User Manual: Wlm2 Wlta WLTD WLTP Wlct2
User Manual: Wlm2 Wlta WLTD WLTP Wlct2
User Manual
www.oj.dk
CONGRATULATIONS
BR-0965-A10
2
CONTENT
QUICKGUIDES
Quick guide analogue room sensors .............................................................. 4
Quick guide WLCT2 programmable Room controllers ................................... 4
Quick guide for Master modules ..................................................................... 5
Trouble shooting ............................................................................................. 6
INSTRUCTIONS
Master with Display Type WLM2 .................................................................. 7
Introduction ..................................................................................................... 7
Supply Water Temperature Control ................................................................. 9
Using outdoor compensation module for weather compensation .................. 9
Service Menu................................................................................................. 11
3
QUICKGUIDES
QUICK GUIDE ANALOGUE ROOM SENSORS
1 These room sensors have an adjustment knob, which enables you to increase or decrease the room
temperature setting by up to 4˚C.
2 room sensors type WLTM-19 and WLTD-19 have a slide switch for selecting the mode of operation of the
room sensor. Four different modes can be selected: Auto, Day, Night and OFF
TA TD TM
Auto: Roomsensor will follow the temperature settings of the master, or if the room sensor
belongs to an area controlled by a WLCT2 room controller, it will follow the automatic sequence
of temperatures and timings set in the WLCT2.
Day: It will control the room temperature according to the (DAY) setting defined in the master
(typically 20˚C).
Night: It will control the room temperature according to the (NIGHT) setting defined in the
master (typically 15˚C).
OFF: It will control the room temperature according to the (OFF) setting defined in the master
(typically 5˚C). This setting is intended to be a ”frost protection” mode and is used if the room
is to be left unoccupied for long periods.
WLTM-19 & WLTD-19 are recommended for guest rooms and other infrequently used rooms,
asthey allow simple override of the automatic timing sequence.
2 Setting areas
If not already done by the installer, the WLCT2 room controller can be used to set the operating times and
temperatures of room sensors (channels) in addition to controlling its own room.
To achieve this, do the following on the WLCT2 room controller:
a. Enter the “InFo” menu by pressing the up and down button simultaneously for 4 seconds.
b. Find the “ArEA” menu with the down button and press OK.
c. The display shows “CH 1” (channel 1).
- Press OK button.
4
- Select “On” if this channel (room sensor) should be controlled by the WLCT2 room controller, or “OFF” if not.
- Now press OK button to get to the next channel (CH 2) and repeat this step until all required channels have been selected “On”.
d. After all channels are set up, find the “ESC” menu entry and press OK.
NB: If different times and temperatures are required for other channels (room sensors) within the system, more than one WLCT2 room controller can be
used. Care must be taken to ensure that the action of selecting a channel “On” is not made on more than one WLCT2 room controller.
2-events (wake and sleep). Each event can have a separate temperature & time.
Each event is indicated on the display by the symbols ( )
To adjust these settings:
a. Press OK button for 5 seconds.
b. The display shows the wake up time for Monday to Friday.
c. To adjust the hours use the up and down buttons and press OK.
d. Now adjust the minutes using the up and down button and press OK.
e. Now adjust the desired wake up temperature using the up and down button and press OK.
f. Now repeat b to e for the leaving time and temperature, the return time and temperature and the sleep time and temperature.
g. Now repeat b to e for Saturday and Sunday wake and sleep times and temperatures.
NB: To set up different types of event programs, change to Fahrenheit scale, change to AM/PM clock or change of other advanced settings - please
refer to the section Instructions WLCT2.
Other advanced settings can be changed-See section “Master with display type WLM2”.
5
TROUBLE SHOOTING
- If any LED is flashing on master - Please refer to section “Error indication”.
2 If the room is controlled by a WLCT2 room controller, check that the time and temperatures are
set correctly.
3 If the room sensor has got an override switch (WLTM or WLTD), the switch may be set in the “off”
or “night” position.
4 For rooms with floor sensors, the maximum floor limit setting could be preventing the room
reaching the desired temperature.
2 The room sensor is placed in a position that does not represent the general temperature in the
room.
3 If the room is controlled by a WLCT2 room sensor, check that the time and temperatures are set
correctly.
4 If the room sensor has got an override switch (WLTM or WLTD), the switch may be set in the “day”
position
5 For rooms with floor sensors, the minimum floor limit setting could be increasing the room
temperature above the desired setting.
6
INSTRUCTIONS
Introduction
Max. 27˚C
Maximum Floor limit temperature for room sensors with limit sensor (floor sensor)
Min. 17˚C
Minimum Floor limit temperature for room sensors with limit sensor (floor sensor)
8
Supply Water Temperature Control
Master with Display Type WLM2 Using supply water sensor for limitation of supply water:
A limit sensor should be used with the WLM2 1FS & WLM2 3FS, but can be used without the weather
compensation module (WLOC-19). In this case the master will control the supply water temperature
flowing into the system via the 3 or 4 port mixing valve and actuator. The factory default setting is
45˚C, but can be changed via the master display.*
Winter
-3ºC
Outdoor temperature
Winter
45ºC Design supply water temperature at outdoor temperature –3°C
Design supply water temperature if used without outdoor compensation module.*)
Return
Summer
20ºC
Outdoor temperature
Summer
25ºC
Supply water temperature at outdoor temperature 25ºC
9
Max supply temperature
The max allowed supply water temperature is set according to the design requirements of the
installation (line A on the curve). This is the safely maximum.
Master with Display Type WLM2
Weather compensation
Winter
A design outdoor temperature and the corresponding design supply
water temperature are set (point B). To increase the heat output, adjust
the supply water temperature higher, until you feel comfortable (we
recommend only a 2 degree adjustment of this temperature at a time, and
time allowed for the system to respond).
Then set the supply water temperature that you require when the outside temperature is at
20˚C. The default is 25˚C.
To start the summer shut down at a lower temperature level, reduce the outdoor
temperature setting, and/or reduce the supply water temperature at this setting.
The master calculates the supply water temperature on the line C to 1 if an outdoor design
temperature of -3˚C is selected, or on the line C to 2 if the outdoor is selected at -10˚C. The
intersection point on the line of the actual outdoor temperature indicates the calculated
supply water temperature.
10
Service Menu
Service menu
Master with Display Type WLM2
55ºC Push accept to enter
The controller will automatically return to main menu after 30 minutes.
OK no failures
E0 to E11 if a failure is present. See page 13 for explanation.
LS= Low signal on wireless room sensors/controllers
LB= Low battery on wireless room sensors/controllers Submenu 2
Push accept to enter and see which unit has the failure
Submenu 2a
Push accept to enter and see which master it is that has the error and what error it is.
Using the “up” and “down” button, select which masters status should be shown on the right side of the display.
>ID11 - ? E:CHANNEL
ID12 - ?
ID21 - ?
Possible Errors:
“LOADING STATUS...” : Receiving information from the network.
“STATUS OK”: No errors detected
“NET-COMM ERROR” : Communication is missing to that master. Please check the connection or remove
the master from memory with a hard reset.
“E1-E11”: The same errors as shown in section “Error Indication” under “Flashing Power LED”
“E:CHANNEL”: This is a channel error which has to be checked locally on that master.
11
Read-out
-2.4°C
Outdoor temperature
Master with Display Type WLM2
Read-out
⇄ 49.2ºC
39.2ºC
Actual supply water temperature
Actual application sensor temperature
Read-out
44.4ºC Calculated setpoint by the controller for the supply water temperature
Push accept for 3 sec. to change PI-action & 0-10V out
Read-out
Control signal for the mixing valve.
3.5V
At 10 V the mixing valve is fully open (unless the output setting has been changed to 10-0, in which case at
10 V, the valve will be fully closed)
Read-out
--- Room temperature in the different rooms. Push accept (✓), and the up and down keys to select another
24.0°C room. The actual room temperature is shown in the centre of the display. If a maximum limitation sensor
22.9°C is connected the measured temperature is shown above the room temperature, and if a minimum limitation
sensor is connected, the temperature is shown below.
Return
12
INSTRUCTIONS
To enable cooling, switch the slider on the right hand side to the cooling position.
The system now switches into cooling with a set point than is 3˚C above the master day set point.
(In case the WLAC-1 module is connected to a BMS controlled signal, the BMS system will make the decision when to
switch to cooling – please leave the slider on the WLAC-1 in position heat).
• By using a humidity sensor the system limits the formation of condensation on floor surfaces due to high humidity.
• If a dehumidifier is being used it will activate if high humidity limits the cooling function.
• When cooling is enabled the cooling set point will be pre-determined by the master
and will override any settings in any clock thermostat to ensure optimum energy efficiency.
BA/FS Cooling mode Day cooling temperature Day heat temperature + 3°C
K-factor = 0.1
Adaptive PWM control Max allowed Room temperature fluctuation +/- 0.5°C
14
Error Indication
During normal operation the power LED will be ON when the master control is energised. The red output Channel LED’s
(1 to 8 on the master, and 9 to 14 on the add-on module) will indicate if the channel output relay is ON/OFF.
An error / fault message is shown by flashing the power LED or one of the red output Channel LED’s. From the number of flashes
on any one LED, the problem can be diagnosed, and identified from the following:
The error number will be indicated by the number of flashes, with a pause of less than a 1/2 second between the flashes. The indication will be followed by a
pause of 2 seconds, following which the sequence will be repeated. The failure code can also be seen in the service menu on WLM2-FS MASTERS (submenu 2).
The appropriate output channel LED can flash, indicating that the room sensor or room contoller on that channel has a fault/error. The failure code can
also be seen in the service menu (submenu 2a).
E1, 1 flash The master has lost communication to the room sensor. The fault is corrected by re-establishing the connection to the Room
Sensor and the fault condition will be automatically reset once correct communication is resumed. If the room sensor is
defective and has to be changed, or if it has been deliberately removed, it is necessary to make a HARD RESET. (NOTE: If the
room sensor is of the WIRELESS type, the error/fault message could be an indication that the power has failed, and that the
internal battery of the room sensor needs to be replaced)
E2, 2 flashes The internal sensor in the room sensor/controller is defective. The fault can only be corrected by replacing the room sensor/
Controller. Remember to make a HARD RESET after installing the new room sensor/controller.
E3, 3 flashes The limit sensor on the room sensor/controller is defective. Replace the faulty sensor. Reset is NOT required.
Error Indication
E4, 4 flashes Defective WLCT2 room controller. If a room controller operating a group of room sensors becomes defective, the remaining
room sensors will continue control within the maximum and minimum limits programmed into the Room controller.
E5, 5 flashes Two or more room controllers are trying to control this output. Check “AREA” setting on the room controllers.
E6, 6 flashes Channel output number one is configured as a dehumidifier output, error caused by a room sensor/controller also being set to
control this output.
RESET
There are 2 different reset actions that can be used.
HARD RESET
If the ‘✓’ button is pressed for 5 seconds, a HARD RESET will be initiated. (Indicated by all the red output LED’s(1-8) lighting in sequence). This reset
will remove from the system any room sensor unit with a defective input sensor, or a defective AO module. The fault message will be reset but the
defective items will no longer participate in the system. To add or replace a new unit, please refer to “Replacing equipment - Replacing a faulty sensor/
controller”. To erase the identity of the defective component from the master memory a HARD RESET must be performed Hard resets do not alter the
temperature settings already programmed into the master control.
FACTORY RESET
If the (√ ) button is pressed for more than 15 seconds, a total factory reset will be initiated. This is indicated through flashes of channel LEDs 1,3, 5 and
7 alternating with channel LEDs 2, 4, 6 and 8 (while the “√” button is pressed).
A factory reset will put all programmed temperature settings back to the factory defaults. It will also remove all room sensors/Controllers from the
master memory, and reset the system to accept only those room sensors/Controllers that are functioning correctly.
To reconnect room sensors/controllers, please refer to “Replacing equipment - Replacing a faulty sensor/controller”.
16
INSTRUCTIONS
In addition to the immediate area of control set, within the WLCT2-x9, and selected via the ‘AREA’ setting contained within its
internal menu, the WLCT2-x9 can control the time and temperature characteristics of other sensor (up to 14) fitted to the WLM2
master, this has been designed to maximise comfort and efficiency and promote energy saving and associated cost savings.
Where the WLCT2-x9 is controlling other areas the +/- 4°C setting of those areas will now operate from the WLCT2-x9
settings, e.g. A WLCT2-x9 is set to 22°C and has been given control over ‘Area 1’, the WLTA-x9 fitted in ‘Area 1’ now has
a control range of 18°C(-4°C) to 24°C (+4°C).
In addition to the standard WLCT2-x9 room controller, you may have fitted to your system one of the following;
WLCT2-x9/2: This control allows the operation of a secondary heat source, for a specific area, as a boost function
operating in conjunction with the underfloor heating.
WLCT2-x9/R: This control is used for the control of radiators in a domestic central heating circuit.
WLCT2-x9/HW: This control is used for the production of hot water control within a system.
Upon installation your installer should have set up the WLCT2-x9 control to suit your needs, should you
need to change any of the setting please follow the instruction detailed in following pages.
The WLCT2-x9: can be reset by pressing the button marked ‘R’ (see fig 1), this will allow you to return to the factory
settings at any time. The default factory settings are detailed after the WLCT2-x9 programming section of
this manual.
Getting Started
Fig. 1 Buttons
A: B: C:
Display Adjustment OK -
down accept
D: E: F:
17
Display
G: H: I:
Type WLCT2 (and WLCT2/R/HW/2)
G K Automatic Manual Time and
mode mode temperature
H
J: K:
J
Day number 4-event symbol
Wake Out
I Night Home
First time power is connected the clock and day will be flashing and must be set. If you need to adjust the
time of the thermostat at a later date, insert a pin into the hole marked (see fig. 1) for setting of time and
day. Adjustment should be made for change in summer and winter time.
18
ArEA - (Group of rooms)
The rooms that are to be set as part of the WLCT2 area will follow the temperature settings of the room controller example, an area could
be the living room, kitchen, and children’s rooms, having a high room temperature requirement during afternoon and early evening, and
a lower temperature during the early part of the day and at night. Each room sensor will have a channel number, designated CH1, CH2
Type WLCT2 (and WLCT2/R/HW/2)
etc. The appropriate channel number of any room sensor is determined by the numbered output on the master control which is actually
switching the valve/actuator for that area.
For example, a system may have the kitchen room sensor operating master output # 4, and the childrens room sensor operating master
output #5. If the WLCT2 room controller is then situated in the living room, and operating output #1, then the WLCT2 need be programmed
to control outputs 1, 4, & 5. (Each room sensor will have been set to operate its appropriate output ch see separate instructions).
To do this, enter the ArEA sub menu., and press OK ( ) button. CH 1 will be displayed; use the OK ( ) button and then the UP (△) button
to change the setting to ON. Press OK ( ) and CH 2 is displayed. Use the UP (△) button until CH4 is displayed, press OK ( ), and change
to ON. Repeat this for CH 5. All three room sensors will now operate under the control of the WLCT2 room controller.
In total up to 14 Channels can be programmed in this way, and it is possible to have more than a single room controller, each own sub
room sensors operating to its schedule and temperatures.
Set the Channels / Rooms (Ch) to ON if they should follow the settings
of this clock thermostat.
19
Daily Use of the room sensor
Wake up The day has been split into 4 events describing a typical day. When the room sensor is in
this 4-event mode it will change the temperature to the required level automatically at the
programmed times. As standard the room controller has days 1 to 5 (Monday to Friday)
Sleep Leave with 4 events and days 6 and 7 (Saturday and Sunday) with 2 events. Each events allows
home you to increase or decrease the set temperature. For programming see page 17.
Please, see page 18 - PRO - 4-event sequence to alter the daily event sequence.
Return
4-event clock mode/ In automatic mode, the clock function symbol ( ) and one of the 4-event symbols ( ) will be
automatic mode: indicated. Programming page 17.
Comfort mode:
Temporary override
To temporarily override any temperature in the 4-event schedule program, press the UP (△) button once, to show
5 secs.
the temperature in the display, and press UP (△) or DOWN (▽) again to increase or decrease the temperature. The
display will flash for 5 seconds, and will then revert to the time. The override will operate until the next programmed
event when the thermostat will resume the automatic programme.
20
Programming 4-Event Clock Time and Temperature
These settings will be valid for days 1-5 showing on the display. : Time and temperature
To program the days 6 and 7, repeat the above. Days 6 and 7
are usually Saturday and Sunday, and only have two events
(generally morning ON and evening OFF).
: Time and temperature
The temperature can be set within the range of +5 to +35˚C.
It is also possible to select the heating OFF at that event by
reducing the setting to 5˚C, and then pressing the (▽) once
Day 6 - 7
more.
Note that when programming the “Sleep” time (event 4), : Time and temperature
please ensure that this time is before midnight (00:00).
21
Advanced Settings and Read-out
Press both UP (△) and DOWN (▽) buttons together for 3 seconds. INFO is displayed.
Continue pressing the UP(△) button until you reach one of the desired sub menus, PRO, Hi Li, Scal, and ArEA (For explanations, see
Type WLCT2 (and WLCT2/R/HW/2)
below. Select the sub menu with the OK ( ) button.
INFO - Information
The values of the actual measured room temperature and the floor temperature can be seen.
The floor temperature is only shown if a floor sensor is installed.
22
Hi Li - Floor sensor. Max and min allowed temperature of the floor surface
A limit sensor can be connected to the room controller.
Max limitation is used for safety to prevent high floor temperatures. For example wooden floor constructions which should not
be allowed to exceed a maximum of 27˚C. The value can be set from 5˚C up to 55˚C. The value can also be set to OFF (adjust the
Type WLCT2 (and WLCT2/R/HW/2)
temperature to 55˚C and push button up once more).
Low limitation is used where the temperature of the floor is required never to fall below the minimum set temperature. Example in
kitchens or bathrooms with tiles. The value can be set from 5˚C up to 55˚C. The value can also be set to OFF (adjust the temperature to
5˚C and push button down once more). Remember the max limit temperature must be set higher than the min limit temperature.
The limit temperatures defined in the room controller will be valid for all the room sensors with limit sensor (type WLTD-19) which are part
of the area allocated to the WLCT2 unit.
For example, a system may have the kitchen room sensor operating master output # 4, and the childrens room sensor operating
master output #5. If the WLCT2 room controller is then situated in the living room, and operating output #1, then the WLCT2 need
be programmed to control outputs 1, 4, & 5. (Each room sensor will have been set to operate its appropriate output ch see separate
instructions).
To do this, enter the ArEA sub menu., and press OK ( ) button. CH 1 will be displayed; use the OK ( ) button and then the UP (△) button
to change the setting to ON. Press OK ( ) and CH 2 is displayed. Use the UP (△) button until CH4 is displayed, press OK ( ), and change
to ON. Repeat this for CH 5. All three room sensors will now operate under the control of the WLCT2 room controller.
In total up to 14 Channels can be programmed in this way, and it is possible to have more than a single room controller, each own sub
room sensors operating to its schedule and temperatures.
23
Type WLCT2 (and WLCT2/R/HW/2)
Set the Channels / Rooms (Ch) to ON if they should follow the settings
of this clock thermostat.
ON
Press the DOWN (▽) button to activate or de-activate the 2 step
function.
Press OK ( ) to confirm.
OFF
tEn Use the UP (△) or DOWN (▽) button to change the temperature
P setpoint in the 2-step function.
( If the actual room temperature is higher than the setpoint minus this
setting, the second output will not be activated)
3.0°C
ESC - Escape
Press OK ( ) button to end programming and to return to scheduled
programme.
25
Reset to fatctory Settings - room controllers
NOTE: If more than one WLCT2 is present on the system, please copy this page.
Press the pin button R for 3 secs. and the thermostat returns to
Type WLCT2 (and WLCT2/R/HW/2)
Group Room
factory settings.
Remember to set time, day and area. Ch 1 Off
Ch 2 Off
4-event time and temperature Own settings
Ch 3 Off
Standard Special Special Special
WLCT2-x9 WLCT2-x9/R WLCT2-x9/2 WLCT2-9/HW Ch 4 Off
Time Temperature Temperature Temperature Temperature Time Temperature
Ch 5 Off
Day 1-5
Ch 6 Off
06:00 21˚C 21˚C 21˚C 50˚C
Ch 7 Off
08:00 19˚C 19˚C 19˚C 30˚C
Ch 8 Off
16:00 22˚C 22˚C 22˚C 50˚C
Ch 9 Off
22:30 17˚C 17˚C 17˚C 30˚C
Ch 10 Off
Day 6-7
Ch 11 Off
08:00 22˚C 22˚C 22˚C 50˚C
Ch 12 Off
23:00 17˚C 17˚C 17˚C 30˚C
Ch 13 Off
Other settings
Ch 14 Off
4-event sequence - 4:52 4:52 4:52 4:52
26
Domestic hot water control
It is possible to control the domestic hot water temperature with a special version of the WLCT2, called
WLCT2-X9/HW) to ensure optimum energy saving.
A hot water sensor is connected to the controller and measures the temperature in the storage cylinder.
Type WLCT2 (and WLCT2/R/HW/2)
• To change the temperature of the domestic hot water, just change the set point in
the WLCT2-X9/HW by using the up or down button.
• The 4-event system in the WLCT2-X9/HW can be used to save energy when hot water
is not needed..
WLCT2/HW
Radiator control
It is possible to control a radiator circuit room temperature with a special version of the WLCT2 called
a WLCT2-X9/R) to ensure optimum energy saving.
The controller measures the temperature in the room, and a zone valve is then controlled via the WLM2
master, which in turn activates the boiler on demand.
• To change the temperature of the radiator circuit , just change the set point in the WLCT2-X9/R
by using the up or down button.
• The 4-event system in the WLCT2-X9/R can be used to save energy when heat is not needed.
WLCT2/R
2 step heating
A special version of the WLCT2 called WLCT2-X9/2 is capable of controlling an additional heat source
in a room. In addition to the primary under floor heating output, the room controller is now able to
control a second output as a boost function, which will be activated only if the temperature cannot be
achieved by the primary under floor heating output within a preset time period.
Temp: If the actual room temperature is higher than the setpoint minus this setting, the second
output will not be activated.
Time: This parameter decides how long the actual temperature is allowed to remain below the
setpoint minus the TEMP setting before the second output is activated.
27
INSTRUCTIONS
Auto: The controller will follow the temperature settings of the master, or if the Room sensors
belongs to a zone group using a WLCT2 Room controller, it will follow the automatic sequence of
temperatures and timings set in the WLCT2.
Day: It will control the room temperature according to the (DAY) setting defined in the master
(typically 21°C).
Night: It will control the room temperature according to the (NIGHT) setting defined in the master
(typically 17°C).
OFF: It will control the room temperature according to the (OFF) setting defined in the master
(typically 5°C). This setting is intended to be a ”frost protection” mode and is used if the room is
to be left unoccupied for long periods.
WLTM-x9 & WLTD-x9 are recommended for guest rooms and other infrequently used rooms, as they
allow simple override of the automatic timing sequence.
28
OJ ELECTRONICS A/S OJ ELECTRONICS UK OJ ELECTRONICS A/S
STENAGER 13B CRUSADER PARK C/O ROBERT BIELECKI
DK-6400 SØNDERBORG WARMINSTER UL. BRZOZOWA 4
DENMARK WILTSHIRE, BA12 8SP 58-160 SWIEBODZICE
UNITED KINGDOM POLAND
NB
The following chart enables you to write down the zone name, the number of loops serving it, and the control
thermostat type. PLEASE LEAVE THIS INSTRUCTION WITH THE CLIENT.
CH 1 1
CH 2 2
CH 3 3
CH 4 4
CH 5 5
CH 6 6
CH 7 7
CH 8 8
CH 9 9
CH A 10
CH B 11
CH C 12
CH D 13
CH E 14
5 7 6 4 0 A