PLEASE ADDRESS ANY CORRESPONDENCE TO WATER SUPPLY (NETWORK) DEPARTMENT
Your Ref   :
Our Ref    :   WSN 92802/50              Tel   :  6330 4108
Date       :   1 Dec 2021                E-mail : roland_chan@pub.gov.sg
To Relevant Professional Institutes, Associations Societies, Statutory Boards, Government
Organisations, Developers, Qualified Persons, Professional Engineers, Licensed Plumbers,
Suppliers, Testing Laboratories.
Dear Sir/Madam
SINGAPORE STANDARD SS 636:2018 – CODE OF PRACTICE FOR WATER
SERVICES – AMENDMENT NO. 4
       This circular is to inform you of the latest amendments to the Singapore Standard
SS 636:2018 – Code of Practice for Water Services.
2       The amendments (cited as “Amendments No. 4, July 2021”) have been uploaded
by Enterprise Singapore at the Singapore Standards eShop website. You can access the
amendments by scanning the QR code below. A copy of the amendments is also attached.
3       We would like to highlight Section 7.1.19 b) of SS 636:2018, which outlines the
requirement of the installation of an intelligent access / locking system with facial
recognition and remote surveillance capabilities at the access doors and openings to the
rooms / enclosures housing the water tanks to further strengthen its security against
unauthorized access. Please note that the above requirement strictly applies to projects
where the Notification of Water Service Installation (WSI) Works By Professional
Engineer (PUBWTR-0-WSW01) is submitted after 1 April 2022.
4      All Professional Engineers and Licensed Plumbers are reminded to take note of
the amendments to SS 636:2018 and ensure compliance.
5        We would appreciate it if you could bring the contents of this circular to the
attention of your members/staff. Please do not hesitate to contact Mr Zhafri at 6885 2416
or muhd_zhafri_mohd_shaharuddin@pub.gov.sg if you need further clarification.
Yours faithfully
ROLAND CHAN
PRINCIPAL ENGINEER (WATER DEMAND MANAGEMENT & INSPECTORATE)
for DIRECTOR
WATER SUPPLY (NETWORK) DEPARTMENT
Enclosed
                             Singapore Standard SS 636 : 2018
                           Code of practice for water services
                                 AMENDMENT NO. 4
                                          July 2021
1. Page 26, 7.1.13
   Replace clause 7.1.13 c) with:
   c)      properly screened with non-corrodible or corrosion-resistant stainless steel mosquito-
           proof netting of aperture size not exceeding 0.65 mm to prevent ingress of any
           animal, insect or foreign material. The netting shall be properly secured using a
           stainless steel clip.
2. Page 26, 7.1.14
   Replace clause 7.1.14 with:
   Every isolated compartment of a storage tank shall be fitted with a tap for sampling purposes
   located anywhere between the top water level and the outlet pipe level or on the outlet pipe
   from the compartment of the storage tanks. If the sampling tap is fitted on the outlet pipe, it
   shall be fitted upstream of the valve.  The sampling tap shall be under lock and key and
   accessible only to authorised persons.
3. Page 27, 7.1.17
   Replace clause 7.1.17 with:
   Every wash-out pipe from the bottom of the storage tank shall be fitted with a tap before the
   valve for sampling purposes and such a tap shall be under lock and key and accessible only
   to authorised persons.
4. Page 27, 7.1.19
   Replace clause 7.1.19 b) with:
   b)      The access door at each tank enclosure (e.g. fencing gate) and its ancillary
           equipment including all water tank covers shall be securely locked with high-quality,
           strong and durable hinges, latches and locks with non-duplicable keys (i.e. patented
           keys that cannot be duplicated without proper authorisation). Alternatively, smart /
           intelligent biometric locking systems affording equivalent level of security shall be
           provided.
           For access doors and openings to the rooms / enclosures housing the water tanks,
           an intelligent access / locking system with facial recognition and remote surveillance
           capabilities shall be provided, and this can replace the mechanical lock and key
           system. Where multiple roof tanks enclosures are provided at the rooftop, the
           intelligent access / locking system shall be provided only for access to roof, as a first
           line of security. The locking system shall detect and send alerts to a backend
           monitoring station in the event of abnormal events such as forced entry, access by
           unauthorised personnel and tampering of the system. This locking system shall have
           a comprehensive audit trail.
                                              1
                                         COPYRIGHT
                              Singapore Standard SS 636 : 2018
                                     Amendment No. 4
5. Page 29, 7.3.9
   Insert the following new clause 7.3.9 after 7.3.8:
   The manufacturer’s or supplier’s specifications and instructions of all water fittings and
   materials shall be strictly followed during installation, maintenance, inspection, replacement
   and repairs.
6. Page 52, 10.4.11
   Replace clause 10.4.11 with:
   All vents and pipe ends shall be properly covered with non-corrodible or corrosion-resistant
   stainless steel nettings to prevent the ingress of any animal, insect or foreign matter into the
   tanks. These nettings shall be properly secured using stainless steel clips that are in
   good condition and have not been tampered with.
                                                2
                                           COPYRIGHT
                                                                                                                                                                                                                                                                  1
                                                                                                                                                          Background
                                                                                                                                                          Intent: To Enhance Water Tank Security
                                                                                                                                                           Water tank security is critical as it has a direct impact on the
                                                                                                                                                            quality of water supply to consumers
                                                                                                                                                           PUB collaborated with HDB to explore technological solutions
                                                                                                                                                            such as Facial Recognition System (FRS) to mitigate the risk of
                                                                                                                                                            unauthorized access into the restricted areas within HDB blocks
                                                                                                                                                            given existing measures
     Enhanced Water Tank                                                                                                                                   Following a successful pilot trial at Punggol Northshore, HDB has
                                                                                                                                                            implemented FRS for new HDB BTOs launched from Nov 2020
      Security Measures
                                                                                                                                                           SS 636 (Code of Practice for Water Services) amended to make it
                       Zhafri Shah                                                                                                                          mandatory for FRS to be installed at all buildings with water tanks
          Water Supply Network Department                                                                                                                   except landed residential properties                                          HDB Pump Room
                                                                                                                                                                                                                                       (housing low level tank)
                     30 Nov 2021
0                                                                                                                                                     1
                                                                                                                                                  2                                                                                                               3
     Singapore Standard SS 636 - Amendment No. 4 July 2021                                                                                                Enhanced Security Measures for Water Tanks
      Replacement of clause 7.1.19 (b)
                                                                                                                                                             A Facial Recognition System (FRS) shall be provided to enhance the security of
                                                                                                                                                             potable water tanks. The FRS shall include (but not limited to) the following
    7.1.19 For water tanks in developments other than landed
    residential premises:
                                                                                                                                                             functionalities:-
                                                                       4. Page 27, 7.1.19
    (a) the water tanks and their ancillary equipment shall be         Replace clause 7.1.19 (b) with:
        housed in an adequately secured and locked dedicated           (b) The access door at each tank enclosure (e.g. fencing gate) and its
        tank/pump room or located within an adequately secured         ancillary equipment including all water tank covers shall be securely                                  Enable secure access control via facial authentication
        and locked enclosure. The room/enclosure housing the           locked with high-quality, strong and durable hinges, latches and locks
        water tanks and their ancillary equipment shall be             with non duplicable keys (i.e. patented keys that cannot be
        segregated from other services such as equipment for           duplicated without proper authorisation). Alternatively, smart /
        telecommunications, lifts, firefighting or ACMV. The           intelligent biometric locking systems affording equivalent level of
        enclosure for water storage tanks shall not be used for        security shall be provided.                                                                            Detect and send real-time alerts to a backend monitoring
        storage of items such as flammable liquids or chemicals.
                                                                       For access doors and openings to the rooms / enclosures housing the
                                                                                                                                                                                 station in the event of abnormal activities such as:
    (b) all water tank covers and access doors and openings to the     water tanks, an intelligent access / locking system with facial
                                                                       recognition and remote surveillance capabilities shall be provided,
                                                                                                                                                                                                   a. Forced entry
    rooms/enclosures housing the water tanks and their ancillary
                                                                       and this can replace the mechanical lock and key system. Where
    equipment shall be securely locked with high-quality, strong
                                                                       multiple roof tanks enclosures are provided at the rooftop, the
                                                                                                                                                                                        b. Access by unauthorized personnel
    and durable hinges, latches and locks with non-duplicable keys
                                                                       intelligent access / locking system shall be provided only for access to
    (i.e. patented keys that cannot be duplicated without proper
    authorisation).                                                    roof, as a first line of security. The locking system shall detect and                                                  c. Tampering of system
                                                                       send alerts to a backend monitoring station in the event of abnormal
    (c) all water tank covers shall be adequately secured by bolting   events such as forced entry, access by unauthorised personnel and
    or fastening with stainless steel brackets/fasteners that are      tampering of the system. This locking system shall have a
    integrated with the tanks or otherwise fastened onto the tanks     comprehensive audit trail.                                                                                      Provide a comprehensive audit trail
    with non-corrodible or corrosion-resistant tapered round nuts.
2                                                                                                                                                     3
                                                                                                                              4                                                                                                                              5
       Where shall FRS be installed? Which access door?                                                                                 Schematic for Low level tanks
                            Are there multiple enclosures
        Tanks level                                       Where shall FRS be installed?                                                            Area/room with single                                        Area/room with multiple
                            housing the water tanks?
                                                                                                                                                      tank enclosure                                                tank enclosures
                                No                                 FRS shall be installed at the last access
                                (e.g. HDB Pump Room)               door leading to the low level tanks.
        Low level                                                                                                                          Access door (optional)                                        Access door (optional)
        tanks                   Yes                                FRS shall be installed at each of the last
                                                                                                                                                                                                         FRS                            FRS Other Services
                                (e.g. 3 x tank clusters at         access door leading to the low level tanks                                               FRS                   Other Services
                                Condo basement carparks)           (i.e. each tank cluster)                                                                          Fence gate
                                No
                                (e.g. rooftop with 1 tank          FRS shall be installed at the last access
                                                                                                                                                                                                                           Fence gate
                                enclosure typically at small       door leading to the high level tanks.
        High level              private buildings)
        tanks                                                      FRS can be provided at the common
                                Yes                                access door to the roof. Not compulsory
                                (e.g. most HDB rooftops)           to install FRS at each of the last access
                                                                                                                                                                    Fencing                                Fencing                       Fencing
                                                                   door to the high level tanks.
                                                                                                                                  Fence gate = last access door
4                                                                                                                                 5
                                                                                                                              6                                                                                                                              7
       Schematic for High level tanks                                                                                                                         What if there are no Other Services?
                 Rooftop with single tank                                      Rooftop with multiple                                                                                                            Area/room/rooftop with
                                                                       FRS
                       enclosure                                                 tank enclosures                                                                                                   FRS               water tanks only
                                                                                                                                                                                                               (strictly no Other Services)
                                                                                                                                       Other services refer to services
           Access door                                                 Access door                                                     other than the potable water
                                                                                                                                                                                                     Access door
                                                                                                                                       service installations (WSI). These
                           FRS                    Other Services                     Fence gate with Padlock Other Services
                                                                                                                                       include but not limited to:
                                     Fence gate                                                                                        • Fire services
                                                                                                                                       • Telco service
                                                                                                                                       • Solar panel equipment
                                                                                                                                       • Lift services/motor room
                                                                                                                                       • NEWater/Sanitary services
                                                                                                                                       • Other maintenance services (e.g.
                                                                                                                                          Gondola, ACMV etc)
                                   Fencing                               Fencing                             Fencing
Fence gate = last access door
6                                                                                                                                 7
                                                                                                                 8                                                                                                                              9
       FAQs                                                                                                                  FAQs
    1. When will the new security requirements (i.e. FRS) be enforced?                                                    5. “Alternatively, smart / intelligent biometric locking systems affording equivalent level of security
    The requirements strictly apply to projects where the Notification of Water Service Installation (WSI)                     shall be provided.” Is biometric only limited to fingerprint access?
    Works By Professional Engineer is submitted after 1 April 2022. We will issue a circular in Dec 2021 to               If there are multiple water tank enclosures provided at the rooftop, FRS can be provided at the common
    notify the industry on the new requirements.                                                                          access to roof, as a first line of security. In this case, the access door at each tank enclosure can be secured
                                                                                                                          using conventional mechanical locking system OR other forms of biometric security solutions such as
    2. Where shall FRS be installed for Intermediate level tanks?                                                         fingerprint, iris or even facial recognition technology.
    Same as Low level tanks. FRS shall be installed at the last access door leading to the intermediate level             Similarly, biometric locks can also be installed at all water tank covers (i.e. replace conventional padlock).
    tanks. If there are multiple enclosures, each of the last access door shall be provided with FRS.
                                                                                                                          6.    Does this mean that no more conventional mechanical locking system is allowed?
    3. Why are there different requirements for low level and high level tanks?                                           If there are multiple water tank enclosures provided at the rooftop, FRS can be provided at the common
                                                                                                                          access to roof, as a first line of security. It is not compulsory to install FRS at each water tank enclosure (i.e.
    Low level tanks and intermediate tanks are generally more accessible compared to high level tanks.
                                                                                                                          conventional mechanical locking system is still allowed at fence gates).
    For example, low level tanks are typically located at the basement carpark whereas high level tanks
    are housed within the rooftop with limited access (accessible by maintenance personnel only).
                                                                                                                          7. Are there any specific locations where the FRS cannot be installed? Can the FRS be installed at any
                                                                                                                              part of the common access to the roof?
    4. Who maintains the FRS?
                                                                                                                          To comply with the Fire Code, the FRS should NOT be installed directly in front or adjacent to the exit door
    It is the legal responsibility of the Town Councils, MCSTs and building owners to ensure proper security              which leads to the common corridor. Instead, it should be installed at a higher position, as close to the
    of the water tanks including the maintenance of the FRS within their premises.                                        rooftop level as possible. If in doubt, please approach SCDF Fire Safety Department (FSD) for clarification.
8                                                                                                                     9
                                                                                                                                                                                                                                                12
                                                                                                                 10
       FAQs                                                                                                                  Summary of Water Tank Security Measures
    8. Must be FRS record video footage at times even when it is not in use? How long must the footage
        be kept?
                                                                                                                             Security               Measures
    While recommended, it is not compulsory for the FRS to function as a live CCTV. The FRS should only                      Components
    capture the essential moments with the necessary date/time stamps (e.g. short video clips during point of
                                                                                                                             Detect & Respond       •   FRS at access doors housing water tanks (NEW)
    access, abnormal events such as brute forced entry, when the access door is open etc.).
                                                                                                                             (Infrastructural &     •   Building owners to timely respond and investigate into alerts of abnormal events
    Should the FRS double as a live CCTV, the CCTV footage should be kept for a month (i.e. 30 days), which is               Operational)               triggered by FRS
    the standard industry practice.
    Notwithstanding, the backend system should keep all access records (in soft copy written format) of                      Deter & Delay          •   Locks with non-duplicable keys at access doors & tank covers
    persons granted access to the restricted areas housing the water tanks for a minimum period of 1 year.                   (Infrastructural)      •   Stainless steel brackets at tank covers
                                                                                                                                                    •   Dedicated fencing enclosure to segregate water tanks (Notification submitted after
                                                                                                                                                        March 2015)
                                                                                                                             Deter & Delay          •   Building owners to keep proper access records (e.g. key movement book)
                                                                                                                             (Operational)          •   Building owners to conduct regular checks at water tank areas
10                                                                                                                    12
     Thank you