Bulletin 4983-DC
Surge and Filter Protection
Product Overview/Catalog Number Explanation/Product Selection
Bulletin 4983-DC DIN Rail Filter and Surge Protective Table of Contents
Devices
Small combination (filter and SPD) package size
Product Selection ...... this page 0
Features Isatrol technology
Specifications.............. 8-94
All-mode transient protection with exceptional Line to Neutral value Approximate
of 25 kA Dimensions................... 8-94
LED power indication 1
Form C contact for remote status indication Standards Compliance
DIN Rail mountable UL 1283
Bulletin 4983-DC is the combination of a filter and a surge protective UL 1449
device. The Bulletin 4983-DC product meets both UL 1449 and UL IEC 61643-1
1283. This product allows transient and noise protection in one small EN 61643-11
2
CSA C22.2
package.
Certifications
cURus Recognized
Component (File No. 3
E334011, Guide VZCA2,
VZCA8), (File No. E316867,
Guide FOKY2)
CSA
CE Marked 4
Cat. No. Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all 5
combinations will produce a valid catalog number.
4983 — D C 120 3
a b c d 6
a b c d
Mount Type Voltage Current Rating
Code Description Code Description Code Description Code Description 7
D DIN Rail C Combo UL 1449/UL 1283 120 120V 3 3A
240 240V 5 5A
10 10 A
20 20 A
8
DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC
Max.
Continuous
Maximum
Discharge Current Nominal UL1449 Voltage Protection
9
Operating 8/20µs (Imax) [kA] Discharge Rating (VPR) [V AC]
Connection Voltage Current
Mode Frequency (MCOV) (Uc) L/G L/N N/G 8/20µs (In) L/G L/N N/G L-L
AC Network [Hz] [V AC] [kA] Ampacity [A] Cat. No.
3.0 4983-DC120-03 10
5.0 4983-DC120-05
120V AC 150 600 400 600 -
10 4983-DC120-10
20 4983-DC120-20
L/G, L/N, N/G 47...63 10 25 10 3
3.0
5.0
4983-DC240-03
4983-DC240-05
11
240V AC 320 1200 - - 800
10 4983-DC240-10
20 4983-DC240-20
12
13
www.ab.com/catalogs Preferred availability cat. nos. are bold.
Publication A117-CA001A-EN-P 8-93
Bulletin 4983-DC
Surge and Filter Protection
Specification/Approximate Dimensions
Specifications
0 Connection/Mounting Type
Enclosure
Series/DIN Rail mount
Metal, DIN Rail mount, product label
3 A — 1 lb
5 A — 1 lb
Approximate Weight
10 A — 1.5 lbs
20 A — 1.5 lbs
1 Line — Neutral
Line — Line
Modes of Protection
Line — PE
Neutral — PE
Certifications UR Recognized, CSA, CE Marked
2 Typical Cat. A Ringwave Rating < 60V peak
Typical Cat. B Ringwave Rating < 100V peak
Single green LED indicating MOV integrity
Status Indication
Single form C contact (10 A @ 250V AC, 5 A @ 100V DC)
3 Response Time
Normal mode: < 0.5 ns
Common Mode: < 5 ns
Operating Temperature -40…+60 °C derate linearly to 60% @ +70 °C
Fusing Appropriate external fusing is required
Normal Mode (100 kHz…50 MHz) — 90 dB min.
4 Frequency Response 100 kHz…50 MHz Common Mode (5…50MHz) — 60 dB min.
50 kHz cut-off frequency
Approximate Dimensions
Note: Dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.
5
7
1.92
(48.77) 3.72 3.08 LINE
0.18
(94.49) (78.23) (4.57)
2.85 0.17
(72.4) (4.32)
8 + + +
LN 0.16
(4.06)
LINE
35mm
DIN RAIL
MOUNTING
9 4.84
(122.94)
STATUS
LOAD
NC COM NO L N
10 + + + + + +
LOAD
WIRE RANGE
24-12 AWG
(9X)
11
12
13 Cat. Nos. 4983-DCxxx-03, -DCxxx-05
www.ab.com/catalogs Preferred availability cat. nos. are bold.
8-94 Publication A117-CA001A-EN-P
Bulletin 4983-DC
Surge and Filter Protection
Approximate Dimensions
Note: Dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.
3
2.56
(65.02) 3.72
(94.49)
4
L N
LINE
STATUS
35 mm
DIN RAIL
5
MOUNTING
4.84
(122.94) 6
NC COM NO
LOAD
L N
7
8
WIRE RANGE
26-10 AWG
(9X)
9
10
11
Cat. Nos. 4983-DCxxx-10, -DCxxx-20
12
13
www.ab.com/catalogs Preferred availability cat. nos. are bold.
Publication A117-CA001A-EN-P 8-95