0% found this document useful (0 votes)
448 views45 pages

Dike Capacity and Relief Valve Sizing

This document provides steps to design a pressure relief valve for liquid service. It gives various parameters like discharge coefficient, pressure drop, density, flow rate, specific gravity, upstream and back pressures. Using these values in equations, it calculates the required orifice area as 1.1580517 square inches for a flow rate of 300 gallons per minute against a pressure drop of 110 psi.

Uploaded by

mitul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
448 views45 pages

Dike Capacity and Relief Valve Sizing

This document provides steps to design a pressure relief valve for liquid service. It gives various parameters like discharge coefficient, pressure drop, density, flow rate, specific gravity, upstream and back pressures. Using these values in equations, it calculates the required orifice area as 1.1580517 square inches for a flow rate of 300 gallons per minute against a pressure drop of 110 psi.

Uploaded by

mitul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 45

Storage Tank Capacity (Assumed) 10

STEP:1 Calculate the minimum amount that your dike is required to hold in KL:
11 KL

STEP:2 Determine the volume of the dike in cubic meter


12 m3

STEP:3 Divide the answer from step 2 by the conversion factor below to convert the size of the dike
12.0 KL

STEP:4 Compare the answers in Step 1 and Step 3 to determine if the dike will hold 110% of the vol
The answer in Step 3 must be equal to or greater than the answer in Step 1.

Ref: http://www.pstif.org/apps/dike_calculation_sheet_e.pdf
KL

d to hold in KL:

below to convert the size of the dike in cubic meter to KL

LENGTH (a) 4
if the dike will hold 110% of the volume of the tank. WIDTH (b) 2
e answer in Step 1. HEIGHT (c) 1.5

No of Steps Design Data


Step1 11.00 Design Volume
Step2 11.99 4.00
Step3 11.99 2.00
Condition Check 1.50

m
m
m

Design Data

a
b
c
For All Storage Tank Total Capacity (Assumed) 33

STEP:1 Calculate the minimum amount that your dike is required to hold in KL:
Use the total Volume (KL) of all tanks siphoned together
36.3 KL

STEP:2 Determine the volume of the dike in cubic meter


200 m3

STEP:3 Determine the displacement of other tanks within the diked area
This calculation must be repeated for each additional tank within the diked area.
17.2 m3

STEP:4 Determine the total available volume of the diked area in cubic meter.
182.8 m3

STEP:5 Divide the answer from step 4 by the conversion factor below to convert the size of the dike
182.8 KL

STEP:6 Compare the answers in Step 1 and Step 5 to determine if the dike will hold 110% of the vol
The answer in Step 5 must be equal to or greater than the answer in Step 1.

Ref: http://www.pstif.org/apps/dike_calculation_sheet_e.pdf
KL

d to hold in KL:
er

ked area
nk within the diked area.
Tank No Capacity (KL)
1 18
n cubic meter. 2 10
3 5

below to convert the size of the dike in cubic meter to KL LENGTH (a) 10
WIDTH (b) 8
HEIGHT (c) 2.5
if the dike will hold 110% of the volume of the tank.
e answer in Step 1. No of Steps
Step1 36.30
Step2 73.14
Step3 34.07
Step4 39.07
Step5 39.07
Condition Check

39.93
Length Diameter Assume L=2*D
2.71 1.36
2.52 1.26
2.31 1.16

m
m
m

Design Data
Design Volume
2.24 a
6.60 b
4.95 c
Problem Statement For Gas Service
Design a pressure relief valve for the following service.
Solution
Data Given:
Protected equipment : Separator vessel
Relief service Fuel Gas
Reason for relief Blocked gas discharge
Relieving Rate(W) 10,000 kg/hr
Gas
RatioDensity : heats for the gas
of specific 4.1 kg/m3
(CP/CV) 1.35
Compressibility factor of gas (Z) 0.95
Relieving temperature 293 K
Set pressure : 5 barg
Accumulation 10 %
Back pressure at relief valve discharge 0.5 barg
Type of relief valve Conventional

Step:1
The first step is to determine whether the gas flow type is critical or sub-critical.
For this purpose the critical flow pressure (Pcf) downstream to the relief valve has to be calculated using the followin
P1 Relieving pressure upstream to relief valve in bara
P1 6.5 barg (including 10% accumulation)
k 1.35 Ratio of specific heats of the gas .. (CP/CV)
Pcf Critical flow pressure for the given flow conditions in bara
k/k-1 3.8571
k+1/k-1 6.7143
Pcf = 3.48953291954512

If the pressure downstream or back pressure of the relief valve is lower than the critical flow pressure, then the flow i
In this case, the actual pressure downstream to the relief valve cannot fall below the critical flow pressure even if muc
Mass flow relieved cannot increase any further, for the given set of flow conditions upstream to the valve.
In the present case, back pressure (1.5 bara) < Pcf (3.5 bara). Hence the flow is of critical type.

Step:2
Next step is to use the relief valve sizing procedure given for critical flow type gas relief valve. The following equatio
A Orifice area requirement in mm2
Kd 0.975 Coefficient of discharge for gas service
Kb 1 capacity correction factor due to back pressure (for conventional relief valv
KC 1 combination correction factor for use of rupture discs (for absence of rupt
M 11.5 Cm of Nozzle Diameter
C Coefficient for fire case as a function of k (CP/CV) as per following equation

C= 351.595335073394
A= 22.08 Cm2
0.014244691539152 Square meter
Step:3
The next higher available orifice area should be selected for the pressure relief valve to be actually installed. Referrin
Relief valve sizing calculator,Next high available orifice area is selected to be A = 23.20 cm2 and the corresponding d
which correspond to different nozzle sizes for suction and discharge nozzles of the pressure relief valve. For a '4M6' v
alculated using the following equation

ow pressure, then the flow is said to be of critical type.


al flow pressure even if much lower pressure exists further downstream to the valve.
am to the valve.
type.

valve. The following equation is used,

(for conventional relief valves with near atmospheric backpressure)


e discs (for absence of rupture disc upstream to the valve)

ation
actually installed. Referring to the table of standard orifice sizes given in EnggCyclopedia's
cm2 and the corresponding designating letter is 'M'. Available valve size is '4M6'
re relief valve. For a '4M6' valve suction nozzle is of 4" size and discharge nozzle of 6" size.
Problem Statement For Liquid Service
Design a pressure relief valve for the following service.
Solution
Data Given:
Kd 0.65 effective discharge co efficient
Delta P 110 Pressure drop across the orifice
Gc 1 Gravitational Constant
Rho 1 Density of fluid

u 9.64105803322 distance/time

Unit-1 1 In2
This 2 Lines are written only for unit
consistency do not change this unit or value
Unit-2 1 Psi^0.5 during calculation
38 Gallon Per Minute
Q 300 Volumetric flow of liquid gallon Per Minute
G 1 Specific gravity of liquid
Kw 1 Adjustment factor for back pressure
Kv 1 Adjustment factor for viscocity
P1 110 Upsteam relieving pressure psig
P2 0 Total Back pressure psig

A 1.15805172783 In2
0.0007471 Square meter
Problem Statement
Design a pressure relief valve for the following service.
Solution
Data Given:
A
W 21500
K 0.975
P1 225
262.2
Ksh 1

Kn 1

Kb 1

A= 1.6330291152
0.0010536
For Steam Sizing
ef valve for the following service.

Minimum required effective discharge area


Required relieving capacity,
Effective coefficient of discharge
Relieving pressure,
This is the set pressure (psig) +overpressure(psi) + atmospheric pressure (psia).
Capacity correction factor due to the degree of superheat in the steam.
For saturated steam use Ksh = 1.00.
Capacity correction factor for dry saturated steam at set pressures
above 1500 psia and up to 3200
Capacity correction factor due to back pressure.
For conventional valves with superimposed (constant) back pressure exceeding critical

In2
Square meter
10% Overpressure (lb/hr)

In2
pounds per hour

pounds per square inch

psia.

eding critical
Valve Sizing and Selection
Metric Units
Case:1 Gas and Vpour Sizing 10% over pressure (Kg/hr)
A
C 344

K 0.975
Kb 1

M 19
P1 1450
1696
T 323
W 2675
Z 1

A= 255.161549112399

Case:2 Steam Sizing 10% over pressure (Kg/hr)


A
W 9750
K 0.975
P1 1550
1806
Ksh 1

Kn 1

Kb 1

A= 1054.26356589147

Case:3 Liquid Sizing Spring loaded Valves Styles JLT-JOS,JLT-JBS, Series 900 AND Series BP
A
G 1.23
Q 475
P1 690
P2 207
Delta P 552
Kv 1
Kw 0.866
A= 411.676293538434
Valve Sizing and Selection
Metric Units
Vpour Sizing 10% over pressure (Kg/hr)
Minimum required effective discharge area,
Coefficient determined from an expression of the ratio of
specific heats of the gas or vapor at standard conditions Use C = 315 if value is unkown.
Effective coefficient of discharge. K = 0.975
Capacity correction factor due to back pressure.
For standard valves with superimposed (constant) back pressure exceeding critical
Molecular weight of the gas or vapor obtained from standard tables
Relieving pressure, kiloPascals absolute. This is the
set pressure (kPa) + overpressure (kPa) +atmospheric pressure (kPa)
Absolute temperature of the fluid at the valve inlet,
Required relieving capacity,
Compressibility factor

square mm

zing 10% over pressure (Kg/hr)


Minimum required effective discharge area
Required relieving capacity
Effective coefficient of discharge. K = 0.975
Relieving pressure. This is the
set pressure (kPaa) + overpressure (kPa) + atmospheric pressure (kPa)
Capacity correction factor due to the degree of superheat in the steam.
For saturated steam use Ksh = 1.00
Capacity correction factor for dry saturated steam at set pressures above 10346 kPaa and
up to 22,060 kPaa.
Capacity correction factor due to back pressure.
For conventional valves with superimposed (constant) back pressure exceeding critical
(constant) back pressure exceeding

square mm

izing Spring loaded Valves Styles JLT-JOS,JLT-JBS, Series 900 AND Series BP
Minimum required effective discharge area
Specific gravity of the liquid at flowing conditions
Required relieving capacity, liters per minute at flowing temperature
Set Pressure
Back Pressure
Differential pressure This is set pressure (kPag) + overpressure (kPa) - back pressure (kPag)
Flow correction factor due to viscosity of the fluid at flowing conditions
Capacity correction factor due to back pressure on bellows or Series BP valves on liquid service
square mm
Square millimeters.

For Natural gas

degrees Kelvin (°C + 273)


kilograms per hour.

Square millimeters
kilograms per hour

kiloPascals absolute

Square millimeters.

Litre/Minute
Kpag
Kpag
(kPa).
For non viscous fluid
liquid service
Requirements for Thermal Venting Capacity in English Unit
Tank Capacity Inbreathing Outbreathing
Column 1 Column 2 Column 3 Column4

Flash Point above Flash Point below


100°F or Normal 100°F or Normal
Boiling Point Boiling Point
above 300°F below 300°F
Barrels Gallons SCFHAir SCFHAir SCFHAir
60 2,500 60 40 60
100 4,200 100 60 100
500 21,000 500 300 500
1,000 42,000 1,000 600 1,000
2,000 84,000 2,000 1,200 2,000
3,000 126,000 3,000 1,800 3,000
4,000 168,000 4,000 2,400 4,000
5,000 210,000 5,000 3,000 5,000
10,000 420,000 10,000 6,000 10,000
15,000 630,000 15,000 9,000 15,000
20,000 840,000 20,000 12,000 20,000
25,000 1,050,000 24,000 15,000 24,000
30,000 1,260,000 28,000 17,000 28,000
35,000 1,470,000 31,000 19,000 31,000
40,000 1,680,000 34,000 21,000 34,000
45,000 1,890,000 37,000 23,000 37,000
50,000 2,100,000 40,000 24,000 40,000
60,000 2,520,000 44,000 27,000 44,000
70,000 2,940,000 48,000 29,000 48,000
80,000 3,360,000 52,000 31,000 52,000
90,000 3,780,000 56,000 34,000 56,000
100,000 4,200,000 60,000 36,000 60,000
120,000 5,040,000 68,000 41,000 68,000
140,000 5,880,000 75,000 45,000 75,000
160,000 6,720,000 82,000 50,000 82,000
180,000 7,560,000 90,000 54,000 90,000
Requirements for Thermal Venting Capacity In MKS Unit
Tank Capacity Inbreathing Outbreathing
Column 1 Column 2 Column 3 Column4

Flash Point Flash Point


above 37.8°C below 37.8°C
or Normal or Normal
Boiling Point Boiling Point
above 148.9°C below 148.9°C
Litrs Litrs M3/Hr M3/Hr M3/Hr
7154.4 79 1.69896 1.13264 1.69896
11924 133 2.83160 1.69896 2.83160
59620 667 14.15800 8.4948 14.15800
119,240 1,333 28.31600 16.9896 28.31600
238,480 2,667 56.63200 34 56.63200
357,720 4,000 84.94800 51 84.94800
476,960 5,333 113.26400 68 113.26400
596,200 6,667 141.58000 85 141.58000
1,192,400 13,333 283.16000 170 283.16000
1,788,600 20,000 424.74000 255 424.74000
2,384,800 26,667 566.32000 340 566.32000
2,981,000 33,334 679.58400 425 679.58400
3,577,200 40,000 792.84800 481 792.84800
4,173,400 46,667 877.79600 538 877.79600
4,769,600 53,334 962.74400 595 962.74400
5,365,800 60,000 1047.69200 651 1047.69200
5,962,000 66,667 1132.64000 680 1132.64000
7,154,400 80,001 1245.90400 765 1245.90400
8,346,800 93,334 1359.16800 821 1359.16800
9,539,200 106,667 1472.43200 878 1472.43200
10,731,600 120,001 1585.69600 963 1585.69600
11,924,000 133,334 1698.96000 1,019 1698.96000
14,308,800 160,001 1925.48800 1,161 1925.48800
16,693,600 186,668 2123.70000 1,274 2123.70000
19,078,400 213,335 2321.91200 1,416 2321.91200
21,463,200 240,002 2548.44000 1,529 2548.44000
For tanks subject to fire exposure, the required venting capacity shall be determined by

You might also like