Calculation for Fire Pump Room Ventilation
Ventilation Fans will work at same ACH in case of fire @ 10 ACH & normal mode
with 6 ACH
Area = 34 m²
Hight = 3.15 m²
Volume = 107.1 m³
One Air Change 62.5 CFM
Ventilation Air Required @ Noraml Case 6 ACH 375 CFM
Ventilation Air Required @ Fire Case 10 ACH 625 CFM
assume 10% more for frsh air fan fire pump room should be +ve all the time
Ventilation Air Required @ Noraml Case 6 ACH 413 CFM
Ventilation Air Required @ Fire Case 10 ACH 688 CFM
Get Required Fresh Air Fan
Normal Mode 413 CFM
Fire Mode 688 CFM
Get Required Exhaust Air Fan
Normal Mode 375 CFM
Fire Mode 625 CFM