PCS-978
Transformer Protection
                                                                                   The PCS-978 numerical protection system can provide
                                                                                   full-scheme protection and control in one rack for various
                                                                                   transformer applications, including two-winding transformers,
                                                                                   three-winding transformers and auto-transformers. It also
                                                                                   can be used to protect shunt reactors. Up to 36 analog input
                                                                                   channels including current and voltage inputs are provided.
                                                                                   The extensive functional library, programmable logic and
                                                                                   configurable I/O are integrated to meet flexible applications.
     Functions                                                                     The unique current differential protection includes the
                                                                                   unrestraint current differential element, percentage restraint
     Protection and Control                                                        current differential element and DPFC differential element.
     •	 Transformer restrained current differential protection. (87PT)
        Three slopes are provided for the restraint characteristic of              The PCS-978 reserves two sets of CT input for dual-breaker
        percentage current differential protection. It also integrates             protection in one-and-a-half breaker and ring breaker
        the inrush current blocking, CT saturation discrimination,                 arrangements. To enhance the accuracy of data sampling,
        over excitation blocking, CT ratio compensation and unique                 the frequency-tracking function is used to trace the real-time
        vector group compensations.                                                current/voltage value.
     •	 Unrestrained current differential protection. (87UT)
        The unrestraint current differential protection instantaneously
                                                                                        Biased current differential protection consists of CT
        responds and clears a serious fault immediately.
                                                                                        saturation and harmonic blocking elements
     •	 DPFC baised current differential protection. (87DT)
                                                                                    •	 Reactor DPFC biased current differenital protection.
        Deviation of Power Frequency Component (DPFC)
                                                                                       (7/87DR)
        differential current protection is sensitive to turn-to-turn fault
                                                                                       DPFC biased current differential protection is regardless of
        and high resistance fault and is immune to load current.
                                                                                       the load current and is sensitive to small internal fault current
                                                                                       within the reactor.
     •	 Reactor restraint current differential protection. (87R)
        Inrush current can be distinguished to avoid maloperation of
                                                                                    •	 Restricted Earth Fault Protection. (REF)
        current differential protection by detecting harmonic
                                                                                       Zero sequence differential protection is used as REF for
                                                                                       each Wye-connection winding to detect sensitive ground
     •	 Reactor unrestrained current differential protection.
                                                                                       fault. Up to 3 REF protections are provided.
        (50/87UR)
                                                                     Read more on the web
94    read more on www.nrelect.com                                    www.nrelect.com
•	 Winding differential protection. (87W/87N)                               •	 Phase overcurrent alarm element. (50PAlm)
   Winding differential protection has high sensitivity to internal            The output could be used for the initiation of cooling system
   earth faults. Up to 3 winding differential protections are                  and this element is not supervised by General Fault Detector
   provided.                                                                   element.
•	 Inter-turn fault protection. (32G/21G)                                   •	 Phase-to-phase impedance protection for HV and MV side.
   Inter-turn protection consists of zero-sequence power                       (21P)
   directional element and zero-sequence impedance element.                    Users have options to select the forward direction or
                                                                               backward direction by logic setting, and power swing
•	 Overexciation protection. (24)                                              blocking logic is integrated to improve the safe operation.
   Overexcitation protection based on the ratio of voltage and
   frequency is provided.                                                   •	 Phase-to-ground impedance protection for HV and MV side.
                                                                               (21G)
                                                                               Users have options to select the forward direction or
•	 Underfrequency and overfrequency protection. (81U/81O)
                                                                               backward direction by logic setting, and power swing
   Under frequency protection with df/dt blocking and over
                                                                               blocking logic is integrated to improve safe operation.
   frequency protection are both provided. The frequency is
   derived from positive-sequence voltage.
                                                                            •	 Power swing blocking. (68)
                                                                               The unique power swing blocking logic is integrated to
•	 Mechanical protection. (MR)
                                                                               improve the safe operation of impedance protection.
   Under frequency protection with df/dt blocking and over
   frequency protection are both provided. The frequency
                                                                            •	 Voltage and current drift auto adjustment.
   is derived from positive-sequence voltage. Up to eight
                                                                               The relay continually and automatically traces the voltage
   channels of mechanical protection are provided for tank.
                                                                               and current drifts and adjusts the zero point to the normal
                                                                               value.
•	 Four stage phase overcurrent protection (50P/51P/67P)
   Overcurrent protection can be supervised by voltage
                                                                            •	 Frequency tracking.
   element, harmonic element and directional element. IDMT
                                                                               Frequency tracking is provided to accommodate the
   curves complied with IEC and ANSI are provided for
                                                                               frequency shift in power system.
   selection. Up to four overcurrent protections are provided.
•	 Four stage zero sequence overcurrent protection for each                 Monitoring and Metering
   side. (50N/51N/67N)                                                      •	 CT saturation detection.
   Overcurrent protection can be supervised by voltage
                                                                            •	 Inrush current detection.
   element, harmonic element and directional element. IDMT
   curves complied with IEC and ANSI are provided for                       •	 Overexcitation detection.
   selection. Up to four zero-sequence overcurrent protections              •	 Harmonic blocking function.
   are provided.                                                            •	 CT failure detection supervision.
                                                                            •	 VT failure detection supervision.
•	 Two-stage residual overvoltage protection. (59G)
   IDMT curves complied with IEC and ANSI are provided for                  •	 Tripping circuit supervision.
   selection.                                                               •	 Self diagnostic.
                                                                            •	 Fault Recorder.
•	 Two-stage definite-time and inverse-time phase overvoltage
   protection. (59P)
   IDMT curves complied with IEC and ANSI are provided for                  Communications
   selection.                                                               •	 Two 10Base-T/100Base-TX (RJ45) ports and two optional
                                                                               100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for
•	 Four-stage undervoltage protection. (27)                                    non-time-critical message, IEC 60870-5-103 over TCP/IP or
   Rate-of-change of voltage is provided for the blocking.                     DNP 3.0
                                                                            •	 Two RS-485 rear ports with IEC 60870-5-103
•	 Thermal overload protection. (49)
   Thermal overload protection based on fundamental current                 •	 Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling
   or harmonic current is provided for tripping and alarm.                     Value and GOOSE for time-critical message
                                                                            •	 One RS-485 rear port for clock synchronization
•	 Breaker failure protection. (50BF)                                       •	 One RS-232 rear port for printer
   Breaker failure protection for each breaker is supplied to
                                                                            •	 One faceplate RJ45 port for testing and setting
   initiate re-tripping and adjacent breaker tripping.
                                                                            •	 Clock synchronization via Pulse-Per-Second, IRIG-B and
•	 Pole disagreement protection. (62PD)                                        SNTP
   External binary input and zero-sequence/negative-sequence
   current are used to detect the pole disagreement state of the
   circuit breaker.
                                                              Read more on the web
                                                               www.nrelect.com                                     read more on www.nrelect.com   95
     Features
     •	 CT transient detection element based on the ratio of                              •	 The restraint current differential protection with initial restraint
        zero-sequence current to positive-sequence current is                                slope consists of sensitive and conventional differential
        provided for REF to eliminate the influence of CT transient                          elements as well as independent CT saturation criterion.
        characteristic difference.
                                                                                          •	 Maximum 4 group CT and 1 neutral CT inputs for REF
     •	 The PCS-978 provides RTD input module and DC mA input                                protection are provided.
        module to detect the oil-temperature.
                                                                                          •	 The CT saturation detection function based on 2nd and 3rd
     •	 Maximum six groups of CT inputs for differential protection                          harmonics is adopted to avoid maloperation.
        are provided.
                                                                                          •	 The amplitude of residual voltage is compensated to ensure
     •	 24 vector groups are available for the application to two-                           that the zero-sequence power directional element can
        winding transformer.                                                                 distinguish the direction correctly when system impedance is
                                                                                             too small.
     •	 288 vector groups are available for the application to
        3-winding transformer.                                                            •	 Voltage for overexcitation protection calculation is the RMS
                                                                                             value of three phase voltages which is not affected by
     •	 Optional inrush current distinguished principle is provided:
                                                                                             frequency fluctuation.
        harmonic criterion (second harmonic and third harmonic) or
        waveform distortion.                                                              •	 Directional element can be selected to control each stage
                                                                                             phase overcurrent protection with three options: none
     •	 There are two optional modes for harmonic criterion:
                                                                                             direction, forward direction and reverse direction.
        self-adaptive blocking mode and phase-to-phase cross
        blocking mode. Self-adaptive blocking mode can prevent                            •	 Disturbance records are composed of 64 fault reports and
        maloperation during transformer energization effectively and                         64 disturbance waveforms. The file format of waveform
        ensure high speed for internal faults under normal operation.                        is compatible with international COMTRADE91 and
                                                                                             COMTRADE99 file. Up to 80 analog inputs and 200 binary
     •	 Fifth harmonic or third harmonic criterion applied to detect
                                                                                             inputs can be recorded, and three oscillograph triggering
        overexciation condition.
                                                                                             mode are supported.
     •	 The Δ→Y vector group compensation is used to adjust
                                                                                          •	 The relay is compatible with IEC 61850-8-1 MMS, GOOSE
        the phase angle of secondary current and the inrush
                                                                                             and IEC 61850-9-2 Sampling Value and provides the
        current feature is reserved in each phase to realize phase-
                                                                                             independent interfaces for station bus and process bus
        segregated inrush current restraint for percentage differential
                                                                                             respectively.
        protection.
     •	 The DPFC restraint current differential protection is immune
        to load current but sensitive to small internal fault current
        within the transformer.
     Technical data
     Power Supply
      Standard                                                                       IEC 60255-11:2008
      Voltage Range                                                                  88 to 300 Vdc or 88 to 264 Vac
      Permissible AC ripple voltage                                                  ≤15% of the nominal auxiliary voltage
                                                                                     <30W (for conventional substation application)
                                     Quiescent condition
                                                                                     <35W (for smart substation application)
      Burden
                                                                                     <35W (for conventional substation application)
                                     Operating condition
                                                                                     <40W (for smart substation application)
     Analog Current
      Standard                                                                       IEC 60255-27:2005
      Phase rotation                                                                 ABC
      Nominal frequency (fn)                                                         50Hz, 60Hz
      Nominal range                                                                  fn±5Hz
      Rated Current (In)                                                             1A                                     5A
      Linear to                                                                      0.05In ~ 40In
                                                           continuously              4In
                                                           for 10s                   30In
      Thermal withstand capability
                                                           for 1s                    200In
                                                           for half a cycle          250In
      Burden                                                                         <0.2VA/phase                                     < 0.25VA/phase
                                                                          Read more on the web
96    read more on www.nrelect.com                                            www.nrelect.com
Analog Voltage
 Standard                                                                      IEC 60255-6, IEC60288
 Phase rotation                                                                ABC
 Nominal frequency (fn)                                                        50Hz, 60Hz
 Nominal range                                                                 fn±5Hz
 Rated phase-to-phase voltage (Un)                                             100~130V                      200V (Broken delta for residual voltage)
 linear to                                                                     1~170V                        1~233V
                                                       continuously            200V                          220V
 Thermal withstand capability                          10s                     260V                          380V
                                                       1s                      300V                          420V
 Burden                                                                        < 0.20VA/phase @Un            < 0.8VA/phase@Un
Transducer Input
 Standard                           IEC 60255-1:2009
 Input range                        0-20mA                                      0-10V                                0-250V
 Input resistance                   235Ω                                        8.8kΩ                                248kΩ
 Accuracy                           0.5 class                                   0.5 class                            0.5 class
Binary Inputs
 Standard                           IEC 60255-1:2009
 Rated voltage                      24V              30V                48V                  110V        125V            220V                 250V
 Rated current                      1.2mA            1.5mA              2.4mA                1.1mA       1.25mA          2.2mA                2.5mA
 Pickup voltage                     13V~17V          17V~21V            26V~34V              60.5V~77V   60.5V~77V       121V~154V            121V~154V
 Dropout voltage                    90% of pickup voltage
 Maximum permissive voltage         300Vdc
 Withstand                          2000VAC, 2800VDC(continuously)
 Resolving time for logic input     <1ms
Binary Outputs
 Item                                                       Tripping contact                                Signal contact
 Output mode                                                Potential free contact
                                                            5A@250V AC                                      8A@380V AC
 Continuous carry
                                                            5A@250V DC                                      8A@250V DC
 Pickup time                                                <8ms                                            <10ms
 Drop-off time                                              <5ms (not include delay time by software)       <8ms
                                                            6A@3s                                           10A@3s
 Short duration current                                     15A@0.5s                                        20A@0.5s
                                                            30A@0.1s                                        30A@0.2s
                                                            0.6A@48VDC                                      0.7A@48VDC
 Breaking capacity (L/R=40ms)                               0.2A@110VDC                                     0.3A@110VDC
                                                            0.1A@220VDC                                     0.2A@220VDC
                                                            380V AC                                         380V AC
 Maximal working voltage
                                                            250V DC                                         250V DC
 Test voltage across open contact                           1000V RMS for 1minute                           1200V RMS for 1 minute
Mechanical Specifications
 Enclosure dimensions (W×H×D)                            482.6mm×177.0mm×291.0mm
 Mounting                                                Flush mounted
 Trepanning dimensions (W×H)                             450.0mm×179.0mm, M6 screw
 Housing color                                           Silver grey
 Protection class: IEC 60255-1:2009
 Front side                                              IP40, up to IP51 (Flush mounted)
 Other sides                                             IP30
 Rear side, connection terminals                         IP20
 Pollution degree                                        2
Ambient Temperature and Humidity Range
 Standard                                                   IEC 60255-1:2009
 Operating temperature                                      -40°C to +70°C Note: The operating temperature of LCD is -20°C ~ +70°C
 Transport and storage temperature range                    -40°C ~ +70°C
 Permissible humidity                                       5% ~ 95%, condensation not permissible
 Altitude                                                   <3000m
                                                                      Read more on the web
                                                                      www.nrelect.com                                            read more on www.nrelect.com   97
     Communication Port
     - EIA-485 Port
      Baud rate                                   4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
      Protocol                                    IEC 60870-5-103:1997
      Maximal capacity                            32
      Transmission distance                       <500m
      Safety level                                Isolation to ELV level
      Twisted pair                                Screened twisted pair cable
     - Ethernet Port
      Connector type                              RJ-45
      Transmission rate                           100Mbits/s
      Transmission standard                       10Base-T/100Base-TX
      Transmission distance                       <100m
      Protocol                                    IEC 60870-5-103:1997 or IEC 61850
      Safety level                                Isolation to ELV level
     - Optical Fiber Port
      Characteristic                               Plastic optical fiber                             Glass optical fiber
      Terminal                                     BFOC/2.5 (OR F-SMA)                               BFOC/2.5 (OR F-SMA)
      Fibre size                                   Step-index 980/1000 μm                            Graded-index 62.5/125 μm
      Transmission distance                        Up to 40m                                         Up to 1000m
      Wave length                                  660nm                                             820nm~860nm
      Temperature range                            -5°C ~+55°C                                       -5°C ~+55°C
      Minimum receiving power                      Min. -20dBm                                       Min. -24dBm
      System reserve                               Min +3dB                                          Min +3dB
     - Print Port
      Type                                        RS-232
      Baud Rate                                   4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
      Printer type                                EPSON® 300K printer
      Safety level                                Isolation to ELV level
     - Clock Synchronization Port
      Type                                        RS-485
      Transmission distance                       <500m
      Maximal capacity                            32
      Timing standard                             PPS, IRIG-B
      Safety level                                Isolation to ELV level
     Type test
     - Environmental tests
       Dry cold test                        Per IEC60068-2-1:2007
       Dry heat test                        Per IEC60068-2-2:2007
       Damp heat test, cyclic               Per IEC60068-2-30:2005
     - Mechanical tests
       Vibration                            Per IEC 60255-21-1:1988 Class I
       Shock and bump                       Per IEC 60255-21-2:1988 Class I
     - Electrical tests
       Standard                             IEC 60255-27:2005
       Dielectric tests                     Test voltage 2kV, 50Hz, 1min
       Standard                             IEC 60255-5:2000
       Impulse voltage tests                Test voltage 5kV
       Overvoltage category                 III
       Insulation resistance measurements   Isolation resistance >100MΩ@500VDC
     - Electromagnetic Compatibility
                                            Per IEC 60255-22-1:2007
      1MHz burst disturbance test           Common mode: class III 2.5kV
                                            Differential mode: class III 1.0kV
                                            Per IEC60255-22-2:2008 class IV
      Electrostatic discharge test          For contact discharge: 8kV
                                            For air discharge: 15kV
                                                            Read more on the web
98    read more on www.nrelect.com                           www.nrelect.com
                                             Per IEC 60255-22-3:2007 class III
                                             Frequency sweep
                                             Radiated amplitude-modulated
                                             10V/m (rms), f=80…1000MHz
Radio frequency interference tests           Spot frequency
                                             Radiated amplitude-modulated
                                             10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
                                             Radiated pulse-modulated
                                             10V/m (rms), f=900MHz
                                             Per IEC 60255-22-4:2008
Fast transient disturbance tests             Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
                                             Communication terminals: class IV, 2kV, 5kHz, 5/50ns
                                             Per IEC 60255-22-5:2008
                                             Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test                          Common mode: 4kV
                                             Differential mode: 2kV
                                             Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
                                             Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
                                             Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
                                             class V, 100A/m for 1min, 1000A/m for 3s
                                             Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
                                             class V, 6.4/16μs, 1000A/m for 3s
                                             IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
                                             class V, 100kHz & 1MHz–100A/m
                                             IEC60255-11: 2008
Auxiliary power supply performance           Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
                                             Voltage short interruptions: 100ms for interruption without rebooting
                                                             Read more on the web