Hydrostatic Test Procedure
Prepared By
Approved by Accepted By
Name Hohewed $. TDeoranin Heute Wiad Dry
Position act acu i
AZ
cia bala ee LP,
Date 1/07/2019 1707/2019 off6712019S Hydrostatic Test [imcau fo
NEW AQUA Procedure ae —
Index
4. Scope
2. References:
3. Pressure Gauges
4, Test Medium
5. Filling with Test Medium and Venting
6. Holding Time and Close Examination
7. Release of Pressure
8, Report
9. Attachments= Hydrostatic Test [mn 2°"
NEW AQUA Procedure i ag
1.0 SCOPE
20
3.0
40
This procedure is applicable to Boilers, Boiler Extemal Piping and pressure Vessels
constructed to ASME Code Sec. 1, Vill, Div. 1 . Italso applies to Code items
Repairs and Alterations in accordance with the National Board Inspection Code
(NBIC),
This procedure describes the method used for Hydrostatic Test of Code items
manufactured by New Aqua.
‘The hydrostatic test shall be conducted by MM and witnessed by QCM and Al
References
ASME Code Sec. |
‘ASME Code Sec. Vill, Div. 1
‘ASME Code B31.1
National Board Inspection Code
Incase of any conflicts between client specification and Code requirements , the
Code requirements shall govern.
Pressure Gauges
‘At least one calibrated pressure gauge shall be directly connected to the Code item
being tested at the highest point, and shall be visible to the operator controlling the
test.
The pressure gauge shall have a range of about double the test pressure, but shall
not be less than 1 % for boiler & boiler external piping for pressure vessel the
pressure gage range will be between 1% to 4 times the test pressures.
‘An additional calibrated pressure gauge may be fitted at a suitable location visible
to the operator controlling the pressure at all time. If nor fitted at the highest point,
then the test pressure shall be accordingly corrected for the static head difference.
Al gages shall be calibrated against a standard dead - weight tester or a calibrated
master gage. Gages shall be recalibrated at any time that there is reason to believe
that they are in error
Test Medium
The test medium shall normally be potable water for carbon and low alloy steel
Code items.
For high alloy steel, such as austenitic stainless steels, demineralized water shall
be used.Procedure No. HD-001
= Hydrostatic Test fasion 0
NewAQUA | Procedure Es ae
5.0 _ Filling with Test Medium and Venting
‘Test medium shall be supplied to the Code item being tested through a connection
at the lowest point. The filling connection shall be fitted with a suitable valve.
‘Nozzies or other openings at the top of item being tested shall be left open during
filling to allow for proper and complete venting of air.
‘When the item being tested is completely filled with the test medium, all openings
shall be closed, not fully secured tightened while pumping is in progress to ensure
‘complete venting, and then secularly tightened.
‘The pressure is then raised gradually uni the specified test pressure is reached
Then all valves are securely tightened.
The test pressure shall be at least the test pressure required by the applicable Code
‘section and as specified on the Approved for Construction drawing, but shall not
exceed the limits detailed in Table 1
The test medium temperature shall not be less than tha started in Table 2.
6.0 Holding Time and Close Examination
The test pressure shall be maintained for at least 10 minutes, and then reduced
gradually to the close examination pressure as stated in Table No. 3
Close visual examination of all joints and connections shail then be carried out for
any signs of leakage and/or deformation.
The metal temperature during the close examination shall not exceed that stated in
Table No. 2.
7.0 Release of Pressure
Upon completion of the test, the pressure shall be released by opening the valve at
the highest connection and allowing the pressure to drop gradually to atmospheric
pressure. The item being tested shall then be drained through a connection at the
bottom, while leaving sufficient opening at top open.
8.0 Report
‘The result of test will be recorded on the attached Hydrostatic Test Form.Fi Procedwe No, HO-001
S Hydrostatic Test — [poison :0
NEW AQUA Procedure ee ea
rest Pressure for New Pressure Vessel & Piping System
[Code Hydrostatic Pneumatic
[ASME Section "5X MAWP Not Permitied
Boiler —Heating ASME Section IV 4.5X MAWP_ Not Permitted
Pressure Vessel | ASME Seoton VI Tox mae 1.XMAWP
TaxDesign
Power Piping ‘ASME Section 831.1 | 1.5X>Design Pressure | 5 2XDesk
T.2xDesign|
Process Piping _| ASME Section B 31.3. | 1.5X Design Pressure | 2XDesk
Table (2): Maximum and minimum metal temperatures during Hydrostatic Test
‘Applicable Code | Minimum test metal temperature
‘Maximum metal
Section temperature during
close examination
‘ASME Code sec. 1 | The temp.of used water notless | 120°F (49°C)
than the ambient temp. but in no
case less than70°F (20°C)*
‘ASME Code sec. __| 63°F (17°C) above MDMT 20°F (49°C)
Vill, Div. 4
National board For Boilers & BEP as for Sec. |, 120°F (49°C)
inspection Code —_| above.
For pressure vessels 60°F (16°C).
Unless notch toughness properties
permit lower temperatures
* no part of boll shal be subject to a ganeral membrane stress greatr than 90% of the yield srenath
Table (3): Pressure during close examination
Applicable Code Section
Close examination pressure
Remarks
‘ASME Code sec. |
Pressure equal to MAWP
‘ASME Code sec. Vill, Div. 1
‘Test pressure divided by 1.3
National board inspection
Code (NBIC)
Pressure equal to MAWP, when test
pressure is in excess of MAWP,
otherwise test pressure.
9.0 Attachments: HDR-form001=
NEW AQUA Rev.:
DATE:
Report no.:
PROJECT
CLIENT
JOB. NO.
SERIAL NO.
DWG. NO.
PROCEDURE NO.
SERIAL NO.
MANUFACTURER,
RANGE
DUE DATE OF CALIBRATION
CERTIFICATE NO.
TEST Position
TEST MEDIUM
TEST TEMP.
METAL TEMP.
WATER TEMP.
TEST PRESSURE
HOLDING TIME
DATE OF TEST
Quality Control Inspector :
Authorized Inspector :
HDR-form0o1