Designation : PANEL ''A'' Mounting: SURFACE MOUNTED
System : Enclosure: NEMA - 12
Location : ELECTRICAL ROOM Feed: TOP
CONNECTED LOAD OVERCURRENT CONDUCTORS
CKT. PROTECTION (CU. WIRE) RACEWAY QUANTITY REMARKS
LOAD DESCRIPTION AMPERE
NO. VA
AT AF P SIZE (MM2) TYPE SIZE TYPE CO LIGHT MOTOR
1 PANEL A1 108790 268.1 24.9 13.1 13.1 50 100 3 3-50 + 1-14 (G) THHN CABLE TRAY
2 ECB-A2 18844 39.9 20 25.7 50 100 3 3-22 + 1-8.0 (G) THHN PVC
TOTAL 108790 268.1 64.8 33.1 38.8
UPGRADE MAIN
= [ 268.1+(1.732 X 64.8) A ] X 0.8DF + (0.25 X 69) EXISTING PROTECTION: 300AT/400AF, 3P,500V, 60HZ BOLT-ON, MCCB
IT DEMANDED LINE CURRENT: PROTECTION TO
= 321.8 AMPS EXISTING SUB-FEEDER: 2 SETS 3 - 100MM2 THHN + 1 - 14MM2 THHN (G) IN 50MM DIA. CONDUIT 400A, 3P
NOTE: PANEL A1 PRIMARY LINE CURRENT IS MULTIPLIED BY
SECONDARY TO PRIMARY VOLTAGE RATIO OF DRY TYPE
TRANSFORMER (380V/220V) (Vs/Vp = Ip/Is)