Get in Step With Synchronization
Get in Step With Synchronization
Daniel L. Ransom, PE
                                                            Senior Member IEEE
                                                           Basler Electric Company
                                                            12570 S tate Route 143
                                                        Highland, Illinois 62249 US A
                                                         danielransom@basler.com
          ABSTRACT-This paper presents a review of power                  connecting together two power systems. At first it was
          system synchronization. When two sources are                     considered too complex; it was too difficult to match the
          paralleled, it is crucial to close the interconnecting circuit   frequency of two ac (alternating current) power systems
          breaker when both sources are in voltage, frequency,             so that these systems could be paralleled to share
          and phase coincidence.                                           growing loads. During the War of Currents George
            Operators can synchronize manually, or use the latest,         Westinghouse and Thomas Edison became adversaries,
          state-of-the-art autosynchronizers (ANSI/IEEE device             with Edison promoting direct current (dc) and
          25A) [1] and sync-check relays (ANSI/IEEE device 25) to          Westinghouse endorsing alternating current (ac) as the
          automate closing.                                                standard for electric-power distribution.
          Generator and bus synchronization share most                        Three-phase ac power distribution "won" the war
          principles, with some important differences for each type        because of the ease of converting one ac voltage level
          of synchronization. For generation plants, closing               to another to distribute electric power. However, the
          manually or applying an automatic synchronizer                   problem of paralleling ac systems was more difficult with
          depends a lot on the plant configuration and operating           ac than with dc. In dc systems only the amplitude needs
          mode. For bus-line applications, synchronizing depends           to be matched. However, in ac systems the magnitude,
          on power-system stiffness, motor loads, and whether a            frequency, and angle of the two systems must be
          wye-delta transformer is between the line and bus.               matched to connect the power systems (from different
          Methods for attaining proper synch-check and fast                generator sources) in parallel with minimal system
          synchronization are discussed.                                   disturbance.
                                                                              Early attempts at paralleling power-system sources
          Index terms-synchronization, sync check, synchronizer,           were aided by Nicola Tesla's work on three-phase ac
          closing, protective relays, voltage, frequency, phase            power systems. Rudimentary investigation showed the
                                                                           possibility of paralleling sources. Soon it was apparent
                                                                           that sources must match in voltage amplitude,
                             I.         INTRODUCTION                       frequency, and especially in phase angle, to eliminate
                                                                           disturbances in the power system upon paralleling.
            Synchronization is the process of matching the
          voltage, frequency, and phase angle of a source (a
          generator) to an existing power system, making it                           III.    CONSIDERATIONS FOR
          possible to operate these systems in parallel. When
          paralleled, the synchronized power systems can                                        SYNCHRONIZATION
          exchange power and load flows. Sources must have                   Certain conditions must be met to reach
          (nearly) identical voltage magnitude, frequency, and             synchronization, where two ac systems can be
          phase-angle relationships to parallel two systems safely.        connected with no harm to both systems and to the
          Proper synchronization provides the following outcomes:          connected loads. The oncoming source must match
               •   Minimum disturbance to the two paralleled               these power-system quantities to those of the existing
                   systems                                                 system:
               •   Minimum shock to an oncoming generator                      •    Phase sequence
                   (mechanical and electrical)                                 •    Voltage amplitude
               •   Equipment lasts longer; saving money                        •   Frequency
               •   Rapid loading of the oncoming generator                     •    Phase angle
                   provides power to loads quickly
            When two segments of a grid are disconnected, these
          segments cannot exchange power and load again until
          the systems are brought back into synchronization.                  A.    Phase Sequence
                                                                 402
of the oncoming generator need to be matched to the
                                                                    Existing -....,---- A
existing source.
                                                                  Source (Bus)_-+ .,....
                                                                                    ____ B        ____
                                                         403
generator source. The supervisory sync-check relay (25)       switching, one of the generators can pick up the dead
compares the voltage difference, slip frequency, and          bus and start the synchronizing process for the
phase-angle (slip) differences between the oncoming           remaining generators. An anticipatory synchronizer is
generator and the station bus. These parameters and           best for this application (see subsection below).
some typical ranges are listed in Table 1. (Caution:            As the prime mover brings the oncoming generator to
some relays use an actual-difference-voltage setting,         speed, the generator voltage is applied to the
and some relays use a percentage-voltage-difference           synchronizer. Fig. 4 shows a typical synchronizer block
setting.) The supervisory 25 relay does not allow a circuit   diagram. When the generator input voltage reaches a
breaker close until all of these parameters are satisfied.    minimum threshold, the synchronizer begins to sense
                                                              both the oncoming generator and the existing bus for
        Table 1. Typical Sync-Check Parameters                voltage, frequency and phase angle. The order of
Parameter                     Typical Value                   operation is the following:
                                                                   •    Compare voltages
Voltage Difference            4-8 V (secondary)                    •    Compare frequency
Phase (Slip) Angle            0°-30°                               •    Change voltage to match bus
                                                                   •    Change frequency to match bus
Slip Frequency                0.10 Hz                              •    Compare phase angle
                                                                   •    Issue a close command to the intertie circuit
  The sync-check relay output contacts are in series                    breaker (52)
with the operator control switch. Circuit breaker closing
occurs only when the operator manually closes the
                                                                 Main Bus
switch, and the supervisory relay contacts are closed.
Fig. 3 shows the timing of the operator-commanded
close and the sync-check-relay close as the voltage                                         Bus
phasor approaches 0 degrees.                                                                Sensing
                                o·
                                                                                                      25A
                                                                                                  Synchronizer
                                                                                        t----I 52a/b
                                                                              52
                                                                                        )----1 Out
                                                                                         Close
                                      Phasor
                                     Rotation
   c.    Automatic Synchronization
                                                                                              Frequency
                                                                          Prime-Mover         Correction
  Manual and assisted-manual paralleling schemes
                                                                            Governor
have a shortcoming. These methods require skilled
operators at the controls to adjust voltage and frequency
to avoid costly damage to equipment caused by
                                                                    Fig. 4 Synchronizer Connection Diagram
improper       synchronization.       With      automatic
synchronization, the automatic synchronizer (25A)
monitors voltage, frequency, and phase angle. The                When first applied, the synchronizer senses a large
synchronizer outputs correction signals to a generator        difference between the sources for voltage and
governor to achieve voltage matching and frequency            frequency. The synchronizer begins to output corrective
matching, and provides the circuit-breaker-close output       amplitude voltage signals and corrective frequency
contact.                                                      signals to the oncoming generator to match it with the
  Because of the importance of restoring electrical           bus. The process occurs recursively until the oncoming
power following an emergency outage, a dedicated              generator is synchronized with the bus and the
automatic synchronizer should be used for each                synchronizer commands the intertie circuit breaker to
generator, allowing the generators to parallel to each        close.
other and to the main bus as quickly as possible. If the         The circuit breaker cannot close instantaneously. To
automatic synchronizing equipment includes dead-bus           achieve circuit-breaker closure exactly at zero degrees,
                                                              the synchronizer must initiate the breaker-close signal in
                                                        404
advance. The circuit-breaker blades close at minimal
phase difference. [3]                                               V.      THE AUTOMATIC SYNCHRONIZING
  The autosynchronizer gives the close command while                                       PROCESS
the slip-frequency rate is moving slowly, approaching the
zero-degree phase angle. The synchronizer calculates              In the automatic synchronizing process the generator
the advance angle, issuing the close command early to          starts, and the synchronizer starts as the generator
compensate for circuit-breaker-closing time. This              comes up to speed. As the generator accelerates and
capability minimizes system transients by closing at zero      approaches the system frequency, the synchronizer
degrees (at "midnight" on a clock face).                       commands governor controls for raising and lowering
  The anticipatory autosynchronizer compensates for            voltage and frequency.
the actual breaker closing time plus the output-relay             The raise and lower outputs can be set to continuous
contact-travel time (the time for moving the armature of       mode or proportional mode. Continuous mode turns the
the physical output relay [6 to 8 ms]). The synchronizer       required logic output on until it is in the synchronization
"anticipates" the actual point of synchronism.                 window or overshoots it. Proportional mode toggles the
  The anticipatory synchronizer calculates the advanced        voltage and frequency outputs based upon the
angle (AA) that is required to compensate for the circuit     calculated error, and on the respective pulse-width and
breaker closing time by monitoring the slip-frequency          pulse-interval settings. [4]
rate and the preset slip-rate value for breaker closing. It       The voltage monitoring portion of the automatic
also adds the constant of the physical relay contact           synchronizer adjusts the voltage regulator to bring the
movement time to complete the calculation. The                 generator terminal voltage within the synchronization
mathematical relationship is the following:                    window. Next, the phase-monitoring circuitry calculates
        AA=360 (TcB+TR) Fs                            (1)      the advance angle required to close the circuit breaker at
   Where:                                                      a zero-degree phase difference based on the actual slip
  AA is the advance angle, which is the electrical phase       frequency and on the (preset) circuit-breaker-closing
      angle of the generator with respect to the system        time.
      bus when the synchronizer initiates a close                Fig. 5 illustrates the relationship among slip frequency,
      command                                                  circuit-breaker-closing time, and the advance angle
  T CB is the circuit-breaker close time. This is the time     required prior to closing the circuit breaker at zero
      between the initial application of the close             degrees.
      command and the actual contact of the circuit
      breaker poles
  TR is the response time of the output relay (6-8 ms)         ADVANCE
  Fs is the slip frequency                                     ANGLE
                                                                     30·1---+---+-��;.L-, ""--I�=-----4
   Reducing the advance angle AA also reduces the
absolute value of the slip frequency FS (which is the
maximum permissible speed difference for which a
generator is allowed to close onto the bus). Lesser slip             20·1---+-----,l.��, �t---+---�
frequencies produce less system disturbance and
machine damage (known as "softer").
   Larger slip frequencies allow synchronization to be               10·1--�¥-.,.c.-+_-
accomplished faster, but there is more system
disturbance ("harder"). These considerations should be
weighed:
     •   How fast must the generator be on line?                                0.1      0.2       0.3      0.4      0.5
     •   How critical is the generator?                                        CIRCUIT BREAKER CLOSING TIME (SECONDS)
     •   How expensive is the repairing/replacing the
                                                                         Fig. 5 Sync-Check Closing Quantities
         generator versus the cost of possible outage
         (down) times?
   A proper synchronizer application accounts for these           A sync-check relay (25) should be used with the
considerations, as well as others that are unique to the       automatic synchronizer (25A) to safeguard the generator
system.                                                        circuit breaker from closing out of phase; see Fig. 5. The
                                                               sync-relay does not allow closing if there is a problem
                                                               with the synchronization point provided by the automatic
                                                               synchronizer. [5]
                                                         405
  DC BUS +                                                       auxiliary transformer changes phase connection and
                             s=    Interlocks
                                                                 voltage level. With some sync-check relays this might be
                                                                 necessary when the pt inputs are separated by a
                                                                 wye/delta transformer, as shown at PSEC. Again, a
  Enable 43M    i                          i      Enable 43A
                            $
                                                                 modern, numeric relay can offer phase and voltage
                                                                 matching for this situation.
Manual Close                                      25A Close
                T                           T                       Today, many generators are impedance grounded to
                                   - - - - ---'
                                                                 limit damage caused by ground faults. Connecting the
                               �
                 L..----t- 25Sync             Check              pts from phase to ground gives an unreliable voltage
                                                                 level to the sync-check relay because the neutral is
                                                                 offset by the grounding impedance. Phase-to-phase pts
  DC BUS-                                                        should be used for sync-check inputs instead of phase
                                                                 to-ground signals.[61
                                                                    A fast sync-check function makes possible critical
  Fig. 5 Supervise Autosynchronizer (25A) with Sync
                                                                 applications such as motor-bus transfers. Modern,
                     Check (25)
                                                                 numeric relays have response time less than one power
                                                                 system cycle. [71
               VI.      ApPLICATIONS
  Applications for a sync-check relay (25) and an                    B.   Synchronizer Applications
automatic synchronizer (25A) are straightforward.
However, experience in the field shows that these                   Applying an autosynchronizer depends on the plant
applications have circumstances that should be                   and on the operation mode. A standby system requires
considered.                                                      that the generators are at speed and are closed online
                                                                 quickly. Some applications will tolerate a hard sync in
                                                                 exchange for a fast close (little down time). However, a
   A.    Sync-Check Applications                                 prime power plant with natural gas generators and/or
                                                                 heat recovery will require a longer time to come online.
  The basic sync-check (25) application is shown in                 In the past an anticipatory automatic synchronizer was
Figure 6. A potential transformer (pt) P on the system           expensive to apply to a number of machines on a
bus provides bus data to the sync relay. The pt at X             dedicated, one-to-one basis. A sequencing circuit was
provides the line-voltage data on the generator side of          used to switch the anticipatory synchronizer from one
the circuit breaker. The sync-check relay (25) monitors          generator to another. Sequencing a synchronizer adds
these potentials when comparing sources for                      time to system restoration, as well as complexity to the
synchronism check.                                               overall control circuitry.
  Main Bus                                                          Today, a dedicated autosynchronizer (25A) is not
                                                                 expensive. By applying a modern protective relay with a
                                                                 built-in synchronizer on a per-machine basis the need for
                                                                 sequencing         logic     is      eliminated.     Each
                                                                 synchronizer/governor/generator combination (together
                                                                 with the voltage-regulating equipment) can be optimized
                                                                 for performance and synchronizing speed.
                          25
                                             Transformer
                         Sync
                                             (if needed)            C.     Breaker-Failure Protection
                        Check
                                                                    A flashover can occur when a source is synchronizing
                                                                 to an existing power system. As the source voltage on
                                                                 one side of the circuit breaker slips past the bus voltage
        Fig. 6 Typical Sync-Check Connections                    on the other side of the circuit breaker, there are points
                                                                 where the voltage is 180 degrees out of phase. It is at
                                                                 this point that the voltage difference across the circuit
   It is important to have the same pt connections, or use       breaker is twice nominal. A destructive flashover can
a method to adjust the relay sync-check inputs. If there         strike if the circuit breaker is not rated suffiCiently, or is
is a phase-to-phase connected pt at P, then the pt at X          compromised (there might be a mechanical failure such
should be a phase-to-phase connection as well. Some              as an insulating gas leak).
modern, numeric (digital) relays offer phase matching as            A flashover can damage a generator and the
well as voltage matching. Another benefit of modern              connected generator step-up (GSU) transformer.[81 This
relays is the enhanced isolation between the sync-check          situation calls for breaker-failure protection (50BF) to trip
input circuits.                                                  the surrounding breakers to remove the flashover.
   If phase matching and voltage matching are not                (Because it is arcing, there is no reason to issue a trip to
available in the sync-check relay, then an interposing           the already open generator circuit breaker.)
                                                           406
                                                             [5]    Hartmann, G.; "Automatic Synchronizing for
                                                                   Generation and Tie Lines," Western Protective
               VII.     CONCLUSIONS                                Relay Conference (WPRC), Oct. 1991
                                                             [6]   Thompson, M.J., "Fundamentals and advancements
   Power-system operation is improved by applying a
                                                                   in generator synchronizing systems," Protective
thorough understanding of synchronized closing and
          .                                                        Relay Engineers, 2012 65th Annual Conference
synchron!zat!on. Proper application of the many
                                                                   TAMU, vol., no., pp.203,214, 2-5 April 2012
synchronization methods helps to prevent expensive
                                                                   doi: 10.1109/CPRE.2012.6201234
outages and equipment damage.
                                                             [7]   Ransom, D.L.; Chelmecki, C., "Using GOOSE
   M�dern sync-check relays (25) match voltage
                                                                   messages in a main-tie-main scheme," Industry
amplitude, frequency, and instantaneous phase angle.
                                                                   Applications Society Annual Meeting (lAS), 2012
Fast sync check makes possible critical main-tie-main
                                                                 IEEE , vol., no., pp.1,8, 7-11 Oct. 2012
applications (such as fast motor bus transfer).
                                                                 doi: 10.1109/IAS.2012.6374119
   Oncoming generators support power-system loads
                                                             [8] Wieck, H.; Gutman, I.; Ohnstad, T., "Investigation of
faster and with less connection disturbance when
                                                                 Flashover      Performance       of    Snow-Covered
pr�perly synchronized. These results are achieved by
                                                                 Breakers," Dielectrics and Electrical Insulation, IEEE
uSing an anticipatory, automatic synchronizer (25A). This
                                                                 Transactions on,       vo1.14, no.6, pp.1339,1346,
synchronizer issues the close command in advance of
                                                                 December                                          2007
the precise synchronization point, adjusting for the
                                                                 doi: 10.1109ITDEI.2007.4401216
circuit-breaker delay, for contact-closure delay ' and for
varying slip frequency.
   Use phase-to-phase pt connections on high                                      IX.     VITA
impedance-grounded power systems.
   Contingencies should be considered for a failed sync        Daniel (Dan) Ransom, P.E., has 40 years of industrial
close attempt. Apply circuit-breaker-failure protection      and utility electronics experience, including many years
(50BF) when needed to prevent flashover.                     In motor-protection development and application
                                                             support. He has been a consulting engineer for power
                                                             system protection and for communications systems. Dan
               VIII.     REFERENCES                          IS an electrical engineering graduate (BSEE) of Gonzaga
                                                             University, Spokane, Washington, USA; he also holds a
                                                             liberal arts degree from Washington State University in
[1]  G. ANSI/IEEE C37.90, Standard for Relays and
                                                             Pullman, WA. He is a Senior Member of the IEEE ' with
     Relay Systems Associated with Electric Power
                                                             membership in the lAS (Industry Applications), PES
     Apparatus, IEEE, 2005
                                                             (Power Engineering), Communications societies and he
[2] Jonnes, J., "Empires of Light," Random House, 2003,
                                                             is a voting member of the SA (Standards Ass�ciation).
     ISBN-10: 0375507396
                                                             To date, he has one US patent. He is a Professional
[3] Horak ' J., "Introduction to Synchronizing," Basler
           .                                                 Electrical Engineer in numerous USA states. Dan joined
     Electnc
                                                             Bas�er Electri� in 2010 and is Principal Application
     Technical Resource Library, 2005
                                                             Engineer. He IS the application engineer for the West
[4] Beckwith,      T.;      "Automatic    Synchronizing
                 .                                           region     of    the   United    States   and   Canada.
     ConSiderations and Methods," Western Protective
     Relay Conference (WPRC), Oct. 1985
407