0 ratings0% found this document useful (0 votes) 153 views30 pagesElectrical
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
ELECTRICAL LAYOUT AND ESTIMATE
Service Entrance Cable is of the types SE and USE. A
single or multi-conductor assembly provided with or without
an over all covering, primarily used for service wire.
stee! wire at core
FIGURE 2-6 SERVICE ENTRANCE CABLE
Power and Control Tray Cable (TC). This is a factory
assembled two or more insulated conductors with or without
associated bare or covered grounding under a metallic sheath
This is used for installation in cable trays, raceways, or where
it is supported by messenger wire.
Flat Cable Assi y of
conductors formed integrally with an insulating material web
designed specially for field installation in metal surface of
raceways:
Flat Conductor Cable (FCC) consists of three or more
flat copper conductor placed edge to edge separated and
enclosed within an insulating assembly, This type of
used for general purposes such as: appliance branch ¢
and for individ branch circuits, especially in hard
continuous floor surfaces and the like
Medi
cond)
or
volts
Voltage Cable (MV Cable) is a single or multi-
tor solid dielectric insulated cable rated at 2,000 volts
igher. This type is used for power system up to 35,000The MV
Trade name | Medium Voltage Solid Dielectric.
Type letter MV — 75; MV —85; MV — 90.
Maximum operating temp 75° C; 85° C, MV 90°C
Application : Dry or wet locations, rated at 2,000 volts
or higher
nt types and characteristics
nr
Insulation : Thermoplastic or thermosetting
6. Outer covering; Jacket, Sheath or Armor
Individually cotor—coded,
600 V. insulated conductors
Filler material
Binding tape
tala
ote
Type UF — plastic; see NEC article 339
Type TC — plastic; se NEC articie 340
Type ALS —aluminum; see NEC article 331
Type CS—copper; see NEC article 332
FIGURE 2-6 ALL 600 VOLTS JACKETED CABLES
Conductor
Conductor insulation
o
insulation
Nylon jacket
wo)
FIGURE 2-7
wire such as Type T and Type TW
te No BAW, ‘and stranded from No. 6 AWG
and larger.
Typical construction of jacke'
conductors normally solid throug!“ELECTRICAL LAYOUT AND ESTIMATE
2-3 Ampacity of Electrical Conductors
. ‘Ampacity is defined as the ability of the wire or conductor
to carry current without overheating. Conductor resistance to
current flow, generate not only heat but also contribute to the
voltage drop expressed in the following equation:
Voltage drop in wire = Circuit current x Resistance of wire
Power loss in wire = Circuit current x Voltage drop
P = Ix(IxR)
P=I17?R
Power Loss is equal to the components resistance times
the current squared. This power loss being converted into
heat, must be dissipated. A small wire diameter can safely
carry more current in proportion to its weight. The use of
copper wire is most preferred. Section 3.1.2.1 of the National
Electrical Code provides that:
“Conductor size and rating shall have sufficient ampacity
to carry load. They shall have adequate mechanical strength
and shall not be less than the rating of the branch circuit and
not less than the maximum load to be served.”
Conductors Ampacity is determined by the maximum
operating temperature that its insulation can withstand con-
tinuously without heating. Current flow and conductor’s resis-
tance normally generates heat. Thus, the Operating temperature
depends upon the amount of current flow, »
environment. Environment refers to either enclosed or open
condition on which the wire is placed
The Ampacity or ability of the conductor to carry lead
increases as the sizes of conductor increases. If more than 3
conductors are inserted into a conduit, the temperature als?
and it requires derating of
7 8 of the conductors ampacttY
as prescribed in Tables 2-5, 2 MGLOTS | SINE
increas
6 and 2-7CONDUCTORS AND WIRING ACCESSORIES
TABLE 2-5 ALLOWABLE AMPACITIES OF INSULATED COPPPER
CONDUCTORS NOT MORE THAN 3 WIRES IN RACEWAY
60°C
(140° F)
‘Temperature Ratings of ConductorABLE 2-7 TYPICAL AMBIENT TEMPERATURE
Minimum rating required
Location Temperature Conductor insulation
‘Well ventilated normally
heated building 30°C See note below
Building with such major
heat sources as power 40°C SG
stations or industrial
processes
Poorly ventilated spaces as°c
such as attics
Furnaces and boiler room | Min. 40° C 7c
Max. 60° C 90°C
Outdoor in shade in air 40°C eS
In thermal insulation 45°C fae
Direct solar exposure 45°C 7s°c
Place above 60°C 110°C
Note: 60°C up to No. 8 AWG copper wire and 75° C for bigger than No. 8
SOURCE: The National Electrical Code
Derating of Conductors Ampacity ~ mcans that, the full
amount of allowable ampacity, is reduced to a certain percent-
age due to the environmental condition it is exposed of and the
number of wires placed imside the conduit. The current rating
of wire in a free air environment is higher than those placed
inside the conduit. Concomitant with this, if the ambient tem
perature is above 30° C, the allowable ampacity will be fe
duced by the factors given in Table 2-6CONDUCTORS AND WIRING ACCESSORIES
2-4 Raceway
Raceways are channels or wiring accessories so designed
for holding wires, cables or busbars that are either made of
metal, plastic, or any insulating mediums.
The common types of raceways for houschold wirng
1, The conduits
2. The connectors and other accessories
TABLE 2-8 CHARACTERISTICS OF RACEWAYSNae ee 14 | b | 44 b | 56
3000 ey B27 bel Boe) ad
fo: |b. | 20 b | 20
14 | 17 | 28 17 | 68
4000 12 1s 24 15 s3
10} 11 | 20 | 1 | 41
S71 4a 77] 2
— +—
14 | 61 | 97 | 61 | 234
12 | 54 | 82 54 184
6000 10 | 38 | 6s | 38 | 141
8 27 | 41 27 27
Eo 6 | 20] 25 | 20 | 38
a8CONDUCTORS AND WIRING ACCESSORIES
Other Types of Raceways
Aside from the conduits and connectors, there are other
type of raceways such as
Conduit coupling, elbows and other fittings
Conduit supports, such as clamps, hanger, etc
Cable trays, cable bus, etc
Metal raceways
Nonmetal raceways and other
waunesists pass andthe ike
The Purpose of Electrical Conduits are:
1. To provide a means for the running wires from one
point to another.
To physically protect the wires.
To provide a grounded enclosure.
To protect the surroundings against the effect of fault
in the writing.
5. To protect the wiring system from damage by the
building and the occupants.
6. To protect the building and the occupants from
damage by the clectric system.
Connector
‘Connector is a metal sleeve usually made of coppeT that #§
slipped over and secured to the butted ends of conductors if
making a joint.
Connector is otherwise called splicing sleeveCONDUCTORS AND WIRING ACCESSORIES
750,000
32"
FIGURE 2-9
STANDARD SIZE OF CONDUIT FOR INSTALLATION OF WIRE CABLE
41fy 2 OC
ot 4 “o* Clamp
Malleable tron
re Manger rod
R.H, thread
& : - LH thread
paren Forged Steel Turnbuckle
1 Beam clamp
Side Beam Clamp
FIGURE 2-10 OTHER TYPES OF RACEWAYS
= QS «ap
Compression Type
Rain Tight Coupling
Compression Type
ain Tight Connection
2» = © «6
tome saiocssdien atl 8 09 Coup Inautated
Connector insisted
FIGURE 2-11 VARIOUS TYPES OF EMT CONNECTORS
42CONDUCTORS AND WIKING ACCESSORIES
7 in One Conduit (mm)
Gude! t 2 ¢ «¢ € € fie
TABLE 2-9 MAXIMUM NUMBI mn OV Wi
Number of Wir
IN A CONDULT
rr) 3s 8 #9 2 20 S) 2 ee
2 @ 19 90 $9 30 3S (aber cee
10 19 20 20 2 26° 26 Seb oak ee
8 1% 20 26 3 28 $8) a2 Dasa
6 0 © 82 88 Se 8. SO ee ee
s 20-92 (88 a ee ee
4 20 32 2 “6 650 60 % 50 os
3 20 #32 32 38 6606 60 |} OO Cee ae
2 20 320 (38 8 0s
1 20 38 38 8 8 Of & 75 78
° 2 98 6 © @ 68 7 75 75
00 2 60 O° On re es
000 28 80) 6600 O37 7S
e000 32 SO) 63} 75 7S 8 tO
. 20000 2 50 63 63 «76 7 88 8B 100
22500 32 68. 9 08S) hee
250000 32 63 63 7m 75 88
300000 32 63 7 75 «88 88
350000 32 63 «75 88 88 100 .
400000 32 75 75 88 100 100
e 450000 a ce} 7 88 6100 413
500000 38 7S ci] ge 100 «113
550000 3 = 88
‘600000 50 5 88
650000, SO 88 88
700000 so 88 8BA Convenience outlet or attachment cap is a device that
by insertion into a receptacle establishes connection between
the conductor of the flexible cord and the conductors
connected permanently to the receptacle.
@ oo 8)
ne normal Tepe 15 am Fa
2pole2wire one locking device — Sinale tvoe grounding: -
FIGURE 2-12 VARIOUS CONVENIENCE OUTLETr
CONDUCTORS AND WIRING ACCESSORIES
Wall Outlet. The common Wall Outlet is called
Convenience Outlet And to call it: wall plug is not correct &
plug is another name for the attachment cap on the wire
coming from a device such as lamps or appliancescal yy nc sir stiches ond fencdon
as outlets. This is an important thing to clarify specially
en payment is to be made from a contract based on the
number of outlets.
An Outlet on the other hand. refers only to the box itself It
does not include the items. The receptacle device is not an
electrical load but rather an extension of the box wiring. The
outlet is separate from the load device even if it is included as \
part of the device.
The Pull Box is a box with a blank cover that is inserted in
one or more runs or raceways to facilitate pulling-in the ;
conductors. It may also serve to distribute the conductors.
Receptacles are contact device installed at the outlet for
the connection of a single attachment plug. Receptacles are :
included in the general. classification of wiring devices. It
includes all receptacles and their matching cap (plug), wall
switches, small dimmers, and outlet box mounted lights
Receptacle is defined by the National Electrical Code as:
“4 contact device installed at the outlet for the connection
of a single attachment plug.”
Any number of receptacles mounted together in one oF
more coupled boxes is classified as ome outlet, The lower the
number of outlets the lower is the cost. A circuit with 6 duplex
receptacles individually mounted ts normally more than twice
the cost of the same 6 receptacles installed in two outlets group
of three gang each. Receptacles are descmbed and
according to the pole of wires
®CONDUCTORS AND WIRING ACCESSORIES
Mounting the Receptacles
1. A wall convenience receptacle is vertically mounted
between 30 to 45 centimeters above the finished floor
line.
2. In industrial areas, shops, workroom and the like, the
mounting height is from 105 to 110 centimeters. This
is above the table height horizontally mounted so that
the cords will not hang on top of each other.
3. The GFI or GFCI (ground fault circuit interceptor) re-
ceptacle should be installed on locations where sensi-
tivity to electric shock is high such as in wet areas.
Switch
A Switch is a device that open or closed the circuitry in an
electric circuit.
Special
actuator plate
‘Specification Grade
switches
19, 20 and 3G-ampere
Maintained contact
15 and 20
i ampere
bg ew (Double throw, center oft)
aTNNN jaaRas
RR_ZRN
RRS
The General use switch is intended for use in the general
distribution and branch circuit rated in amperes, It is capable
of interrupting the rated current at a rated voltage
The General use snap switch is a form of general use
switch installed in flush device boxes or an outlet box cover
The Isolating switch is a switch intended for isolating an
electric circuit from the source of power
48CHAPTER
THE BRANCH CIRCUIT
3-1 Introduction
Electric Circuit refers to the complete path traversed by
an electric current. In short, electric circuit is the entire house
wiring installation.
Branch Circuit is defined by the National Electrical Code
(NEC) as: “the circuit conductors between the final over cur-
rent protective device and the outlets.” Meaning, the branch
circuit is only the wiring installed between the circuit over cur-
rent protective device i.e. fuse or circuit breaker, and the out-
lets.
a ee
In practice however, it is a common knowledge that the
branch circuit comprises the following:
5 1. The source of voltage
2. The wiring and
3. The loadFlexibility of the Circuit means that the installation can
accommodate all probable pattern arrangements and location
of the loads for expansion, or future development.
Reliability and Efficiency of Service means to have a
continuous service and supply of power that are all dependent
on the wiring system.
Reliability of electric power in a facility is determined by
two factors:
1. The utility service
2. Building electric system
Safety means that independent service can be used in lieu
of emergency equipment as backup for normal services. For
reliability of the circuitry, the following principles should be
considered.
1. To provide double emergenc: 2 c
lected weak points inthe system. tupment St 8
2. That the electrical service and the building distribution
eee en eo oui so that the power can reach the
3. Critical loads within the facility must be pinpointed 1
determine the best way to serve them by providing a re
liable power either from the outside source, or bY
standby power packaye for them, i
50THE BRANCH CIRCUIT
4. The system design must readily detect any equipment
failure and to be corrected automatically
Der oe cir fates a ee
costs. These two cost-factors stand in inverse
one another. Over design is as bad as under design. i
The Effect of Acquiring Low Cost Equipment
1. High energy cost
2. Higher maintenance cost
3. Shorter life
Energy Consideration is a complex one considering the
following factors:
Energy laws and codes
Budget
Energy conservation technique
Energy control
eee
Space Allocation — must consider the following:
Easy maintenance
Ventilation
Expandability
Limitation of access
pee
Protective device
Generally 15, 20 amperes_as follows: -
General purpose branch circuit supplies
tacles.
Z pliance branch circuit supplies outlets intended
Ae feeding appliances. Fixed lighting however, is not
supplied.
Generally 20 amperes
FIGURE 3-3 APPLIANCE BRANCH CIRCUIT
3. Individual branch circuit is designed to supply a sin-
gle specific item.
‘Size required
for item fed
_
Single ttem
FIGURE 3.4 INDIVIDUAL BRANCH CIRCUITTHE BRANCH COU
3.2 Civcuiting Guidelines
There are many ways of doing the eireuitey but there is ne
optimum or perfect way of doing it, However, there are certain
miles and guidelines promulgated by the National Kheetrteal
Code (NEC) for flexibility, economical and convenient way of
installing a eirouitry
1 The Code requires sufficient circuitry to supply resin
dential load of 30 watts per square meter in buildings
excluding porches, garages and basements.
2. The requirement of 30 watts per square meter is up to
80 sq. m. for a 20 amperes circuit (2,400 watts) or 60
square meters for 15 amperes circuit (1,800 watts),
3. Good practice suggests that the load should not exceed
1,600 watts for a 20 amperes circuit and 1,200 watts
for a 15 amperes circuit. Thus
a) Observe a minimum load of 1,200 watts on a
15 amperes circuit with a maximum area of 40.
square meters.
b) A maximum load of 1,600 watts on a 20 am-
peres circuit with a maximum area of 53
square meters,
4. The Code requires a minimum of 20 amperes appli~
ance branch circuit to feed all small appliance outlets
in the kitchen, pantry, dining and family room, iss
The general purpose branch Se cre ciee ae ef
amperes circuit, wired with No. 1: being, th
minimum size of conductor wire required for all
venience outlet.
Circuit load on a
the values given"ELECTRICAL LAYOUT AND ESTIMATE
a) For 15 amp circuit: a5 Sues
b) For 20 amp circuit: ee 8 outlets
8. Convenience receptacles should be planned Properly,
so that in case of failure by any one of the circuitry,
the entire area will not be deprived of power supply. In
terms of reliability of service, each area should be pro-
vided alternately with different circuits.
9. All kitchen outlets should be fed from at least two of
these circuits.
10. The Code further stipulated that; “all receptacles are
potential appliance outlet and at least two circuits
‘shall be supplied to serve them.”
11. Certain outlets in the room shouid be designed as ap-
pliance outlet like:
a) All kitchen receptacles
b) Dining room receptacles
c) One in the living room
12. The Code requires that, “at least one 20 amperes cir-
cuit supply the laundry outlets.”
13. If air conditioner is anticipated, provide a separate cir-
cuit for this particular appliance
TABLE 3-1 BRANCH CIRCUIT CAPACITY - ELECTRIC HEAT
Maximum Watts
Circuit Breaker Size 120 volts 240 volts
45 amp. 1440 2880
20 amp. 1920 3840
30 amp. 2880 5760
54THE BRANCH Crmcurr
TABLE 3-7 BRANCH CIRCUIT REQUIREMENTS
16 amp | 20 amp | 30 w
Maximum size of conductor Not4 2
Minimum size taps No14 4
Over current device rating | 15 amp 20 %»
Lamp holders permitted Anytype| Any type] H.Outy | H.Duty
Receptacte rating permitted| 15 amp| 15-20 20 40-60 | 50
Maximum load 15amp| 20 30. 40. 50
Other Good Practices in Circuiting
1. Lighting and receptacles should not be combined in a
single circuit.
2. Avoid connecting all building ieee on a single cir-
cuit
3. Lighting and receptacles should be supplied with cur-
rent from at least two circuits so that, if a single line is
out, the entire area is not deprived of power.
4. Do not allow combination switch and receptacle out-
lets,
5. Provide at least one receptacle in the bathroom, and
one outside the house. Both must be Ground Fault Cir-
cuit Interrupter (GFCI) type.
Provide switch control for
switch is a nuisance.
Convenience outlet though counted as part of the gen-
eral lighting load shall be limited to 6 convenience
outlets on a 15. amperes cicant and Sfoonyeniensercut
lets on a 20 BDO circuit.
closet lights. Pull chainAs a Rule. branch circuit should be protected fro
current. Hens; an over all current protective devices
installed in all branch circuitries.
The function of the over-current protective devices
open the circuit (disconnect the line) when the current
capacity of the equipment being protected is exceeded.
circuit protective device represents the source of voltage. It,
always connected at its hot line end to the voltage source
jts load end to the circuit wiring. Apparently, it becomes
source of voltage.
The Panel Board where:n the over current protective
vice is a part, the busbars become the source of voltage as
look upstream from the over current devices. The Nation
Electrical Code also defines the branch circuit as “shat portit
of the circuit beyond the over current device. oa
Causes of Over Current
There are two principal causes of over current
1. Overload in the equipment or conductors
2. Short circuit or ground fault
Both were the results of excessive current flow in the
cuit. The primary function of the over-current devices #
protect the branch circuit and the load device against exce
current supply. However, regardless whether the excess
rent is being caused by an equipment problem of ove!
or by a circuit problem such as un-intentional ground fal
protective devices has but one purpose - to interrupt t
in case there is an excess current flow in the circuit.
_ When the over current protective devices senses
sive flow of current, it automatically open the circuit OF
56‘THE BRANCH CIRCUIT
cut off the line to prevent the excessive flow of current in cre-
ating damages to the circuit or to the equipment. The over cur-
rent device automatically opens the line to release the exces-
sive current. The action of the over current protective device is
called “Clearing” because it clears the circuit of the fault or
over current load. It therefore acts in the same manner as the
mechanical device to relieve the machine from excessive pres-
sure
The over current protective devices are installed in circuits
to protect the following:
The wiring
The transformer
The lights
Appliances and other equipments
Beye
On the Protection of Conductors, the National Electrical
Code provides that: “Conductors shall be protected against
over current in accordance with their ampacities.”
By definition, Over Current is any current in excess of
the rated capacity of the equipment or the rated ampacity of
the conductor. It was clear that both the equipment and the
wire installation shall be protected from the over current flow.
Electrical equipment has its own rated ampacity. Simi-
larly, electrical conductors have also their respective allowable
ampacity. Thus, any load in excess of their rated or allowable
ampacity, could damage the circuit or the equipment
Application of Over-current Protection is also Governed
by the Following Rules:
1. That the over-current protection devices should be in-
stalled on the line or supply side of the equipment be-
ing protected. :
2. The over-current protective devices shall be placed in
all underground conductors of the protected circuits.OUT AND ESTIMATE
ELECTRICAL LAY
3. All equipment should be protected. in accordance with
: ing capacity. 2
ifs current catryine Oe protective devices should be
-current ;
os ee caecubled and protected from physical dame
ages and away from easily ignited materials. ae
5. Conductors size should not be reduced in a circuit or
tap unless the smallest wire 1S protected by the circuit
over current devices.
Neo Taps may be made if smaller con-
ductor is protected by main feeder
protection (100 amp. circuit breaker
for No.2 wire)
100 amp.
No.2 RHW (115 amp.)
Taps up to 7 m. long is allowed if
tap conductors has minimum 1/3
ampacity of main and terminates
in a single circuit breaker or set of
1/3 capacity = 130 = 45 amp fuses which limits the current on
3 the tap to the wire capacity. 40 a.
fuse limits current on 45 amp
capacity wire.
7.5 m. Maximum
Taps up to 3 m. long are allowed
Provided they have suflicient capa
city for the circuit they feed, say
No. 10 RHW if the wiring feeds 2-15 amp. cil-
in conduit cuits, it must have 30 amp capa-
city and should be No. 10 AWG,
2-15 amp circuit RHW wire or equal rating.
3 m. maximum
Main feeder No.1/0 RHW Taps of any length may be made if
130 amp capacity conductor is protected at the tap
point by and approximately
fie TT overe
em Teurrent device.
Feeder
FIGURE 3-5 PERMISSIBLE TAP ARRANGEMENTS
5BTHE BRANCH CIRCUIT
3-4 Fuse, Breaker and Panel Board
Fuse is defined as; an over all current protective device
with a circuit opening fusible element which opens (break)
when there is an over current in the circuit.
‘The Fuse is a one time protective device to be replaced after
the fault is cleared. It is the simplest and most common type of
circuit protective device used in most house wiring installa-
tions. It is available in hundred design ratings and shapes but
basically, the same in functions
Generally, fuse consist of a fusible link or wire that easily
melt at low temperature classified into two types
1. The Cartridge type which is enclosed in an insulating
fiber tube and
2. The Plug Fuse type enclosed in a porcelain cap.
TABLE 3-3 FUSE RATING AND CONSTRUCTION
Current Ratings
0 to 10
15, 20, 25 to 30
mas. 150 v. to ground
0 to 10
35, 40, 45, 50 to 60
70, 80, 90,100, 110, 125, 150
175, 200, 225, 250, 300, 350
400, 450, 500, 600
800, 1000, 1200, 1600, 2000
2500, 3000, 4000, 5000, 6000
Circuit Breaker
The Circuit Breaker is an over-curn
designed to function as a switch. Basi:
Cartridge type with ferrules
single and dual element
250 and 600 volts
Cartridge type, knife blade
contacts: 250 and 600 volts
Cartridge type bolted
knife blade contacts; 600 volts
ent protective device
ically, a circuit breaker is
59i
equipped with an automatic tripping device to Protect tt
pranch circuit from overload and ground fault. Circuit breaker
can be manually tripped, so that, in many cases, it also acts ag _
circuit switch. 7
Trip or Tripping refers to the cutting-off or disconnection
of the current supply.
Advantages of Circuit Breaker Over the Fuse
1. The circuit breaker act as switch aside from its being an
over current protective device.
2. Unlike the fuse that has to be ciscarded after it was
busted due to an over current flow, the circuit breaker
trips off automatically and after correcting the fault, it is
again readily available for switch on.
(b) Single Element Knife
(a) Common Household Piug Blade Fuse
Thermal cutout element Ferule contact
Short circhit fuse link Knife blade contact
Dual element - time delay fuse with Edison base, ferrule contag®
and knife blade contacts respectively
FIGURE 3-5 STANDARD TYPE OF FUSE
Circuit breaker can be multiple pole installed with 12
3 poles which will simultaneously protect and ;THE BRANCH CIRCUIT
one to three lines. The fuse on the other hand, is a single
pole, installed on a single wire that could only protect a
single electric line.
The circuit breaker position is easier to detect. It could
be closed, tripped, or open right at the handle. On the
contrary, the busted fuse could not be detected easily be-
cause the melted fusible element is inside the fuse cas-
ing
The circuit breaker can be manually tripped so that in
many Cases, it also acts as the circuit switch
Conventisnat i caa Ger
breaker ie breaker
wired into wired toto
preree Dane! tox
l
1 fie
} (deer
1k
| fer
:
7A
f
fl Load nowe:
wire
leek)
Equipment toed
ground Coiled white oe
wire connects to wl
Neutral bus Pere! neutral
Equipment ground bus
All connections to the CBS circuit breaker are si
{0 those of conventional breakers except for the
addition of ¥ neutral connection.
FIGURE 3-7 BRANCH CIRCUIT PROTECTION |