocol of 1987 and
the subsequent Copenhagen agreement of 1992 mandate a reduction in the production of
ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a phased manner, with an
eventual stop to all production by the year 1996. In response, the refrigeration industry
has developed two alternative refrigerants; one based on Hydrochloro Fluorocarbon
(HCFC), and another based on Hydro Fluorocarbon (HFC). The HCFCs have a 2 to 10%
ozone depleting potential as compared to CFCs and also, they have an atmospheric
lifetime between 2 to 25 years as compared to 100 or more years for CFCs (Brandt,
1992). However, even HCFCs are mandated to be phased out by 2005, and only the
chlorine free (zero ozone depletion) HFCs would be acceptable.
Until now, only one HFC based refrigerant, HFC 134a, has been developed. HCFCs are
comparatively simpler to produce and the three refrigerants 22, 123, and 124 have been
developed. The use of HFCs and HCFCs results in slightly lower efficiencies as
compared to CFCs, but this may change with increasing efforts being made to replace
CFCs.
Absorption Refrigeration
The absorption chiller is a machine, which produces chilled water by using heat such as
steam, hot water, gas, oil etc. Chilled water is produced by the principle that liquid
(refrigerant), which evaporates at low temperature, absorbs heat from surrounding when it
evaporates. Pure water is used as refrigerant and lithium bromide solution is used as
absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat
extracted from process, diesel generator sets etc. Absorption systems require electricity to
run pumps only. Depending on the temperature required and the power cost, it may even
by economical to generate heat / steam to operate the absorption system.
As lithium bromide
solution is diluted, the
effect to absorb the
refrigerant vapor reduces.
In order to keep
absorption process, the
diluted lithium bromide
solution must be made
concentrated lithium
bromide.
Absorption chiller is
provided with the solution
concentrating system by
the heating media such as
steam, hot water, gas, oil,
which performs such
function is called
generator.
The concentrated solution
flows into the absorber
and absorbs the refrigerant
vapor again.
A typical schematic of the absorption refrigeration system is given in the Figure 4.3.
Evaporative Cooling
There are occasions where air conditioning, which stipulates control of humidity up to 50
% for human comfort or for process, can be replaced by a much cheaper and less energy
intensive evaporative cooling.
The concept is very simple and is the same as that used in a cooling tower. Air is brought
in close contact with water to cool it to a temperature close to the wet bulb temperature.
The cool air can be used for comfort or process cooling. The disadvantage is that the air is
rich in moisture. Nevertheless, it is an extremely efficient means of cooling at very low
cost. Large commercial systems employ cellulose filled pads over which water is sprayed.
The temperature can be controlled by controlling the airflow and the water circulation
rate. The possibility of evaporative cooling is especially attractive for comfort cooling in
dry regions. This principle is practiced in textile industries for certain processes.
Vapor
Evaporating Condensing Pressure
Refrigerant Enthalpy (kJ / COP**carnot
Press (kPa) Press (kPa) Ratio
kg)
R - 11 20.4 125.5 6.15 155.4 5.03
R - 12 182.7 744.6 4.08 116.3 4.70
R - 22 295.8 1192.1 4.03 162.8 4.66
R - 502 349.6 1308.6 3.74 106.2 4.37
R - 717 236.5 1166.5 4.93 103.4 4.78
o o
* At -15 C Evaporator Temperature, and 30 C Condenser Temperature
** COP carnot = Coefficient of Performance = Temp.Evap. / (Temp.Cond. -TempEvap.)
The choice of refrigerant and the required cooling temperature and load determine the
choice of compressor, as well as the design of the condenser, evaporator, and other
auxiliaries. Additional factors such as ease of maintenance, physical space requirements
and availability of utilities for auxiliaries (water, power, etc.) also influence component
selection.
reciprocating, centrifugal and, more recently, screw compressors, and scroll compressors.
Water-cooled systems are more efficient than air-cooled alternatives because the
temperatures produced by refrigerant condensation are lower with water than with air.
Centrifugal Compressors
Older centrifugal machines are not able to reduce load much below 50%. This is because
of “surge” in the impeller. As the flow through the impeller is choked off, the gas does
not acquire enough energy to overcome the discharge pressure. Flow drops abruptly at
this point, and an oscillation begins as the gas flutters back and forth in the impeller.
Efficiency drops abruptly, and the resulting vibration can damage the machine. Many
older centrifugal machines deal with low loads by creating a false load on the system,
such as by using hot gas bypass. This wastes the portion of the cooling output that is not
required.
Another approach is to use variable-speed drives in combination with inlet guide vanes.
This may allow the compressor to throttle down to about 20% of full load, or less, without
false loading. Changing the impeller speed causes a departure from optimum
performance, so efficiency still declines badly at low loads. A compressor that uses a
variable-speed drive reduces its output in the range between full load and approximately
half load by slowing the impeller speed. At lower loads, the impeller cannot be slowed
further, because the discharge pressure would become too low to condense the refrigerant.
Below the minimum load provided by the variable-speed drive, inlet guide vanes are used
to provide further capacity reduction.
Reciprocating Compressors
Reciprocating compressors suffer less efficiency loss at partial loads than other types, and
they may actually have a higher absolute efficiency at low loads than the other types.
Smaller reciprocating compressors control output by turning on and off. This eliminates all
part-load losses, except for a short period of inefficient operation when the machine starts.
Screw Compressors
excessive internal leakage. There are other methods of reducing capacity, such as suction
throttling that are inherently less efficient than the previous two.
Scroll Compressors
The features of various refrigeration compressors and Figure 4.7 Scroll Compressor
application criteria is given in the Table 4.3.
4 Air Conditioning Temp. Range0.7-0.9 kW/TR 0.63kW/TR 0.65 kW/TR 5000 kcal/TR 2575 kcal/TR 7500 kcal/TR 2000 kcal/TR 4615 kcal/TR
Subzero Temp. Range1.25 to 2.5 ----- 1.25 to 2.5
----- ----- ----- ----- 6666 kcal/hr
kW/TR kW/TR
R11,R123,R134a R22, R134a Pure
5 Refrigerant R22, R12 Pure Water Pure Water Pure Water Pure Water
Ammonia Ammonia Ammonia
Water-LiBr Water-LiBr Water-LiBr Water-LiBr Ammonia-
6 Absorbent ------ ------ ------
solution solution solution solution LiBr solution
Typical single unit capacity range
7 30 TR & 30 TR & 50 TR &
Air Condition temp. range 1-150 TR 300 TR & above 50-200 TR 30 TR & above 30 TR & above
above above above
Subzero temp. range 10-50 TR ------ 50-200 TR ----- ----- ----- ----- 30 TR & above
Reduces at part Reduces at part Improves by
8 Typical COP at Part Load upto 50% Marginal Improvement at Part Load No variation
load load 15-20%
5-6 mm Hg 5-6 mm Hg 5-6 mm Hg
2.5-3.5 bar a 5-6 mm Hg 1.2kg/cm2(a)
Typical Internal Pressure Levels -Low 0.15-0.40 bar a 2-5.5 bar (abs) (abs) (abs)
11-12 bar (abs) 18 kg/cm2(a)
9 -High 1.20-1.50 bar a 18-20 bar 60-70 mm Hg 370-390 mm 60-70 mm Hg
-5 to 50oC 2 kg/cm2 (a) -25 to +150oC
Typical Internal Temp. Levels -25 to 50oC o
-25 to 50 C (abs) Hg (abs) (abs)
+4 to 160oC
+4 to 75oC +4 to +130oC +4 to 130oC
• In a centralized chilled water system, apart from the compressor unit, power is
also consumed by the chilled water (secondary) coolant pump as well
condenser water (for heat rejection to cooling tower) pump and cooling tower
fan in the cooling tower fan. Effectively, the overall energy consumption
would be towards:
− Compressor kW
− Chilled water pump kW
− Condenser water pump kW
− Cooling tower fan kW, for induced / forced draft towers
The specific power consumption for certain TR output would therefore have
to include:
− Compressor kW/TR
− Chilled water pump kW/TR
− Condenser water pump kW/TR
− Cooling tower fan kW/TR
The overall kW/TR is the sum of the above.
COPCarnot = Te / Tc - Te
This expression also indicates that higher COPCarnot is achieved with higher evaporator
temperature and lower condenser temperature.
But COPCarnot is only a ratio of temperatures, and hence does not take into account the
type of compressor. Hence the COP normally used in the industry is given by
In the field performance assessment, accurate instruments for inlet and outlet chilled
water temperature and condenser water temperature measurement are required, preferably
with a least count of 0.10C. Flow measurements of chilled water can be made by an
ultrasonic flow meter directly or inferred from pump duty parameters. Adequacy check
of chilled water is needed often and most units are designed for a typical 0.68 m3/hr per
TR (3 gpm/TR) chilled water flow. Condenser water flow measurement can also be made
by a non-contact flow meter directly or inferred from pump duty parameters. Adequacy
check of condenser water is also needed often, and most units are designed for a typical
0.91 m3/hr per TR (4 gpm / TR) condenser water flow.
In case of air conditioning units, the airflow at the Fan Coil Units (FCU) or the Air
Handling Units (AHU) can be measured with an anemometer. Dry bulb and wet bulb
temperatures are measured at the inlet and outlet of AHU or the FCU and the refrigeration
load in TR is assessed as ;
Q × ρ × (h in − h out )
TR =
3024
Use of psychometric charts can help to calculate hin and hout from dry bulb, wet bulb
temperature values which are, in-turn measured, during trials, by a whirling
psychrometer.
Power measurements at, compressor, pumps, AHU fans, cooling tower fans can be
accomplished by a portable load analyzer.
Estimation of air conditioning load is also possible by calculating various heat loads,
sensible and latent based on inlet and outlet air parameters, air ingress factors, air flow,
no. of people and type of materials stored.
Although the kW/ TR can serve as an initial reference, it should not be taken as an
absolute since this value is derived from 100% of the equipment's capacity level and is
based on design conditions that are considered the most critical. These conditions occur
may be, for example, during only 1% of the total time the equipment is in operation
throughout the year. Consequently, it is essential to have data that reflects how the
equipment operates with partial loads or in conditions that demand less than 100% of its
capacity. To overcome this, an average of kW/TR with partial loads ie Integrated Part
Load Value (IPLV) have to be formulated.
The IPLV is the most appropriate reference, although not considered the best, because it
only captures four points within the operational cycle: 100%, 75%, 50% and 25%.
Furthermore, it assigns the same weight to each value, and most equipment usually
operates at between 50 % and 75% of its capacity. This is why it is so important to
prepare specific analysis for each case that addresses the four points already mentioned,
as well as developing a profile of the heat exchanger's operations during the year.
There is a tendency of the process group to operate with high safety margins which
influences the compressor suction pressure / evaporator set point. For instance, a process
cooling requirement of 150C would need chilled water at a lower temperature, but the
range can vary from 60C to say 100C. At 100C chilled water temperature, the refrigerant
side temperature has to be lower, say –50C to +50C. The refrigerant temperature, again
sets the corresponding suction pressure of refrigerant which decides the inlet duty
conditions for work of compression of the refrigerant compressor. Having the optimum /
minimum driving force (temperature difference) can, thus, help to achieve highest
possible suction pressure at the compressor, thereby leading to less energy requirement.
This requires proper sizing of heat transfer areas of process heat exchangers and
evaporators as well as rationalizing the temperature requirement to highest possible value.
A 10C raise in evaporator temperature can help to save almost 3 % on power
consumption. The TR capacity of the same machine will also increase with the evaporator
temperature, as given in Table 4.4.
Refrigeration
Evaporator Specific Power Increase in
Capacity*
Temperature (0C) Consumption kW/ton (%)
(tons)
5.0 67.58 0.81 -
0.0 56.07 0.94 16.0
-5.0 45.98 1.08 33.0
-10.0 37.20 1.25 54.0
-20.0 23.12 1.67 106.0
* 0
Condenser temperature 40 C
Towards rationalizing the heat transfer areas, the heat transfer coefficient on refrigerant
side can be considered to range from 1400 – 2800 watts /m2K.
The refrigerant side heat transfer areas provided are of the order of 0.5 Sqm./TR and
above in evaporators.
Condensers in a refrigeration plant are critical equipment that influence the TR capacity
and power consumption demands. Given a refrigerant, the condensing temperature and
corresponding condenser pressure, depend upon the heat transfer area provided,
effectiveness of heat exchange and the type of cooling chosen. A lower condensing
temperature, pressure, in best of combinations would mean that the compressor has to
work between a lower pressure differential as the discharge pressure is fixed by design
and performance of the condenser. The choices of condensers in practice range from air
cooled, air cooled with water spray, and heat exchanger cooled. Generously sized shell
and tube heat exchangers as condensers, with good cooling tower operations help to
operate with low discharge pressure. values and the TR capacity of the refrigeration plant
also improves. With same refrigerant, R22, a discharge pressure of 15 kg/cm2 with water
cooled shall and tube condenser and 20 kg/cm2 with air cooled condenser indicate the kind
of additional work of compression duty and almost 30 % additional energy consumption
required by the plant. One the best option at design stage would be to select generously
sized (0.65 m2/TR and above) shell and tube condensers with water-cooling as against
cheaper alternatives like air cooled condensers or water spray atmospheric condenser
units.
Specific Power
Condensing Refrigeration Increase in
Consumption
Temperature (0C) Capacity (tons) kW/TR (%)
(kW / TR)
After ensuring procurement, effective maintenance holds the key to optimizing power
consumption.
Heat transfer can also be improved by ensuring proper separation of the lubricating oil
and the refrigerant, timely defrosting of coils, and increasing the velocity of the secondary
coolant (air, water, etc.). However, increased velocity results in larger pressure drops in
the distribution system and higher power consumption in pumps / fans. Therefore, careful
analysis is required to determine the most effective and efficient option.
Fouled condenser tubes force the compressor to work harder to attain the desired
capacity. For example, a 0.8 mm scale build-up on condenser tubes can increase energy
consumption by as much as 35 %. Similarly, fouled evaporators (due to residual
lubricating oil or infiltration of air) result in increased power consumption. Equally
important is proper selection, sizing, and maintenance of cooling towers. A reduction of
0.550C temperature in water returning from the cooling tower reduces compressor power
consumption by 3.0 % (see Table 4.6).
Efficient compressor operation requires that the compression ratio be kept low, to reduce
discharge pressure and temperature. For low temperature applications involving high
compression ratios, and for wide temperature requirements, it is preferable (due to
equipment design limitations) and often economical to employ multi-stage reciprocating
machines or centrifugal / screw compressors.
Multi-staging systems are of two-types: compound and cascade – and are applicable to all
types of compressors. With reciprocating or rotary compressors, two-stage compressors
are preferable for load temperatures from –20 to –580C, and with centrifugal machines for
temperatures around –430C.
In multi-stage operation, a first-stage compressor, sized to meet the cooling load, feeds
into the suction of a second-stage compressor after inter-cooling of the gas. A part of the
high-pressure liquid from the condenser is flashed and used for liquid sub-cooling. The
second compressor, therefore, has to meet the load of the evaporator and the flash gas. A
single refrigerant is used in the system, and the work of compression is shared equally by
the two compressors. Therefore, two compressors with low compression ratios can in
combination provide a high compression ratio.
For temperatures in the range of –460C to –1010C, cascaded systems are preferable. In
this system, two separate systems using different refrigerants are connected such that one
provides the means of heat rejection to the other. The chief advantage of this system is
that a low temperature refrigerant which has a high suction temperature and low specific
volume can be selected for the low-stage to meet very low temperature requirements.
During part-load operation, the evaporator temperature rises and the condenser
temperature falls, effectively increasing the COP. But at the same time, deviation from
the design operation point and the fact that mechanical losses form a greater proportion of
the total power negate the effect of improved COP, resulting in lower part-load efficiency.
Capacity regulation through speed control is the most efficient option. However, when
employing speed control for reciprocating compressors, it should be ensured that the
lubrication system is not affected. In the case of centrifugal compressors, it is usually
desirable to restrict speed control to about 50 % of the capacity to prevent surging. Below
50 %, vane control or hot gas bypass can be used for capacity modulation.
The efficiency of screw compressors operating at part load is generally higher than either
centrifugal compressors or reciprocating compressors, which may make them attractive in
situations where part-load operation is common. Screw compressor performance can be
optimized by changing the volume ratio. In some cases, this may result in higher full-load
efficiencies as compared to reciprocating and centrifugal compressors. Also, the ability of
screw compressors to tolerate oil and liquid refrigerant slugs makes them preferred in
some situations.
The selection of refrigeration systems also depends on the range of temperatures required
in the plant. For diverse applications requiring a wide range of temperatures, it is
generally more economical to provide several packaged units (several units distributed
throughout the plant) instead of one large central plant. Another advantage would be the
flexibility and reliability accorded. The selection of packaged units could also be made
depending on the distance at which cooling loads need to be met. Packaged units at load
centers reduce distribution losses in the system. Despite the advantages of packaged units,
central plants generally have lower power consumption since at reduced loads power
consumption can reduce significantly due to the large condenser and evaporator surfaces.
Many industries use a bank of compressors at a central location to meet the load.
Usually the chillers feed into a common header from which branch lines are taken to
different locations in the plant. In such situations, operation at part-load requires extreme
care. For efficient operation, the cooling load, and the load on each chiller must be
monitored closely. It is more efficient to operate a single chiller at full load than to
operate two chillers at part-load. The distribution system should be designed such that
individual chillers can feed all branch lines. Isolation valves must be provided to ensure
that chilled water (or other coolant) does not flow through chillers not in operation.
Valves should also be provided on branch lines to isolate sections where cooling is not
required. This reduces pressure drops in the system and reduces power consumption in
the pumping system. Individual compressors should be loaded to their full capacity before
operating the second compressor. In some cases it is economical to provide a separate
smaller capacity chiller, which can be operated on an on-off control to meet peak
demands, with larger chillers meeting the base load.
Flow control is also commonly used to meet varying demands. In such cases the savings
in pumping at reduced flow should be weighed against the reduced heat transfer in coils
due to reduced velocity. In some cases, operation at normal flow rates, with subsequent
longer periods of no-load (or shut-off) operation of the compressor, may result in larger
savings.
Depending on the nature of the load, it is economical to provide a chilled water storage
facility with very good cold insulation. Also, the storage facility can be fully filled to
meet the process requirements so that chillers need not be operated continuously. This
system is usually economical if small variations in temperature are acceptable. This
system has the added advantage of allowing the chillers to be operated at periods of low
electricity demand to reduce peak demand charges - Low tariffs offered by some electric
utilities for operation at night time can also be taken advantage of by using a storage
facility. An added benefit is that lower ambient temperature at night lowers condenser
temperature and thereby increases the COP.
In overall plant design, adoption of good practices improves the energy efficiency
significantly. Some areas for consideration are:
Design of cooling towers with FRP impellers and film fills, PVC drift
eliminators, etc.
Use of softened water for condensers in place of raw water.
Use of economic insulation thickness on cold lines, heat exchangers,
considering cost of heat gains and adopting practices like infrared
thermography for monitoring - applicable especially in large chemical /
fertilizer / process industry.
a) Cold Insulation
Insulate all cold lines / vessels using economic insulation thickness to minimize heat
gains; and choose appropriate (correct) insulation.
b) Building Envelop
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains.
Minimise the air conditioning loads by measures such as roof cooling, roof painting,
efficient lighting, pre-cooling of fresh air by air- to-air heat exchangers, variable
volume air system, otpimal thermo-static setting of temperature of air conditioned
spaces, sun film applications, etc.
ii) Ensure adequate quantity of chilled water and cooling water flows, avoid bypass
flows by closing valves of idle equipment.
iii) Minimize part load operations by matching loads and plant capacity on line; adopt
variable speed drives for varying process load.
iv) Make efforts to continuously optimize condenser and evaporator parameters for
minimizing specific energy consumption and maximizing capacity.
QUESTIONS
List the types of refrigeration plants by operating principle and by
1. applications?
REFERENCES
1. Technology Menu on Energy Efficiency (NPC)
2. ASHRAE Hand Book
3. NPC Case Studies
4. PCRA Literature
5. Vendor Information