EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS


EasyLogic PM2000 series
Technical Datasheet
The EasyLogic™ PM2000 multi-function power and energy meter
Offering all the measurement capabilities required to monitor and electrical installation in a single 96 x 96 mm unit, with LED
or LCD display options.

Applications
Cost management applications

• Bill checking to verify that you are only charged for the energy you use
• Aggregation of energy consumption, including WAGES, and cost allocation per area, per usage, per shift or per time
within the same facility
• Energy cost and usage analysis per zone, per usage or per time period to optimise energy usage

Network management applications

• Metering of electrical parameters to better understand the behaviour of your electrical distribution system
• Power quality analysis
PB115532

PB120538

LCD display LED display

Version: 1.0 - 16/06/2021


PLSED310091EN
1
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000
PB120539

Introducing EasyLogic PM2000 series, next generation power meter which offers all
the measurement capabilities required to monitor an electrical installation in a
single 96 x 96 mm unit. PM2000 meters are available in LED and LCD display
variants.

• PM2100 series:
– LED display type: Intuitive navigation with self-guided, three buttons,
bright red colour LEDs of 14.2 mm height. Two columns of LEDs
indicate the parameter name chosen for display.

• PM2200 series:
– LCD display type: Monochrome graphical LCD of 128 x 128 pixels lets
users read all three phase values simultaneously. The bright display
enables easy reading even in extreme lighting conditions and viewing
angles. with intuitive menus, multi-language text, icons and graphics.
PM2100 series LED display meter
• Network management:
– Power Quality analysis: THD % and individual harmonics to 15th or 31st order.
– Measurement of True PF and Displacement PF.
– Recording Min/Max values of instantaneous parameters with date and
timestamp.
PB115531

– Optional IO modules comprising either 2 Digital Inputs and 2 Outputs, or


2 Analog Inputs and 2 Outputs, or 2 Digital Inputs and 2 Relay Outputs for
comprehensive WAGES monitoring.
– Calculates % unbalance for voltage & current.
– Embedded 2 D/I and 2 R/O or 2 A/I and 2 A/O in PM2125 and PM2225
meters.

• Main characteristics:
– Easy to install: Mounts using two clips, no tools required. Compact 54
mm depth, connectable up to 480 ±10% AC Volts L-L without voltage
transformers for installations compliant with measurement category III, and
double insulated.
– Easy to operate: Intuitive navigation with self-guided menus and LED
for test and calibration on site or lab. Heartbeat LED indicates normal
functioning and communication status if connected to RS-485 network.
– Product standard compliance
PM2000 LCD display – Active energy Class 1.0 as per IEC 62053-21
– Active energy Class 0.5S as per IEC 62053-22 (partial compliance for
active energy test clause only)
Feature selection – Reactive energy Class 1.0 as per IEC 62053-24 (partial compliance
Commercial ref. number Model for reactive energy test clause only)
METSEPM2110 PM2110 – Tested in accordance with IEC 62052-11 standard for
– 5 A, I-nominal
METSEPM2120 PM2120
– 1 A, I-nominal (field settable).
METSEPM2125C2AI2AO PM2125C+1

METSEPM2125C2DI2RO PM2125C+1

METSEPM2130 PM2130

METSEPM2210 PM2210

METSEPM2220 PM2220

METSEPM2225C2AI2AO PM2225C+1

METSEPM2225C2DI2RO PM2225C+1

METSEPM2230 PM2230

METSEPM2KDGTLIO22 PM2K2DIDO

METSEPM2KANLGIO22 PM2K2AIAO

METSEPM2KANLGIO11 PM2K1AIAO

METSEPM2K2DI2RO PM2K2DIRO

See your Schneider Electric representative for complete


ordering information.

+1
Available in China only

2 Version: 1.0 - 16/06/2021


PLSED310091EN
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000
• Main characteristics: (cont'd)
– Power quality analysis: The PM2000 offers THD % measurements and
Individual harmonics up to15th order in PM2x20 and PM2x25C variants
and up to 31st in PM2x30 variants.
– Load management: Simultaneous display of peak, present, predicted &
rising demands of all the four demand parameters (W, VA, VAR, Amps)
– Billing: Tenant billing/utility meter cross check (where local regulations are
not applicable).
– Timer: Active load timer, Meter operation timer and Run hours timer. These
features help advise maintenance requirements and scheduling.
– Password: Field configurable password for securing set up information
and prevent tampering of integrated values.
– Cyber security: Option for disabling RS-485 port through front panel
keys against unauthorized access. It helps during installation and trouble
shooting of communication network.
– LED display: Auto scaling, 9+3 digits for energy, 4 digits for other
parameters.
– LCD display: 5 digits for energy, 5 or 6 digits for other parameters, with
auto scaling.
– Daily time snapshot: Snapshot of Avg Voltage, Avg Current, Total Active Power
& Energy delivered as measured by the meter at configurable time of day. The
static page will be refreshed with new values at a configured time next day.
– Rate counters: 2 configurable counters display values in custom specified
units based on energy recorded (e.g., kgCO2 carbon emission or energy
cost).
– Energy preset feature: Write the energy values during maintenance
operation or replacement of meters. Configuration is through ION set up
utility tool.
– Auto reset: Monthly reset of all energies and max demand based on
configurable day of the month at fixed 00 Hrs (PM2220, PM2230).
– Suppression current: To disregard induced or negligible current flowing in
the circuit, minimum value of current detection can be settable from 5 to
99 mA, default is 5 mA (all variants).
– Retrofit register: Legacy modbus registers to read 50 parameters (meters
with communication port).
– Quadrant based VARh: Available through communication.
– Multi-tariff energy - 4 multi tariff registers, can be activated through
command, TOU or Input mode with Digital IO card (PM2230).
– Non-resettable energy (Del & Rec values of Wh, VARh, VAh) counter on
display and communication that cannot be reset to zero (PM2210/20/30).
– Configurable favorite page: Pick and configure any 4 parameters for
display from the list of - V L-L, V L-N, Amps, F, W-tot, VA-tot, VAR-tot, PF
and Wh-Del, VAh-Del, VARh-Del (PM2220, PM2230).
– Whetting output voltage: Can be used for excitation of status input signal,
available in PM2K2DIRO module.

Version: 1.0 - 16/06/2021


PLSED310091EN
3
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000 PM2000 technical specifications


General
Use on LV and MV systems with onsite programmable PT/CT ratio
Basic metering with THD %, Individual Harmonics, RTC and min/max readings
PB114317

Instantaneous rms values


Current Average line current of 3-phase, per-phase, and
calculated neutral current
Average voltage of L-L, L-N parameters, and per-
Voltage phase
Frequency Any available line
Real, reactive, and apparent power Total and per-phase value
Displacement power factor Average and per-phase signed, four quadrant
True Power Factor Average and per-phase signed, four quadrant
% Unbalance Among the phase for Amps, V L-N, V L-L
Energy values stored in non-volatile memory
Four quadrant measurement for Accumulated energy values for Active, Reactive &
Delivered (Forward or Import) and Apparent Energy parameters, quadrant basis
Received (Reverse or Export) energy Net & Total (absolute) values
Timer Accumulated time counters for active load timer,
meter operation timer, run hours and power outage
counter
Rear of PM2000 closed
Old Registers Facilitates retrieval of last cleared energy values
Demand values
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
PB114318

Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Demand sync methods Thermal, Timed, Command Sync, and Clocked Sync
Demand calculation mode Sliding, fixed and rolling block
Demand intervals Settable from 1 to 60 minutes, in steps of 1 minute
Display
PM2100 series Bright red colour LED display, 7 segment LED, ~ 14.2
mm height, 3 rows with 4 digits per row, Auto range
PM2200 series Full scape, monochrome graphical LCD of 128 x 128
pixels with viewable area of 67 x 62.5 mm
Visualization mode for signs IEC or IEEE type in LCD display meter
Communication
RS-485 serial Channel connection Industry standard Modbus RTU
protocol
Integration with software SCADA / DCS / PMS / EMS / BAS / BMS software

Rear of PM2000 open Native Plug and Play support Schneider Electric energy management system software
- EcoStruxure™ Power Monitoring Expert, EcoStruxure™
Power Operation, & ION Setup programming support
Min/Max values
Minimum & Maximum value For 8 parameters, viz., V L-L, V L-N, Amps, PF, Hz,
recording of 3-ph average or total W, VA, VAR with date and time stamp, resettable
separately through set up mode
Alarms
Alarming with time stamping in A different combination of set point driven alarms
PB114321

PM2x30 meters and digital alarms with 1 s time stamping. The alarms
can be programmed and combined to trigger digital
outputs, the meter keeps an alarm logs with the active
and historical alarms with date and time stamping in
40 registers
Diagnostics
Diagnostic page Indicates LED/LCD status, sl number, diag pages for
communication, OS & RS version
Lock/ Un-Lock
Page Lock & Unlock Unique feature to ensures that commonly referred
(PM2100 series) page is restored in 4 minutes of inactive time
Rate 1 counter +2
kgCO2 emission (example) Rate counter can be configured to display the
CO2 emission in kgCO2 format based on the kWh
measured either in delivered or received direction.
Rate 2 counter+2
Tariff counter (example) Rate counter can also be configured to calculate the
Rear of PM2000 without I/O module electricity cost based on the energy consumption in
customized currency format.
Configurable snapshot
Configurable snapshot+2 Snapshot of Avg Voltage, Avg Current, Total Active
Power & Energy delivered as measured by the meter
at configurable time in Hours:Minutes format. Static
page is refreshed with new values by next day at pre-
configured time.
+2
Available in PM2220/PM2230 (LCD) meters

4 Version: 1.0 - 16/06/2021


PLSED310091EN
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000 PM2000 electrical characteristics


Electrical characteristics
Type of measurement True RMS 64 samples per cycle
Measurement accuracy
Current, average & per-phase ±0.5 %
PB114320

Voltage, average & per-phase ±0.5 %


Frequency ±0.05 %
Power Factor, average & per- ±0.01
phase
Power (W-Active, VA- Apparent) ±0.5 %
Power (VAR- Reactive) ±1.0 %
Real/Active Energy (Wh) Class 0.5S as per IEC 62053-22 and Class 1.0 as per
IEC 62053-21 for both CT nominal of 5 A and 1 A+3,
complies to IEC 61557-12 Class 0.5 (PM2x30/PM2x25)
Reactive Energy Class 1.0 as per IEC 62053-24
Apparent Energy ±0.5 %
THD % and ±5 % FS for THD % and Individual harmonics
Individual Harmonics- V & A
Input-voltage
VT primary 999 kV L-L max, secondary voltage depends on VT
ratio
Rear of PM2000 with I/O module
U nominal 277 V L-N/480V L-L
Measured V with full range 20-277 V L-N/35 - 480 V L-L, cat III
20-347 V L-N/35 - 600 V L-L, cat II
Permanent overload 750 V AC L-L
Impedance => 5 MΩ
Frequency nominal 50/60 Hz
PB114319

VA burden < 0.2 VA at 240 V AC L-N


Input-current
CT ratings Primary adjustable 1 A to 32768 A
Secondary 1 A or 5 A I-nominal field settable
Measured Amps with over 5 mA to 6 A
range and Crest Factor
Over current withstand Continuous 12 A, 10s/hr 50 A, 1s/hr 500 A
Impedance < 0.3 mΩ
Frequency nominal 50/60 Hz
VA Burden <0.024 VA at 6 A
AC control power
Rear of PM2000 with I/O module disconnected Operating range 44- 277 V AC ±10%
(80-277 V AC ±10% for PM2x30/PM2x25)
Burden <6 VA at 277 V AC L-N
(<8 VA for PM2x30 and PM2x25)
Frequency 45 to 65 Hz
Ride-through time 100 ms typical at 120 V AC and maximum burden
(50 ms with Analog IO card for PM2x30)
400 ms typical at 230 V AC and maximum burden
(50 ms with Analog IO card for PM2x30)
DC control power
Operating range 48-277 V DC ±10% (100-277 V DC ±10% for PM2x30/
PM2x25)
Burden < 2 W at 277 V DC
(< 3.3 W for PM2x30 and PM2x25)
Ride-through time 50 ms typical at 125 V DC and maximum burden
Real time clock
RTC with battery backup 3 years (when meter is in Power OFF condition)
Displays update
Instantaneous 1s
Demand 15 s
Harmonics 5s
Wiring configuration
User programmable 1ph, 2w, L-N
1ph, 2w, L-L
1ph, 3w, L-L with N (2phase)
3ph, 3w, Delta, Ungrounded
3ph, 3w, Delta, Corner Grounded+4
3ph, 3w, Wye, Ungrounded+4
3ph, 3w, Wye Grounded+4
3ph, 3w, Wye, Resistance Grounded+4
3ph, 4w, Open Delta, Center-Tapped+4
3ph, 4w, Delta, Center-Tapped+4
3ph, 4w, Wye, Ungrounded+4
3ph, 4w, Wye Grounded
3ph, 4w, Wye, Resistance Grounded+4
+3
For 1 A CT nominal, additional error of ±1 % from 50 mA to 150 mA, ±2 % for current > 10
mA to < 50 mA. Partial standard compliance for Class 0.5S meter type (energy test clause only)
+4
Through communication in PM2100 series meters

Version: 1.0 - 16/06/2021


PLSED310091EN
5
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000
PM2000 series mechanical characteristics
Mechanical characteristics
Weight ~ 300 gm
IP degree of protection IP54 front side, IP30 meter body as per IEC 60529;
Upgrade to IP65 front side with Optional accessory kit METSEIP65OP96X96FF
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 54 mm maximum (depth of the meter from housing mounting flange) and 13 mm (protrusion of
meter from housing flange). Meter depth with IO module is 74 mm
Mounting position Vertical
Panel thickness 5 mm maximum
Environmental characteristics
Operating temperature Meter -10 to +60 °C (14 to 140 °F)
Storage temperature Meter -25 to +70 °C (-13 to 158 °F)
Humidity rating 5 to 95 % RH non condensing
Pollution degree 2
Altitude ≤ 2000 m (6562 ft) Category III
Product life Minimum 7 years
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 Ed-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 No. 61010-1, for 600V AC
Measurement Category (Voltage CAT III up to 480 V L-L
and Current inputs) CAT II up to 600 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 Ed-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH, PEP, RoHS complied
Other certification RCM (Australia), EAC (Russia)
Communication
RS-485 port Modbus RTU: 2-Wires, with ground & shield, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None,
1 stop bit if parity is Odd or Even, 2 stop bits if None
DLF3000: Firmware update through communication port
Pulse Output – POP Max 40 V DC, 20 mA 20 ms ON time
Configurable pulse weight from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Isolation 2.5 kV RMS, double insulated
Protection features Password protected for set-up & clearing energy and Min/Max data
Display language (LCD) English, Spanish, French, Chinese, German, Portugese, Russian, Turkish
Technical publication Printed installation guide (IG) with the meter in multi language (EN, ES, FR, DE, PT, RU, TR, ZH)
Human machine interface

Display type LED display: 7 segment LED, ~ 14.2 mm height, 3 rows with 4 digits per row 2 columns of LEDs, one on
each side of the LED panel to indicate the parameters under measurement
LCD display: Monochrome graphical LCD of 128 x 128 pixels with viewable area of 67 x 62.5 mm
Keypad / Buttons PM2100 series: 3 buttons for navigation & combination of 2 buttons for performing set-up, Lock/unlocking of
page, Diagnostic page operation
PM2200 series: 4 buttons for intuitive navigation of HMI/ UI pages
Calibration LED Indicator Red colour, meter constant is configurable from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Communication activity Green LED (for indicating RS-485 interface or heart beat pulse)

6 Version: 1.0 - 16/06/2021


PLSED310091EN
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000 PM2000 series electrical characteristics of IO modules


Status Inputs (Digital Inputs)
Voltage ratings 18.5 to 36 V DC, OFF 0 to 4 V DC
Input resistance 110 kW
PB115529

Max Frequency 2 Hz (T ON min = T OFF min = 250 ms)


Detect Time 20 ms
Update time 1s
Isolation 2.5 kV RMS
Supported models Available as default feature in PM2125/ PM2225 and
Expandable option in PM2130/ PM2230 meter model
Application Integration of Breaker status or other non-electrical
devices like steam, water, gas meter through pulse inputs
Display support Available on PM2230/PM2225 (LCD type).
In PM2130/PM2125 meter, data is available through
communication only.
Set up and configuration Through set-up software
Digital Outputs
Voltage ratings 40 V DC max, 20mA max
On Resistance 50 W max
Meter constant Configurable from 1 to 9999000 k_h (kWh, kVARh, kVAh)
Rear of PM2200 with I/O module
Pulse width 20, 25, 50, 100 ms
Pulse frequency (typical) 25 Hz
Leakage current 1 micro Amps
Isolation 2.5 kV RMS
Supported models Available as default feature in PM2125/ PM2225 and
Expandable option in PM2130/ PM2230 meter model
DIDOISO

Alarm conditions 23 set point driven standard alarms, 4 Unary alarms, 2


Digital inputs status
Application Pulse output: configurable for energies
upper / lower limit: configurable for 9 parameters with 14
set point: V L-L, V L-N, Amps, F, V-THD %, W-tot, VA-tot,
VAR-tot, PF-avg
Display support Available on PM2230/PM2225 (LCD type).
In PM2130/PM2125 meter, data is available through
communication only
Set up and Configuration Through set-up software
Analog inputs
Measurement scale 4-20 mA
Input impedance ≤300 W
Digital I/O module
Max source impedance >500 W
Update rate 1s
Accuracy 1 % of Full scale at ambient temp 0.1 %/K for de-rating
Voltage ratings Typical 12 V (max 30 V)
Power Consumption <1.5 W
Isolation 2.5 kV RMS
PB115540

Supported models Expandable option in PM2130/PM2230 meter models


Application Configurable for inputs from flow rates, RPM, fluid level,
oil pressure, temperature measurement devices or
transducers with option of 81 different Uni code selection.
Configuration via set up software
Display Available on PM2230 (LCD type). In PM2130 meter, data is
available through communication only
Set up and configuration Through set up software
Analog outputs
Scale 4-20 mA
Load impedance ≤600 W
Update rate 1s
Analog I/O module Accuracy 1 % of Full scale at ambient temp
Voltage ratings Typical 12 V (max 30 V)
Power Consumption <1.5 W
Isolation 2.5 kV RMS
Supported models Expandable option in PM2130/ PM2230 meter models
Application Analog outputs can be associated to 40 different
instantaneous parameters
Display Available on PM2230 (LCD type). In PM2130 meter, data is
available through communication only
Set-up & configuration Through set-up software
Mechanical characteristics
Mechanical dimension 90.5 mm W x 53 mm H x 14.67 mm D (without connector)
Weight 50 gm

Version: 1.0 - 16/06/2021


PLSED310091EN
7
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000
PM2000 series electrical characteristics of IO modules
Mechanical characteristics
Mechanical dimension 90.5 mm W x 53 mm H x 14.67 mm D (without connector)
PB120599_sm

Weight 50 gm
Relay Outputs
Voltage rating 30 V DC 5A load
250 V AC 8A, PF=1.0
250 V AC 6A, PF=0.4
Output Frequency 0.5 Hz maximum (1 second ON / 1 second OFF)
Relay type Mechanical, Form A, Potential free
Isolation 2.5 kV RMS
Supported models Available as default feature in selected references in
PM2125/PM2225 model.
Expandable options in PM2130/PM2230 model.

Alarm conditions 23 set point driven standard alarms, 4 Unary alarms,


Digital Input Relay Output module 2 Digital inputs status
Application Upper / lower limit: configurable for 10 parameters with 23
set points: V L-L, V L-N, Amps, F, V-THD %, W-tot, VA-tot,
VAR-tot, PF-avg, last, present & predicted parameters for
3 power demands
Display and communication Available on PM2230/PM2225 (LCD type).
In PM2130/PM2125 meter, data is available through
communication only
Set up and Configuration Through ION set up software utility tool

8 Version: 1.0 - 16/06/2021


PLSED310091EN
EASYLOGIC POWER & ENERGY METERS FUNCTIONS AND CHARACTERISTICS

PM2000
Feature set summary PM2110 PM2120 PM2125C PM2130 PM2210 PM2220 PM2225C PM2230
Accuracy Class for Wh 1.0 0.5S 1.0 0.5S
Accuracy Class for VARh 1.0
Accuracy for VAh ±0.5 %
Amps, per-phase, average and
calculated neutral current b
Voltage, V L-N, V L-L, per-phase and
average b
True PF True PF
Power Factor True PF True PF
Displacement PF+4 Displacement PF
Frequency, any available phase b
Power: W, VA, VAR: per phase and total
b

Current Current
3-phase unbalance % Current Current
Voltage+4 Voltage
Demand parameters (Present, Last, b b b b
Predicted and Peak for W, VA, VAR, A) (no timestamp) (no timestamp)
Date and Time stamp for peak demand

Energy: Wh, VAh, VARh (4 quadrant) Delivered, Received Delivered,


Delivered, Delivered, Received
Delivered (Import or Forward), Received Total+4, Net+4, Received,
Received Total, Net, Last cleared
(Export or Reverse) Last cleared+4 Total, Net
Active load timer, meter operating timer, b
run hours and power outage counter Through com

THD %: Voltage L-N or L-L, Amps per


phase
b
Individual harmonics for Voltage, Current,
Up to 15th+4 Up to 15th+4 Up to 31st+4 Up to 15th Up to 15th+4 Up to 31st
per-phase
Min/ Max with real time clock For avg or b
total of V L-L, V L-N, Amps, PF, Hz, W,
Through com
VA, VAR parameters with date and time
stamp of occurrence
RTC/battery+6 b b b b b
Communication Pulse Output RS-485 Pulse Output RS-485
Expandable Analog IO module+5 b b
PM2K2AIAO: 2 input & 2 output channels
PM2K1AIAO: 1 input & 1 output channel
Expandable Digital IO module+5 Embedded b Embedded b
PM2K2DIDO: 2 input & 2 output channels
Expandable DI RO module +5
Embedded b Embedded b
PM2K2DI2RO: 2 Digital input, 2 Mech with 2DI/RO with 2DI/RO
Relay output channels
Whetting output voltage: 24V DC, 8 mA
max load
Customizable data logging up to 2 b b
parameters. Option to select Power (W,
VA, VAR) Bi-directional energy (±Wh,
±VAh, ±VARh), Demand (W, VA, VAR, A)
with configurable interval and duration
(e.g. 2 parameters for 60 days at 15
minutes interval)
Alarms: 14 set point driven alarms from 9 b b b b
parameters (V L-L,
V L-N, Amps, F, V-THD %, W-tot, VA-tot,
VAR-tot, PF-avg), 4 Unary alarms (meter
power up, meter reset, meter diagnostic,
phase reversal) and 2 digital inputs status
(with DI/DO card only)
Daily time snapshot of Avg Voltage, Avg b b
Current, Total active power & Energy
delivered as measured at configurable
time of day+7
Rate counters: 2 configurable counters to b b
display values in customer specified units
base on energy measured (e.g., kgCO2
emission or energy cost)+7

+4
Through communication only
+5
Any one IO module can be used at a time with PM2130 or PM2230 meter. The control power range with IO module (including PM2125/ PM2225 references) shall
be 72 to 304 V AC L-N or 90 to 304 V DC.
+6
Battery backup duration 3 years when meter is in Power OFF condition.
+7
Configurable snapshot and rate counter features (not available in PM2125/ PM2225 meters)

Version: 1.0 - 16/06/2021


PLSED310091EN
9
EASYLOGIC POWER & ENERGY METERS DIMENSIONS AND CONNECTION

PM2000
PM2000 LCD display legend description

A Menu selection buttons


PB115535

B Energy pulsing LED (red) Heartbeat / communications LED (green)

C Navigation or menu selections:

Exit screen and go up one level

Move cursor up list of options

Move cursor down, display more options

Move cursor one character to the left

Scroll right and display more menu items

+ Show next item in list or increase the highlighted value


_ Show previous item in list

D Maintenance & alarm notification area


PB115536

E Control power

F Voltage inputs

G Current inputs

H RS-485 / POP

I Gasket

J IO channel slot - optional accessory for PM2230, embedded in PM2225 meter

PM2000 LED display legend description


A Phase measurements (VL-N, VL-L, I, kVA, kW, kVAR, PF, V-THD %, I-THD %)
PB120540

B Demand measurements (DM=Demand, PrsDM=Present demand,


PrdDM=Predictor demand, MD=Maximum demand))

C RTC Date & time

D Negative indicator

E Navigation key to navigate down

F Energy readings Apparent enegry, Active energy, Reactive energy

G Navigation key to navigate up

H OK Enter key

I Energy pulsing LED (red) Heartbeat / communications LED (green)

J x 1000 indicator
PB115538

K System measurements Vavg, kVA, F, lavg, kW, In, PFavg, kVAR, lunb

L Control power L1, L2

M Input voltage terminals V1, V2, V3, VN

N Input current terminals I1+, I1-, I2+, I2-, I3+, I3-

O RS-485 communications / POP terminals

P Gasket

Q IO channel slot - optional accessory for PM2130, embedded feature in


PM2125 meter

10 Version: 1.0 - 16/06/2021


PLSED310091EN
EASYLOGIC POWER & ENERGY METERS DIMENSIONS AND CONNECTION

PM2000
PM2000 meter rear view Meter installation
PB114323

PM2000 multi-function meter mechanical dimensions


PB114324

PM2000 Digital and Analog IO module mechanical dimensions


PB115539_m

See the appropriate Installation Guide for correct installation instructions.

Version: 1.0 - 16/06/2021


PLSED310091EN
11
www.se.com

Schneider Electric Industries SAS


35, Rue Joseph Monier
CS 30323
92506 Rueil Malmaison Cedex

RCS Nanterre 954 503 439


Capital social 928 298 512 €
www.se.com

June 2021
EasyLogic™ PM2000 Series As standards, specifications and designs develop from time to time, please
PLSED310091EN ask for confirmation of the information given in this document.

© 2021 - Schneider Electric. All rights reserved.


All trademarks are owned by Schneider Electric Over 75 % of Schneider Electric products
Industries SAS or its affiliated companies. have been awarded the Green Premium ecolabel.

You might also like