Heinzmann Basic Systems E 1-F / E 2-F: Electronic Speed Governors
Heinzmann Basic Systems E 1-F / E 2-F: Electronic Speed Governors
KG
                                                                                        Engine & Turbine Controls
                                                                                        Am Haselbach 1
                                                                                        D-79677 Schönau (Schwarzwald)
                                                                                        Germany
                                                                                        Phone      +49 7673 8208-0
                                                                                        Fax        +49 7673 8208-188
                                                                                        E-mail     info@heinzmann.com
                                                                                        www.heinzmann.com
                                                                                        V.A.T. No.:   DE145551926
                                       HEINZMANN
                                      Electronic Speed Governors
Basic Systems
E 1-F / E 2-F
Copyright 2001 by Heinzmann GmbH & Co. KG. All rights reserved. This document may not be reproduced or handed on to third parties.
HEINZMANN shall not be held liable for any indirect and direct dam-
age nor for any incidental and consequential damage that results from
application of any of the examples, data or miscellaneous information
as given in this manual.
HEINZMANN shall not provide any guarantee for the design and planning
of the overall technical system. This is a matter of the operator its planners
and its specialist engineers. They are also responsible for checking whether
the performances of our devices match the intended purpose. The operator is
also responsible for a correct initial start-up of the overall system.
                                                                                                                                      Contents
                                                               Contents
                                                                                                                                          Page
Contents..................................................................................................................................... 1
Page............................................................................................................................................ 1
1 Abbreviations......................................................................................................................... 1
3 Application............................................................................................................................. 5
8 Setpoint Adjuster................................................................................................................. 13
   8.1 Setpoint Potentiometer for Generator Applicationen with Droop ......................... 13
   8.2 Setpoint potentiometer for all speed Governors with large speed variation.......... 14
      8.2.1 1-Turn Potentiometer............................................................................................. 14
      8.2.2 10-Turn Potentiometer........................................................................................... 15
   8.3 Motorized Potentiometer ............................................................................................ 15
   8.4 Electronical Potentiometer ......................................................................................... 15
12 Electrical Connection........................................................................................................ 26
   12.1 Governor Connection Diagram for KG 1-04-F and KG 2-04-F............................ 26
   12.2 Governor Connection Diagram for KG 1-08-F and KG 2-08-F............................ 27
   12.3 Connection of Power Supply .................................................................................... 28
   12.4 Connection of Shielding ............................................................................................ 29
   12.5 Checking of Shielding................................................................................................ 31
16 Index of Figures................................................................................................................. 44
1 Abbreviations
E         ...                   complete Basic System
IA        ...                   Magnetic Pickup
KG        ...                   Control Unit
StG       ...                   Actuator
SW        ...                   Setpoint Potentiometer
KB        ...                   Harness
SyG       ...                   Synchronizer Unit
LMG       ...                   Load Measuring Unit
SA        ...                   Load Anticipation Unit
LKG       ...                   Load Control Unit
LSchG     ...                   Load Switch Unit
FSchG     ...                   Frequency Switch
EA-KG . . .                     Flexible Mount for Control Unit
BSBG      ...                   Acceleration Limiter
LTG       ...                   Load Sharing Unit
EFP       ...                   Electronic Foot Pedal (Transducer)
ESW      ...                    Electronic Setpoint Potentiometer
ÜG        ...                   Monitoring Unit
SFBG      ...                   Fuel Limiter
VFSchG . . .                    Fuel Switch
PG        ...                   Test Unit
SV        ...                   Plug Connection
SpAG      ...                   Voltage Matching Unit
    - Personnel
    - Product and machine
    - The environment
The signal words used in this publication are specifically designed to direct your attention to possi-
ble damage extent!
                    Safety instructions are not only denoted by a signal word but also by hazard
                    warning triangles. Red hazard warning triangles indicate immediate danger to
                    life. Yellow hazard warning triangles indicate a possible risk to life and limb.
                    Hazard warning triangles can contain different symbols to illustrate the dan-
                    ger. However, the symbol used is no substitute for the actual text of the safety
                    instructions. The text must therefore always be read in full!
                    This symbol does not refer to any safety instructions but offers important
                    notes for better understanding the functions that are being discussed.
       Note
                    They should by all means be observed and practised. The respective text is
                    printed in italics.
In this publication the Table of Contents is preceded by diverse instructions that among
other things serve to ensure safety of operation. It is absolutely imperative that these
hints be read and understood before commissioning or servicing the installation.
    2.3 Before Putting an Installation into Service after Maintenance and Repair
        Works
       Check on all slackened screw connections to have been tightened again!
       Make sure the control linkage has been reattached and all cables have been recon-
        nected.
       Make sure all safety devices of the installation are in perfect order and are working
        properly!
3 Application
The electronic HEINZMANN speed governors of the series E 1-F and E 2-F are all-electronic
and therefore do not require mechanical drives. The respective electric actuators StG 1-F and
StG 2-F are actively positioned in either direction by a power output stage.
This provides for very simple and cost-efficient installation on the engine so that these gover-
nors can be used for relatively simple governing tasks.
Their use is especially recommendable when the requirements with respect to governing qual-
ity are high. These governors offer very short response times with little overshooting and high
accuracy of speed control both with and without droop as may be required by the application.
Tasks such as automatic synchronization, load sharing, load anticipation, etc., can be carried
out in a very simple manner by means of a series of accessories (please refer to our leaflet
“Accessories“ and to our manuals for accessories).
                                  Injection
                                    pump
Engine Generator
Actuator
Pick up
Control unit
                         Feedback
                                                                  P- (Gain)
                          Power                                  I- (Stability)
                          drive                                                               Actual Speed
                                                                D- (Derivative)
                                    Start fuel                                                                  Setpoint conditioner
                                                    Droop                                     Setpoint        (only for speed variation)
                                                                          Overspeed
+ -
5 Mode of Operation
The electronic speed governors of the basic systems E 1-F and E 2-F are PID-governors de-
signed for diesel or gas engines. The actuator output shaft rotation is 68°, thus allowing direct
coupling to a carburator butterfly valve or a gas mixer.
Current speed is normally sensed as magnetic pickup frequency by means of a contactless
inductive sensor on the starting gear ring and compared with set speed. If there is a difference
between current and set speed the actuator is made to react accordingly and to eliminate the
speed deviation.
The governors are designed as PID controls that depending on the specific application allow
of operation both by the functions droop zero and by droop.
Droop zero is to be understood as adjusting speed to the pre-defined speed setpoint independ-
ently of engine load (for instance, 1,500 rpm for generator sets).
Droop, i.e. a permanent speed deviation in dependence on engine load, is required for vehicle
applications as well as for retrofitting or modernizing existing generator sets where a me-
chanical speed governor has been replaced by an electronic one.
The basic systems E 1-F and E 2-F can be combined with accessories such as synchronizers,
load measuring/sharing units and current anticipation units, etc.
                                                                                                  speed setpoint
                                                                                                  potentiometer             3
                                                                                                         cw                 4          setpoint                                                                                                                                 Current
                                                                                                                                      conditioner                                                                                                                              limitation
                                                                                                                            5
                                                                                                  250                                                              derivative
                                                                                                         ccw
                                                                                                                                                                                                                                                                            0V
                                                                                                                                                                                                                                             9            10
                                                                                                               brown
                                                                                                                                                                                                                   TP 6
                                                                                                     input synchronizer                                                                                                           TP 6
                                                                                                                                                                                                                                  actuator
                                                                                                               white                                 droop
                                                                                                     input kW sharing                                                                                             1,5 - 5 V
                                                                                                                                                                                                                                  feedback
                                                                                                                                                                                                                    8
                                                                                                              0V
                                                                                               contact opens if adjusted
                                                                                               switch point is reached
                                                                                               don’t forget the freewheel diode!
9
7 Magnetic Pickup IA...
     7.1 Specification
     Principle                                          Inductive sensor
     Distance to pickup wheel                           0.3 up to 0.6 mm
     Output voltage                                     0.5 up to 20 Volt
     Signal form                                        Sine (depending on tooth shape)
     Resistance                                         approx. 52 Ohm
     Temperature range                                  - 55 °C up to +120 °C
     Vibration                                          < 10g, 10 up to 100 Hz
     Shock                                              < 50g, 11 ms half sine wave
     Protection grade
                    magnetic pickup                     IP54
                    plug                                IP20
     7.2 Installation
     The installation of the pickup has to be arranged in such a way as to obtain a frequency as
     high as possible. The Frequency (by Hz) is calculated according to the formula
                                       n(1 / min)* z
                          f (Hz)   =
                                             60
                          z        =   number of teeth on the pickup wheel
     Example:
                          n        =   1500
                          z        =   160
                                        1500*160
                          f        =                   = 4000 Hz
                                           60
     It should be taken care that speed can be measured by the pulse pickup without any bias.
     For best results therefore, the speed pickup should take engine speed from the crankshaft.
     A suitable position for this is, e.g., the starter gear (but not the injection pump wheel).
     The pickup gear must consist of magnetic material (e.g., steel, cast iron).
4 mm (at least/
4 mm (at least)
0.5 - 0.8 mm
7.5 Dimensions
L1 16 L2
                                                                          17
                    G
L 33
              Dimension          L
                                                       G                        Remarks
                 Type          (mm)
              IA 01 - 38        38                 M 16 x 1,5
              IA 02 - 76        76                 M 16 x 1,5              corresponding
              IA 03 - 102       102                M 16 x 1,5                      plug
              IA 11 - 38        38           5/8"-18UNF-2A                     SV6-IA-2K
              IA 12 - 76        76           5/8"-18UNF-2A                (010-02-170-00)
              IA13 - 102        102          5/8"-18UNF-2A
8 Setpoint Adjuster
The standard versions of the basic system E 1-F with control unit KG 1-04-F or KG 1-08-F
and of the basic system E 2-F with control unit KG 2-04-F or KG2-08-F are shipped as
idle/maximum speed governors and will therefore not normally require an external setpoint
adjuster except a jumper on the 3-pole setpoint plug.
             The setpoint plug with the link must always be connected. When not connected,
             the governor will not work. For safety reasons the actuator will then always be in
 Note        a shutdown condition.
By connecting an external setpoint potentiometer the control unit may be used as a variable
speed governor. The 5 k potentiometers as described in chapter 8.2 provide an adjustment
range of 1:3.
On request, the potentiometers can be supplied with analogue adjustment knob with lock in
place of the standard rotating knob. In this case, ordering specification is SW..-..-m.
Equally, instead of the knob a clamping fixture can be provided. In this case, order specifica-
tion should be SW ..-..-k instead.
                                                             14       3/8" - 32 NEF - 2A
                                             Ø 26
                                     22
9,5
8.2 Setpoint potentiometer for all speed Governors with large speed variation
                                                              14       3/8" - 32 NEF - 2A
                                               Ø 26
                                       22
9,5
                                                                        3/8" - 32 NEF - 2A
                                                              20
                                               Ø 22
                                         16
8,8
     creased or increased by pulses from the external equipment. The sensitivity and ramp time
     of the unit is adjustable. For more information refer to manual E 97 001 - e.
   9.1 General
   Since there exist various basic systems and applications there are different control units
   available, e.g.,
   KG 1-04-F         Standard Unit for Basic System E 1-F
   KG 1-08-F         Unit for E 1-F with plug for accessory units (e.g. SyG 02, LMG 11)
   KG 2-04-F         Standard Unit for Basic System E 2-F
   KG 2-08-F         Unit for E 2-F with plug for accessory units (e.g. SyG 02, LMG 11)
   Special equipment such as military versions are available on request.
   9.2 Specification
   Voltage supply                                     12 / 24 V DC
   Residual ripple                                    max. 10 % at 100 Hz
   Current consumption of actuator                    max. 5 A
   Current consumption of control unit                approx. 150 mA (+ current of actuator)
   Permissible voltage dip at
   maximum current consumption                        max. 10 % in control unit
   Fuse protection of governor                        8A
   Operating temperature                              - 40 up to + 70 °C
   Humidity                                           up to 80 %
   Pickup frequency
                           Standard version           3100 up to 7000 Hz
                           different ranges           available on request
   Steady state variation                             +/- 1/4 %
   Speed variation due to temperature for
   frequency greater than 1500 Hz
   between -40°C and +70°C                            +/- 1 %
   Speed switchpoint                                  fully adjustable up to approx. 20 %
                                                      above max. operating frequency
   Start fuel limitation                              30 up to 100 %
   Droop                                              0 up to 15 %
   Protection grade                                   IP 20
   Weight                                             approx. 1 kg
9.3 Dimensions
Serial No.:
                        Am Haselbach 1
                        D - 79677 Schönau (Schwarzwald)
                                                           for Basic System E
                        Germany
                        Phone: (0 76 73) 82 88 - 0
                        Telefax: (0 76 73) 82 88 - 188
                                                                                                  6,6
                                                                                         40,5
                                                                                  76,5
     9.4 Mounting
     For installation, any place can be chosen where there is the least possible amount of vibra-
     tion and the lowest possible ambient temperature; it should be kept in mind to take the
     maximum cable lengths into account. There should be no strong magnetic fields in the vi-
     cinity of the control unit to avoid disturbances.
                         l   50%     Füllu
                     F ue                  n   g
               0%                                         0
             10
                                                                    R
                                          HEINZMANN
                                          GmbH+Co. KG
                                          Sp e e d G o ve r n o r
Co m p a n y
                                          Am Haselbach 1
                                          79677 Schönau
                                          Germany
                                          Tel.: (07673)8208-0
Fax: (07673)8208-188
Actuator StG1-02-F
   A multipolar magnetized permanent magnet is mounted on the actuator shaft. Opposite the
   permanent magnet an armature is fixed. When current is fed to the armature, torque in one
   direction is obtained. Changing the polarity of the current results in changing the torque di-
   rection.
   The control feedback is also fixed on the shaft. The actuator has a contactless feedback
   system that informs the control unit of the fuel position. Therefore, when speed or load
   change, the control unit is able to manipulate the actuator current, so the actuator will be
   forced to the required position until there is no difference between set speed and actual
   speed.
   If the actuator strikes against a stop, as may occur, e.g., under parallel mains operation or
   may be caused by engine overload or cylinder failure, the current limitation will take effect
   after approx. 20 seconds; by this the current to the actuator is reduced to a value that can-
   not harm the motor.
   The actuator is maintenance-free.
     10.2 Mounting
     The actuator must be mounted firmly on the engine by means of reinforced brackets. Un-
     stable arrangements, as caused by weak bracket material or missing stiffenings, have to be
     avoided by all means; they are bound to intensify vibrations, which will lead to premature
     wear of the actuator and the connecting linkage!
10.3 Specifications
                The lengths of the actuator lead must not be changed later on as this would
                have an adverse effect upon the measurement of the feedback as preset at the
     Note       factory.
10.5 Dimensions
                                                                                                17,5
                     53
                                                  6 8°
                                                                                                                  15
                                                                                         M6
     57
                                                   HEINZMANN
                                                               R                        17
                                                   GmbH+Co.
                                                                                                                             8
                                 Technical Data
                           Actuator StG1-02-F
                                                                                                                        17
                            for Basic System E1-F                       22
                                                                   M8                           10       40
              6                     92                                                  20,6              60
                                  104                                                                   101,1
17,5
                                                                                                                  15
                                                                                         M6
                                                                             32 °
                                                                                        15,6
                                                                                    8
                                                                                                                        17
                                                                             53
                          45 °
                                                  45°
                                                                                                10       40
                                                                                         18,6             60
                                                                                                         62,5
                                                                                                        101,1
11 Regulating Linkage
                                                                       5
                                              50
                                              16,5
Ø 8H8 13
Actuator
Stop lever
                                                       Displacement angle
                                                                                                                    Full load position
                                                                        68°
                                                                         50%
                                                                 Fuel               F üllu
                                Throttle valve            0%
                                                                                          ng
                                                                                             10
                                                                                                0%
                                                                                                                R
                                                                                        HEINZMANN
                                                                                        GmbH+Co.
                                                                                        Sp e e d Go ve rn o r
Co mp a n y
                                                                   Technical Data
                                                               Actuator StG1-02-F
                                                               for Basic System E1-F
Voltage 12 / 24
                                                                                                                                               +
                                                                                            Engine starter battery or
                                                                                            isolated supply/ battery
                                                                                            with charger
                                                                                            Rating 40 Ah
                                                                                                                                                                                                                                                           12 Electrical Connection
Fuse 8 A
                                                                                            Governor on/off
                                                                                            Switch 10 A
L1 L2 L3 N
Actuator
                                                                                                                                       12 V or 24V
                                                                                                                                                 +
                                                                                            Engine starter battery or
                                                                                            isolated supply/ battery
                                                                                            with charger
Fuse 8 A
                                                                                            Governor on/off
                                                                                            Switch 10 A
L1 L2 L3 N
Actuator
27
                                                                                                                                                                                                                                                             12 Electrical Connection
12 Electrical Connection
     HEINZMANN                                                     HEINZMANN
     Actuator                                                      Actuator
     StG ...                                                       StG ...
                                    Engine                                                    Engine
                                                                   Actuator cable
                                                                   L2
     Actuator cable
     L2
                                                                                                                          Battery
                                                                                                                       12 V or 24 V
                           (+)                                                                     L1                  -
                                                                                                                                  +
                           (-)                                                          (-)                                                   (+)
                                                                                        (+)
                                                                                                                                              (-)
     HEINZMANN        L1                         -                                            Governor      8 A slow
     Control unit                                 Battery                                      On/Off                                          Supply further units
                                                 +                 HEINZMANN
                                                                   Control unit
                                                                                                                       -
                                                                                                                                  +
                                             +
                                 Governor
                                  On/Off         Charger                                                                Charger
                                             -
WRONG, the ripple voltage fromn the charger is fed                        CORRECT, the electronic speed governor is connected directly
directly to the electronic speed governor .                               to the battery.
This will damage the actuator!                                            In this application the governor doesn’t see the ripple from the charger.
Notice! Coils (e.g. stopping solendoids gas valves) have to be equipped with a protective circuit to elimenate inductance voltages.
Diode type e.g. 1N4002
                                  If there are battery chargers with rapid charge mode installed in the
                                  plant, the rapid charge mode should no be used during operation.
     Warning
   The minimum line sizes for the feed line L1 must be for lengths of
     up to 7 m                     2 x 1,5 mm²,
     from 7 to 12 m                2 x 2,5 mm² and
     from 12 to 20 m               2 x 4,0 mm².
                       When power supply, battery and cabling have been correctly dimen-
                       sioned, then on starting the engine or with the actuator operating at
                       maximum current consumption (approx. 5 Amps), there may occur no
   Warning
                       greater a drop of the supply voltage directly at the control unit than of
                       approx. 2 Volts maximum.
     If a line with shielding is wired via a terminal strip, the shielding has to be connected to the
     terminal strip without contact to a negative line or ground.
     The following arrangements are frequently encountered, they may, however, cause gover-
     nor disturbances.
- Battery
- Battery
Note
Serial No.:
                                  Am Haselbach 1
                                  D - 79677 Schönau (Schwarzwald)
                                                                    for Basic System E
                                  Germany
                                  Phone: (0 76 73) 82 88 - 0
                                  Telefax: (0 76 73) 82 88 - 188
SV 1-KG-2K
SV 1-KG-4G SV 1-KG-3K
                                                                                                          SV 1-KG-5K
     SV 1-KG-4K
Pick up
                                                                                                         Link
                                                                                  SV 1-StG-6K
Actuator
SV 1-StG-6G
Actuator
Serial No.:
                                       Am Haselbach 1
                                       D - 79677 Schönau (Schwarzwald)
                                                                         for Basic System E
                                       Germany
                                       Phone: (0 76 73) 82 88 - 0
                                       Telefax: (0 76 73) 82 88 - 188
yellow
yellow
     14.3 Linkage
     Mount the linkage between the actuator and the fuel system according to instructions (refer
     to chapter 11). Check that there is no backlash in the linkage between actuator and fuel
     system and that the linkage is moving freely and without friction.
   The red LED will go out when cranking speed is higher than 50 rpm.
   If the LED fails to go out, there is no signal from the magnetic pickup or the distance be-
   tween pickup and fly wheel is too large.
Serial No.:
                                  Am Haselbach 1
                                  D - 79677 Schönau (Schwarzwald)
                                                                                  for Basic System E
                                  Germany
                                  Phone: (0 76 73) 82 88 - 0
                                  Telefax: (0 76 73) 82 88 - 188
Indication in millivolt
                                                 At actuator            At actuator
                                                  0% zero               100% max.
                                                                                                             HEINZMANN
                                            0%             100%      0%            100%
Position at actuator
Position 2 (Feedback)
                                                                                                         PG - 01
                                                        Position 3 (Simulator)
         Connect the test unit PG 01 to the control unit as shown in the figure. Then set the
         switch from test unit to position 3. Turn the test unit off, then on again or carefully
         move the regulating linkage. The test unit will now simulate the engine (refer to man-
         ual E 83 008-e, Test Unit PG 01).
         If there exists an external setpoint potentiometer turn it into its rightmost position
         (right stop). Then use the internal multiturn potentiometer “Speed” of the control unit
         to set the frequency associated with operating speed.
     b) HEINZMANN has been informed of the number of teeth and the operating speed when
        the order is placed. In this case, the control unit is set to the operating frequency speci-
        fied by the customer before it leaves the factory. The operating frequency setting is in-
        dicated on the name plate.
     c) If HEINZMANN has not been informed of the desired operating frequency before the
        control unit is shipped, the frequency is set to 4000 Hz. When commissioning the en-
        gine then speed must be corrected if necessary by means of the internal multiturn po-
        tentiometer.
                  If it is not possible to set the desired operating speed the jumper for determin-
        Note
                  ing the frequency range must be checked (see chapter 5.1).
Warning
Serial No.:
                                  Am Haselbach 1
                                  D - 79677 Schönau (Schwarzwald)
                                                                    for Basic System E
                                  Germany
                                  Phone: (0 76 73) 82 88 - 0
                                  Telefax: (0 76 73) 82 88 - 188
     Droop potentiometer         counter clockwise to min. stop end reduces the droop to zero
     (isochronous).
     Droop potentiometer       clockwise to max. stop end produces a droop of approx. 15 %
     over the complete actuator angular travel range. If for example, 40 % of the angular travel
     between zero load and full load is used, the max. droop is correspondingly smaller
     ( approx. 6 %).
For this application the KG 1-08-F or KG 2-08-F with the synchronizer input is required.
Warning
Adjustment procedure:
1. Start the GenSet to rated speed (e.g. 50 Hz) without connecting the external steering.
2. Measure the voltage on the synch. Input (brown cable) to 0.V (blue cable):
3. Adjust the offset voltage in the external steering exact to the measured level.
  (There must not be a speed change if you connect the steering to the governor and the
   synchronization is not active).
4. Turn Droop potentiometer 60 to 70% clockwise (results about 4% Droop, depending on the
   used actuator travel, see Figure 26)
5. This adjusted Droop (4% = +/- 2 Hz at 50 Hz generator frequency) gives the operating
   range for synchronization and load setting.
  Was the measurement on the synch. input e.g. 4V is your electrical operation range
   4% from 4V = 160mV ! This is the value for your Gain adjustment.
                                                                                       Full load position
                                                    No load position
                                   1/min
                           Speed
Load range
1440
                                           0      20 %                                80 %                  100 %
                                                      Operation angle on the actuator
                                             Trouble Shooting
                   Symptoms                                       Possible Causes
Governor does not open on starting                  Supply voltage not available, too low or
                                                    poles reversed
                                                     Control lamp must be on when power sup-
                                                     ply is on and must go out from approx. 50
                                                     rpm upwards
                                                    No signal from magnetic pickup
                                                     Excessive pickup clearance
                                                     (desired range approx. 0.5-0.8 mm)
                                                     Check resistance at plug (unplugged at
                                                     control unit) from pickup cable
                                                     (approx. 52 ). Wrong value means pickup
                                                     or cable defective
                                                     Check starting speed voltage at plug (un-
                                                     plugged at control unit) from pickup cable
                                                     (approx. 0.5 V AC)
                                                    No plug or speed setpoint potentiometer
                                                    connected to setpoint input or a potentiome-
                                                    ter with too high resistance is used. Max.
                                                    value is 5 k
                                                    Speed setting at minimum position
                                                    Wrong installation of actuator (rotation di-
                                                    rection)
                                                    Actuator    blocked      or   linkage    adjusted
                                                    wrongly
                                                    Control unit defective
                                                    Actuator defective,    measure resistance be-
                                                    tween
                                                      brown - white        approx. 4 
                                                      yellow - green       approx. 7 
                                                      yellow - grey        approx. 60 
                                                    Poor plug contact in control box
Actuator opens directly when DC voltage is          Failure in shielding of magnetic pickup or
applied to control unit                             setpoint potentiometer
                                                    Control unit defective
For this application the KG 1-08-F or KG 2-08-F with the synchronizer input is required.
Adjustment procedure:
1. Start the GenSet to rated speed (e.g. 50 Hz) without connecting the external steering.
2. Measure the voltage on the synch. Input (brown cable) to 0.V (blue cable):
3. Adjust the offset voltage in the external steering exact to the measured level.
  (There must not be a speed change if you connect the steering to the governor and the
   synchronization is not active).
4. Turn Droop potentiometer 60 to 70% clockwise (results about 4% Droop, depending on the
   used actuator travel, see Figure 26)
5. This adjusted Droop (4% = +/- 2 Hz at 50 Hz generator frequency) gives the operating
   range for synchronization and load setting.
  Was the measurement on the synch. input e.g. 4V is your electrical operation range
15 Order Information
When ordering, please note the individual units:
Control Unit:
  KG 1-04-F or KG 1-08-F or KG 2-04-F or KG 2-08-F
Associated Actuator:
  refer to chapter 10.4
Leverarm:
  RH 1 - 01
Magnetic Pickup:
 Standard IA 00-38 with 1.6 m cable                   or refer to chapter 7.5
Setpoint Adjuster:
   Standard plug with link                            or refer to chapter 8
Cable for Connection of Accessory Units:
  L 5, standard plug with 1.6 m cable                 other lengths on request
Further Informations:
16 Index of Figures
Figure 1: Block Diagram of Control Circuit .............................................................................. 6
Figure 2: Block Circuit Diagram of Governors E 1-F and E 2-F............................................... 9
Figure 3: Clearance of Magnetic Pickup.................................................................................. 11
Figure 4: Dimensions of Pickup with CableStandard Version ................................................ 12
Figure 5: Dimensions of Pickup with Plug .............................................................................. 12
Figure 6: Setpoint Potentiometer SW 13-1-o (250 R).............................................................. 13
Figure 7: Setpoint Potentiometer SW 01-1-o (5 k) ............................................................... 14
Figure 8: Setpoint Potentiometer SW 02-10-o (5 k) ............................................................. 15
Figure 9: Dimensions of Control Unit...................................................................................... 18
Figure 10: Sectional Drawing of Actuator StG 1-02-F ............................................................ 19
Figure 11: Dimensions of StG 1-02-F and StG 2-02-F............................................................ 22
Figure 12: Lever Arm for StG 1 and StG 2.............................................................................. 23
Figure 13: Linkage for Diesel Engines .................................................................................... 24
Figure 14: Linkage for Gas Engines ........................................................................................ 25
Figure 15: Connection Diagram for KG 1-04-F and KG 2-04-F ............................................. 26
Figure 16: Connection Diagram for KG 1-08-F and KG 2-08-F ............................................. 27
Figure 17: Correct Connection of Power Supply ..................................................................... 28
Figure 18: Shielding of Magnetic Pickup ................................................................................ 29
Figure 19: Shielding via Terminal Strip................................................................................... 30
Figure 20: Faulty Shieldings .................................................................................................... 30
Figure 21: e.g. Magnetic Pickup Shielding Check................................................................... 31
Figure 22: Harness with Plug Designations ............................................................................. 32
Figure 23: Governor Adjustment Sheet ................................................................................... 33
Figure 24: Connection of Test Unit PG 01 .............................................................................. 35
Figure 25: Droop Potentiometer............................................................................................... 38
Figure 26: Droop curve at 4% and 1500 rpm........................................................................... 39