Thickness of Rockwool Insulation
Thickness of Rockwool Insulation
OF ROCKWOOL
INSULATION
In accordance with BS5422:2009
THE THICKNESS OF ROCKWOOL INSULATION THE THICKNESS OF ROCKWOOL INSULATION
ROCKWOOL stone wool does not thermally age and therefore the thicknesses
shown can be relied upon to provide the required insulation performance for the
lifetime of the host structure.
Alu-zinc 0.18
NOTE 1 The above values provide a useful guide to surface emissivity. However, it should be noted that the
emissivity of a material varies with temperature and surface finishes. Therefore, the precise emissivity should
be ascertained where a high degree of accuracy is required.
It is a dimensionless number between 0 (for a perfect reflector) and 1 (for a perfect Minimum insulation thickness for chilled and cold water steel pipes to control
emitter). The emissivity of a surface depends not only on the material but also on 6 condensation on a high emissivity outer surface (0.9) with an ambient temperature of 9
the nature of the surface. For example, a clean and polished metal surface will have +25°C and a relative humidity of 80%
a low emissivity, whereas a roughened and oxidised metal surface will have a high Minimum insulation thickness for chilled and cold water copper pipes to control
emissivity. The emissivity also depends on the temperature of the surface. 7 condensation on a high emissivity outer surface (0.9) with an ambient temperature of 10
+25°C and a relative humidity of 80%
Knowledge of surface emissivity is important for accurate heat transfer calculations.
Minimum insulation thickness for chilled and cold water steel pipes to control
So what does this mean to me? 8 condensation on a low emissivity outer surface (0.05) with an ambient temperature of 11
Low emissivity surfaces (e.g. aluminium, stainless steel etc.) produce a higher +25°C and a relative humidity of 80%
surface temperature but lower heat loss than high emissivity surfaces (e.g. painted
steel, cloth etc.) when compared at the same operating conditions and insulation Minimum insulation thickness for chilled and cold water copper pipes to control
thickness. 9 condensation on a low emissivity outer surface (0.05) with an ambient temperature of 12
+25°C and a relative humidity of 80%
Consider a 169 mm O.D. hot water pipe running at 75°C with an ambient
temperature of 15°C insulated with 50 mm thick RockLap H&V Pipe Section: Indicative thickness of insulation for cooled and chilled water systems to control heat
10 13
gain – Low emissivity outer surfaces
Based on ambient temperature 20°C (still air), horizontal pipe.
Indicative thickness of insulation for cooled and chilled water systems to control heat
11 14
gain – High emissivity outer surfaces
Other surface
Material Emissivity (ε) temp (oC) Heat loss (W/m) Minimum insulation thickness for condensation control on ductwork carrying chilled air
12 15
in ambient conditions: indoor still air temperature
Aluminium 0.05 28.8 25
13 +25°C, relative humidity 80%, dewpoint temperature 21.3°C 16
Cloth 0.90 24.0 27
14 Indicative thickness of insulation for ductwork carrying warm air to control heat loss 17
For personnel protection applications, high emissivity claddings are best.
Indicative thickness of insulation for chilled and dual-purpose ducting to control heat
15 18
For heat conservation, low emissivity claddings are best. transfer
Indicative thickness of insulation for non-domestic heating services to control heat loss
16 19
– Low emissivity outer surfaces
Indicative thickness of insulation for non-domestic heating services to control heat loss
17 20
– High emissivity outer surfaces
Indicative thickness of insulation for non-domestic hot water service areas to control
18 21
heat loss – Low emissivity outer surfaces
Indicative thickness of insulation for non-domestic hot water service areas to control
19 22
heat loss – High emissivity outer surfaces
Indicative thickness of insulation for domestic heating and hot water systems having
20 23
low emissivity outer surfaces
Minimum insulation thickness to protect steel pipes against freezing under selected 76 12 25 16 25 20 25
28 33
industrial process conditions 89 12 25 16 25 21 25
Minimum insulation thickness required to give protection against freezing – Selected 102 12 25 17 25 21 25
29 34
commercial and institutional conditions
114 12 25 17 25 22 25
Minimum insulation thickness to protect against freezing – Selected domestic cold
30 35 140 13 25 18 25 23 25
water systems (12 hour period)
Minimum insulation thickness to protect against freezing – Selected domestic cold 169 13 25 18 25 24 25
31 36
water systems (8 hour period) 219 13 25 19 25 24 25
245 14 25 19 25 24 25
If the design/operating conditions of your particular application/scheme does not
273 14 25 19 25 24 25
correspond to those detailed in the tables, please contact ROCKWOOL Technical
Solutions for calculations to meet your specific design criteria. 324 14 25 20 25 25 25
356 14 30 20 30 25 30
406 14 30 20 30 26 30
456 14 40 20 40 26 40
508 15 40 20 40 26 40
558 15 40 21 40 26 40
610 15 40 21 40 27 40
NOTE 1
Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where
the ambient air temperature is greater than 25ºC and/or the relative humidity
exceeds 80%, these thicknesses will not be sufficient to control condensation.
NOTE 2
These thicknesses only apply where the vapour barrier has a dark, matt finish.
NOTE 1
Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where
the ambient air temperature is greater than 25ºC and/or the relative humidity
exceeds 80%, these thicknesses will not be sufficient to control condensation.
NOTE 1
Insulation thicknesses in this table have been calculated according to BS EN ISO
12241:2008 using standardised assumptions: horizontal pipe in still air at 25ºC,
emissivity of outer surface of insulated system as specified.
NOTE 2
Thicknesses derived solely against the criteria noted in this table may not
necessarily satisfy other design requirements such as control of condensation.
NOTE 3
Heat gain relates to the specified thickness and temperature.
Minimum 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint)
139.7 29 30 8.52 36 40 9.49 43 45 10.45
temperature inside Calculated Advised Calculated Advised Calculated Advised
168.3 29 30 9.89 37 40 10.97 44 45 11.86 duct (ºC) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm)
219.1 29 30 12.27 37 40 13.57 45 45 14.61 15 26 30 14 25 9 25
273.0 30 30 14.74 37 40 16.28 45 45 17.48 10 47 50 24 25 15 25
5 67 70 34 40 22 25
NOTE 1
0 86 90 44 50 28 30
Insulation thicknesses in this table have been calculated according to BS EN ISO
12241:2008 using standardised assumptions: horizontal pipe in still air at 25ºC,
emissivity of outer surface of insulated system as specified. NOTE 1
Thicknesses given are calculated in accordance with BS EN ISO 12241:2008 based
NOTE 2 on 0.6m vertical flat surface of rectangular duct but are also adequate for horizontal
Thicknesses derived solely against the criteria noted in this table may not surfaces.
necessarily satisfy other design requirements such as control of condensation.
NOTE 2
NOTE 3 Thicknesses given are calculated specifically against the criteria noted in the table
Heat gain relates to the specified thickness and temperature. These thicknesses may not satisfy other design requirements.
NOTE 3
Refer to Annex B, Table B. 1 for surface emissivities of common finishing materials.
In situations where the ambient air temperature is greater than 25ºC and/or the
relative humidity exceeds 80%, these thicknesses will not be sufficient to control
condensation.
Table 13 – Ductwrap
Table 14 – Ductwrap
External surface emissivity External surface emissivity
Minimum thickness of ROCKWOOL Ductwrap (mm) Minimum thickness of ROCKWOOL Ductwrap (mm)
0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint)
Max Heat Loss Calculated Advised Calculated Advised Calculated Advised Max Heat Loss Calculated Advised Calculated Advised Calculated Advised
(W/m²) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm) (W/m²) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm) thickness (mm)
16.34 31 40 37 40 39 40 6.45 50 50 58 60 61 70
NOTE 1 NOTE 1
Heat loss relates to the specified thickness and temperature. Heat loss relates to the specified thickness and temperature.
NOTE 2 NOTE 2
Insulation thicknesses in this table have been calculated according to BS EN ISO Insulation thicknesses in this table have been calculated according to BS EN ISO
12241:2008 using standardised assumptions: horizontal duct at 35°C, with 600 mm 12241:2008 using standardised assumptions: horizontal duct at 13ºC, with 600 mm
vertical sidewall in still air at 15°C, emissivity of outer surface of insulated system as vertical sidewall in still air at 25ºC, emissivity of outer surface of insulated system as
specified. specified.
NOTE 1 NOTE 1
Insulation thicknesses in this table have been calculated according to Insulation thicknesses in this table have been calculated according to
BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at
15°C, emissivity of outer surface of insulated system as specified. 15°C, emissivity of outer surface of insulated system as specified.
NOTE 2 NOTE 2
Heat loss relates to the specified thickness and temperature. Heat loss relates to the specified thickness and temperature.
NOTE 3 NOTE 3
The thicknesses in this table are applicable to pipes serving commercial solar hot The thicknesses in this table are applicable to pipes serving commercial solar hot
water panels. water panels.
Outside diameter of steel Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm) Outside diameter of steel Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
pipe on which insulation pipe on which insulation
thickness has been based thickness has been based
(mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m) (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
17.2 23 25 6.60 17.2 27 30 6.60
21.3 25 25 7.13 21.3 29 30 7.13
26.9 27 30 7.83 26.9 32 35 7.83
33.7 29 30 8.62 33.7 33 35 8.62
42.4 30 30 9.72 42.4 35 35 9.72
48.3 32 35 10.21 48.3 37 40 10.21
60.3 33 35 11.57 60.3 35 35 11.57
76.1 35 35 13.09 76.1 43 45 13.09
88.9 35 35 14.58 88.9 43 45 14.58
114.3 38 40 17.20 114.3 44 45 17.20
139.7 39 40 19.65 139.7 45 45 19.65
168.3 40 40 22.31 168.3 46 50 22.31
219.1 40 40 27.52 219.1 47 50 27.52
273.0 41 45 32.40 273.0 48 50 32.40
NOTE 1 NOTE 1
Insulation thicknesses in this table have been calculated according to Insulation thicknesses in this table have been calculated according to
BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60°C in BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60°C in
still air at 15°C, emissivity of outer surface of insulated system as specified. still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 2 NOTE 2
Heat loss relates to the specified thickness and temperature. Heat loss relates to the specified thickness and temperature.
Outside diameter of copper Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm) Outside diameter of copper Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
pipe on which insulation pipe on which insulation
thickness has been based thickness has been based
(mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m) (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
8.0 - - 7.06 8.0 - - 7.06
10.0 - - 7.23 10.0 - - 7.23
12.0 - - 7.35 12.0 - - 7.35
15.0 - - 7.89 15.0 - - 7.89
22.0 15 20 9.12 22.0 19 20 9.12
28.0 17 20 10.07 28.0 21 25 10.07
35.0 18 20 11.08 35.0 22 25 11.08
42.0 19 20 12.19 42.0 24 25 12.19
54.0 20 20 14.12 54.0 25 25 14.12
NOTE 1 NOTE 1
Insulation thicknesses in this table have been calculated according to Insulation thicknesses in this table have been calculated according to
BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60°C in BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60°C in
still air at 15°C, emissivity of outer surface of insulated system as specified. still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 2 NOTE 2
Heat loss relates to the specified thickness and temperature. Heat loss relates to the specified thickness and temperature.
NOTE 3 NOTE 3
This table is applicable to pipes serving solar hot water panels. This table is applicable to pipes serving solar hot water panels.
NOTE 1 NOTE 4
Insulation thicknesses in this table have been calculated according to The thermal conductivity of insulation materials increases with mean NOTE 1
BS EN ISO 12241:2008 using standardised assumptions: horizontal temperature and for any given material. The use of a different thermal Thicknesses given are calculated specifically against the criteria noted in the table,
pipe in still air at 20°C. Surface emissivity corresponding to outer conductivity can be required for each operating temperature. Adopting these thicknesses may not necessarily satisfy other design requirements.
surface specified.
NOTE 5 NOTE 2
NOTE 2 These thicknesses may not satisfy other design requirements, in To simplify the use of this table the values shaded have been adjusted to avoid the
Maximum heat loss values for intermediate operating temperatures particular those for control of surface temperature (see Table 22, specification of apparently anomalous results given by the calculation method in
may be deduced by interpolation. Table 23 and Table 24). BS EN ISO 12241, due to the transition from turbulent to laminar flow.
NOTE 3 NOTE 6
Heat loss measured in Watts per metre (W/m) relates to the specified To simplify the use of this table the values shaded have been
thickness and temperature. adjusted to avoid the specification of apparently anomalous results
given by the calculation method in BS EN ISO 12241, due to the
transition from turbulent to laminar flow.
NOTE 1 NOTE 1
Thicknesses given are calculated specifically against the criteria noted in the table, Thicknesses given are calculated specifically against the criteria noted in the table,
Adopting these thicknesses may not necessarily satisfy other design requirements. Adopting these thicknesses may not necessarily satisfy other design requirements.
NOTE 2 NOTE 2
To simplify the use of this table the values shaded have been adjusted to avoid the To simplify the use of this table the values shaded have been adjusted to avoid the
specification of apparently anomalous results given by the calculation method in specification of apparently anomalous results given by the calculation method in BS
BS EN ISO 12241, due to the transition from turbulent to laminar flow. EN ISO 12241, due to the transition from turbulent to laminar flow.
Operating temperature (ºC) Initial temperature: +5ºC Minimum Initial temperature: +5ºC Minimum
ambient air temperature: -10ºC ambient air temperature: -10ºC
Outside diameter of 50 100 150 200 Evaluation period: 12 hours Permitted Evaluation period: 12 hours Permitted
copper pipe (mm) Heat loss (W/m pipes, W/m² flat) ice formation nil ice formation 10%
12.0 15 52 99 158 Thickness of ROCKWOOL RockLap H&V Pipe Section (mm)
15.0 18 63 120 191
Outside diameter Inside diameter of Calculated thickness Advised thickness Calculated thickness Advised thickness
17.2 21 70 135 215 of steel pipe (mm) pipe (bore) (mm) (mm) (mm) (mm) (mm)
21.3 25 84 162 258 21.3 16.0 - - - -
22.0 25 87 166 265 26.9 21.6 - - - -
26.9 30 103 197 315 33.7 27.2 - - 251 -
28.0 31 106 204 326 42.4 35.9 - - 89 90
33.7 36 124 239 383 48.3 41.8 452 - 59 60
42.0 44 150 289 464 60.3 53.0 173 - 34 35
42.4 44 151 292 468 76.1 68.8 87 90 23 25
48.3 50 169 326 524 88.9 80.8 62 70 19 20
54.0 55 186 359 578 114.3 105.3 40 40 13 25
60.3 60 205 395 636 168.3 158.6 23 25 9 25
67.0 66 224 433 698 219.1 207.9 17 25 6 25
76.1 73 250 484 781
80.0 77 261 505 816 NOTE 1
88.9 84 286 554 895 Thicknesses given are calculated specifically against the criteria noted in the table
These thicknesses may not satisfy other design requirements.
101.6 94 321 623 1007
NOTE 2
108.0 99 339 657 1063 Some of the insulation thicknesses given are too large to be applied in practice but
114.3 104 356 691 1118 a selection is included to highlight the difficulty in protecting small diameter pipes
against freezing. To provide the appropriate degree of frost protection to certain
139.7 124 424 824 1336 sizes of pipes, it may be necessary to provide additional heat to the system, for
168.3 146 499 971 1577 example by circulating the water or heat tracing.
Operating conditions:
Initial temperature: +2ºC Minimum Initial temperature: +2ºC Minimum Normal installation inside the building Extreme installation - inside the
ambient air temperature: -6ºC (indoor ambient air temperature: -10ºC inside the envelope of the insulation building but outside the envelope of
unheated) Evaluation period: 12 hours (outdoor) Evaluation period: 12 hours Initial temperature +7ºC Minimum the insulation Initial temperature +2ºC
Permitted ice formation 50% Permitted ice formation 50% ambient air temperature -6ºC Minimum ambient air temperature -6ºC
Outside diameter Inside diameter of Evaluation period 12 hours Permitted Evaluation period 12 hours Permitted
Thickness of ROCKWOOL RockLap H&V Pipe Section (mm) ice formation 50% ice formation 50%
of pipe (mm) pipe (bore) (mm)
Calculated thickness Advised thickness Calculated thickness Advised thickness Outside diameter Inside diameter of
Thickness of ROCKWOOL RockLap H&V Pipe Section (mm)
Copper pipes (mm) (mm) (mm) (mm) of pipe (mm) pipe (bore) (mm)
Calculated thickness Advised thickness Calculated thickness Advised thickness
15.0 13.6 66 - 315 - Copper pipes (mm) (mm) (mm) (mm)
22.0 20.2 19 20 47 50
15.0 13.6 49 - 66 -
28.0 26.2 12 20 24 25
22.0 20.2 17 20 19 20
35.0 32.6 9 20 16 20
28.0 26.2 11 20 12 25
42.0 39.6 7 20 12 20
35.0 32.6 8 20 9 20
54.0 51.6 5 20 8 20
42.0 39.6 6 20 7 20
76.1 73.1 4 25 6 25
54.0 51.6 5 20 5 20
108.0 105.0 3 25 4 25
76.1 73.1 3 25 4 25
Calculated thickness Advised thickness Calculated thickness Advised thickness
Steel pipes (mm) (mm) (mm) (mm)
108.0 105.0 2 25 3 25
Calculated thickness Advised thickness Calculated thickness Advised thickness
21.3 16.0 40 40 142 - Steel pipes (mm) (mm) (mm) (mm)
26.9 21.6 19 20 43 45
21.3 16.0 32 40 40 40
33.7 27.2 13 20 25 25
26.9 21.6 16 20 19 20
42.4 35.9 8 20 15 20
33.7 27.2 11 20 13 20
48.3 41.8 7 20 12 20
42.4 35.9 7 20 8 20
60.3 53.0 5 20 9 20
48.3 41.8 6 20 7 20
76.1 68.8 4 25 6 25
60.3 53.0 5 20 5 20
88.9 80.0 3 25 5 25
76.1 68.8 4 25 4 20
88.9 80.0 3 25 3 25
NOTE 1
Thicknesses given are calculated specifically against the criteria noted in the table
These thicknesses may not satisfy other design requirements. NOTE 1
Thicknesses given are calculated specifically against the criteria noted in the table
NOTE 2 These thicknesses may not satisfy other design requirements.
Some of the insulation thicknesses given are too large to be applied in practice but
a selection is included to highlight the difficulty in protecting small diameter pipes NOTE 2
against freezing. To provide the appropriate degree of frost protection to certain Some of the insulation thicknesses given are too large to be applied in practice but
sizes of pipes, it may be necessary to provide additional heat to the system, for a selection is included to highlight the difficulty in protecting small diameter pipes
example by circulating the water or heat tracing. against freezing. To provide the appropriate degree of frost protection to certain
sizes of pipes, it may be necessary to provide additional heat to the system, for
NOTE 3 example by circulating the water or heat tracing.
Assumed densities (ƿ) and heat capacities (cp) are as follows:
NOTE 3
• ƿ water = 1,000 kg/m³, cp water = 4,200 J/kg.K; Assumed densities (ƿ) and heat capacities (cp) are as follows:
• ƿ steel = 7,840 kg/m³, cp steel = 455 J/kg.K • ƿ water = 1,000 kg/m³, cp water = 4,200 J/kg.K;
Interested?
For further information, contact the Technical Solutions Team on 01656 868490
or email technical.solutions@rockwool.co.uk
Visit www.rockwool.co.uk to view our complete range of products and services.
Copyright ROCKWOOL February 2018.
ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY
Tel: 01656 862 621
info@rockwool.co.uk
rockwool.co.uk