Section Q - Ventilation:: Chapter 511-6-1
Section Q - Ventilation:: Chapter 511-6-1
SECTION Q - VENTILATION:
REFERENCES
Chapter 511-6-1:
.05 Equipment and Utensils. Amended. (2) Design and Construction (j) Ventilation Hood Systems, Filters.
.05 Equipment and Utensils. Amended. (2) Design and Construction (n) Exhaust Ventilation Hood System.
.05 Equipment and Utensils. Amended. (3) Design and Construction (d) Ventilation Hood Systems, Adequacy.
.05 Equipment and Utensils. Amended. (5) Acceptability of Existing Equipment.
.07 Physical Facilities. (2) Design, Construction, and Installation (j) Heating, Ventilating, Air Conditioning,
Systems Vents.
.07 Physical Facilities. (3) Numbers and Capacities. (g) Mechanical Ventilation.
.07 Physical Facilities. (5) Maintenance and Operation. (d) Cleaning Ventilation Systems, Nuisance and Discharge
Prohibition.
NFPA 96, 2004 Edition, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.
NFPA 101, 2000 Edition, Life Safety Code.
International Fire Code (IFC), as adopted by the Chapter 120-3-3 of the Rules and Regulations State Minimum Fire
Safety Standards.
II. Background1:
1
Source: Section 12 – Ventilation – FDA 2008 Plan Review for Food Establishment Guidance Document.
01/08/2013 Page Q1 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
2. Proper capture and venting of gases, heat, grease, vapors, and smoke generated by
cooking equipment is important; for not only fire prevention and sanitation purposes,
but for maintaining the health and well being of the establishment’s food service
employees and consumers. In order to help prevent dangerous or unhealthful
conditions within a food service establishment, it is critical that exhaust ventilation
systems be designed, constructed, and operated in compliance with all applicable state
laws and local codes.
3. The additional heat and moisture loads generated by equipment and appliances shall be
accounted for in the design of the HVAC system.
1. The State’s minimum requirements for Type I commercial kitchen hood ventilation
system ducts and exhaust equipment shall be designed, constructed and installed in
accordance with the Life Safety Code (LSC) NFPA 101 and NFPA 963. Other
commercial kitchen hood ventilation system ducts and exhaust equipment shall comply
with the requirements of the International Mechanical Code.
2. The State’s minimum requirements for fire suppression systems for commercial
cooking equipment shall be established by the Life Safety Code and NFPA 96.
Commercial cooking appliances required to have a Type I hood shall be provided with
an approved automatic fire suppression system – see Illustration Q-11 for example.
IV. State or Local Fire Marshall Office4: Counties with over 100,000 persons and
municipalities with over 45,000 persons are mandated by law to enforce the state's
minimum rules and regulations on such buildings in their area of jurisdiction. Resolutions
can be submitted by municipalities under 45,000 persons adopting the enforcement
responsibilities from the state. If a county or municipality is not required to conduct
enforcement, the State Fire Marshal’s Office enforces O.C.G.A. 25-2-14 which lists the
facilities under the jurisdiction of the State Fire Marshal’s Office.
2
Source: Table 102.10: Codes Reference Guide – Chapter 120-3-3-.04 State Minimum Fire Safety Standards with
Modifications – State of Georgia.
3
As adopted within Chapter 120-3-3 Georgia State Minimum Fire Safety Standards, this standard provides the minimum fire
safety requirements related to the design, installation, operation, inspection, and maintenance of all cooking operations.
4 Reference: O.C.G.A. 25-2-12 (a) (1) and (b)
5
Source: Page 12 of Section 12 – Ventilation 2008 FDA Food Establishment Plan Review Guide Document
01/08/2013 Page Q2 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
3. For heat and steam producing equipment, the hood or ventilation system controls
humidity, heat and unwanted condensation.
c. Size of the room or area where the proposed equipment will be installed,
including ceiling height;
d. How the proposed equipment will be operated, e.g., the types of food prepared,
how often, etc;
h. Method of producing heat, e.g., gas, electricity, solid fuel, etc.: Cooking
equipment that uses solid fuel e.g., wood or charcoal, must be provided with a
separate exhaust system.
6
Source: Pages 5 & 6, “Cooking Equipment Exhaust Ventilation Exemption Guide For The Local Enforcement
Agency” dated September 2009 published by the California Conference of Directors of Environmental Health and
Section 507 in the 2006 International Mechanical Code as adopted by Georgia Department of Community Affairs
(DCA)
01/08/2013 Page Q3 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
B. Although following Listing Q-1 of appliances typically does not require mechanical
ventilation, Listing Q-1 shall not be deemed to supersede any state or local building
and fire code requirements. In addition, Listing Q-1 does not preclude the local
Health Authority and any enforcement agency from requiring the installation of
mechanical exhaust ventilation when the operation of the cooking equipment in a
specific location may or actually results in a sanitation or safety violation. Each
local Health Authority having jurisdiction will have to evaluate equipment in
Listing Q-17on a case-by-case basis:
Listing Q-18
• Coffee Equipment:
o Urn or brewer
o Roaster (electric)
• Corn on the Cob Warmer
• Clam Shell Grill/Panini – (for heating non-grease producing foods such as
tortillas, pastries, rolls, sandwiches from precooked meats and cheeses)
• Crepe Maker (no meats)/Waffle Cone Maker/Waffle Iron
• Hot Dog Warmer - Hot Plate (electric and induction cooker) and Roller-Cooker
• Electrical Holding/Warming Ovens and Portable ovens (light-duty microwave, cook
and hold, ovens utilizing visible and infrared light technology)
• Popcorn Popper (without external grease vapor release)
• Rethermalizers (single light-duty electric)
• Rice Cookers and Egg Cookers (electric)
• Rotisserie (Electric and enclosed with max. ambient cavity temperature of 250ºF)
• Electrically heated Steam Table
• Toaster – countertop (bread only)
• Under-counter-type commercial warewashing machines
• Warewashers and potwashers that are provided with heat and water vapor exhaust
systems that are supplied by the appliance manufacturer and are installed in accordance
with the manufacturer’s instructions
Note: The additional heat and moisture loads generated by such appliances as those listed
above shall be accounted for in the design of the HVAC (Heating, Ventilation and Air-
Conditioning) system.
7
Reference: Section 507.2.2. Type II hoods, Exception #4, Georgia 2006 International Mechanical Code as
adopted by the Georgia Department of Community Affairs (DCA) Board as mandated and applicable to Georgia.
8
Source: Cooking Equipment Exhaust Ventilation Exemption Guide For The Local Enforcement Agency
September 2009 as published by the California Conference of Directors of Environmental Health
01/08/2013 Page Q4 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
VI. Cooking Equipment Duty Rating Relative to Type of Exhaust Ventilation System:
1. Background9:
A. Cooking can be described as a process that adds heat to raw or precooked food. As
heat is applied to the food, effluent is released into the surrounding environment.
This effluent release includes water vapor, organic material released from the food
itself, and heat that was not absorbed by the food being cooked. Some forms of
reheating, such as rethermalizing limit the effluent released to the space but still
emit water vapor to the surrounding space.
B. The hot cooking surface (or fluid, such as oil) and product vapors create thermal air
currents (typically called a thermal plume) that are received or captured by the
hood and then exhausted. If this thermal plume is not captured and contained by
the hood, they become a heat load to the space. The velocity of these thermal
plumes depends largely on the surface temperature of the cooking equipment, and
varies from 25 feet per minute over some steam equipment, to 200 feet per minute
over some char-broilers. Thus, the strength of the thermal plume is a major factor
in determining the exhaust rate.
C. Because of the variation in velocity of thermal plumes and the quantity of grease
and smoke produced, cooking equipment typically classified in four duty rate
categories: light duty (such as ovens, steamers, and small kettles up to 400F),
medium duty (such as large kettles, ranges, griddles, and fryers up to 400F), heavy
duty (such as broilers, char-broilers, and woks up to 600F) and extra heavy duty
(such as solid-fuel-burning equipment - wood, charcoal, etc. - up to 700F).
9
Source: Heat Load Based Design – Radiant, Convective and Conductive HEAT
10
Source #1: energy design resources, design brief, Commercial Kitchen Ventilation Design,
Southern California Edison – reported source: ASHRAE Standard 154
Source #2: Section 507 - Georgia 2006 International Mechanical Code as adopted by Ga. Dept of Community
Affairs
01/08/2013 Page Q5 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
Listing Q-2
• Barbeque
• Charbroiler – Underfired
• Tandoor Oven – (Clay oven mainly used in the preparation of Indian dishes.
Other Asian cultures use it as well.)
• Chinese Range – (Wok)
Listing Q-3
Listing Q-4
01/08/2013 Page Q6 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
Listing Q-5
2. A hood shall be designed to provide thorough cleaning of the entire hood. Grease
gutters shall drain to an approved collection receptacle that is fabricated, designed and
installed to allow access for cleaning. Exhaust ventilation hoods and devices shall be
designed and installed to prevent grease or condensation from collecting on walls,
ceilings, and fire suppression supply piping and from dripping into food or onto food
contact surfaces12.
3. Type I Hoods13:
A. Type I hood systems are installed where cooking appliances produce grease or
smoke, such as occurs with griddles, fryers, broilers, ovens, ranges and wok ranges.
Type I hood systems shall be designed and installed to automatically activate the
exhaust fan whenever cooking operations occur. The activation of the exhaust fan
shall occur through an interlock with the cooking appliances, by means of heat
sensors or by other approved means.
11
Source: 507.2 Where required – Section 507 Commercial Kitchen Hoods – GA 2006 International Mechanical
Code as adopted by the Georgia Dept. of Community Affairs.
12
Source: 507.8 Cleaning and grease gutters - Section 507 Commercial Kitchen Hoods – GA 2006 International
Mechanical Code as adopted by the Georgia Dept. of Community Affairs.
13
Source: 507.2.1 Type I hoods & 507.2.1.1 Operation - Section 507 Commercial Kitchen Hoods – GA 2006
International Mechanical Code as adopted by the Georgia Dept. of Community Affairs.
01/08/2013 Page Q7 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
B. A Type I hood shall be installed with a clearance to combustibles of not less than 18
inches. Clearance is not required for gypsum wallboard attached to noncombustible
structures if a smooth, cleanable, nonabsorbent and noncombustible material is
installed between the hood and the gypsum wallboard over an area extending not
less than 18 inches in all directions14.
4. Type II Hoods15:
C. See Illustrations Q-1, Q-8, Q-9 and Q-12 for examples of a Type II Hood system.
1. Make up air shall be supplied during the operation of commercial kitchen exhaust
systems that are provided for commercial cooking appliances. The amount of makeup
air supplied shall be approximately equal to the amount of exhaust air. Makeup air
shall be provided by gravity or mechanical means or both.
2. If make-up air were not provided, the building would be under a negative pressure,
which could cause the following serious problems:
A. The exhaust fan would not be capable of exhausting the design volume of air
because the air would not be available.
B. Negative pressure would cause improper venting of water heaters, space heaters, or
the individually vented gas appliances in the establishment.
C. A negative pressure will cause a surge of unconditioned outside air into the
building whenever the doors are opened, which may also allow the entrance of flies
into the establishment.
14
Source: 507.9 Clearances for Type I hood - Section 507 Commercial Kitchen Hoods – GA 2006 International
Mechanical Code as adopted by the Georgia Dept. of Community Affairs.
15
Source: 507.2.2 Type II hoods - Section 507 Commercial Kitchen Hoods – GA 2006 International Mechanical
Code as adopted by the Georgia Dept. of Community Affairs.
16
Source: 508 Commercial Kitchen Makeup Air – GA 2006 International Mechanical Code as adopted by the
Georgia Dept. of Community Affairs.
01/08/2013 Page Q8 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
4. For a consistent and regulated flow, make-up air should be mechanically introduced by
a fan or gravity. Outside windows and doors shall not be used for the purpose of
providing make-up air. Air conditioning systems may also serve as a source of make-up
air,
5. Make-up air controls should be interlocked with exhaust controls to ensure that the
units operate simultaneously. Replacement air shall be filtered and may also be
tempered by a separate control. The air velocity through the make-up air system should
be low enough to avoid the possibility of drafts. It is desirable to have the kitchen
under a very slight negative pressure to prevent any filtration of cooking odors from the
kitchen into the dining room. The supply of make-up air is frequently introduced at
some point in close proximity to the hood to avoid the removal of conditioned air that
has been heated or cooled.
6. The State’s minimum requirements for commercial kitchen makeup air in Type I hoods
shall be in accordance with the Life Safety Code, NFPA 101 17and NFPA 9618.
Commercial kitchen makeup air for Type II hoods shall comply with the requirements
of the International Mechanical Code.
1. Canopy:
A. The inside lower edge of canopy-type I and II hood shall overhang or extend a
horizontal distance of not less than 6 inches beyond the edge of the top horizontal
surface of the appliance on all open sides. The vertical distance between the front
lower lip of the hood and the cooking surface shall not exceed 4 feet. The hood
shall be permitted to be flush with the outer edge of the cooking surface where the
hood is closed to the appliance side by a non-combustible wall or panel.
B. Canopy hoods both wall and island should have a minimum depth of two feet. No
overhang will be required on sides where aprons are installed; however, side
overhang shall be required when less than full side curtains are provided
(Illustration Q-2). The dimensions of the hood are, in all cases, larger than the
cooking surface to be covered by the hood.
C. Canopy hoods are generally installed so that the bottom of the hood is between
6.5 feet and 7 feet above the finished floor (Illustration Q-3.); however, the
vertical distance between the lower lip of the hood and the cooking surface shall
not exceed 4 feet.
17
National Fire Protection Association - Life Safety Code
18
National Fire Protection Association – Standard for the Ventilation Control and Fire Protection of Commercial
Cooking Operations
19
Source: 507.12 Canopy size and location & 507.14 Noncanopy size and location – Section 507 – GA. 2006
International Mechanical Code as adopted by the Georgia Department of Community Affairs.
01/08/2013 Page Q9 of 27
Rules and Regulations Food Service – DPH Chapter 511-6-1
Food Service Establishment Manual for Design,
Installation and Construction
2. Non-canopy:
A. Non-canopy type hoods shall be located a maximum of 3 feet above the cooking
surface. The edge of the hood shall be set back a maximum of 1 foot from the edge
of the surface.
B. Ventilator or Backshelf Hood: Backshelf hoods are designed to mount to the wall
directly behind the cooking equipment. This type of hood is often used where
ceiling height is a factor. It is normally placed closer to the cooking surfaces than
a canopy hood, and works well in light to medium duty cooking applications. The
ventilator hood is not used for char broilers or similar high heat and grease
producing cooking equipment. It does not have the capture area of a canopy hood
and is not able to effectively handle large surges of cooking emissions (steam,
heat, vapors, smoke etc.) See Illustration Q-4 and Illustration Q-12 for example.
C. Eye-Brow Hoods:
a. Eye-brow hoods are acceptable for use with either Type I or Type II hoods. The
eye-brow hood shall overhang, or extend a horizontal distance of at least six
inches, beyond all areas of the equipment out of which steam, grease, odors,
smoke, or heat will be emitted – see Illustrations Q-5 and Q-6.
b. An eyebrow hood is designed to immediately remove heat from the oven at the
point of emission or as the door is opened. It must effectively ventilate the door
openings or product entry/exit points of the equipment served.
c. The eyebrow-type oven hood shall be located above the product transfer
openings or doors and shall extend the width of the oven-baking cavity. An
eyebrow-type hood shall be of a rectangular or box type construction with a
recommended minimum of 12 inches of front overhang.
d. Filters shall be provided and they shall be easily accessible for cleaning.
e. When the width of the product transfer openings or doors is less than the width
of the oven-backing cavity, the hood shall be designed to extend beyond the
edge of the product transfer openings or doors a minimum distance of 3 inches
but not to extend beyond the width of the oven.
a. Waterwash hoods operate under the following principles. As the exhausted air
moves at a high velocity past a baffle system, the heavier-than-air particles of
grease are thrown out of the airstream by centrifugal force. The extracted
grease is collected in grease gutters within the hood until removed by the daily
cleaning cycle. The cleaning cycle is initiated when the exhaust hood is turned
off. Hot detergent water is automatically sprayed onto the baffles system,
thereby removing the grease deposits from the baffles. This wastewater is then
drained off to the sewer or other approved waste removal system.
a. Where it is not possible to exhaust the air to the out-of-doors and at the
discretion of the code official and or health authority, a non-ducted, self-
contained exhaust system may be a viable option for the food establishment.
20
Source: Cooking Equipment Exhaust Ventilation Exemption Guide For The Local Enforcement Agency as
published by the California Conference of Directors of Environmental Health.
21
Source: 507.1 General – Exceptions – Section 507 Commercial Kitchen Hoods – GA 2006 International
Mechanical Code as adopted by the Georgia Department of Community Affairs.
e. The cooking equipment and exhaust system shall be interlocked such that when
the hood is not functional or when the hood is operating at less than 85%
efficiency, the cooking equipment will not operate.
g. Since a nonducted exhaust system does not normally remove the heat from the
exhausted air, the establishment’s HAVC system and the nonducted exhaust
system must be engineered to balance the establishment’s HAVC system.
Additional air conditioning will be required to meet the increase BTUs being
returned to the room in addition to other heat generating equipment. Due to this
increased air handling capacity demand of HAVC with nonducted exhaust
system characteristic, nonducted exhaust systems are considered equipment and
facility specific and as such, they and the HAVC system both must be
engineered and installed to the specific ventilation requirements of the proposed
food service facility.
i. The design nonducted exhaust hoods must be such that grease and condensate
cannot drip back onto the cooking surfaces.
X. Dishwashing Appliances:
1. A Type II Hood is not required for dishwashers and potwashers provided with heat and
water vapor exhaust systems that are supplied by the appliance manufacturer and
installed in accordance with their instructions. See Illustration Q-8 Pants Leg Exhaust
System in Section Q of Part I within the online Food Service Manual for Design,
Installation and Construction for an example of a typical installation.
2. The top and side of the vestibule shall extend 10 inches horizontally over the
drainboard on each end of the warewashing machine. The design shall prevent
drippage from the hood and duct onto utensils and equipment. The machine
manufacturer’s recommended air quantities (Q) shall be used or the following:
3. Ductwork with reduced area or fixed control damper may be used on entrance.
4. The minimum net air-flow for Type II Hoods used for dishwashing appliances shall be
100 CFM per linear foot of hood length22. See Illustration Q-9 within Section Q-
Ventilation of Part I within the online Food Service Manual for Design, Installation and
Construction for an example of a typical installation.
1. Grease filters for type I hoods shall be equipped with listed grease filters designed for
the specific purpose. Grease collecting equipment shall be provided with access for
cleaning.
2. Filters shall be of such size, type and arrangement that will permit the required quantity
of air to pass through such units at rates not exceeding those for which the filter or unit
was designed or approved. Filter units shall be installed in frames or holders so as to be
easily removable without the use of separate tools, unless designed and installed to be
cleaned in place and the system is equipped for such cleaning in place.
3. Removable filter units shall be of a size that will allow them to be cleaned in a
dishwashing machine or pot sink. Filter units shall be arranged in place or provided
with drip-intercepting devices to prevent grease or other condensate from dripping in
food or on food preparation surfaces.
4. Filters shall be installed at an angle of not less than 45 degrees for the horizontal and
shall be equipped with a drip tray beneath the lower edge of the filters24. See
Illustration Q-10.
A. The extractor filter removes grease in the exhaust process by centrifugal motion or by
impingement on a series of baffles. The manufacturer’s optimum rating of the filter
should be used in calculating the filter area required in the exhaust system. Standard
size filters should be used to avoid additional cost and to allow ease of replacement.
Any space in the filter bank not covered by filters/extractors shall be fitted with sheet
22
Source: 507.13.5 Dishwashing appliances – Section 507 Commercial Kitchen Hoods – 2006 International
Mechanical Code as adopted by the Georgia Depart. of Community Affairs.
23
Source: 507.11.1 Criteria - Section 507 Commercial Kitchen Hoods – 2006 International Mechanical Code as
adopted by the Georgia Depart. of Community Affairs.
24
Source: 507.11.2 Mounting position – Section 507 Commercial Kitchen Hoods - 2006 International Mechanical
Code as adopted by the Georgia Depart. of Community Affairs.
25
Reference: Section III, Part 15-Ventilation, 2000 FDA Food Establishment Plan Review Guide
B. The filter area required for an exhaust system can be calculated by using the
following formula:
a. Formulas:
C. Assume we have a canopy hood with a minimum required airflow of 4250 CFM.
The hood will be equipped with baffle-type filters with a nominal size of 16
inches x 20 inches and they will have an actual filtering surface of 14 inches x 18
inches. (Nominal size minus the frame equals the actual filtering area.) The
optimum operating velocity of the stated filters is 360 FPM. How many 16”x 20”
filters would be necessary for the canopy hood system?
b. Calculations:
Step 3. Divide the 12 sq.ft. of needed filter area by sq.ft. per filter:
1. Commercial food service hoods shall exhaust a minimum net quantity of air as
determined by the type of hood and cooking appliances. Where any combination of
heavy-duty, medium-duty and light-duty cooking appliances are utilized under a single
hood, the exhaust rate required for the heaviest duty appliance covered by the hood
shall be used for the entire hood.
2. Extra heavy, heavy and medium cooking appliances must use a Type 1 ventilation
exhaust hood system. Light duty cooking appliances may use a Type I or Type II
ventilation exhaust hood system.
3. The amount of air exhausted through a hood exhaust system is dependent upon the size
of the hood, its particular installation, and its use. There are several methods available
for determining the amount of air to be exhausted. With the exception of systems
engineered for specific equipment and specifications that are approved by local code
officials and or the Health Authority. Below is a summary of the method generally
accepted in the industry; however, the method approved by the local codes should be
followed in the design of the system:
A. Exposed linear foot method. This method of calculating the exhaust air volume is
based on the total exposed linear footage of the hood and the capture velocity relative
to its application
B. Standard square foot method. This method of calculating exhaust air volume is based
on the size of the opening in the hood (length x width) and the capture velocity
relative to the installation of the hood
C. Square feet of cooking surface method. This calculation of the volume of exhausted
air depends on the size, temperature, and design of the cooking equipment and the
minimal capture velocity required to keep smoke, vapors, and fumes under the hood.
4. The International Mechanical Code uses the exposed linear foot method for calculating
the minimum net airflow based on hood type and category of cooking appliance. Table
Q-1 has the minimum air volumes that shall be used to calculate the amount of air
exhausted for hood system and cooking category.
TABLE Q-126
Minimum Net Airflow (cubic feet per minute / linear foot of hood length) based on the Type of
Hood Allowed and Cooking Appliances Category
* Light duty cooking appliances can use Type 1 or Type II hoods. All other categories use Type I
hoods.
5. Exposed Linear Foot Method Exhaust Ventilation Hood System Sample Calculation:
B. If the cooking equipment is extra heavy duty, we are required to use a Type 1
canopy hood, either, double-island, wall-mounted or single. A
ventilator/backshelf/pass-over or eyebrow hood is not allowed to be used over
extra heavy-duty appliances. The calculations use a standard volume of air per
linear foot of exposed side of hood. The air volume is based on the type of hood
(i.e. three side canopy, wall-mounted canopy) and type of appliance.
a. Select the proper category for the cooking appliance (extra-heavy, heavy,
medium or light). Deep fat fryers are considered extra heavy-duty cooking
appliances.
b. Select the appropriate type of hood for the category of cooking appliance
(wall mounted, three sided, etc.). Table Q-1 lists the type of hoods that can be
used for extra heavy-duty cooking appliances. For this example, we are using
a single island canopy.
26
Source: 507.13.1, 507.13.2, 507.13.3 – Section 507 Commercial Kitchen Hoods – 2006 International Mechanical
Code as adopted by the Georgia Depart. of Community Affairs.
i. Step 1. Find the total linear feet of hood: there are 4 exposed sides on a
single island canopy.
ii. Step 2. Select the net airflow volume for a single canopy hood used
over an extra heavy-duty cooking appliance.
See Table 1. Single Island Canopy used over Extra Heavy Duty
Appliance
Minimum Net Airflow = linear feet of hood x net airflow per linear
foot of hood
Example Results:
32 feet of linear hood x 700 cfm per linear foot of hood = 22, 400 cfm
c. The net quantity of exhaust air shall be calculated by subtracting any airflow
supplied directly to a hood cavity from the total exhaust flow rate of a hood.
1. Prior to the issuance of a food service permit, the permit applicant shall provide
documentation to the Health Authority verifying that his or her ventilation system(s)
serving food service equipment have been installed correctly; have been tested and
operating properly as per applicable Codes; and that it has been approved by
applicable State and or local code officials.
27
Source: 507.16 Performance test - Section 507 Commercial Kitchen Hoods – 2006 International Mechanical
Code as adopted by the Georgia Depart. of Community Affairs.
ILLUSTRATION Q-1
Dishwasher with Heat and Water Vapor Exhaust System
This Type II Hood system is called a Pans Leg Hood due to the two duck work
located at the entrance and exit of the warewashing machine looks like the legs of a
pair of pants.
ILLUSTRATION Q-2
Canopy Hood with Side
ILLUSTRATION Q-3
Canopy Hoods
Canopy Hood Over Pizza Ovens Island Hood Installed Over Cook Line
The overhang of the hood depends on the distance between the top of the cooking surface
and the hood.
Six inches is the minimum required overhang for canopy hoods
The higher the hood is hung above six feet six inches the more overhang you should have.
Canopy hoods must be installed so that the bottom of the hood is between 6.5 feet and 7
feet above the finished floor.
ILLUSTRATION Q-4
Backshelf Exhaust Hood
Backshelf Hood
ILLUSTRATION Q-5
Eye Brow Hood on a Pizza Oven
ILLUSTRATION Q-6
Eye Brow Hood on a Conveyor Oven
ILLUSTRATION Q-7
Water Wash Cleaning Type Hood
ILLUSTRATION Q-7
Waterwash Exhaust Hoods
The open cabinet of the above self-cleaning (or Waterwash Hood) ventilation
hood reveals the automatic cleaning unit apparatus. Notice the cleaning agent in
the visible jug that is connected to the cleaning unit. Instructions on how to
operate the self-cleaning unit are located in the pouch on the cabinet door.
ILLUSTRATION Q-8
Pant Legs Exhaust
ILLUSTRATION Q-9
Typical Installation of a Canopy Hood over Warewashing Machine
ILLUSTRATION Q-10
Grease Filter Placement
ILLUSTRATION Q-11
Example of Automatic Fire Suppression Systems28
Exhaust ventilation systems for all grease producing cooking equipment is the
jurisdiction of the state or local Fire Marshal and building officials. The plan
Reviewer should refer applicant to the appropriate agency.
28
Source: Automatic Fire Suppression System borrowed from: Greenheck Building Value in Air, Schofield, WI and
from the current 2008 FDA Plan Review Training Course #FD207 presentation materials.
ILLUSTRATION Q-1229
29
Source: design brief Commercial Kitchen Ventilation Design, Architectural Energy Corporation, Boulder,
Colorado, and Fisher Nickel Inc., San Ramon, California under auspices of the California Public Utilities
Commission.
ILLUSTRATION Q-13
Examples of Ventless Hood Systems
Ventless hoods are somewhat controversial. There are certain applications where they may be
appropriate. In situations where a grease duct cannot go up to a roof due to living quarters above
or cannot utilize a side discharge through a wall, they may be appropriate. Routine maintenance
has been a common problem. Also, without a well designed HVAC system, heat dispersal is a
problem. The local Health Authority must evaluate these type exhaust hood systems on a case-by-
case basis.