END-CLIENT M/s.
MATRIX AGRO PRIVATE LIMITED IP/TR/F/UVR/42
CLIENT M/s. DATTA POWER ENGINEERS TR No. IPSE /HYD/ 000
LOCATION 6MW MAPL BIOMASS PLANT, CHINCHOLI SHEET OF
TEST REPORT FOR UNDER VOLTAGE RELAY
Date: 25.12.2021
1. Equipment Details
Location : 11Kv VCB Panel Room
Panel : 7.5MVA Trafo FDR
Designation : Inst. Under Voltage Relay
Make : Alstom
Model : VAGM22AF171G
Serial No : 31757033
Auxiliary Coil : 110V AC
2. Secondary Injection Test :
Setting Voltage: 88V
Phase Reference PICK UP (V) DROP OFF (V)
Ph - Ph 85 101
3. Remarks:
Relay FIT FOR SEVICE.
M/s. INEL PSE M/s. INEL PSE
References Witnessed By
Tested By Verified By
NAME VIVEKANANTHAN.D NIRMAL KUMAR
SIGNATURE
DESIGNATION TESTING ENGINEER MANAGER -TECHNICAL