TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 01, OUTGOING 01, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2604VC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 1T 1T 1T 800 G 860 G 830 G 1T 1T 1T
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 23 26 22
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 48.3 37.5 28.8
Y- Phase 47.7 37.7 27.9
B- Phase 48.2 37.6 28.5
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.8 169.6 22.7
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 28.3 V DC 26.5 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7. Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 01, OUTGOING 01, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd
Metering Prote. Acc.class of Acc.class of
Phase Ratio, Amps Serial No.
core VA core VA Mete. Core Protn. Core
R 300 / 1-1-1 1612403 15 15/VK 0.5 5P10 / PS
Y 300 / 1-1-1 1612404 15 15/VK 0.5 5P10 / PS
B 300 / 1-1-1 1612408 15 15/VK 0.5 5P10 / PS
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 Kv 57.G 64.G 107 G
Primary to Secondary (Core – 1), 5 kV 20 G 18 G 28 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 19 G 25 G 30 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
3.1.0 Ratio test on 300A
3.1.1 Metering core:
Injected primary Measured secondary Current measured
Phase Polarity Ratio
current, Amps current, Amps at meter, Amps
R 150 / 300 0.50 / 1.01 OK OK OK
Y 150 / 300 0.51 / 1.05 OK OK OK
B 150 / 300 0.50 / 0.99 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 0.49 / 1.02 OK OK OK
Y 150 / 300 0.50 / 0.99 OK OK OK
B 150 / 300 0.51 / 0.99 OK OK OK
3.1.3 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 0.51 / 1.01 OK OK OK
Y 150 / 300 0.50 / 1.02 OK OK OK
B 150 / 300 0.51 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2605VC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 958 G 868 G 930 G 830 G 810 G 841 G 789 G 808 G 768 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 29 27 28
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 43.2 36.2 25.6
Y- Phase 44.3 36.1 25.8
B- Phase 43.6 36.3 25.4
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 46.5 167.4 23.8
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 27.6 V DC 27.8 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7.0 Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
8.0 Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd
Metering Prote. Acc.class of Acc.class of
Phase Ratio, Amps Serial No.
core VA core VA Mete. Core Protn. Core
R 600-300 / 1-1 1612336 15 15 0.5 5P10
Y 600-300 / 1-1 1612337 15 15 0.5 5P10
B 600-300 / 1-1 1612338 15 15 0.5 5P10
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 Kv 65.G 68.G 75 G
Primary to Secondary (Core – 1), 5 Kv 26 G 22 G 28 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 29 G 26 G 27 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
3.1.0 Ratio test on 600/300A
3.1.1 Metering core:
Injected primary Measured secondary Current measured
Phase Polarity Ratio
current, Amps current, Amps at meter, Amps
R 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.03 OK OK OK
Y 150 / 300 / 450 / 600 0.26 / 0.51 / 0.76 / 1.01 OK OK OK
B 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.02 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 / 450 / 600 0.25 / 0.49 / 0.76 / 1.01 OK OK OK
Y 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.00 OK OK OK
B 150 / 300 / 450 / 600 0.25 / 0.49 / 0.76 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF POTENTIAL TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1.0 Name Plate details of potential transformer :
Make of PT: Crompton Greaves ltd
Phase Ratio, Volts Serial No.
R 33000/√3/110/√3/110/√3 16/018962
Y 33000/√3/110/√3/110/√3 16/018970
B 33000/√3/110/√3/110/√3 16/018969
CT core no. VA CLASS
CORE-1 (METERING) 100 0.5
CORE-2 (PROTECTION) 100 3P
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 kV 70 G 83 G 67 G
Primary to Secondary (Core – 1), 5 kV 35 G 40 G 30 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 31 G 38 G 29 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
Injected primary Measured Metering Measured Protection
Phase Polarity Ratio
voltage, Volts voltage, P-P Volts voltage, P-N Volts
RY 419 1.41 0.809 OK OK
YB 420 1.43 0.810 OK OK
BR 419 1.41 0.808 OK OK
3.1 Metering core: 1
Injected primary Measured Metering Measured Protection
Phase Polarity Ratio
voltage, Volts voltage, P-P Volts voltage, P-N Volts
RY 419 1.43 0.808 OK OK
YB 420 1.42 0.809 OK OK
BR 419 1.43 0.807 OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for voltmeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 03, BUS COUPLER, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2606VC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 1T 1T 1T 1T 1T 1T 1T 1T 1T
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 26 24 25
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 39.6 31.8 23.8
Y- Phase 39.5 31.6 24.2
B- Phase 39.7 31.5 23.7
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 43.5 168.2 24.3
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 28.3 V DC 27.2 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7. Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 04, TRUNKING CHAMBER, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2606AVC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 752 G 762 G 787 G 668 G 687 G 678 G 708 G 723 G 713 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 32 34 31
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 39.5 34.5 27.8
Y- Phase 39.7 34.3 27.6
B- Phase 39.6 34.2 27.9
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.5 166.8 24.5
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 28.1 V DC 26.3 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7. Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2607VC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 983 G 976 G 965 G 832 G 851 G 822 G 786 G 768 G 776 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 29 27 30
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 49.8 39.8 28.7
Y- Phase 49.5 39.4 28.6
B- Phase 49.7 39.6 28.7
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 45.6 167.8 21.9
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 26.4 V DC 24.3 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7. Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd
Metering Prote. Acc.class of Acc.class of
Phase Ratio, Amps Serial No.
core VA core VA Mete. Core Protn. Core
R 600-300 / 1-1 1612339 15 15 0.5 5P10
Y 600-300 / 1-1 1612334 15 15 0.5 5P10
B 600-300 / 1-1 1612335 15 15 0.5 5P10
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 Kv 54.G 62.G 56 G
Primary to Secondary (Core – 1), 5 Kv 26 G 24 G 27 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 30 G 28 G 31 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
3.1.0 Ratio test on 600/300A
3.1.1 Metering core:
Injected primary Measured secondary Current measured
Phase Polarity Ratio
current, Amps current, Amps at meter, Amps
R 150 / 300 / 450 / 600 0.24 / 0.51 / 0.74 / 1.00 OK OK OK
Y 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.03 OK OK OK
B 150 / 300 / 450 / 600 0.24 / 0.49 / 0.74 / 1.01 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.01 OK OK OK
Y 150 / 300 / 450 / 600 0.25 / 0.50 / 0.74 / 0.99 OK OK OK
B 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF POTENTIAL TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1.0 Name Plate details of potential transformer :
Make of PT: Crompton Greaves ltd
Phase Ratio, Volts Serial No.
R 33000/√3/110/√3/110/√3 16/018971
Y 33000/√3/110/√3/110/√3 16/018973
B 33000/√3/110/√3/110/√3 16/018974
CT core no. VA CLASS
CORE-1 (METERING) 100 0.5
CORE-2 (PROTECTION) 100 3P
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 kV 65 G 76 G 96 G
Primary to Secondary (Core – 1), 5 kV 43 G 46 G 48 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 34 G 36 G 35 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
Injected primary Measured Metering Measured Protection
Phase Polarity Ratio
voltage, Volts voltage, P-P Volts voltage, P-N Volts
RY 419 1.42 0.810 OK OK
YB 420 1.41 0.813 OK OK
BR 419 1.43 0.811 OK OK
3.1 Metering core: 1
Injected primary Measured Metering Measured Protection
Phase Polarity Ratio
voltage, Volts voltage, P-P Volts voltage, P-N Volts
RY 419 1.40 0.812 OK OK
YB 420 1.42 0.811 OK OK
BR 419 1.41 0.812 OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for voltmeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 06, OUT GOING 02, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2608VC
1.3 Breaker Type : VCB
1.4 Rated Voltage : 33 KV
1.5 Rated Current : 1250 A
1.6 Closing Coil : 110 V DC
1.7 Tripping Coil : 110 V DC
1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation
Resistance Close Condition Open Condition
Test.
Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B
Ohms, Ω 869 G 875 G 863 G 786 G 768 G 765 G 806 G 814 G 803 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 27 26 28
4. Time Interval Test.
Phase Closing Time, Ms Opening Time, mS C/O Time, mS
R- Phase 46.2 38.4 29.4
Y- Phase 46.8 37.3 28.7
B- Phase 46.5 37.5 29.5
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.3 168.2 23.7
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil
Voltage 28.6 V DC 26.8 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark
1 Manual Charging of Spring OK
2 Mechanical closing and tripping OK
3 Mechanical interlocks of breaker OK
4 Charging of spring through motor OK
5 Electrical interlocks of breaker OK
6 Tripping through relays OK
Breaker close command blocking when Relays/releases is in operated
7 OK
condition
8 Abnormality, if any NONE
7. Maintenance and General Check- up.
Sr. No. Description Remark
1 Inspection for physical damage OK
2 Cleaning and tightness of breaker bolts OK
3 Breaker rack-in and rack-out OK
4 Alignment of breaker OK
5 Earthling connection OK
6 Abnormality, if any NONE
Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH
Location PANEL: - 06, OUT GOING 02, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd
Metering Prote. Acc.class of Acc.class of
Phase Ratio, Amps Serial No.
core VA core VA Mete. Core Protn. Core
R 300 / 1-1-1 1612406 15 15/VK 0.5 5P10 / PS
Y 300 / 1-1-1 1612405 15 15/VK 0.5 5P10 / PS
B 300 / 1-1-1 1612407 15 15/VK 0.5 5P10 / PS
2.0 Insulation Resistance test :
Values in Ω
Insulation resistance test between
R Y B
Primary to Earth, 5 Kv 68.G 62.G 67 G
Primary to Secondary (Core – 1), 5 kV 29 G 31 G 27 G
Secondary (Core – 1) to Earth, 500 V 1G 1G 1G
Primary to Secondary (Core – 2), 5 kV 32 G 30 G 33 G
Secondary (Core – 2) to Earth, 500 V 1G 1G 1G
Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G
3.0 Ratio, polarity and circuit checks :
3.1.0 Ratio test on 300A
3.1.1 Metering core:
Injected primary Measured secondary Current measured
Phase Polarity Ratio
current, Amps current, Amps at meter, Amps
R 150 / 300 0.49 / 0.99 OK OK OK
Y 150 / 300 0.50 / 1.01 OK OK OK
B 150 / 300 0.51 / 1.02 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 0.52 / 1.02 OK OK OK
Y 150 / 300 0.51 / 1.04 OK OK OK
B 150 / 300 0.52 / 0.99 OK OK OK
3.1.3 Protection core:
Injected primary Measured secondary
Phase Relay operation Polarity Ratio
current, Amps current, Amps
R 150 / 300 0.49 / 0.99 OK OK OK
Y 150 / 300 0.51 / 1.01 OK OK OK
B 150 / 300 0.50 / 0.99 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks
4.1 Inspection for physical damage OK
4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE