Instruction
1        General information
                                         Commissioning instruction NGP+
    Applicable to                                :      NGP8+ to NGP100+
    Safety Instructions                          :      General
    Special Tools                                :      n/a
    Consumables                                  :      n/a
    Printed Matter Number                        :      2946 2002 00
2        Document overview
This document describes the following:
1        General information ........................................................................................................................................................... 1
2        Document overview ........................................................................................................................................................... 1
3        Document Information and History .................................................................................................................................... 1
4        Safety first ......................................................................................................................................................................... 2
5        Safety Precautions ............................................................................................................................................................ 3
6        Installation ......................................................................................................................................................................... 4
7        Installation requirements ................................................................................................................................................... 5
8        Nitrogen generator connections ........................................................................................................................................ 6
9        Voltage selection ............................................................................................................................................................... 7
10       Flow calculation ................................................................................................................................................................. 8
    10.1       Correction factors ....................................................................................................................................................... 8
    10.2       Example ..................................................................................................................................................................... 8
11       Start-up procedure ............................................................................................................................................................ 9
12       Commissioning sheet ...................................................................................................................................................... 16
3        Document Information and History
    Edition           Date                    Description                                                                                   Author
    00                14/03/2016              First Edition                                                                                 Hannes Vertommen
    01                15/09/2016              Info on purity set point, flow calculation and voltage added                                  Hannes Vertommen
    02                22/02/2017              Info for gen2 (step 11) added and info for FF compressors                                     Hannes Vertommen
22/02/2017
PM 2946 2002 00                                                                    Page 1 of 16
4   Safety first
                            Identify the hazard                          Evaluate the risk
                  Take action                           Start work safely
                      KNOW THE SAFETY                  KNOW THE SAFETY
                       RULES OF YOUR                   INSTRUCTIONS OF
                         CUSTOMER                       YOUR MACHINE
                                                            LOCK OUT / TAG OUT
      PERSONAL PROTECTION KEEPS YOU SAFE                   TAKE AWAY THE RISKS
22/02/2017
PM 2946 2002 00                         Page 2 of 16
5    Safety Precautions
Please follow strictly all the safety precautions as per mentioned in the instruction book and as per local regulation as
applicable.
Nitrogen generators produce high purity nitrogen with oxygen enriched waste air.
The standard oxygen concentration in the air around us is equal to 20,9 %, increased or decreased oxygen concentrations
pose specific risk as indicated in the below table:
22/02/2017
PM 2946 2002 00                                        Page 3 of 16
6    Installation
The installation must be done with the following components, in the following order:
 1      Compressor with integrated refrigerant dryer
 2      UD+ filter
 3      QDT filter
 4      PDp filter inlet
 5      Air receiver
 6      Nitrogen generator
 7      Nitrogen buffer vessel
 8      PDp filter outlet (in line C ‘from N2 buffer’)
 9      Needle valve
                     1                          2       3 4               5                   6           7
                                                              A
                                                                                          E
                                                                      B
                                                                              C
                                                    A                     D
                       1               2 3 4                  5               7   8           6               9
22/02/2017
PM 2946 2002 00                                                   Page 4 of 16
7    Installation requirements
Proper ventilation of the generator room is required. If natural ventilation is not sufficient, at least 4 air changes/hour are
required.
Natural ventilation can be sufficient if:
        Ventilation openings have an area bigger than
         1/100 of the room’s floor area
        Ventilation openings are placed diagonally
         opposite each other and aren’t blocked
A room oxygen level detection with an audible/visual alarm is advisable. When working in rooms where the oxygen content
can rise to a dangerous level, a continuous measurement system is necessary.
Alarm levels should be set below 19.5% and above 22.5%.
Put the measuring equipment in the working area and near to the worker. Personal oxygen alarms are always advised when
working around oxygen generators.
If exposed to an oxygen enriched atmosphere, make sure to ventilate your clothing for at least 15 minutes in normal
atmosphere. Do not come near open flames or do not smoke.
The generator is delivered with label 1622 5408 03. This green label can be used to stick on the Nitrogen vessel to
differentiate with the compressed air vessel.
22/02/2017
PM 2946 2002 00                                         Page 5 of 16
8    Nitrogen generator connections
The following connections are present on the Nitrogen generator:
Following sizes of filters, vessels and piping need to be respected:
 NGP+                               #        8 – 12      15 – 20       25 – 35    40 – 50       60 – 70         85       100
 UD+ filter                         2
 QDT filter                         3
                                                           To be verified with NGP 8-100+ product sizing calculator
 PDp filter in                      4
 PDp filter out                     8
 Air and Nitrogen buffer vessel    5&7       150 L        280 L         500 L      1000 L        1000 L       1500 L    2000 L
 N2 outlet pipe diameter            E         1/2”         1/2”          3/4”         1”           1”           1”        1”
 Air piping diameter              A&B         1/2”         3/4”           1”          1”         1 1/4”       1 1/2”    1 1/2”
 Connection to and from
                                  C&D         1/2”         3/4”           1”          1”         1 1/4”       1 1/2”    1 1/2”
 N2 buffer vessel
 Exhaust connection <3m                     1x DN70      1x DN70       1x DN70    1x DN70       2x DN70      2x DN70   2x DN70
 Exhaust connection >3m                    1x DN100     1x DN100       1x DN100   1x DN100     2x DN100     2x DN100   2x DN100
22/02/2017
PM 2946 2002 00                                       Page 6 of 16
9    Voltage selection
The generator is designed to work on 115V/60Hz and 230V/50Hz. Ex-factory, the generator is wired to operate at 230V.
If the generator needs to work at 115V, the wiring of the transformer inside the cubicle needs to be changed.
                                                                                                    Transformer
22/02/2017
PM 2946 2002 00                                      Page 7 of 16
10 Flow calculation
Based on inlet air pressure and temperature, the performance of the CMS adsorbant inside the generator will change.
Increased temperatures will result in reduced capacity, increased pressure in improved capacity.
In order to have the generator running in optimal conditions, we need to make sure that the customer doesn’t consume more
nitrogen from the nitrogen receiver than what the generator is capable to deliver. This can be achieved by limiting the flow
after the nitrogen receiver by means of a needle valve.
To regulate this consumption, the maximum capacity of the generator needs to be known, this can be calculated with the
AML data and correction factors.
Note: refer to the business portal for the latest AML data
10.1 Correction factors
 P
          4     4.5     5     5.5     6     6.5     7     7.5     8     8.5     9     9.5    10     10.5   11     11.5   12     12.5   13
 [BAR]
 %       0,56   0,63   0,71   0,77   0,85   0,93    1     1,07   1,13   1,19   1,25   1,3    1,35   1,4    1,45   1,5    1,54   1,58   1,61
 PPM     0,52   0,6    0,67   0,75   0,83   0,91    1     1,04   1,09   1,11   1,13   1,15   1,16   1,17   1,18   1,2    1,21   1,23   1,25
 T
          5     10     15     20     25     30     35     40     45     50      55     60
 [°C]
 %        1      1      1      1     0,98   0,95   0,92   0,88   0,83   0,78   0,72   0,66
 PPM     1,02   1,02    1      1     0,96   0,93   0,88   0,83   0,78   0,72   0,67   0,62
10.2 Example
NGP35+ | Purity 99.5% | Working pressure: 11.5 bar | Inlet air temperature 40°C
In this case the generator is capable of delivering 50.37m³/h so we need to make sure this is the maximum flow that can be
consumed by the customer by limiting the flow with a needle valve.
22/02/2017
PM 2946 2002 00                                            Page 8 of 16
11 Start-up procedure
 #                Action                                           Information
 1   Make sure that all the ball valves                                 Closed
     between the generator and the
     nitrogen buffer vessel are
     opened.
     The ball valve after the
     compressor must be closed.
     The outlet consumption valve
                                                         Closed
     must be closed.
 2   The following ball valves in the
     generator must be closed:
             BA03
             BA04
             BA05 (if option outlet
              PDP is not selected)                                               BA04 – Nitrogen sample
                                                                                  ball valve to Oxygen
             BA07                                                                       sensor
                                                                                 BA07 – Nitrogen sample
                                                                                       ball valve
                                                                                  BA05 – optional outlet
                                                                                  PDP sensor ball valve
                                                                                 BA03 – inlet air flushing
                                                                                       ball valve
                                          BA04 detail:
                                                                                 BA04 – Nitrogen sample
                                                                                  ball valve to Oxygen
                                                                                         sensor
22/02/2017
PM 2946 2002 00                                     Page 9 of 16
 3   The following ball valves in the
     generator must be opened:
              BA01
              BA02
              BA05 (if option outlet                                 BA01 and BA02
               PDP is selected)
              BA06
                                                                   BA05 – optional outlet
                                                                   PDP sensor ball valve
                                                                   BA06 – Nitrogen purity
                                                                        ball valve
                                          BA01 and BA02 detail:
                                                                   BA02 – PDP ball valve
                                                                     BA01 – Pilot air ball
                                                                     valve (to pneumatic
                                                                          solenoids)
 4   Disable energy efficient mode
     for the refrigerant dryer (ID or
     FD).
     NOTE: This mode can cause an
     increase of outlet dew point and a
     shutdown of the generator.
 5   In case of a stand-alone
     refrigerant dryer: switch on the
     dryer 10 minutes in advance in
     order to cool down the dryer.
22/02/2017
PM 2946 2002 00                                    Page 10 of 16
 6   Start the compressor.
     In case of an integrated
     refrigerant dryer, start the
     compressor with the outlet ball
     valve closed for 10minutes so
     the dryer has time to cool down.
 7   Slowly open the valve after the                           Closed
     compressor for max 25%. The
     inlet vessel will gradually fill with
     dry, compressed air.
     For machines with integrated
     dryer this is extremely
     important. If the valve is
     opened above 25% at initial
                                                ¼ Open
     start, the dryer will not be
     capable of providing a good
     dew point.
 8   Enter the requested nitrogen
     purity in the controller:
     Menu/Settings/Generator/
     Regulation/Purity
     The generator will use this
     setting to calculate what the
     generator capacity is.
     Based on purity set point, inlet
     pressure and inlet temperature,
     the generator will display how
     much nitrogen flow he can
     deliver at the current conditions.
     The generator itself is not
     capable of regulating the
     purity.
     Based on the flow provided to
     the generator or by the pressure
     difference between air and
     nitrogen vessel pressure, the
     purity will be influenced.
     High flow through the CMS
     adsorbent results in low purity.
     Low flow through the CMS
     results in high purity.
     NOTE:
     There will be a warning when purity
     drops below purity set point and
     above minimum purity.
     During flushing, the generator keeps
     on running but the vessel is flushed
     over a nozzle until the purity is again
     above minimum purity setting.
22/02/2017
PM 2946 2002 00                                Page 11 of 16
 9    Enter the minimum required
      nitrogen purity in controller:
      Menu/Settings/Generator
      /Regulation/Minimum Purity
      The controller will use this
      setting to flush the nitrogen
      buffer vessel to the minimum
      purity by opening valve 11.
      NOTE: During flushing, the
      consumer valve V10 is closed and
      no nitrogen is available at the outlet.
                                                                  V11 – Low purity
                                                                   exhaust valve
                                                                V10 – Consumer valve
 10   Make sure the pilot air pressure
      regulator PR03 is set to a
      pressure of 6 bar(g) or 85 psi(g).
                                                                  PR03 – Pressure
                                                                  regulator pilot air
22/02/2017
PM 2946 2002 00                                 Page 12 of 16
 11    Check the inlet dew point on the
       controller display. If this value
       exceeds 5°C, the air receiver
       needs to be flushed until a value
       below 5°C is reached.
       To flush the air receiver, make
       sure the refrigerant dryer is
       switched on. Continue by slowly
       opening the inlet air flushing ball
       valve BA03. Have the ball valve
       opened so that the compressor
       runs at a low speed and the
       refrigerant dryer can lower the
       PDP.
       Close BA03 when the PDP is
       lower than 5°C.
                                                              BA03 – inlet flushing
                                                                  ball valve
       NOTE: The PDP sensor can require
       up to 10 minutes to indicate the
       correct value.
 11    On software generation 2
 bis   (NGP+ from API205450,
       produced since 10/2016),
       manual ball valve BA03 is
       replaced with solenoid valve
       Y14.
       This solenoid will automatically
       open when the inlet dew point is
       too high, flushing the wet air
       through the silencer.
       When the dew point is back ok,
       the valve will close.
                                                             Y14 – inlet flushing ball
                                                                      valve
22/02/2017
PM 2946 2002 00                              Page 13 of 16
 12   Start the generator.
      During start-up, the nitrogen
      buffer vessel is filled through
                                                          OR04 – Filling orifice
      restricted orifice OR04 until the
      pressure difference between the
      air tank and nitrogen buffer
      vessel is less than 0.5 bar.
      During flushing, the nitrogen
      buffer vessel is flushed through
      orifice OR06 by opening V11,
      until the purity in the vessel is
      equal to the min. purity setting.
      Flushing can take up to 2 hours
      for %-generators and up to 6                         OR06 – low purity
      hours for ppm-generators.                             exhaust nozzle
      After flushing, the generator is
      ready for nitrogen production.
                                                           V11 – Low purity
                                                            exhaust valve
 13   Regulate the outlet nitrogen
      pressure with pressure regulator
      PR01 to the requested nitrogen
      pressure.
                                                          PR01 – N2 pressure
                                                              regulator
22/02/2017
PM 2946 2002 00                           Page 14 of 16
 14   Make sure the outlet flow
      (measured by FT01) does not
      exceed the nominal flow of the
      nitrogen generator.
      If the purity drops below the
      minimum purity setting, the
      outlet flow is cut off to enable
                                                         FT01 – N2 flow meter
      flushing of the nitrogen vessel
      (by opening V11).
      The flow can be regulated with
      the needle valve (component 9):
      See chapter Flow calculation for
      the nominal flow of the
      generator.
      Based on the purity set point,
      measured inlet pressure and
      temperature, the generator will
      display the current capacity in
      the screen capacity control.
      (Menu – settings – generator –
      capacity control)
      The flow consumption may not
      exceed the generator capacity
      value.
 15   Verify time and date in the
      Settings menu:
      Menu/Settings/General/Time
      Format dd/mm/yy and hh:mm:ss
 16   Set the flow alarm warning 10%
      above the nominal flow of the
      generator, calculated in chapter
      Flow calculation.
      Menu – Warnings - Flow
22/02/2017
PM 2946 2002 00                          Page 15 of 16
 17   Perform a complete leak test of         Check both the generator and the piping network for leaks.
      the installation. The smallest          Fill the nitrogen buffer tank to the nominal working pressure.
      leak in the nitrogen installation
                                              Stop the generator and wait for one hour while monitoring the pressure in the
      can cause the generator to
                                               adsorbent with the nitrogen outlet valve (downstream N2 buffer vessel) closed.
      malfunction.
                                              If a pressure drop of more than 100 mbar shows after one hour, leaks are
                                               present and have to be fixed before taking the generator in operation.
 18   Set the generator in automatic
      operation mode. This enables
      Standby and Capacity control
      modes.
      In Standby mode, towers A and
      B are pressure less. The
      generator will start producing
      nitrogen flow consumption from
      the nitrogen receiver is detected.
12 Commissioning sheet
To write down all parameters and during during the commissioning, excel sheet 246 2003 00 can be used.
22/02/2017
PM 2946 2002 00                                       Page 16 of 16