DATA SHEET

ANSULITE AFC3B-FP29
3% Freeze-Protected
AFFF Concentrate

Description
ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF (Aqueous
Film-Forming Foam) Concentrate combines fluoro- and
hydrocarbon-surfactant technologies to provide superior fire
and vapor suppression for Class B hydrocarbon fuel fires.
This synthetic foam concentrate is intended for firefighting
applications at 3% solution in fresh, salt, or hard water.
ANSULITE AFC3B-FP29 foam solution utilizes three suppression
mechanisms for rapid fire knockdown and superior burnback
resistance: 009830

n The foam blanket blocks oxygen supply to the fuel.

n Liquid drains from the foam blanket and forms an aqueous


film that suppresses fuel vapor and seals the fuel surface. Approvals, Listings, and Standards
n The water content of the foam solution produces a cooling ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate
effect for additional fire suppression. is designed in accordance with National Fire Protection
Association (NFPA) Standard 11 for Low-, Medium-, and High-
TYPICAL PHYSIOCHEMICAL PROPERTIES AT 77 °F (25 °C) Expansion Foam. The concentrate is approved, listed, qualified
under, or meets the requirements of the following specifications
Appearance Clear amber liquid and standards:
Density 1.05 ± 0.02 g/ml n UL Standard 162, Foam Liquid Concentrates
n ULC S564, Category 1 Foam Liquid Concentrates
pH 7.0 – 8.5
n ICAO
Refractive Index 1.3850 minimum
–  Level B
Viscosity* 5 ± 1 cSt
Spreading Coefficient 3 dynes/cm minimum at 3% dilution ICAO
Level B
Pour Point –31 °F (–35 °C)

Freeze Point –33 °F (–36 °C)
*Cannon-Fenske viscometer at 77 °F (25 °C)
Application
The ANSULITE AFC3B-FP29 Concentrate formulation contains
ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate
short-chain, C-6 fluorochemicals manufactured using a telomer-
is intended for use on Class B hydrocarbon fuel fires with low
based process that does not produce PFOS.
water solubility, such as crude oils, gasolines, diesel fuels,
and aviation fuels. It is not suitable for use on polar fuels with
appreciable water solubility, such as methyl and ethyl alcohol,
acetone, and methyl ethyl ketone. It may also be used in
conjunction with dry chemical agents to provide even greater
fire suppression performance.
ANSULITE AFC3B-FP29 Concentrate can be ideal for fixed, semi-
fixed, and emergency response firefighting applications such as:
n Fuel or chemical storage tanks

n Industrial chemical and petroleum processing facilities

n Truck/rail loading and unloading facilities

n Flammable liquid containment areas

n  Docks and on-board marine systems

n Mobile equipment

One Stanton Street  |  Marinette, WI 54143-2542, USA  | +1-715-735-7411 | www.ansul.com


© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were
current as of document revision date and are subject to change without notice.  |  Form No. F-2015286-03
Foaming Properties Storage and Handling
ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate
may be effectively applied using most conventional foam should be stored in the original supplied package (HDPE
discharge equipment at a 3% dilution with fresh, salt, or hard totes, drums, or pails) or in the recommended foam system
water. For optimum performance, water hardness should not equipment as outlined in Johnson Controls Technical Bulletin
exceed 500 ppm expressed as calcium and magnesium. Storage of Foam Concentrates. The product should be
maintained within the recommended temperature range. If the
ANSULITE AFC3B-FP29 Concentrate requires low energy to concentrate freezes during transport or storage, full product
foam and the foam solution may be applied with aspirating serviceability can be restored upon thaw with gentle re-mixing.
and non-aspirating discharge devices. Non-aspirating devices,
such as handline water fog/stream nozzles or standard sprinkler Factors affecting foam concentrate’s long-term effectiveness
heads, typically produce expansion ratios from 2:1 to 4:1. include temperature exposure and cycling, storage container
Aspirating low-expansion discharge devices typically produce characteristics, air exposure, evaporation, dilution, and
expansion ratios from 3.5:1 to 10:1, depending on the type of contamination. The effective life of ANSULITE AFC3B-FP29
device and the flow rate. Medium-expansion discharge devices Concentrate can be maximized through optimal storage
typically produce expansion ratios from 20:1 to 60:1. conditions and proper handling. ANSULITE concentrates have
demonstrated effective firefighting performance with contents
TYPICAL FOAM CHARACTERISTICS* (Fresh and Sea Water) stored in the original package under proper conditions for more
Proportioning Rate 3% than 10 years.
Expansion Ratio ≥7 Mixing ANSULITE AFC3B-FP29 Concentrate with other foam
concentrates for long-term storage is not recommended. Use in
25% Drain Time (min:sec) ≥ 2:30 conjunction with comparable 3% AFFF products for immediate
50% Drain Time (min:sec) ≥ 4:30 incident response is appropriate.
*per EN 1568-3: 2008 protocol

Inspection
Proportioning ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate
The recommended operational temperature range for should be inspected periodically in accordance with NFPA 11,
ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate EN 13565-2, or other relevant standard. A representative
is –20 °F to 120 °F (–29 °C to 49 °C) per UL-162. However, the concentrate sample should be sent to Johnson Controls Foam
diluted solution will freeze at 32 °F (0 °C). This foam concentrate Analytical Services or other qualified laboratory for quality
can be correctly proportioned using most conventional, properly analysis per the applicable standard. An annual inspection and
calibrated, in-line proportioning equipment such as: sample analysis is typically sufficient unless the product has
been exposed to unusual conditions.
n Balanced and in-line balanced pressure pump proportioners

n Balanced pressure bladder tanks and ratio flow controllers

n Around-the-pump type proportioners Ordering Information


n Fixed or portable in-line venturi type proportioners ANSULITE AFC3B-FP29 3% Freeze-Protected AFFF Concentrate
is available in pails, drums, totes, or bulk shipment.
n Handline nozzles with fixed eductor/pick-up tubes
Approximate
For immediate use: The concentrate may be diluted with fresh Part No. Description Shipping Weight
or sea water to a 3% pre-mix solution.
Pails
For delayed use: Consult Technical Services for guidance 443107 5 gal (19 L) 45 lb (20.4 kg)
regarding suitability of a stored pre-mix solution (fresh water 443107E 5 gal (19 L) 45 lb (20.4 kg)
only).
Drums
443108 55 gal (208 L) 495 lb (224.5 kg)
443108E 55 gal (208 L) 495 lb (224.5 kg)
Materials of Construction Compatibility
Totes*
To help avoid corrosion, galvanized pipe and fittings should 443109 265 gal (1,003 L) 2,463 lb (1,117 kg)
never be used in contact with undiluted ANSULITE AFC3B-FP29 443109E 265 gal (1,003 L) 2,463 lb (1,117 kg)
3% Freeze-Protected AFFF Concentrate. Refer to Johnson
Controls Technical Bulletin Acceptable Materials of Construction For bulk orders, consult an account representative.
for recommendations and guidance regarding compatibility of *Totes are not UL/ULC approved packaging.
foam concentrate with common materials of construction in the
firefighting foam industry.
Safety Data Sheets (SDS) are available at www.ansul.com
If any foam product is discharged into the environment, efforts should be
made to control, contain and collect the discharge for proper disposal, while
following all applicable laws, regulations, and codes. Further information
regarding the use, discharge, and disposal of firefighting foams can be
found at www.ansul.com.
Note: The converted metric values in this document are provided for
dimensional reference only and do not reflect an actual measurement.
ANSUL, ANSULITE, and the product names listed in this material are marks
and/or registered marks. Unauthorized use is strictly prohibited.