Series 600 Conventional Fire Detection Range
Series 600 Conventional Fire Detection
Range Zettler conventional detector
design evolution has resulted in
the creation of the Series 600 range
of unobtrusively styled detectors,
incorporating a number of unique
design features enabling improved
operation, installation and ease of
servicing.
Through innovative design Series 600 detectors have
the ability to reduce installation and servicing time to
a minimum, needing only one visit to the ceiling to
complete the installation and having a park position Features
for the detector to simplify servicing.
• Designed for approval to EN54, LPCB, VdS, SSL, ANPI
and UL
• Low operational voltage
• Backward compatible with M600 Series
• Compatible with 5B and 5BD 5” Bases
• Aesthetically discreet
• Superior performance and reliability
• Designed for rapid installation
• Locking kit included as part of 5” Base
• May be used in systems that meet BS5839 pt1
• Integral and remote alarm LED
• Wiring polarity independent
• IP55 rated 90o C fixed temperature heat detector
ZETTLER MZX
Series 600 Conventional Fire detection Range
General Because of the wide variety of applications that fire
detectors are expected to cover, it is recommended that
Included within the Series 600 range is the conventional a fire risk assessment should be undertaken to determine
enhanced carbon monoxide fire detector (601CH). The the most suitable detector for any application.
incorporation of a reliable electrochemical CO detection
cell and high specification low thermal mass thermistor Optical Smoke 601P
for accurate temperature detection has enabled the
introduction of an enhanced CO detector suitable for fast, 601P detectors are capable of detecting the visible smoke
reliable detection of both slow and fast developing fires. produced by materials which smoulder or burn slowly, i.e.
soft furnishings, plastic foam etc; or “smoke” produced
The complete range has been designed to meet the by overheated but unburnt PVC. These detectors are
requirements of BS (British Standards) and EN (European particularly suitable for general applications and areas
Standards) for fire detectors. All detectors also carry a where cable overheating may occur, e.g. electrical services
mandatory CE mark. areas. Optical only detectors are not suitable for detecting
fast burning fires producing little visible smoke or very
Series 600 Conventional Detectors black smoke.
Series 600 provides the detector part of an automatic fire The novel design of the asymmetrical sampling chamber
detection system. The Series 600 conventional or two and signal processing techniques stop unwanted alarms
state detector is one that provides two output states to caused by very small insects, i.e. thrips. Smoke entering
the controller, either “normal” or a “fire alarm” condition. the sampling chamber scatters the infra-red light pulses
onto a photodiode. These pulses are converted to an
The detectors along with call points are grouped into fire electrical signal which is compared against a preset alarm
zones, with each zone being connected to the control level.
panel; by a separate two wire circuit and having a separate
zone indicator on the panel.
Application
As each type of fire detector responds to a particular “fire
product”, the relative speed of response of the detector is
therefore dependent upon the type of fire being detected.
The range of Series 600 fire detectors have been designed
to provide the earliest possible warning of a fire condition,
with a minimum possibility of false/unwanted alarms.
As smoke is normally present at an early stage in most
fires, smoke type detectors (optical, high performance
optical and ion chamber) are therefore considered the
most useful. When considering the type of smoke
detector for the application, the probable type of fuel
for the fire should be considered, in general terms, fast
developing fires are detected quicker with ion-chamber
detectors, whereas with a slow developing fire an optical
type smoke detector will respond quickest. But for
general fire detection, where there is an equal possibility
of either a “fast” or “slow” fire developing the intelligent
high performance optical detector provides an excellent
detection response.In situations where the installation
of smoke detectors would cause an unacceptable level
of false alarms, heat detectors or the enhanced CO fire
detector may be installed.
ZETTLER MZX
Series 600 Conventional Fire detection Range
High Performance Optical Smoke 601PH These detectors are particularly well suited to sleeping
risks, storage areas and applications where smoke
601PH detectors react to the complete range of fire detectors are prone to false alarm. Incorporation of a
products, from slow smoldering fires, producing visible A1R rate of rise heat detector within the 601CH provides
particles to open flaming fires producing large numbers of extra non-selectable detection modes which allows the
very hot smaller sized aerosols. The combination of optical detector to operate in a wide variety of applications where
and heat technology allows detection of clear burning fire combined risks mean that CO detection alone would be
products which hitherto could only be easily detected by insufficient.
ion-chamber detectors.
The integrated rate-of-rise heat detector acts as a normal
For normal ambient conditions the HPO behaves as a heat detector, additionally enhancing the sensitivity of the
normal detector. Only when a rapid rise in temperature is carbon monoxide detector if a rapid change of temperature
detected does the sensitivity of the detector increase and is detected by the detectors thermistor.
the presence of smoke will confirm a fire condition which
will be transmitted as an alarm level. Ion Chamber Smoke 601I
The 601PH design incorporates a unique “mousehole” 601I detectors are offered for old specifications which
optical chamber with an unrivaled signal to noise ratio still call for ionisation smoke detectors. The 601CH and
providing high resilience to dust and dirt which means 601PH detectors offer improved performance, significantly
reduced servicing costs. In addition a unique chamber lower false alarms and environmental compatibility for
cover actually draws slow moving smoke into the chamber smoke detection applications. The 601I nevertheless offers
to provide a more responsive detector. detection of visible and invisible fire aerosols (products of
combustion) and are therefore capable of detecting the
Heat, Rate-of-Rise 601H-R, Fixed early presence of hot smoldering and flaming fires,
Temperature 601H-F and 631H-F such as wood, paper etc.
Heat detectors offer an acceptable, but less sensitive They use a dual ionisation chamber in which the air is
alternative to smoke detectors if environmental conditions ionised by a single radioactive source. The presence of
rule out their use. The 601H-R (rate-of-rise), 601H-F and smoke in the sampling chamber causes a change in the
631H-F (fixed temperature) detectors detect abnormally balance voltage, between the two chambers. This is then
high rates of rise of temperature and abnormally high compared against an alarm level. Technical Publications
(static) temperatures respectively. Customers are advised that a full range of product
application and design information documents are available
For general use and particularly where the ambient for this range via our website at www.zettlerfire.com
temperature may be low, a rate-of-rise heat detector
601H-R is to be preferred. A fixed temperature limit is also Document Numbers
incorporated in these detectors. In many environments,
e.g. kitchens, canteens and boiler rooms, sudden, large Series 600
changes in temperature are considered normal therefore 601PH 01C-02-D2
rate-of-rise detectors are generally not suitable in these 601CH 01C-02-D3
cases and a slower response fixed temperature 601H-F or 601I 01C-02-D4
631H-F detector should be used.
601H-R/601H-F/631H-F 01C-02-D5
Enhanced Carbon Monoxide 601CH 601P 01C-02-D6
601CH detectors are generally faster than ion-chamber
and optical detectors in responding to fires that start by
smoldering. They are also more tolerant of positioning and
can be mounted in locations where there are likely to be
obstacles to free smoke plume movement.
ZETTLER MZX
Series 600 Conventional Fire detection Range
Technical Specifications Note: Ion chamber radiation source americium 241<
33.3kBq
Mechanical
Detector Material FR110 “Bayblend” Fire Resistant Electromagnetic Compatibility
Dimensions See diagram below These detectors comply with the following:
Weight See Specification Summary Product family standard EN50130-4 in respect of
Colour White Conducted Disturbances, Radiated Immunity, Electrostatic
Discharge, Fast Transients and Slow High Energy
Environmental & Electrical EN61000-6-3 for Emissions
Reset Time 2 - 5 seconds
Relative Humidity 0 - 95% non-condensing
Wiring Connections SEM Terminal 2 x 1.5 mm2
ZETTLER, is a leading brand of fire detection products in the European market. The ZETTLER fire detection product line includes a wide range of
EN54 CPD approved fire detection products carrying approvals and cross-listings, including VdS and NF. The ZETTLER product lines are available
through ZETTLER Authorised Distributors as well as many Johnson Controls offices around the world.
Tyco Fire & Security GmbH, Victor von Bruns Strasse 21, CH-8212 Neuhausen am Rheinfall, Switzerland
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are
subject to change without notice.
PSF123ZT Issue – 2. September 2017 www.zettlerfire.com