108   CONTROL LOOP FOUNDATION: BATCH AND CONTINUOUS PROCESSES
General Symbol
                         Ball Valve
                         Globe Valve
                         Damper
            Figure 7-12. Excerpt from ISA-5.1 Valve Body and Damper Symbols
      When a positioner is used with a valve, the diaphragm representation may
      be combined with a representation of the actuator and the valve body, as
      is illustrated in Figures 7-16 to 7-19. The failure mode of the valve (i.e., fail
      open or fail closed) is often indicated by the valve symbol in control sys-
      tem documentation.
      A special actuator symbol is defined by the standard for motorized actua-
      tors. Motorized actuators are used in some industry segments because
      upon loss of power, the last valve position is maintained. Also, better reso-
      lution may be achieved using a motorized actuator for a specific applica-
      tion, such as the basis weight valve that is used to regulate the thick stock
      flow to a paper machine in paper manufacturing. [6] Solenoid actuators
      that are used to automate valves used in on-off service are shown using a
      special symbol.
      Installation details are provided in the loop diagram documentation.
      Some of details may also be provided in the P&ID. For example, the P&ID
      and loop diagram may show the orifice that must be installed to measure
      flow using a differential pressure transmitter. Hand-operated valves that
      are used to block flow during startup or maintenance are shown since they
      impact process operation if not properly set up. Also, the installation of
      inline instrumentation, such as a magnetic flowmeter, is commonly shown
      in a unique manner in the control system documentation. In addition,
      measurement elements such as an RTD or a thermocouple are shown since
      they may be physically installed some distance from the field transmitter
      or the control system. To provide a consistent means of documenting the
      physical installation, the ISA-5.1 standard includes symbols for many of
      these common installation details and field devices. A sample of some of
      these symbols is shown in Figure 7-14.
                      CHAPTER 7 – CONTROL AND FIELD INSTRUMENTATION DOCUMENTATION   109
                           Generic actuator,
                            Spring-diaphragm
                           Spring-diaphragm with
                            positioner
                           Linear piston actuator
                            with positioner
                           Rotary motor operated                M
                            actuator
                           Solenoid actuator for                S
                            on-off valve
                  Figure 7-13. Excerpt from ISA-5.1 Actuator Symbols
        Restriction Orifice, With
           Flow Transmitter                                                  FT
        Hand Valve
                                                   FT
        Inline Measurement
        Measurement Element                              TE
              Figure 7-14. Excerpt from ISA-5.1 Symbols for Other Devices
7.7   Equipment Representation
      A representation of major pieces of process equipment is normally
      included in control system documentation. This allows the field instru-
      mentation installation to be shown in relationship to the process equip-
      ment. Example process equipment representations are illustrated in
      Figure 7-15.
      A general vessel representation may be appropriate for vessels, agitators,
      heat exchangers, and pumps that do not play an important role in the con-
      trol system. For example, an agitator on a tank may not directly impact the
      control associated with the tank level. A special representation is provided
110   CONTROL LOOP FOUNDATION: BATCH AND CONTINUOUS PROCESSES
         Vessel, Jacketed Vessel,
         Reactor
         Atmospheric Tank, Storage
         Heat Exchange
         Agitator
         Pump
                   Figure 7-15. Examples of Process Equipment Symbols
      for a reactor. A jacketed vessel symbol may be used when a vessel is
      heated or cooled by circulating liquid through an outside shell. Such a
      design is commonly used in the batch industry, and permits the vessel’s
      contents to be heated or cooled without coming in contact with the circu-
      lating liquid. A symbol is also provided for flat-bottomed and cone-
      shaped storage tanks that are open to the atmosphere. The examples
      include a representation of a heat exchanger, which is used to heat or cool
      a liquid stream. A symbol is defined for an agitator that may be used to
      ensure good mixing of liquids in a vessel. Also, a pump symbol is shown
      in these examples.
7.8   Documentation Examples
      The four examples included in this section are designed to illustrate many
      of the recommendations of the ISA-5.1 standard. In the first example,
      questions and answers are used to highlight specific points that have been
      covered in this chapter. A review of these questions will hopefully serve to
      reinforce your understanding of concepts and terminology that will be
      used in later chapters. By studying the control system and field instru-
      mentation documentation, a lot can be learned about the process and the
      way the control system is designed to work. Such background information
      can be extremely helpful when you are working with or troubleshooting
      the control system for a new process.
      7.8.1 Example – Basic Neutralizer Control System
      The neutralizer process may be used to adjust the pH of a feed stream. The
      field devices and process controls that would typically be provided to this
                               CHAPTER 7 – CONTROL AND FIELD INSTRUMENTATION DOCUMENTATION          111
  process are shown in this piping and instrumentation diagram illustrated
  in Figure 7-16.
  After reviewing this diagram, consider the following questions and
  answers.
                                                            Feedforward   AC     FT          FC
                                                                          104    105         105
             Reagent                               Signal
             Stage 1     FT                        Characterizer
                         102         AC      AY
                                     103     103
                                                                                FC            Reagent
                      FC                                                                      Stage 2
                                                                                       FV
FC                             AV                                                      105
101                            103
                   FV
                   101                       AT
FT                                           103
101                        Static Mixer
             FC
      Feed
                                                           Neutralizer
                                                                                              FV
                                                                          AT                  106
                                                                          104
                                                                           Discharge    FC
              Figure 7-16. Example – Basic Neutralizer Control System
                  Question: What tag number convention is shown in this
                  example?
                  Answer: The expanded tag number convention, defined by
                  the ISA-5.1 standard, is not used in this example since the
                  tag only contains function letters and a loop number.
                  Question: Flow measurements are made using FT101,
                  FT102, and FT105. What type of measurement technique is
                  used by these field devices?
                  Answer: The field device is shown as installed inline and
                  the liquid is conductive. Thus, a magnetic flowmeter is
                  installed.
                  Question: Do the valves have digital positioners?
                  Answer: Yes, an electric signal is shown going directly to a
                  box located on each valve. The pneumatic line from the
112   CONTROL LOOP FOUNDATION: BATCH AND CONTINUOUS PROCESSES
              actuator is also tied to this box. Therefore, we can assume
              that these valves are installed with a valve positioner.
              Question: What type of valve is being used to regulate
              flow?
              Answer: The general valve body symbol is used and thus
              the type of valve is not indicated in this drawing.
              Question: Is the plant operator able to access the control
              functions indicated by AC103, AC104, FC101, and FC105?
              Answer: Yes, the circle indicating these control functions
              contains a horizontal line that indicates the operator may
              access this function.
              Question: Can the operator access flow measurements
              FT101, FT102, and FT105, as well as analytic (pH) measure-
              ments AT103 and AT104?
              Answer: No, the circle indicating these measurement func-
              tions does not include a horizontal line. In this case, these
              measurements are not directly accessed by the operator.
              Question: Are any on-off (blocking) valves used in this
              process?
              Answer: Yes, two blocking valves are shown with electric
              on-off actuators.
              Question: What function is provided by AC103?
              Answer: The function letters of the tag number indicate
              that the function is analytic control.
              Question: What measurement is used by AC103 in per-
              forming its control function?
              Answer: Since an electric signal line is shown from AT103
              to AC103, then control must be based on the measurement
              AT103 (pH).
              Question: What is the purpose of the function shown
              between AT103 and AC103, that is, AY103?
              Answer: On the diagram, this function is noted as Signal
              Characterization. When a complex calculation is done, it is
              often represented by a single function with AY noted inside
              the circle and a note provided to explain the purpose of this
              function.
                CHAPTER 7 – CONTROL AND FIELD INSTRUMENTATION DOCUMENTATION   113
       Question: Does the vessel have an agitator?
       Answer: Yes, the figure shows an agitator impeller in the
       vessel, powered by a motor on top of the vessel.
       Question: Is the pump fixed speed or variable speed?
       Answer: Since control of the process is done using a regu-
       lating valve, then it may be assumed that the pump is fixed
       speed.
       Question: How could the liquid in the vessel be heated?
       Answer: A heat exchanger is shown in the recirculation line
       and could be used to heat (or cool) the liquid in the vessel.
       Question: How is the pH of the incoming stream adjusted?
       Answer: The output of AC103 and AC104 go to a valve and
       flow loop, respectively, that regulates the flow of reagent to
       the inlet stream and recirculation line. Thus, it may be
       assumed that reagent is used to adjust pH.
7.8.2 Example – Basic Column Control
The basic column control system shown in Figure 7-17 is somewhat more
complicated than the basic neutralizer control system. However, after
studying this example, it will become clear that many of the components
that make up the column control system are similar to those used in the
basic neutralizer control system. As we have seen, what is learned by
working with one process may be often applied to another process. Once
you become familiar with a few processes, it becomes easier to work with
other processes.
7.8.3 Example – Batch Reactor Control System
Batch processing plays an important role in some industries. In a batch
process, a vessel is charged with feed material that is processed in the ves-
sel through mechanical or chemical means (or both). At the end of the pro-
cess, the product—which may be a finished product or an intermediate
product for use in another process—is removed from the vessel. The batch
reactor example illustrated in Figure 7-18 is known as “continuous feed
batch,” in which feed material is continuously added to the vessel
throughout part or all of the batch processing. The reaction takes place,
and finally the product is pumped from the vessel. In comparing the basic
components to those seen in the previous two examples, the only new ele-
ment introduced by this example is an eductor (a device that produces
vacuum by means of the Venturi effect) that is used to remove gases cre-
ated by the batch reaction.
114   CONTROL LOOP FOUNDATION: BATCH AND CONTINUOUS PROCESSES
                                                                                                                   PV
                                                            PC                                                     115
                                                            115
                                                                                                            FO         Vent
                                                     Feedforward         LC
                                             FT111                                                   LT
                 Feed Tank                                               117                         117
                                                                                     Distillate                    FC
                                                                         FC                                        118
                                                                                     Receiver
                                                                         114
                                                        FV                                                                               FV
                                     PT                 114                                                                              118
                                     115                                 FT                                        FT
                                                        Reflux FO        114                                       118
                                                                                                                                    FC
                  FC                                                                                              Overheads
                  111
                                    FV                                FT111     Feedforward
                                    111
                  FT
                                                            RTD
                                              Column        TT
                  111                Feed                                                TC
                               FC
                                                            116                          116
                                                                                                                         Storage Tank
           FC                                                LC
           110                                               113
                         FV
                         110                                                   FC
           FT                                                                  112
                                                             LT
           110                                               113                                     FV
                  FC     Steam                                                                       112
                                                                               FT
                                                                   Bottoms     112
                                                                                           FC
                               Figure 7-17. Basic Column Control System
                                                                                                            PC
                                                                                                            128
                                                     TC                                                                             FO
                                                     126                                 PV                 PT
                                                                                         127                           PV
                                                                                                            128
                  FC                          TT                                                                       128
                  122                         126                                              Vent System
                                                                                FO
                                                                                                                              Eductor
                                    FV                             TV
                                    122                            126
                  FT
                  122                                                    PC
                               FC                           FO
                                Anti-Foam                  Coolant       127       TC
                                                                                   124
                  FC
                                                                         PT
                  121                                                                          TT
                                    FV                                   127
                                                                                               125
                                    121
                  FT                                                                                       TC
                  121          FC                                                                          125
                                    Feed B
                   FC                                                              TT                                    TV
                   120                                                             124                                   125
                                    FV
                                    120                                                                                  Coolant
                                                                                                                  FO
                  FT
                  120          FC    Feed A                                  LT
                                                     Batch Reactor                                         LC
                                                                             123                           123
                                                                                                                          LV
                                                                                                                          123
                                                                                                Discharge          FC
          Figure 7-18
                          Figure 7-18. Example – Batch Reactor Control
                   CHAPTER 7 – CONTROL AND FIELD INSTRUMENTATION DOCUMENTATION                  115
7.8.4 Example – Continuous Feed and Recycle Tank
In studying the example of a continuous feed and recycle tank shown in
Figure 7-19, you will note that the only new function that was not con-
tained in a previous example is FFC133. The function letters of the tag
number indicate that this new function is ratio control. The line connec-
tions indicate that the ratio control is implemented using two feed streams
to Reactor 1.
           FC
           135
                            FV
                            135
           FT                                          Recycle
           135
                      FC
          Makeup                       Recycle Tank
                                                             FC
    LC                     LT                                133
    134                    134                                                 FV
                                                                               133
                                                             FT
                                                             133         FC         Reactor 1
                                                                  FC
                                                                  132
                                                      FFC                           FV
                                                      133                           132
                                                PC                FT
                                                130               132
          Feed Tank                                                          FC Reactor 1
                                  FO
                                                            FC
                                          PV                131
                                          130   PT                            FV
                                                130                           131
                                                            FT
                                                            131
                                                                        FC    Reactor 2
          Figure 7-19. Example – Continuous Feed and Recycle Tank
Knowing the tag number and symbols on a P&ID is the first step in under-
standing which measurement and control functions have been installed on
the process. As the examples shown in Figure 7-16 to 7-19 illustrate, a
basic understanding of the control and process is possible if you are famil-
iar with the tag number and symbols on the P&ID. Later chapters on con-
trol implementation will address how the control functions shown on the
P&ID and loops sheet are implemented.
116   CONTROL LOOP FOUNDATION: BATCH AND CONTINUOUS PROCESSES
References
      1.      The International Society of Automation (ISA). http://
              www.isa.org.
      2.      International Electrotechnical Commission (IEC). http://
              www.iec.ch.
      3.      OSHA Standard 29 CFR 1910.119, Process safety management of
              highly hazardous chemicals. http://www.osha.gov.
      4.      ISA-5.4-1991, Instrument Loop Diagrams, Research Triangle Park,
              NC: ISA (ISBN 1-55617-227-3).
      5.      Skousen, Philip. Valve Handbook – Second Edition, Chapter 1.5.1,
              McGraw-Hill Handbook (ISBN: 0071437738).
      6.      Lehtinen, Marjaana. More speed and accuracy for basis weight
              control, pp. 22–24, Automation 1, 2004.