Generator Specs for Engineers

This document provides specifications for a 100 kVA diesel generator set including: - The generator is rated for 100 kVA/80 kW output at 380-440V, 50Hz, with a 139.1A current at 0.8 power factor. - The generator set is powered by a 4 cylinder, 4.87L, inline diesel engine rated for 93kW at 1500 RPM. - Key components include a brushless alternator, radiator, fuel tank, battery, and control panel. - The generator set is designed to operate in ambient temperatures up to 50°C and includes standard accessories such as a radiator, fuel tank, battery, and control panel.

Uploaded by

csarankumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
207 views2 pages

Generator Specs for Engineers

This document provides specifications for a 100 kVA diesel generator set including: - The generator is rated for 100 kVA/80 kW output at 380-440V, 50Hz, with a 139.1A current at 0.8 power factor. - The generator set is powered by a 4 cylinder, 4.87L, inline diesel engine rated for 93kW at 1500 RPM. - Key components include a brushless alternator, radiator, fuel tank, battery, and control panel. - The generator set is designed to operate in ambient temperatures up to 50°C and includes standard accessories such as a radiator, fuel tank, battery, and control panel.

Uploaded by

csarankumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Diesel Generator Set Specifications Sheet- 100 kVA

Generator Specifications: Alternator Specification:


Genset Manufacturer Greaves Power Voltage 380-440V
Genset Rating Prime Power Frequency 50Hz
Genset Output ( KVA / KW ) 100 / 80 Current @ 0.8PF (Amps) 139.1
Genset Model GPW II-PII-100 Type 4 Pole , Rotating field
Engine rating or Max. Power at rated RPM, in Brushless (Permanent
93 (126.5) Exciter Type
KW (BHP) magnet optional)
Engine Model 4G11TAG25 6, fixed.
Leads: Quantity , type 12, re connectable
Engine Type TCAC
(Optional)
No. of Cylinders / Cylinder arrangement 4 / Inline Solid State
Voltage regulator
Displacement (L) 4.87 Insulation Class H ,
Bore & Stroke (mm) 108 X 133 Temperature rise 125 Deg. C (Class H)
Compression ratio 16.8 Bearing: Quantity , type 1,Sealed
Flexible disc Closed
Rated RPM 1500 Coupling
Coupled
Governor: Type /Class of Governing Mechanical/G2
Voltage regulation : No load to full load 2 Phase sensing,±1%
Over speed trip (rpm) 1650
One step load acceptance 100% of rating
Air cleaner type / Qty Dry / 01 Unbalance load capability 25% of rated current
Exhaust system
Maximum allowable back pressure, kPa 4.5 Standard scope of supply:

Engine with direct injection, water cooled engine, 4 cylinder, in-line, 4 stroke,
rated at 1500 RPM, conforming to ISO 3046 / BS 5514 has the following
specifications:
- Mechanical FIP
Engine Electrical system: - Mechanical governor /Electronic Governor (Optional)
Charging alternator Voltage / Current (DC) - Turbocharger, exhaust manifold, stainless steel exhaust flexible connection
12V / 35Amps
- Radiator Cooled with after cooled
Starter Motor rated voltage (DC) 12 - Plate type lube oil cooler
12V,88 AH -Filter-fuel, lube oil
Battery Voltage (DC) / Capacity (AH) - Dry type replaceable paper element air cleaner
- Flywheel housing and flywheel to suit single bearing alternator
- Starting motor – Electric, battery charging alternator
- First fill lube oil and coolant
Fuel System:

Recommended Fuel
HSD Alternator: Meccalte / (Optional -Stamford/ Crompton Greaves /equivalent)
-brushless alternator
Fuel tank capacity ( Ltr) 350 - Self-excited, self-regulated
- Class ‘H’ insulation limited to temperature rise of class H
Fuel consumption - LPH at % load - Salient pole revolving field
100% 23.6 - Single bearing
75% 17.4 - Automatic voltage regulator
50% 13
Acoustic enclosure – Engine alternator assembly mounted on AVM with
25% 7.2
Silencer and S.S exhaust bellow suitably optimized to meet stringent sound
emission standards as laid down by MOEF / CPCB
- Base rail with draw-out type fuel tank is provided with a drain plug, air
Lubricating Oil system : Vent inlet and outlet connections, level indicator, manhole etc.
Lube oil sump capacity 10 - Sub-base fuel tank with 13 hours capacity at 75% load.
- 12 V dry, batteries with connecting leads and terminals
Oil change period (Hrs) 500 -90% gloss RAL9003 white pure polyester powder coated, base in black colour.
Oil consumption (% of sfc) ≤ 0.2
Control panel: RAL 9003 W hite Powder coated control panel manufactured
Oil filter quantity (Nos) /type 01 / spin on type with CRCA sheet ,Control Panel is having following features:
15W40 -W ater and lube oil drain outlets located on the outer surface- Leading to ease of
Greaves Maxtherm maintenance and cleanliness.
Recommended Oil Grade API CI4 - MCCB of suitable rating with overload and short circuit protection
- Controller which displays voltage, current, KW, PF, Frequency, KWh.
- Indicating lamps for “Load On” and “Set Running”
Oil Cooler Water cooled - Current transformers of suitable ratings
- Copper cable of suitable capacity with incoming and
Outgoing terminations
Cooling System : - Control fuses duly wired and ferruled
Cooling system is designed for max ambient
50 Power cables: Uninyvin copper conductor cables between Alternator & Control
temp, Deg. C at rated load
panel inside the canopy.
Radiator System capacity, including engine, (L) 25 Ltr
Water pump type Centrifugal, Gear Driven Literature:
Operation Manual
General maintenance & installation Guideline
Foundation Drawing
Parts manual
Generator Controller (GADC-321)

CONTROLER TYPE FEATURES DISPLAY PARAMETER AUDIO VISUAL WARNING SHUT DOWN WITH AUDIO
VISUAL ANNUNCIATION
Compact and
microprocessor based fully
Engine Oil pressure Low Oil pressure Low Oil Pressure
configurable control Unit.

Greaves Advance Digital Graphic display Coolant temperature High Coolant temperature High Coolant temperature
Controller
The unique integrated DG
set controller Fuel level indication % Low Battery Voltage Engine Over speed

Incorporate both engine


and alternator parameter in Battery voltage Low fuel Level Engine underspend
one console
Fully configurable digital
out put Engine rpm Low Fuel

All parameter are settable Over load


DG set Running Hours
and password protected
Generator Volts –
Remote start Phase – Neutral & Under voltage
Phase - Phase
Generator Current Over voltage
(Amps)
Power factor Over frequency
KWHR Under frequency
KW

Optional Items: Open Unit (For Export) Exhaust Silencer - Hospital / Residential grade,
stainless steel, flexible pipe.
Cooling System: Heater Kit for -20 Deg. C Operation / Heater Kit for -30 deg.Cel
Fuel System: Flexible Fuel Lines / SS fuel lines / Fuel Pressure Gauge/ fuel
Electrical Systems: Alternator Space Heater / Higher Rating Battery / Battery flow tank
Charger / Battery Heater / Copper Bus Bar / Sealable kWh / Earth Fault Relay /
Remote Annunciator / Remote monitoring / RTD/BTD Temperature Scanner Enclosed Unit: Sound Enclosure – Super silent / External 990 Lt. Fuel Tank.

AMF &Synchronizing System: AMF panel / AMF with Auto-synchronization Miscellaneous: Air Cleaner (Heavy Duty)/Air Cleaner Restriction Indicator
(Deep Sea / W oodward) Digital / Closed crankcase ventilation

Typical Enclosed GENSET Dimensions & weight

Model Rating Length(mm) Width(mm) Height(mm) Weight(kg)

GPWII-PII-100 100 3000 1350 1884 1600