Proact™ Analog Electric Actuator With Integral Driver: Product Manual 26147 (Revision H, 6/2016)
Proact™ Analog Electric Actuator With Integral Driver: Product Manual 26147 (Revision H, 6/2016)
(Revision H, 6/2016)
Original Instructions
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26455, Customer
Publication Cross Reference and Revision Status & Distribution Restrictions, on
Revisions the publications page of the Woodward website:
www.woodward.com/publications
Revisions—Changes in this publication since the last revision are indicated by a black line
alongside the text.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 26147
Copyright © Woodward 2001–2016
All Rights Reserved
Manual 26147 ProAct Analog
Contents
Woodward 1
ProAct Analog Manual 26147
CHAPTER 10 PRODUCT SUPPORT AND SERVICE OPTIONS .......................... 35
Product Support Options ......................................................................................35
Product Service Options .......................................................................................35
Returning Equipment for Repair ...........................................................................36
Replacement Parts ...............................................................................................36
Engineering Services ............................................................................................37
Contacting Woodward’s Support Organization ....................................................37
Technical Assistance ............................................................................................38
APPENDIX PROACT™ PROGRAM SUMMARY .............................................. 39
Configure Mode Settings ......................................................................................39
REVISION HISTORY .................................................................................. 40
DECLARATIONS ....................................................................................... 41
2 Woodward
Manual 26147 ProAct Analog
Woodward 3
ProAct Analog Manual 26147
4 Woodward
Manual 26147 ProAct Analog
Regulatory Compliance
European Compliance for CE Mark:
These listings are limited only to those units bearing the CE Marking.
EMC Directive: Declared to Directive 2014/30/EU of the European
Parliament and of the Council of 26 February 2014 on
the harmonization of the laws of the Member States
relating to electromagnetic compatibility (EMC)
Other European Compliance:
Machinery Directive: Compliant as partly completed machinery with
Directive 2006/42/EC of the European Parliament
and the Council of 17 May 2006 on machinery.
North American Compliance:
CSA: CSA Certified for Class I, Division 2, Groups A, B, C,
& D, T3 at 74 °C Ambient. For use in Canada and
the United States. This product is certified as a
component for use in other equipment. The final
combination is subject to acceptance by CSA
International or local inspection.
Certificate 1167451
Woodward 5
ProAct Analog Manual 26147
6 Woodward
Manual 26147 ProAct Analog
Chapter 1.
General Information
Introduction
This manual describes the Woodward ProAct™ Analog Actuator for engine
applications. This manual provides installation instructions, describes the control,
and explains the configuration (programming), adjustments (service mode), and
hardware specifications. This manual does not contain instructions for the
operation of the complete engine system. For engine or plant operating
instructions, contact the plant-equipment manufacturer.
Description
The ProAct Analog is a family of electric actuators with integral drivers intended
to be mounted on-engine to control various functions including (but not limited
to): fuel rack positioning, timing control, and throttle valve and wastegate
positioning. The device is effectively a positioner which will accept a desired
position signal from another device in the system, such as a speed control, and
drive to that position. Each unit includes an analog driver interface capable of
controlling the actuator, and provides a signal that represents throttle position.
The ProAct Analog actuator can be commanded to a position via 4–20 mA,
0–200 mA or PWM interfaces. In addition, given an on board position feedback
device, the actual position is available to the system through a position output
signal. This is a highly filtered signal and may not be suitable for closed loop
operation.
Each member of the ProAct Analog family has a different input signal
specification or bi-directional torque output capability as described in Chapter 9
(Specifications) and shown in Table 1-1. In addition, each actuator has a nominal
rotation of 75° at the output shaft. It can be mounted in either a base mount or
flange mount configuration. The units are designed to operate in an on-engine
environment and can therefore withstand high levels of vibration and temperature
extremes. The details of these environmental limits can be found in the
Environmental Specifications section in Chapter 9.
Woodward 7
ProAct Analog Manual 26147
Controller Overview
The position controller interface software is executed on a 16 MHz 6805 8-bit
microcontroller onboard the ProAct Driver. Internal current and position sensors
provide feedback for closed-loop position control. The driver interfaces with an
external speed control via a position demand. The position demand can be an
analog signal (4–20 mA or 0–200 mA) or PWM signal. The ProAct control
monitors all available signals, internal and external, and provides actuator
shutdown if any faults are detected. An analog output provides actual position
indication. Figure 1-1 provides a functional overview of the ProAct Analog.
The ProAct control is field configurable, which allows a single basic design
consisting of four part numbers to be used in many different applications. The
driver must be configured and field calibrated to the specific engine. Figure 1-2
provides an overview of the ProAct Analog driver I/O (inputs/outputs).
Mechanical Setup
Mounting
The ProAct Analog platform is base mounted to tapped holes on the bottom of
the actuator or flange mounted utilizing through-holes provided (see Figure 2-2).
The unit can be mounted in any orientation. All exterior and mounting dimensions
and exterior fasteners are metric. See Chapter 2 (Installation) for details on
mounting and installation.
Output Shaft
The ProAct Analog family output shafts are standard US-customary sizes with
toothed serrations.
Rotation
All ProAct Analog actuators have 73–77 of available travel. The max fuel
direction of this travel is configurable in the clockwise or counterclockwise
direction.
8 Woodward
Manual 26147 ProAct Analog
+15V
Calibrated
Command
Signal
CONTROL SYSTEM
PWM In - INTERFACE
CPU
PWM Cmd Signal
Cal/Safety
Shutdown POSITION
SENSOR CURRENT
SENSOR
4 - 20 mA ANALOG
Position Cmd
0 - 180 mA INTERFACE Cal/Safety
Shutdown CURRENT FEEDBACK
INTERFACE
0 - 5V
POSITION
FEEDBACK
INTERFACE
Customer
Reference
Voltage
InputOption
Woodward 9
ProAct Analog Manual 26147
Mechanical Stops
Internal mechanical actuator stops will only survive a maximum kinetic energy of
0.011 J (0.097 in-lb). If the actuator internal stops are used, the load inertia
should not exceed 3.76E-3 in-lb-s² (4.25E-4 kg-m²). See Chapter 2 (Linkage) for
details on actuator inertia and internal stops. In service, electrical and engine
stops should be set inside the actuator stops. Electrical stops are set via the
CAL/CONFIG routine.
Electrical Connections
There is one interface on the circuit board. Refer to Figure 3-1 for details on
ProAct actuator wiring.
The response of the actuator when the input signal is outside the nominal range
is model-dependent. PWM models will disable the coil drive until the PWM input
signal returns to a nominal range value. At inputs less than 20 mA, the current
model will drive into the min stop, and at inputs greater than 180 mA, it will drive
into the max stop. Current models will continue to drive (to min stop) with no
input signal applied.
10 Woodward
Manual 26147 ProAct Analog
Power Input
The input power has an operational range of 18–32 Vdc, nominal 24 Vdc. Please
reference the electrical specification in Chapter 9 for input power and current
requirements.
The input must be connected to operate the unit. When open, the unit
is forced into a non-operational shutdown state.
Woodward 11
ProAct Analog Manual 26147
Chapter 2
Hardware Installation
This chapter provides instructions on how to mount and connect the ProAct™
Analog actuator into a system. Hardware dimensions are provided for mounting
the ProAct package to a specific application.
Unpacking
Be careful when unpacking the actuator. Check the unit for signs of damage,
such as bent or dented panels, scratches, and loose or broken parts. Notify the
carrier and Woodward if damage is found.
Mounting Location
The ProAct Analog actuator is designed to operate within an ambient
temperature range of –40 to +74 °C (–40 to +165 °F). Mount the driver close
enough to the battery to meet the wire-length requirements (see wiring
instructions in Chapter 3).
The ProAct actuator is designed for installation on the engine. The ProAct
actuator will generate heat, especially when stalled or during other conditions
requiring maximum torque output. The installer must consider the heat
conductivity of the installation bracket, and the operating temperature of the
ultimate heat sink to which the bracket will be attached. Generally the heat
transfer abilities of aluminum and low-carbon steel are better than those of high-
carbon steel or stainless steel.
12 Woodward
Manual 26147 ProAct Analog
Mounting
Models I and II actuators may be installed on a bracket in either base or flange
mount configuration. The base mount configuration requires the use of four
M8x1.25 screws with a minimum engagement of 16 mm. The flange mount
configuration requires the use of four M8 screws through the flange. Whether
base mounting or flange mounting the actuator, torque the four M8 screws to
22.6 Nm (200 lb-in). The actuator may be mounted in any attitude.
The bracket and attaching hardware must be designed to hold the weight and to
withstand the vibration associated with engine mounting. Additionally, the bracket
must be designed to provide a heat sink (heat transfer) from the actuator to the
engine block as described in the Mounting Location section.
Gas Engine Stops—Butterfly valves in carburetors will often bind if rotated too
far toward minimum or maximum. For this reason, the stops in the actuator
should be used at both minimum and maximum positions. Note that the actuator
internal stops will allow up to 1.5 degrees of additional rotation in both directions
during impact (see Figure 2-1).
The engine must always shut down when the actuator is at the minimum stop.
Woodward 13
ProAct Analog Manual 26147
14 Woodward
Manual 26147 ProAct Analog
Linkage
Proper design and installation of the linkage from the actuator to the engine is
necessary for the unit to provide the best control possible.
Certain applications with low inertia may be unstable with high impulse loads and
may require additional system inertia. See troubleshooting guidelines or contact
Woodward for more information.
Ensure that the actuator has ample work capacity to control the fuel supply under
maximum load conditions.
Manually stroke the fuel-control linkage from stop to stop as if the actuator were
moving it. The linkage must move freely, without friction and backlash. Lubricate
or replace worn linkage or fuel control parts as required.
The actuator’s maximum slew rate can place stress on the fuel
system stops and on the linkage between the actuator and the fuel
system. The maximum actuator speed is 1000 degrees per second in
both increase and decrease fuel directions.
Woodward 15
ProAct Analog Manual 26147
The Mass Moment of Inertia (MMOI) for the ProAct Analog actuators are:
Model I, II 4.9E-3 lb-in-s² (5.5E-4 kg-m²)
The fuel system stops must be adequate to absorb the actuator MMOI in addition
to the linkage inertia without damage.
ProAct actuator internal stops are designed to absorb 0.011 J (0.097 in-lb) of
kinetic energy with 1.5 degrees of over travel. If the actuator stops are used, the
load inertia must not exceed 3.76E-3 in-lb-s² (4.25E-4 kg-m²), and the linkage
must be designed to allow the 1.5 degrees of over travel on each end.
Use of good rod-end connectors with as little free play as possible is essential.
Select rod ends which will remain tight and wear well during the nearly constant
movement associated with precise speed control. Low-friction, long-wearing rod
ends are available from Woodward.
The linkage travel and offset should provide travel below steady state idle fuel
and above steady state full load fuel. Woodward “standard” is for no load to full
load actuator stroke (and control output) to provide approximately 2/3 of the stop-
to-stop travel. As an example, 60° linkage travel should be 10° idle and 50° max
load.
The link connecting the actuator lever to the fuel-control lever must be short and
stiff enough to prevent flexing while the engine is running.
Typically, in a linkage system, there may be links and levers which are supported
by customer-supplied bearings. Additionally, there will typically be a section of
the linkage where the mass is supported fully by the actuator output shaft. Please
note when designing these systems that each ProAct Analog actuator is
designed to accept 1.2 kg (2.6 lb) of additional mass at a maximum vibration
level of 10 Gs. Exceeding this mass or vibration level may damage the actuator's
rotor system and shorten the life of the actuator.
Actuator levers are available from Woodward which allow adjustment of the rod
end locations with respect to the center of the actuator shaft. The lever used
must have a 0.625-36 serration.
Adjust the location of the rod end on the lever to achieve the desired actuator
rotation between minimum and maximum positions. The linkage should be set to
use as much of the 75 degrees as possible (at least 60 degrees minimum). To
increase the amount of actuator rotation, move the rod end closer to the actuator
shaft or farther away from the shaft controlling the fuel flow. To decrease the
amount of actuator rotation, move the rod end farther from the actuator shaft or
closer to the shaft controlling the fuel flow.
16 Woodward
Manual 26147 ProAct Analog
Chapter 3
Wiring
This chapter provides instructions on how to connect the ProAct™ actuator into a
system. Ratings and jumper configurations are given to allow wiring and
configuration of the ProAct package to a specific application.
Electrical ratings, wiring requirements, and options are provided to allow full
installation the ProAct actuator into a new or existing application.
Electrical Connections
If you are replacing an earlier ProAct series actuator with the ProAct
Analog model, be sure to remove the original driver, since the ProAct
Analog actuator has an integrated driver.
Refer to Table 1-2 for the customer interface wiring to the external connector, the
representative interface schematic (Figure 2-2), and the Specification section of
the manual for the hardware specifications.
Input power is connected to pin 1(+) and pin 2(–) of the terminal strip.
The terminal block is a screwless cage clamp style block. The spring clamp can
be actuated by pressing down on the thumb levers integral to the block. The
terminal block accepts wires from 0.20—3.3 mm² (24—12 AWG) wire. Two 0.82
mm² (18 AWG) or three 0.5 mm² (20 AWG) wires can easily be installed in each
terminal. Wire for the terminals should be stripped 8–9 mm (0.3 inch).
Woodward 17
ProAct Analog Manual 26147
18 Woodward
Manual 26147 ProAct Analog
Woodward 19
ProAct Analog Manual 26147
Customers must use the grounding point that meets local authority
approval requirements.
Power Source
Power source output must be low impedance (for example, directly from
batteries).
Run an insulated wire directly from the positive (+) battery terminal to a fuse and
on/off switch, then to the correct connection on the driver (see Figure 3-3). Run a
second insulated wire directly from the negative (–) terminal of the battery to the
driver. Neither of these connections needs to be shielded.
Run the power leads directly from the power source to the control. DO NOT
POWER OTHER DEVICES WITH LEADS COMMON TO THE CONTROL (see
Figures 3-3 & 3-4). If the power source is a battery, be sure the system includes
an alternator or other battery-charging device.
When the engine is shut down, the driver powers the actuator into the minimum
stop. If the battery charging system is off when the engine is shut down, this will
cause the battery to be drained. In this case, the power to the ProAct must be
turned off with a switch or relay. Any such switch or relay must be interlocking to
prevent starting the engine when power to the actuator is shut off.
20 Woodward
Manual 26147 ProAct Analog
ProAct Inputs/Outputs
Driver Input Power
The following table summarizes the driver power input requirements. The input
voltage operational range is 18–32 Vdc, 24 Vdc nominal. The power input
provides protection against reverse voltage connection. Refer to Table 3-2 for
maximum cable lengths and wire sizes.
The input power must be fused. Failure to fuse the ProAct could,
under exceptional circumstances, lead to personal injury, damage to
the control valve, and/or explosion.
All fuses should have a voltage rating of at least 100 V and an I²t rating greater
than 2 A for 2 seconds. A typical fast acting fuse will meet these ratings.
* Note—Rated transient torque is not achievable with an 18 V power source on the Model
II. Listed maximum lengths will provide 75% of rated transient torque.
Woodward 21
ProAct Analog Manual 26147
22 Woodward
Manual 26147 ProAct Analog
Woodward 23
ProAct Analog Manual 26147
Chapter 4
Setup, Calibration, and Adjustments
General Description
Setup and calibration are provided through test points located on the printed
circuit board (see Figure 4-1).
Setup
The basic setup consists of actuator configuration and stroking. Configuration is
not required on most OEM-supplied units. Configuration is performed using the
Config table in the Appendix.
The setup, configuration, and stroking adjustment must be performed when the
engine is shut down.
Calibration
The ProAct™ control may be calibrated at any time, and calibration takes place
whenever a configuration change is made.
24 Woodward
Manual 26147 ProAct Analog
Chapter 5
Description of Operation
Position Control
The ProAct™ Analog provides closed-loop position control based on an internal
position sensor and the desired position demand signal. Position and current
controllers are utilized to position the output. Position control is provided using a
customer's position demand and an internal driver output while using an internal
position feedback sensor. The driver provides a 0.5–4.5 V analog output for
indication of actual position. Field calibration is available at any time by utilizing
the appropriate jumpers. Calibration must be done with the engine shut down.
Position Demand
The position demand is provided by a single input (factory set for either PWM or
current [current is jumper selectable for either 4–20 mA or 0–200 mA]). The
position demand can be provided by one of two signal sources: analog or PWM
depending on which part number is in use (see Table 1-1). Failure of the position
demand signal will cause the ProAct Analog to shut down and remain shut down
until a valid signal is received.
Woodward 25
ProAct Analog Manual 26147
Configuration
The Calibration Routine provides the capability to alter the configuration of the
output shaft (CW/CCW) and the polarity of the TPS output signal. The unit must
be in a shutdown state to change the configuration.
26 Woodward
Manual 26147 ProAct Analog
Chapter 6
Diagnostics
Shutdowns Detection
A shutdown condition forces the actuator to the power down state regardless of
the demanded position. When the shutdown condition no longer exists, the driver
automatically returns to a non-shutdown state, following the Position Demand
input command. The shutdown condition does not require a “reset” command.
Woodward 27
ProAct Analog Manual 26147
Chapter 7
Software Setup
28 Woodward
Manual 26147 ProAct Analog
To enable the calibration routine, connect a jumper from TP3 to TP6 for 0–200
mA/PWM input or TP3–TP4 for 4–20 mA input. Connect additional test points as
necessary to change the output shaft direction and TPS polarity—see Table
7-1. See Figure 4-1 for test point locations. When power is applied to the unit, the
microprocessor will enter the calibration routine. The output shaft will sweep
slowly from stop to stop in order to find the end points, and then return to the mid
position. It is not necessary to apply an input signal during this time as the
microprocessor assumes 0.5 to 4.5 V as its input. When the calibration is
complete, turn off the power, disconnect all jumpers, and make sure that the
input signal is applied. When power is reapplied the unit will be in the operate
mode.
Woodward 29
ProAct Analog Manual 26147
Chapter 8
Troubleshooting
Introduction
Improper engine operation is often the result of factors other than governor
operation. This chapter gives tips about engine problems which can resemble
governor problems. Make sure the engine is operating correctly before making
any changes in the governor. The following troubleshooting guide is an aid in
isolating trouble to the control box, actuator, wiring, or elsewhere.
Troubleshooting beyond this level is recommended ONLY when a complete
facility for control testing is available.
Carefully review all the wiring connections, the power supply, and the linkage
before making any adjustments to the actuator or driver. Always check the fuel-
control linkage from stop to stop as if the actuator were moving it. The linkage
must move freely without friction and without backlash. Some fuel controls will
present problems at particular fuel or rack positions because of a hesitation or
binding in the linkage.
Fuel supply and injector conditions can also present problems which resemble
governor problems. On spark-ignited engines, distributor, coil, points, and timing
problems can all cause improper operations which may resemble faulty governor
control.
The control can be damaged with the wrong voltage. When replacing
a control, check the power supply, battery, etc., for the correct
voltage.
Troubleshooting Procedure
This chapter is a general guide for isolating system problems. The guide
assumes that the system wiring, soldering connections, switch and relay
contacts, and input and output connections are correct and in good working
order. Make the checks in the order indicated. Various system checks assume
that the prior checks have been properly done.
30 Woodward
Manual 26147 ProAct Analog
Actuators
Is the actuator wiring correct?
Is the direction of the stroke correct? (This is configured using the
CAL/CONFIG routine.)
Has the feedback signal been calibrated? (This is calibrated at the factory.)
Linkage
Is there slop or lost motion?
Is there misalignment, binding, or side loading?
Is there visible wear or scarring?
Does the linkage move smoothly?
Valves
Does the valve move through its proper stroke smoothly?
Does the valve travel its full stroke?
Can mid-stroke be obtained and held?
Does the valve fully seat (close) before the governor reaches full minimum
stroke?
Does the valve fully open before the governor reaches maximum stroke?
Woodward 31
ProAct Analog Manual 26147
Analog Output
If the Analog output is not functioning properly, verify the following:
Check to ensure that voltage is between 0.5 and 4.5 V for full output stroke.
Check the wiring, look for a loose connection at the terminal block pin#6 and
disconnected or misconnected cables.
32 Woodward
Manual 26147 ProAct Analog
Chapter 9
ProAct™ Analog Specifications
Environmental Specifications
Acceptable Range or
Specification Item Qualification Condition Comments
Operating –40 to +74 °C
Temperature
Storage Temperature –40 to 125 °C, unpowered.
Vibration Sine: 3.2 mm peak-to-peak for 2-39.4
Hz, 10 G for 39.4-300 Hz.
Random: 0.01 G²/Hz at 10 Hz, 0.10 at
100 Hz, 0.10 at 1000 Hz, 0.05 at
2000 Hz (12.79 Grms) 3 hours per
axis
Shock MS1—40G 11ms sawtooth
Ingress Protection IP56 per IEC60529
Humidity 60 °C, 95% RH for five days at one
cycle per day
Chemical Resistance The ProAct™ Analog uses materials
proven capable of withstanding
normal engine environment
chemicals per SAE J1455, such as
diesel fuel, engine oil, and antifreeze.
Hardware Specifications
Feature Specification Comments
Shaft 0.625-36 serrations
Mass Moment of Inertia Model I,II—4.9E-3 / 5.50E-4
(lb-in-sec² / kg-m²)
Minimum Steady State Model I—1.7 J (1.25 ft-lb)
Work Output Model II—3.4 J (2.5 ft-lb)
Minimum Transient Work Model I—3.4 J (2.5 ft-lb)
Output Model II—7 J (5 ft-lb)
Rotation 73–77°
Weight Model I—11 kg (25 lb)
Model II—11 kg (25 lb)
Electrical Specifications
Feature Specification
Input Power—max Model I—67 W (transient) / 19 W (continuous)
Model II—251 W (transient) / 65 W (continuous)
Input Current—Max @ +24 Vdc Model I—2.8 A (transient) / 0.8 A (steady state)
Model II—11 A (transient) / 2.7 A (steady state)
Woodward 33
ProAct Analog Manual 26147
I/O Specifications
Analog Input
Input type: 4–20 mA or 0–200 mA, input selectable,
balanced differential input
Max input current (full scale): 25 mA ± 2% (20 mA range)
225 mA ± 2% (200 mA range)
Common mode rejection: –60 dB minimum
Input common mode range: 0–32 V minimum
Safe input common mode volt: ±200 V minimum
Input impedance: 225 Ω (±10%) (20 mA range)
25 Ω (±10%) (200 mA range)
Anti-aliasing filter: 1 anti-aliasing poles at 1 ms (159 Hz)
Resolution: 12 bits (using Gaussian Noise)
Accuracy: ±1.5% of full scale, @ 25 °C
Temp Drift: ±300 ppm/°C (FS), maximum
Analog Output
Output Type: 0–5 V
PWM frequency: 2 kHz
Resolution: 8 bit
Accuracy: ±1.5% of full scale at 25 °C
Temperature Drift: 250 ppm/°C, maximum
Software
Performance
Parameter Specification
Bandwidth (measured at -6 db) > second order, 40 rad/s
–3 db at >8 Hz with low inertia. See ProAct Transfer
Function
Max Slew Rate > 1000 degrees/second
>18.5 rad/s (10% to 90% travel)
Limit Cycle < 0.35 degrees peak to peak with low friction loads
Steady State Error < 3 degrees for loads up to 80% of steady state current
limit.
Integrating control drives steady state error to zero.
Min Load Inertia 0
34 Woodward
Manual 26147 ProAct Analog
Chapter 10
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
Woodward 35
ProAct Analog Manual 26147
Replacement/Exchange: Replacement/Exchange is a premium program
designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime.
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard
mechanical products and some of the electronic products in the field. This
program offers you repair service for your products with the advantage of
knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option, with the exception that the unit will be returned to you in “like-
new” condition. This option is applicable to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
36 Woodward
Manual 26147 ProAct Analog
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our
products. For these services, you can contact the Distributor by telephone or by
email.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodward’s worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact.
You can also contact the Woodward Customer Service Department at one of the
following Woodward facilities to obtain the address and phone number of the
nearest facility at which you can obtain information and service.
For the most current product support and contact information, please visit our
website directory at www.woodward.com/directory.
Woodward 37
ProAct Analog Manual 26147
Technical Assistance
If you need to contact technical assistance, you will need to provide the following information.
Please write it down here before contacting the Engine OEM, the Packager, a Woodward
Business Partner, or the Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Type of Fuel (gas, gaseous, diesel,
dual-fuel, etc.)
Power Output Rating
Application (power generation, marine,
etc.)
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
38 Woodward
Manual 26147 ProAct Analog
Appendix
ProAct™ Program Summary
APPLICATION ________________________________________________
Woodward 39
ProAct Analog Manual 26147
Revision History
Changes in Revision H—
Updated Regulatory Compliance information
Changes in Revision G—
Revision advanced to coordinate with new installation sheet, and to update
manual to latest formats and safety warnings.
Changes in Revision F—
Updated Regulatory Compliance information
New Declaration of Conformity & Declaration of Incorporation
40 Woodward
Manual 26147 ProAct Analog
Declarations
Woodward 41
ProAct Analog Manual 26147
42 Woodward
Manual 26147 ProAct Analog
Woodward 43
We appreciate your comments about the content of our publications.
Send comments to: icinfo@woodward.com