Three Phase DC Rectifier UPS System

The document describes the Orion Three Phase 600VAC/125VDC Rectifier/DC UPS System and Battery Charger. It provides an overview of its key features including three phase AC input, DC output capabilities, control panel display and configuration options. Its applications include utility, communications, manufacturing, commercial and transportation systems that require emergency DC power, battery charging or uninterruptible power.

Uploaded by

Limbaga
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
272 views12 pages

Three Phase DC Rectifier UPS System

The document describes the Orion Three Phase 600VAC/125VDC Rectifier/DC UPS System and Battery Charger. It provides an overview of its key features including three phase AC input, DC output capabilities, control panel display and configuration options. Its applications include utility, communications, manufacturing, commercial and transportation systems that require emergency DC power, battery charging or uninterruptible power.

Uploaded by

Limbaga
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Orion

Three Phase 600VAC // 125VDC Rectifier / DC UPS


System / Battery Charger

March 27, 2008


Three Phase Input to DC Output UPS
Always On’s new Three Phase DC Rectifier enables the controlling and monitoring of the DC
output of the UPS system. This new system compliments our product line with the addition of
the DC output option to our current Three Phase UPS systems.

The versatile Rectifier is designed specifically for:

Utility & Communications:

¾ Power Generation
¾ Substations
¾ Microwave Relay Sites
¾ Switchgear

Manufacturing:

¾ Emergency DC Power
¾ DC Operated Breakers
¾ Alarm Systems

Commercial:

¾ Alarm Systems
¾ Uninterruptible Power Systems
¾ DC Control Systems

Transportation:

¾ Signal Systems
¾ Switchgear
¾ Alarm Systems.

2
Figure 1: Control Panel Display

The Orion System allows authorized personnel to monitor, adjust and maintain the system
through an intuitive, easy to use LCD-display Control Panel. The key functions of the Control
Panel are password protected to prevent unauthorized access.

This interface provides the customer with a wealth of information regarding the status of the
system, key information, logged events and alarms as well control and configuration
functions. These features are described in detail below.

3
Control Panel Features:
The Status Menu Displays:

¾ The input, output and battery functionality


¾ The status of the breakers and contactors
¾ The current statuses of operation mode, phase, output and input
¾ The metering of input / output voltages and current, plus battery capacity.

The Key Information Menu Displays:


¾ The product manufacturer, serial number and part number
¾ The Input / Output voltage ratings
¾ The Unit Power Rating.

The Logged Events and Alarms Menu:

¾ Displays the currently active alarm events and the details


¾ Displays all logged alarm events and the details
¾ Silence Alarm – turns off the alarm (Note: the alarm will sound again if a new alarm
occurs)
¾ Upload - all alarm events are uploaded to a PC.

Battery Equalization / Battery Testing:


¾ Controls the running of the battery equalization function
¾ Controls the running of the battery testing function.

DC Output:
¾ This function controls the enabling and disabling of the DC Output.

4
Configuration Menu:

¾ Set Points:

ƒ High / low voltage limits of output

ƒ High / low current limits of output

ƒ Output voltage.

¾ Set battery equalization level, run frequency and duration.

¾ Set system clock.

¾ Set password for configuration menu access.

¾ Set display brightness and contrast.

5
Product Hardware Features:
Input:

¾ 3 phase power input at 45 to 65 Hz.

¾ Configuration: 600Vac - 3 phase, 3 wire (208 - 480 Vac and other voltages available)

¾ Frequency: 45-65Hz, power factor: 0.80-0.90, THD: 3%.

¾ Input Voltage Range: -10% to +10%.

¾ Monitoring voltages and currents of the DC Rectifier input.

¾ 20 second Walk-in to output enabled.

Output:

¾ Output voltage 125VDC (other models available up to 600VDC)

¾ Overload 150% for up to 60 seconds.

¾ Software adjustment of output voltage.

¾ Current limiting.

¾ Monitoring voltages and currents of the DC Rectifier output.

¾ Zero transfer time.

¾ Parallel for redundancy and capacity.

Environment:

¾ Monitors operating temperature of unit.

¾ Multiple fans – forced air cooling – variable speed with failure alarm.

6
Display:

¾ LCD Display & keypad for menu navigation and data entry.

¾ Software menu for UPS control and monitoring.

¾ Logging of alarms and events.

Connectivity:

¾ Remote monitoring of DC rectifier UPS system via SNMP or web browser.


¾ 8 user Relay output.
¾ Optional connections to Modbus, industrial Ethernet, Profibus or other industrial
Networks.

Battery:

¾ Automatic and programmable Battery Equalization.


¾ Automatic and programmable Battery Test.
¾ Monitor voltages and currents of the DC Rectifier battery bank.
¾ The Battery recharge time is approximately 5 times the discharge time.
¾ Variable backup time.
¾ Each battery string is protected by a circuit breaker.
¾ Temperature compensated charging.

Additional Features:

¾ Audible and visual failure alarm.


¾ DSP (Digital Signal Processor) based monitoring and control system.

7
DC Rectifier Specifications:

GENERAL DATA
True galvanic isolation from input to output Yes
Operating temperature range UPS -40°C to 40°C

Storage temperature range UPS -15°C to +50°C (5°F to 122°F)


Battery 0°C to 40°C (32°F to 104°F)
(VRLA) Storage time is 6 months at 25°C (77°F) Higher temperatures reduce
battery storage time
Relative Humidity 0% to 95%, non-condensing
Maximum Altitude Without Derating <1,500m (5,000ft) No derating
Type Indoor (NEMA 1) [Optional drip shield available] [other configurations
Enclosure available]
Safety Internal front construction
Cooling Forced air (bottom to top)
Colour Manufacturer Colour (Ivory)
Installation Rigging Suitable for handling by forklift / overhead eyehooks
Mounting Casters and Floor mounting brackets / earthquake standard available
Installation and maintenance access Front access required for maintenance
Conduit access Bottom entry standard / top entry available
Standards CSA 107.1, UL 1778, IEC 62040, FCC Class A, EN5009-1, -2
Electrostatic discharge immunity 6kV contact / 8 kV air discharge
Configuration Standard Stand-alone
Optional Multiple units may be paralleled for redundancy or capacity

8
DC Rectifier Specifications:

RECTIFIER
Configuration
Voltage Standard 208 / 480 / 600 VAC, 3 phase, 3 wire + ground (-10% to +15%)
Frequency 45 to 65 Hz
Input Power Factor 0.80 to 0.90
Inrush Current Limited by soft-start circuit
Power walk-in 0 to 100% within 20 seconds
Output Voltage 125VDC (Other voltages available up to 600 VDC)
Output Output Current 25 / 50 / 100 / 150 / 200 A (Up to 600A)
Output Voltage tolerance +/- 1%
DC ripple voltage +/- 2%
DC Ripple Current Maximum 5% of battery capacity expressed in amps

Protection Fuses / Breakers


Internally Current Limited
Specifications are subject to change without notice to reflect upgrades and improvement in technology.

BATTERY
Battery Compatibility Maintenance Free Sealed Lead-acid [Optional NiCD or flooded]
Number of cells Varies with size
Voltage range for Equalization Programmable
Float voltage at 20°C (68°F) 13.5V per battery (programmable)
Low voltage level (Stop Voltage) 10.0V per battery (programmable)
Recharge time to 90% capacity 5 times the discharge time
Battery ground fault detection Standard
Automatic and manual battery test Standard
Programmable Temperature Compensated Charging Standard

9
DC Rectifier Specifications:
EXTERNAL INTERFACE
Alarm contacts Standard 8 form C contacts (user configurable)
Serial communication RS-232/ RS485
Ethernet communications (options) SNMP, Modbus, Profibus, other industrial networks available
Input control signals 8 x 0 to 15VDC optoisolated inputs (user configurable)
Emergency Power Off contacts provided (optional switch)

FRONT PANEL CONTROLS, SIGNALS & ALARMS


Active mimic Diagram Represents the operational status of the UPS, with integrated LED’s and
power flow indicators.
LED Display Displays operational and fault conditions
Audible Alarm Audible signal active when any alarm condition is present
LCD Display Display of UPS metering functions and event history
Keypad Menu navigation and data entry

OPTIONAL FEATURES
Parallel Redundant Operation for redundancy and capacity
Remote status panel Active mimic diagram w/ Stop Operation and Summary Alarms.
Sprinkler protection Drip Shield
Dust protection Air Filters
Battery Cabinets Extend runtimes

10
DC Rectifier Specifications:
MECHANICAL DATA

Dimensions Weight
W (Width) D (Depth) H (Height) Rectifier Floor Loading

550 mm (21.75˝ ) 812 mm (32.00˝ ) 1,600 mm (63.00˝ ) 580 kg (1,279lbs) 1,318 kg/sq.m
(270 lbs/sq.ft)

Specifications are subject to change without notice to reflect upgrades and improvement in
technology.

11
Contact Always On

Always On UPS Systems Inc.

1 – 150 Campion Road,


Kelowna, BC, Canada, V1X 7S8
Phone: (250) 491-9777 Ext 451
Fax: (250) 491-9775
Email: sales@alwayson.com
Website: www.alwayson.com