CEng 6506 Earthquake Engineering lecture Notes
Useful Architectural and
Structural Considerations for
Earthquake Resistant
Design
Contents
Introduction
Regularity of structures
Structural wall configuration in structures with dual wall-
frame lateral load resisting systems
Uniform distribution of mass and stiffness
Effects of non-structural components
Multiple defense lines
Balanced stiffness, strength and ductility
Desirable features of structural materials for Earthquake
resistant design
Basic Design Guidelines from Past Earthquakes
27 December 2017 Addis Ababa University (Dr. Adil Z.) 2
Dr. Adil Z (AAiT) 1
CEng 6506 Earthquake Engineering lecture Notes
Introduction
Buildings are designed by architects and engineers.
Architects are responsible for the architectural
configuration of buildings at the start.
Configuration has to do with the size, shape and
proportion of the 3D form of the building.
Architectural configuration determines the location,
shape and approximate size of structural and non-
structural elements of the building
Any architectural design should incorporate effective
seismic design to minimize EQ hazards.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 3
While the provision of earthquake resistance
is accomplished through structural means, the
architectural design and the decision that
create it, play a major role in determining the
building’s seismic performance
C. Arnold
27 December 2017 Addis Ababa University (Dr. Adil Z.) 4
Dr. Adil Z (AAiT) 2
CEng 6506 Earthquake Engineering lecture Notes
Importance of Conceptual Design
In order to reduce uncertainties of the estimation of the
seismic demands, more attention should be paid to the
conceptual design
Control or decrease ductility demand by:
the use of base isolation
the use of energy dissipating device (Structural controls)
the proper selection of the structural configuration
Provide large ductility with stable hysteretic behavior
Achieve integral action of the whole structure by tying
together the main components and detail the plastic
hinge location carefully
27 December 2017 Addis Ababa University (Dr. Adil Z.) 5
Selection of proper system
configuration for the
superstructure
27 December 2017 Addis Ababa University (Dr. Adil Z.) 6
Dr. Adil Z (AAiT) 3
CEng 6506 Earthquake Engineering lecture Notes
Appropriate Configurations
Simple configuration → simple behavior
Building and its structure Should
be Simple Symmetric and Regular in Plan and Elevation
have a uniform and continuous distribution of mass, stiffness,
strength and ductility.
have the largest possible number of defense lines.
have well separated non-structural components
be detailed so that the inelastic deformations can be constrained
(controlled) to develop in desired regions and according to a
desirable hierarchy
be provided with balanced stiffness and strength between its
members, connections and supports.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 7
Optimal structural configuration
Attributes Benefits
Low width-to-depth ratio Low torsional effects
Low height-to-base width/depth ratio Low overturning effects
Similar storey heights Elimination of weak/soft storey
Short spans Low unit stress and deformation
Symmetrical plan shape Elimination/reduction of torsion
Identical resistance on both axes Balanced resistance in all directions
Uniform plan/elevation stiffness Elimination of stress concentrations
Uniform plan/elevation resistance Elimination of stress concentrations
Uniform plan/elevation ductility High energy dissipation
Perimeter lateral resisting systems High torsional resistance potential
Redundancy High plastic redistribution
Direct load path, no cantilevers Elimination of stress concentration
27 December 2017 Addis Ababa University (Dr. Adil Z.) 8
Dr. Adil Z (AAiT) 4
CEng 6506 Earthquake Engineering lecture Notes
Regularity
An aspect of seismic design of equal if not
greater importance than structural analysis is the
choice of building configuration.
Lack of symmetry (in mass distribution and/or in stiffness,
strength and ductility)
leads to torsional effects
difficult to assess properly
can be very destructive
A regular rectangular plan building with
asymmetrical stiffening irregular (torsion)
27 December 2017 Addis Ababa University (Dr. Adil Z.) 9
Structural Irregularities
Structural
Irregularity
Elevation
Plan Irregularity
Irregularity
Re-entrant Re-entrant
Non parallel Non parallel
Corners (In-plan Corners (Vert
Offset) LRS Offsets) LRS
LRS LRS
Diaphragm Weak/Soft
Discontinuity Discontinuity
Discontinuity Storeys
(Horz) (Horz)
27 December 2017 Addis Ababa University (Dr. Adil Z.) 10
Dr. Adil Z (AAiT) 5
CEng 6506 Earthquake Engineering lecture Notes
Irregular structures or framing systems
SEAOC commentary, 1980
27 December 2017 Addis Ababa University (Dr. Adil Z.) 11
SEAOC commentary, 1980
27 December 2017 Addis Ababa University (Dr. Adil Z.) 12
Dr. Adil Z (AAiT) 6
CEng 6506 Earthquake Engineering lecture Notes
SEAOC commentary, 1980
27 December 2017 Addis Ababa University (Dr. Adil Z.) 13
SEAOC commentary, 1980
27 December 2017 Addis Ababa University (Dr. Adil Z.) 14
Dr. Adil Z (AAiT) 7
CEng 6506 Earthquake Engineering lecture Notes
Regularity in Plan
Simple & symmetrical building plans give
more efficient and
predictable seismic response
A prerequisite for the desirable interaction between
lateral-force-resisting structural system
Reentrant corners inviting stress concentrations, hence
should be avoided.
If necessary separation should be provided
This may lead to a number of simple, compact, and
independent plans
27 December 2017 Addis Ababa University (Dr. Adil Z.) 15
Plan Regularity (Cont’d)
Gaps separating adjacent
structures must large enough to
avoid hammering of adjacent
structures due to out-of-phase
relative motion of the
independent structures
Openings should not
jeopardize diaphragm action of
the slabs and be symmetrically
placed
27 December 2017 Addis Ababa University (Dr. Adil Z.) 16
Dr. Adil Z (AAiT) 8
CEng 6506 Earthquake Engineering lecture Notes
Regularity in Elevation
Tall and slender buildings should be
avoided
Concentration of masses at the top of a
building should be avoided
Setbacks should be avoided
If required, adequate structural separation
should be provided.
Irregularities within the framing system
should be avoided
Any connections (bridging) between two
independent buildings should be such as to
prevent horizontal force transfer between
the two structures
Staggered floor arrangements should be
avoided
27 December 2017 Addis Ababa University (Dr. Adil Z.) 17
Common Failures caused by Irregularities
Torsional effects created by
irregular shape of building
plan (L configuration) and by
a very stiff off-center core
area in a rectangular (regular)
plan building
Typical example
Hotel Terminal, Guatemala
City. Overall view of this 6-
story hotel, illustrating the
torsional failure of the
second story during the 1976
Guatemala Earthquake.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 18
Dr. Adil Z (AAiT) 9
CEng 6506 Earthquake Engineering lecture Notes
Common Failures caused by Irregularities
(Cont’d)
View inside the above building
showing the collapse of the second
story due to shear failure of the
second-floor columns. Note the
significant lateral displacement
(interstory drift to the right) due to
the torsional rotation of the upper
part of the building.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 19
Common Failures caused by Irregularities
(Cont’d)
Close-up of one of the collapsed
columns of the above slide. Note that the
upper floor has displaced to the right and
dropped, and the top and bottom
sections of the column are now side-by-
side. Although the columns had lateral
reinforcement (ties) these were not
enough and at inadequate spacing to
resist the shear force developed due to
the torsional moment which originated in
the second story.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 20
Dr. Adil Z (AAiT) 10
CEng 6506 Earthquake Engineering lecture Notes
Common Failures caused by Irregularities
(Cont’d)
Bridge failure Pounding Soft story
27 December 2017 Addis Ababa University (Dr. Adil Z.) 21
Structural wall Configuration in
structures with dual wall-frame
lateral load resisting systems
27 December 2017 Addis Ababa University (Dr. Adil Z.) 22
Dr. Adil Z (AAiT) 11
CEng 6506 Earthquake Engineering lecture Notes
Possible Shear wall shapes & arrangements
Eccentric SW Basic SW Shapes
arrangements
Symmetrical SW
arrangements
27 December 2017 Addis Ababa University (Dr. Adil Z.) 23
Configuration in wall-frame system
Examples for both preferable and
undesirable positioning of major
lateral-force-resisting elements,
consisting of structural walls and
moment resisting frames.
In all cases the distance between
the CM and CR should be reduced
in order to minimize torsional
effects
27 December 2017 Addis Ababa University (Dr. Adil Z.) 24
Dr. Adil Z (AAiT) 12
CEng 6506 Earthquake Engineering lecture Notes
Uniform Distribution of Mass and
Stiffness
27 December 2017 Addis Ababa University (Dr. Adil Z.) 25
Distribution of Mass in a Building
Dynamic response of a structure depend on
distribution of its reactive masses
amount and distribution of the masses
The smaller the reactive masses, the smaller the
earthquake forces will be
The use of unnecessary masses should be avoided.
i.e. reactive masses are masses that will react to the shaking of
the building foundation.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 26
Dr. Adil Z (AAiT) 13
CEng 6506 Earthquake Engineering lecture Notes
Uniform Mass Distribution (Cont’d)
Damage to a wooden house
due to a heavy roof supported
on a flexible frame. 1971 San
Fernando Earthquake.
Damage to the old portion of the Olive
View Hospital in the 1971 San Fernando
Earthquake. This building had a very
heavy tile roof supported on
unreinforced brick masonry and was
neither designed nor detailed to resist
seismic effects
27 December 2017 Addis Ababa University (Dr. Adil Z.) 27
Uniform Stiffness Distribution
Olive View Hospital, Psychiatric Unit,
San Fernando, California. 1971 San
Fernando Earthquake. This unit was
a 2-story reinforced concrete
building. The structural system was a
moment resisting frame. However, in
the second story there were masonry
walls that added significantly to the
stiffness of this story.
Lightweight concrete was used in the construction of this
building. Note that the building collapsed completely at the
first (soft) story and the second floor dropped to the ground
after moving laterally about 2 meters
27 December 2017 Addis Ababa University (Dr. Adil Z.) 28
Dr. Adil Z (AAiT) 14
CEng 6506 Earthquake Engineering lecture Notes
Uniform Stiffness Distribution (Cont’d)
Imperial County Services
Building. Overall view of this
modern 6-story reinforced
concrete building. Not the
continuous shear wall at the east
end of the building which was
discontinued (offset) at the second
floor level, resulting in a severe
discontinuity and in a practically
open first story (soft story in the
E-W direction).
27 December 2017 Addis Ababa University (Dr. Adil Z.) 29
Uniform Stiffness Distribution (Cont’d)
View of the first story columns
located in the east end of the
building. Note that the explosive type
of failure just above the ground and
the offset between the columns and
the solid shear wall.
Close-up of the failure at the bottom
of the column at the southeast corner
of the building. The failure occurred in
the zone of the column where there
was not adequate confinement of the
concrete and shear reinforcing steel.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 30
Dr. Adil Z (AAiT) 15
CEng 6506 Earthquake Engineering lecture Notes
Effects of non-structural components
27 December 2017 Addis Ababa University (Dr. Adil Z.) 31
Non-structural infill panels and partitions
Earth quake produces story drift.
Causes vertical deformations Change in height
Any infill panel should be designed to deal with both
these movements either by:
Integrating (very stiff frame with flexible infill)
Separating (more preferable for flexible frames)
In the absence of computed
values use the following
minimum separations
20mm for horizontal
40mm for vertical
27 December 2017 Addis Ababa University (Dr. Adil Z.) 32
Dr. Adil Z (AAiT) 16
CEng 6506 Earthquake Engineering lecture Notes
Cladding, wall finishes, windows and doors
In flexible buildings, precast concrete
cladding should be mounted on
fixings which ensure separation from
horizontal drift movements of the
structure
Brittle or rigid finishes should be
avoided or specially detailed Lightweight partition detailed so
stairwells should be free of material that earthquake hammering by the
which may spall or fall structure will damage limited end
Window sashes should be separated strips.
from frame action
Detail of external frame showing
separation of spandrel or parapet
from columns to avoid unwanted
interaction.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 33
Effect of Non-Structural Components
Two-story reinforced concrete building,
Managua, Nicaragua, damaged in the 1972
Managua Earthquake. The slide shows a
reinforced concrete column which was part of
the structural system and which failed due to
its shortening because of the effect of the
masonry wall. The masonry walls were
considered as non-structural elements.
Medical Clinic in El Asnam,
Algeria.Close-up of column failure of
this new 4-story reinforced concrete
building induced by the response of
the building to the 1980 El Asnam
Earthquake.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 34
Dr. Adil Z (AAiT) 17
CEng 6506 Earthquake Engineering lecture Notes
Multiple Line of Defense
27 December 2017 Addis Ababa University (Dr. Adil Z.) 35
Multiple defense lines
A structure should have the largest possible number of internal
and external redundancies. While a high degree of static
indeterminacy is desirable, this is not sufficient. In order that a
building be efficient in resisting severe earthquake shaking, it
should have sufficient ductility, toughness and stable hysteric
behavior under repeated cycles of deformation reversals
Plan view of the Banco de America,
Managua, Nicaragua. This building generally
performed very well during the 1972
Managua Earthquake. Its excellent
performance can be attributed to the
symmetry and uniformity of distribution of
the masses and structural stiffnesses
throughout the building.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 36
Dr. Adil Z (AAiT) 18
CEng 6506 Earthquake Engineering lecture Notes
Multiple defense lines (Cont’d)
The structural system, which can be B. d. America B. Central
considered as a combination of the ductile
walls with a framed tube, is an excellent
system for seismic-resistant design,
providing several lines of defense whereby
the behavior of the whole system can
accommodate the demands of a severe
earthquake.
View of the core service walls and floor area
at the second story of the Banco de America,
Managua, Nicaragua. Note that few of the
marble tiles that cover the reinforced
concrete shear walls have spalled off. This
was the only visible damage in this story after
the 1972 Managua Earthquake.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 37
Multiple defense lines (Cont’d)
Typical floor plan above the fourth floor of
the Banco Central Building, Managua,
Nicaragua. This building had a reinforced
concrete frame as the basic structural
system. Note that the overall configuration
of the reinforced concrete system of the
tower was not symmetric.
View of the stairway after the 1972 Managua EQ. Most
of the stairs were covered with debris that resulted from
the failure of the hollow tile partitions surrounding the
stairs. The damage (structural and non-structural) and
the protection of the contents of this very flexible
moment resisting frame building were in sharp contrast
with those observed in the taller but symmetric
combined coupled shear wall-tubular frame structural
system of the Banco de America Building. There was
also significant structural damage that resulted in the
need to demolish the tower of this building.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 38
Dr. Adil Z (AAiT) 19
CEng 6506 Earthquake Engineering lecture Notes
Balanced Stiffness, Strength and
Ductility
27 December 2017 Addis Ababa University (Dr. Adil Z.) 39
Balanced stiffness, strength and ductility
“A chain breaks at its weakest link”. It is not worthwhile using
strong, stiff and ductile structural members if they are not
properly connected. Collapse and severe damage of buildings
due to lack of good connections is common.
Galerie Algerienne Building, El
Asnam, Algeria, 1980 El Asnam
Earthquake. View of the unit of
this four story RC building which
collapsed in the earthquake. Lack
of adequate reinforcement at the
column-girder connections was
one of the reasons for the
collapse of this unit.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 40
Dr. Adil Z (AAiT) 20
CEng 6506 Earthquake Engineering lecture Notes
Balanced stiffness, strength and ductility (Cont’d)
Naiguata Beach Club Building, Naiguata,
Venezuela, 1967 Caracas Earthquake. This was
a single-story building (approximately 7 meters
high) with a mezzanine at 3 meters above
ground. This slide shows the damage at the
connection between the column and the girder
supporting the mezzanine
Mosque Building, El Asnam, Algeria,
1980 El Asnam Earthquake. View
of the first story column and
column-girder connection at the
second floor level of the mosque.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 41
Balanced stiffness, strength and ductility (Cont’d)
Four Season Apartment Building, Anchorage,
Alaska, 1964 Alaska EQ. General view of the
building after the EQ. The lateral resistance to
earthquake ground motions was essentially
provided by the two slender vertical reinforced
concrete shafts. These shafts failed at the ground
floor level where all the vertical reinforcing bars
in the shafts were spliced
Overall view of an Apartment Building,
Anchorage, Alaska, 1964 Alaska EQ. This
14-story RC structure has as a basic lateral-
resisting structural system a series of
slender walls coupled by spandrel girders
that worked as coupling
girders. Unfortunately these spandrel
girders were not designed (detailed) to
work as coupling girders and therefore
suffered significant damage in the EQ.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 42
Dr. Adil Z (AAiT) 21
CEng 6506 Earthquake Engineering lecture Notes
Desirable features of Structural materials for
Earth quake resistant design
High ductility
High strength-to-weight ratio
Homogeneity
Ease in making full-strength connections
Possibility of suppression of brittle failure
modes
27 December 2017 Addis Ababa University (Dr. Adil Z.) 43
Typical brittle failure modes of common
construction materials
Material of construction Brittle failure mode
Reinforced Concrete Buckling of reinforcement bars
Bond or anchorage failure
Member shear failure
Masonry Out-of-plane bending failure
Global buckling of walls
Sliding shear
Structural Steel Fracture of welds and/of parent material
Bolt shear or tension failure
Member buckling
Member tension failure
Member shear failure
27 December 2017 Addis Ababa University (Dr. Adil Z.) 44
Dr. Adil Z (AAiT) 22
CEng 6506 Earthquake Engineering lecture Notes
Suitable Construction Material for Moderate to
High EQ Loading
Dorwick 2009
27 December 2017 Addis Ababa University (Dr. Adil Z.) 45
Basic design guidelines from past EQ
Prof. S. Mahin U C Berkeley
27 December 2017 Addis Ababa University (Dr. Adil Z.) 46
Dr. Adil Z (AAiT) 23
CEng 6506 Earthquake Engineering lecture Notes
Basic guidelines (cont’d)
Prof. S. Mahin U C Berkeley
27 December 2017 Addis Ababa University (Dr. Adil Z.) 47
27 December 2017 Addis Ababa University (Dr. Adil Z.) 48
Dr. Adil Z (AAiT) 24
CEng 6506 Earthquake Engineering lecture Notes
27 December 2017 Addis Ababa University (Dr. Adil Z.) 49
Architect – Engineer Relationship
While the provision of earthquake resistance is accomplished
through structural means, the architectural design and the
decision that create it, play a major role in determining the
building’s seismic performance
Seismic design is a shared architectural and engineering
responsibility, which stem from the physical relationship
between architectural forms and structural systems.
The interrelation between issues of engineering and architecture
demand that architect and engineer work together from the
inception of the project.
27 December 2017 Addis Ababa University (Dr. Adil Z.) 50
Dr. Adil Z (AAiT) 25
CEng 6506 Earthquake Engineering lecture Notes
Architect – Engineer cont’d
In resistance to gravity loads architectural and
structural decisions may be made independently
of each other. But in resistance to EQ effects,
separating the engineer from the architect is the
formula for disaster.
M. Sozen 1978
27 December 2017 Addis Ababa University (Dr. Adil Z.) 51
References
1. Dowrick, D. J., “Earthquake Resistant Design,” 2nd Edition, John Wiley &
Sons, 1987.
2. Chen, W-F.; Scawthorn, C., “Earthquake Engineering Handbook”, CRC
Press, 2002
3. Naiem, F., “Seismic Design Handbook” Kluwer Press, 2001
4. Kramer, S., “Earthquake Geotechnical Engineering”, Prentice Hall, 1995
5. Paulay, T., Priestley, M.J.N. “Seismic Design of Reinforced Concrete and
Masonry Buildings,” John Wiley & Sons, 1992.
6. Wolfgang Schueller, “High-Rise Building Structures,” John Wiley & Sons,
Inc New York, 1977.
7. Online material from the site http://nisee.berkeley.edu/
27 December 2017 Addis Ababa University (Dr. Adil Z.) 52