Finder Catalog
Finder Catalog
Automation
Industrial applications
Residential and Commercial
2016-2017
Overview
Series Page
Panel thermostats 7T
Filter fans 7F G
Panel heaters 7H
Movement detectors 18 J
Subminiature DIL
relays 2 A
Electronic
circuit boards
Hi-Fi systems
Printers
Toys
Medical and
dentistry
Hoists and
cranes
Dielectric strength
between open contacts V AC 750
Ambient temperature range °C –40…+85
Environmental protection RT III
Approvals (according to type)
3
30 30 SERIES
SERIES Subminiature DIL relays 2 A
Ordering information
Example: 30 series PCB relay, 2 CO (DPDT) - 2 A contacts, 12 V sensitive DC coil.
A A B C D
3 0 . 2 2 . 7 . 0 1 2 . 0 . 0 . 1 . 0
Series A: Contact material D: Special versions
0 = Standard 0 = Wash tight (RT III)
Type
AgNi + Au
2 = PCB mount
C: Options
B: Contact circuit
No. of poles 1 = None
0 = CO (DPDT)
2 = 2 pole, 2 A
Coil version
7 = Sensitive DC
Coil voltage
See coil specifications
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400 120…240 single phase
Rated insulation voltage V AC 250 125
Pollution degrees 1 2
Insulation between coil and contact set
Type of insulation Basic Basic
Overvoltage category I II
Rated impulse voltage kV (1.2/50 µs) 1.5 1.5
Dielectric strength V AC 1000 1000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category I II
Rated impulse voltage kV (1.2/50 µs) 1.5 1.5
Dielectric strength V AC 1500 1500
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 750/1 750/1
Other data
Bounce time: NO/NC ms 1/3
Vibration resistance (5…55)Hz: NO/NC g 15/15
Shock resistance g 16
Power lost to the environment without contact current W 0.2
with rated current W 0.4
Recommended distance between relays mounted on PCB mm ≥ 5
X-2017, www.findernet.com
4
30 SERIES 30
Subminiature DIL relays 2 A SERIES
Contact specification
F 30 - Electrical life (AC1) v contact current (125 V)
A
Cycles
Note:
The rated current of 2 A corresponds to the limiting continuous current.
Coil specifications
DC coil data - 0.2 W sensitive R 30 - DC coil operating range v ambient temperature
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
5 7.005 3.7 7.5 125 40
6 7.006 4.5 9 180 33
9 7.009 6.7 13.5 405 22
12 7.012 8.4 18 720 16
24 7.024 16.8 36 2880 8.3
48* 7.048 36 72 10000 4.8
* Rated power: 0.23 W 1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
X-2017, www.findernet.com
Subminiature PCB
relays 6 A
Copiers
Hi-Fi systems
Washing
machines
Control
systems
Electronic kits
Medical and
dentistry
Electronic
circuit boards
Programmable
controllers
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
32 SERIES 32
Subminiature PCB relays 6 A SERIES
For outline drawing see page 5 Copper side view Copper side view
Contact specification
Contact configuration 1 CO (SPDT) 1 NO (SPST-NO)
Rated current/Maximum peak current A 6/15 6/15
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230 V AC) VA 250 250
Single phase motor rating (230 V AC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220 V A 3/0.35/0.2 3/0.35/0.2
Minimum switching load mW (V/mA) 500 (10/5) 500 (10/5)
Standard contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) — —
V DC 5 - 12 - 24 - 48 5 - 12 - 24 - 48
Rated power AC/DC VA (50 Hz)/W —/0.2 —/0.2
Operating range AC — —
DC (0.78…1.5)UN (0.78…1.5)UN
Holding voltage AC/DC —/0.4 UN —/0.4 UN
Must drop-out voltage AC/DC —/0.1 UN —/0.1 UN
Technical data
Mechanical life AC/DC cycles —/20 · 106 —/20 · 106
Electrical life at rated load AC1 cycles 50 · 103 50 · 103
Operate/release time ms 6/4 6/2
Insulation between coil
and contacts (1.2/50 µs) kV 5 5
XI-2018, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+85 –40…+85
Environmental protection RT III RT III
Approvals (according to type)
3
32 32 SERIES
SERIES Subminiature PCB relays 6 A
Ordering information
Example: 32 series PCB, 1 NO (SPDT-NO) - 6 A contacts, 24 V sensitive DC coil.
A A B C D
3 2 . 2 1 . 7 . 0 2 4 . 4 . 3 . 0 . 0
Series A: Contact material D: Special versions
4 = Standard AgSnO2 0 = Wash tight (RT III)
Type
2 = PCB mount B: Contact circuit C: Options
0=C O (SPDT) 0 = None
No. of poles 3=N O (SPST)
1 = 1 pole, 6 A
Coil version
7 = Sensitive DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250
Pollution degree 2
Insulation between coil and contact set
Type of insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 5
Dielectric strength V AC 4000
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/10 (changeover) 2/— (normally open)
Vibration resistance (5…55)Hz: NO/NC g 10/10 (changeover) 10/— (normally open)
Shock resistance g 20
Power lost to the environment without contact current W 0.2
with rated current W 0.5
Recommended distance between relays mounte d on PCB mm ≥ 5
XI-2018, www.findernet.com
4
32 SERIES 32
Subminiature PCB relays 6 A SERIES
Contact specification
F 32 - Electrical life (AC) v contact current H 32 - Maximum DC1 breaking capacity
DC voltage (V)
Coil specifications
DC coil data - 0.2 W sensitive R 32 - DC coil operating range v ambient temperature
Nominal Coil code Operating range Resistance Rated coil
voltage consumption
UN Umin Umax R I at UN
V V V Ω mA
5 7.005 3.9 7.5 125 40
12 7.012 9.4 18 720 16
24 7.024 18.7 36 2880 8.3
48 7.048 37.4 72 11520 4
Outline drawing
Types 32.21-4000/4300
XI-2018, www.findernet.com
Ultra-slim PCB
Relays (EMR or SSR)
0.1 - 0.2 - 2 - 6 A
Bottling plant
Packaging
machines
Labelling
machines
Road / tunnel
lighting
Burners,
boilers and
furnaces
Timers and
lighting
controls
Electronic
circuit boards
Programmable
controllers
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
34 SERIES 34
Ultra-Slim electromechanical PCB relays 6 A SERIES
For outline drawing see page 9 Copper side view Copper side view
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/
Maximum peak current A 6/10 6/10
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230 V AC) VA 300 300
Single phase motor rating (230 V AC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220 V A 6/0.2/0.12 6/0.2/0.12
Minimum switching load mW (V/mA) 500 (12/10) 50 (5/2)
Standard contact material AgNi AgNi + Au
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) — —
V DC 5 - 12 - 24 - 48 - 60 5 - 12 - 24 - 48 - 60
Rated power AC/DC VA (50 Hz)/W —/0.17 —/0.17
Operating range AC — —
DC (0.7…1.5)UN (0.7…1.5)UN
Holding voltage AC/DC —/0.4 UN —/0.4 UN
Must drop-out voltage AC/DC —/0.05 UN —/0.05 UN
Technical data
Mechanical life AC/DC cycles —/10 · 106 —/10 · 106
Electrical life at rated load AC1 cycles 60 · 10 3
60 · 103
Operate/release time ms 5/3 5/3
Insulation between coil
and contacts (1.2/50 µs)kV 6 (8 mm) 6 (8 mm)
XI-2018, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+85 –40…+85
Environmental protection RT II RT II
Approvals (according to type)
3
34 34 SERIES
SERIES Ultra-Slim solid state PCB relays (SSR) 0.1 - 6 A
For outline drawing see page 9 Copper side view Copper side view
Output circuit
Contact configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms) A 6/50 2/80
Rated switching voltage V 24 DC 240 AC (50/60 Hz)
Switching voltage range V (1.5…33)DC (12…275)AC
Maximum blocking voltage V 33 —
Repetitive peak off-state voltage Vpk — 800
Rated load DC13 W 36 —
Rated load AC15 VA — 300
Minimum switching current mA 1 35
Max. “OFF-state” leakage current mA 0.001 1.5
Max. “ON-state” voltage drop V 0.4 1.6
Supply specification
Nominal voltage (UN)V DC 5 12 24 60 5 12 24 60
Rated power W 0.035 0.085 0.17 0.21 0.06 0.085 0.17 0.21
Operating range V DC 3.5…12 8…17 16…30 35…72 3.5…10 8…17 16…30 35…72
Control current mA 7 7 7 3.5 12 7 7 3.5
Release voltage V DC 4 4 10 20 1 4 10 20
Technical data
Electrical life at rated load cycles > 106 > 106
Operate/release time ms 0.02/0.2 11/11
Insulation between input and output (1.2/50µs)kV 4 4
Ambient temperature range °C –20…+70* –20…+50*
Environmental protection RT III RT III
XI-2018, www.findernet.com
For outline drawing see page 9 Copper side view Copper side view
Output circuit
Contact configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms) A 0.1/0.5 0.2/10
Rated switching voltage V 48 DC 220 DC
Switching voltage range V (1.5…53)DC (90…256)DC
Maximum blocking voltage V 53 256
Rated load DC13 W 2.4 44
Minimum switching current mA 0.05 0.05
Max. “OFF-state” leakage current mA 0.001 0.001
Max. “ON-state” voltage drop V 1 0.4
Supply specification
Nominal voltage (UN)V DC 24 60 24 60
Rated power W 0.17 0.21 0.17 0.21
Operating range V DC 16…30 35…72 16…30 35…72
Control current mA 7 3.5 7 3.5
Release voltage V DC 10 20 10 20
Technical data
Electrical life at rated load cycles > 106 > 106
Operate/release time ms 0.03/0.6 0.4/2.2
Insulation between input and output (1.2/50µs)kV 4 4
Ambient temperature range °C –20…+70* –20…+70*
Environmental protection RT III RT III
Approvals (according to type)
XI-2018, www.findernet.com
* Note: all technical data relates to using the relay directly on PCB or PCB socket type 93.11.
If the relay is used with 35 mm rail socket types 93.01 and 93.51, refer to the technical data of 38 Series; if used
with types 93.60, 93.61, 93.62, 93.63, 93.64, 93.65, 93.66, 93.67,93.68 and 93.69, refer to the technical data of the
MasterINTERFACE 39 Series.
5
34 34 SERIES
SERIES Ultra-Slim PCB relays
Ordering information
Electromechanical relay (EMR)
Example: 34 series Ultra-Slim electromechanical relay, 1 CO (SPDT) 6 A contacts, 24 V sensitive DC coil.
A
A B C D
3 4 . 5 1 . 7 . 0 2 4 . 0 0 1 0
Series A: Contact material D: Special versions
0 = Standard AgNi 0 = Flux proof (RT II)
Type 4 = AgSnO2 9 = Flat version
5 = Electromechanical type 5=A gNi + Au
C: Options
No. of poles B: Contact circuit 1 = None
1 = 1 pole, 6 A 0=C O (SPDT)
3=N O (SPST)
Coil version
7 = Sensitive DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
3 4 . 8 1 . 7 . 0 2 4 . 9 0 2 4
Series Output circuit
9024 = 6 A - 24 V DC
Type 7048 = 0.1 A - 48 V DC
8 = SSR type 7220 = 0.2 A - 220 V DC
8240 = 2 A - 240 V AC
Output
1 = 1 NO (SPST-NO)
Input circuit
See input specifications
Option = 34.51.7xxx.x019
Environmental protection RT I
6
34 SERIES 34
Ultra-Slim PCB relays SERIES
Electromechanical relay
Technical data
Insulation according to EN 61810-1 A
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50 μs) 6
Dielectric strength V AC 4000
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 1/6
Vibration resistance (5…55)Hz: NO/NC g 10/5
Shock resistance g 20/14
Power lost to the environment without contact current W 0.2
with rated current W 0.5
Recommended distance
between relays mounted on PCB mm ≥ 5
Contact specification
F 34 - Electrical life (AC) v contact current H 34 - Maximum DC1 breaking capacity
DC breaking current (A)
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 60 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
DC coil data R 34 - DC coil operating range v ambient temperature
Nominal Coil code Operating range Resistance Rated coil
voltage consumption
UN Umin Umax R I at UN
V V V Ω mA
5 7.005 3.5 7.5 130 38.4
12 7.012 8.4 18 840 14.2
24 7.024 16.8 36 3350 7.1
XI-2018, www.findernet.com
Input specification
Input data - DC types
Nominal Input Operating range Release Impedance Control
voltage code voltage current
UN Umin Umax I at UN
V V V V Ω mA
5 7.005 3.5 12* 1 715 7*
12 7.012 8 17 4 1715 7
24 7.024 16 30 10 3430 7
60 7.060 35 72 20 17000 3.5
* For 34.81.7.005.8240: UMAX = 10 V, I @ 5 V = 12 mA
Output specification
L 34-1 - Output DC current v ambient temperature L 34 - Output AC current v ambient temperature
34.81.7…9024 34.81.7…8240
Max recommended switching frequency (Cycles/Hour, with 50% Duty-cycle) at ambient temperature 50°C, single mounting
Load 34.81.7xxx.9024 34.81.7xxx.8240 34.81.7xxx.7048 34.81.7xxx.7220
24 V 6 A DC1 180 000 — — —
24 V 3 A DC L/R = 10 ms 5000 — — —
24 V 2 A DC L/R = 40 ms 3600 — — —
24 V 1 A DC L/R = 40 ms 6500 — — —
XI-2018, www.findernet.com
Outline drawings
Type 34.51 Type 34.81
A
XI-2018, www.findernet.com
9
34 93 SERIES
SERIES Sockets and accessories for 34 series relays
For technical data and supply versions, refer to the MasterINTERFACE 39 Series – “Relay interface module”
Accessories
16-way jumper link 093.16 (blue), 093.16.0 (black), 093.16.1 (red)
Dual-purpose plastic separator 093.60
Sheet of marker tags 060.48 and 093.48
Technical data
Rated values 6 A - 250 V
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
Ambient temperature°C −40…+70
XI-2018, www.findernet.com
10
93 SERIES 34
Sockets and accessories for 34 series relays SERIES
Accessories
16-way jumper link 093.16 (blue), 093.16.0 (black), 093.16.1 (red)
Dual-purpose plastic separator 093.60
Terminal doubler 093.62
Sheet of marker tags 060.48 and 093.48
Technical data
Rated values 6 A - 250 V
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
XI-2018, www.findernet.com
11
34 93 SERIES
SERIES Sockets and accessories for 34 series relays
Accessories
20-way jumper link 093.20
Plastic separator 093.01
Sheet of marker tags 093.48
Technical data
Rated values 6 A - 250 V
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
Ambient temperature (UN ≤ 60 V/> 60 V)°C −40…+70/−40…+55
Wire strip lengthmm 10
Max wire size Solid wire and stranded wire
mm2 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
XI-2018, www.findernet.com
12
93 SERIES 34
Sockets and accessories for 34 series relays SERIES
Burners, boilers
and furnaces
Washing machines
Hi-Fi systems
Refrigerators
Automation for
blinds, grilles
and shutters
Electronic
circuit boards
Electronic kits
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
36 SERIES 36
Miniature PCB relays 10 A SERIES
• 1 CO (SPDT), 10 A
• Sugar cube size
• PCB mount
Contact specification
Contact configuration 1 CO (SPDT)
Rated current/Maximum peak current A 10/15 (NO) - 5/10 (NC)
Rated voltage/
Maximum switching voltage V AC 250/277
Rated load AC1 VA 2500 (NO) - 1250 (NC)
Rated load AC15 (230 V AC) VA 500 (NO)
Single phase motor rating (230 V AC) kW 0.37 (NO)
Breaking capacity DC1: 28 V A 10 (NO)
Minimum switching load mW (V/mA) 500 (5/100)
Standard contact material AgSnO2
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) —
V DC 3 - 5 - 6 - 9 - 12 - 18 - 24 - 48
Rated power AC/DC VA (50 Hz)/W —/0.36
Operating range AC —
DC (0.75…1.3)UN
Holding voltage AC/DC —/0.5 UN
Must drop-out voltage AC/DC —/0.1 UN
Technical data
Mechanical life AC/DC cycles —/10 · 106
Electrical life at rated load AC1 cycles 50 · 103
Operate/release time ms 10/5
Insulation between coil
and contacts (1.2/50 µs) kV 3
I-2017, www.findernet.com
Dielectric strength
between open contacts V AC 750
Ambient temperature range °C –40…+85
Environmental protection RT III
Approvals (according to type)
3
36 36 SERIES
SERIES Miniature PCB relays 10 A
Ordering information
Example: 36 series miniature PCB relay, 1 CO (SPDT) - 10 A contacts, 12 V DC coil.
A A B C D
3 6 . 1 1 . 9 . 0 1 2 . 4 0 1 1
Series A: Contact material D: Special versions
4 = AgSnO2 1 = Wash tight (RT III)
Type
1 = PCB mount B: Contact circuit C: Options
0 = CO (SPDT) 1 = None
No. of poles
1 = 1 pole, 10 A
Coil version
9 = DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
36.11 DC 4 0 1 1
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250
Pollution degree 2
Insulation between coil and contact set
Type of insulation Basic
Overvoltage category II
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 750/1.5
Other data
Shock resistance g 10
Bounce time: NO/NC ms 1/6
Vibration resistance (5…55 Hz): NO/NC g 14/8
Power lost to the environment
without contact current W 0.4
with rated current W 1.4
Recommended distance between relays mounted on PCB mm ≥ 5
I-2017, www.findernet.com
4
36 SERIES 36
Miniature PCB relays 10 A SERIES
Contact specification
F 36 - Electrical life (AC) v contact current
A
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
Cycles
Coil specifications
DC coil data R 36 - DC coil operating range v ambient temperature
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
3 9.003 2.2 3.9 25 120
5 9.005 3.7 6.5 70 72
6 9.006 4.5 7.8 100 60
9 9.009 6.7 11.7 225 40
12 9.012 9 15.6 400 30
18 9.018 13.5 23.4 900 20
24 9.024 18 31.2 1600 15
48 9.048 36 62.4 6400 7.5
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
I-2017, www.findernet.com
Medical and
dentistry
Control panels
Toys
Automation for
blinds, grilles
and shutters
Electronic
circuit boards
Vending
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
40 SERIES 40
PCB/Plug-in relays 8 - 10 - 12 - 16 A SERIES
Power relays 1 and 2 pole for direct PCB or 40.31/51 40.52 40.61
socket mount
Type 40.31/51
-- 1 CO 12 A (3.5 mm pin pitch)
-- 1 CO 12 A (5.0 mm pin pitch) A
Type 40.52
-- 2 CO 8 A (5.0 mm pin pitch)
Type 40.61
-- 1 CO 16 A (5.0 mm pin pitch)
• Pin length 3.5 mm for PCB mount
• Pin length 5.3 mm for Plug-in mount
• DC coils (650 mW or 500 mW) • 1 CO 12 A on PCB, 10 A with • 2 CO 8 A • 1 CO 16 A
• Cadmium-free contact material available socket • 5.0 mm pin pitch • 5.0 mm pin pitch
• 8 mm Creepage and Clearance, 6 kV (1.2/50µs) • 3.5 mm pin pitch (40.31), • PCB or 95 Series socket mount • PCB or 95 Series socket mount
between coil and contact 5.0 mm pin pitch (40.51)
• Meets EN 60335-1 glow wire requirements • PCB or 95 Series socket mount
• 95 series sockets for PCB or 35 mm rail
mounting (EN 60715) with Screw, Screwless or
Push-in terminals
• Coil Indication and EMC suppression modules
99 series and Timer module 86.30 options
• Environmental protection:
RT II - flux proof (Standard)
RT III - wash tight (Option)
40.31
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+85 –40…+85 –40…+85
Environmental protection RT II*** RT II*** RT II***
Approvals (according to type)
*** See general technical information “Guidelines for automatic flow solder processes” page II.
3
40 40 SERIES
SERIES PCB/Plug-in relays 8 - 10 - 12 - 16 A
Power relays 1 and 2 pole for direct PCB or 40.31/51 40.52 40.61
socket mount
Type 40.31/51
-- 1 CO 10 A (3.5 mm pin pitch)
A -- 1 CO 10 A (5.0 mm pin pitch)
Type 40.52
-- 2 CO 8 A (5.0 mm pin pitch)
Type 40.61
-- 1 CO 16 A (5.0 mm pin pitch)
• AC or DC coils according to type
• Cadmium-free contact material
• 8 mm Creepage and Clearance, 6 kV (1.2/50µs) • 1 CO 10 A • 2 CO 8 A • 1 CO 16 A
between coil and contact • 3.5 mm pin pitch (40.31), • 5.0 mm pin pitch • 5.0 mm pin pitch
• Meets EN 60335-1 glow wire requirements 5.0 mm pin pitch (40.51) • PCB or 95 Series socket mount • PCB or 95 Series socket mount
• 95 series sockets for PCB or 35 mm rail • PCB or 95 Series socket mount
mounting (EN 60715) with Screw, Screwless or
Push-in terminals
• Coil Indication and EMC suppression modules
99 series and Timer module 86.30 options
• Environmental protection:
RT II - flux proof (Standard)
RT III - wash tight (Option)
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+85 –40…+85 –40…+85
Environmental protection RT II** RT II** RT II**
Approvals (according to type)
** See general technical information “Guidelines for automatic flow solder processes” page II.
4
40 SERIES 40
PCB/Plug-in relays 8 - 10 - 12 - 16 A SERIES
Power relays 1 and 2 pole for direct PCB or 40.62 40.xx.6 40.11
socket mount
Type 40.62
- 2 CO 10A (5.0 mm pin pitch)
- DC coils (650 mW or 500 mW) A
- Meets EN 60335-1 glow wire requirements
Type 40.11
-- 1 CO 10 A - flat pack
-- DC (sensitive) coils
Type 40.xx.6
-- Bistable versions of the types 40.31, 40.51,
40.52 and 40.61 • 2 CO 10 A • Bistable (single coil) • 1 CO 10 A
-- Bistable (single coil) • 5.0 mm pin pitch • 3.5 or 5.0 mm pin pitch • PCB mount 12.7 mm high
• PCB or 95 Series sockets mount • PCB or 95 Series socket mount
• Cadmium-free contact material available
• 8 mm Creepage and Clearance, 6 kV (1.2/50µs)
between coil and contact Bistable version (1 coil) types:
• 95 series sockets for PCB or 35 mm rail mounting
(EN 60715) with Screw, Screwless or Push-in
40.31.6…
terminals
• Environmental protection: 40.51.6…
RT II - flux proof (Standard) 40.52.6…
RT III - wash tight (Option)
40.61.6…
5
40 40 SERIES
SERIES PCB/Plug-in relays 8 - 10 - 12 - 16 A
Ordering information
Example: 40 series PCB relay, 2 CO, 230 V AC coil.
A A B C D
4 0 . 5 2 . 8 . 2 3 0 . 0 0 0 0
Series A: Contact material D: Special versions
Type See table below 0 = Standard
1 = PCB - 3.5 mm pinning, flat B: Contact circuit 1 = Wash tight (RT III)
3 = PCB/Plug-in - 3.5 mm pinning 0 = CO (nPDT) 3 = High temperature (+125 °C) wash
5 = PCB/Plug-in - 5 mm pinning 3 = NO (nPST) tight
6 = PCB/Plug-in - 5 mm pinning C: Options
No. of poles 0 = Pin length 5.3 mm (Plug-in relays)
1 = 1 pole 2 = Pin length 3.5 mm (PCB relays)
2 = 2 pole
Coil version
6 = AC/DC bistable
7 = Sensitive DC, 0.5 W
8 = AC (50/60 Hz)
9 = Standard DC, 0.65 W
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Terminal pin Type Coil version A B C D
PCB relay, 40.11 Sensitive DC 2 (AgCdO) - 4 (AgSnO2) 0 0 0
pin length 3.5 mm
40.31/51 Standard DC/sensitive DC 1 (AgNi) 0-3 2 0-1
40.61 Standard DC/sensitive DC 1 (AgNi) - 2 (AgCdO) 0-3 2 0-1
PCB/Plug-in relay 40.31/51 AC/sensitive DC 0 (AgNi) - 2 (AgCdO) - 5 (AgNi+Au) 0-3 0 0-1
pin length 5.3 mm
40.31/51 Standard DC 0 (AgNi) - 2 (AgCdO) - 5 (AgNi+Au) 0-3 0 0-1-3
40.52 AC/sensitive DC 0 (AgNi) - 2 (AgCdO) - 5 (AgNi+Au) 0-3 0 0-1
40.52 Standard DC 0 (AgNi) - 2 (AgCdO) - 5 (AgNi+Au) 0-3 0 0-1-3
40.61 AC/sensitive DC 0 (AgCdO) - 4 (AgSnO2) 0-3 0 0-1
40.61 Standard DC 0 (AgCdO) - 4 (AgSnO2) 0-3 0 0-1-3
40.62 Standard DC/sensitive DC 0 (AgNi) - 4 (AgSnO2) 0 0 0-1
40.31/51/52 Bistable 0 (AgNi) 0 0 0
40.61 Bistable 0 (AgCdO) 0 0 0 VIII-2019, www.findernet.com
6
40 SERIES 40
PCB/Plug-in relays 8 - 10 - 12 - 16 A SERIES
Technical data
Insulation according to EN 61810-1
1 pole 2 pole
A
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm) Reinforced (8 mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 6
Dielectric strength V AC 4000 4000
Insulation between adjacent contacts (40.52, page 4)
Type of insulation — Basic
Overvoltage category — II
Rated impulse voltage kV (1.2/50 µs) — 2.5
Dielectric strength V AC — 2000
Insulation between adjacent contacts (40.52, page 3 + 40.62)
Type of insulation — Basic
Overvoltage category — III
Rated impulse voltage kV (1.2/50 µs) — 4
Dielectric strength V AC — 2500
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/5
Vibration resistance (10…150)Hz: NO/NC g 20/5 (1 changeover) 15/4 (2 changeover)
Shock resistance NO/NC g 20/13 (1 changeover) 20/12 (2 changeover)
Power lost to the environment without contact current W 0.65
with rated current W 1.2 (40.11/31/51) 2 (40.61/52/62)
Recommended distance between relays mounted on PCB mm ≥ 5
VIII-2019, www.findernet.com
7
40 40 SERIES
SERIES PCB/Plug-in relays 8 - 10 - 12 - 16 A
Contact specification
F 40.1 - Electrical life (AC) v contact current F 40.2 - Electrical life (AC) v contact current
A Types 40.31/51/61 (page 3) Type 40.52 (page 3)
Cycles
Limit for 40.31/51 Inductive load AC15
F 40.3 - Electrical life (AC) v contact current F 40.4 - Electrical life (AC) v contact current
Types 40.31/51/61 (page 4) Type 40.52 (page 4)
Cycles
F 40.5 - Electrical life (AC) v contact current F 40.6 - Electrical life (AC) v contact current
Type 40.11 (page 5) Type 40.62 (page 5)
Cycles
8 12
VIII-2019, www.findernet.com
8
40 SERIES 40
PCB/Plug-in relays 8 - 10 - 12 - 16 A SERIES
Contact specification
H 40.1 -Maximum DC1 breaking capacity H 40.2 - Maximum DC1 breaking capacity
Types 40.31/51/52/61 (page 3) Types 40.31/51/52/61 (page 4) and 40.11 (page 5) A
single contact
single contact
2 contacts in series
single contact
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
VIII-2019, www.findernet.com
9
40 40 SERIES
SERIES PCB/Plug-in relays 8 - 10 - 12 - 16 A
Coil specifications
DC coil data - 0.65 W standard (types 40.31/51/52/61/62) DC coil data - 0.5 W sensitive (types 40.31/51/52/61/62)
A Nominal Coil Operating range Resistance Rated coil Nominal Coil Operating range Resistance Rated coil
voltage code consumption voltage code consumption
UN Umin Umax R I at UN UN Umin* Umax R I at UN
V V V Ω mA V V V Ω mA
5 9.005 3.65 7.5 38 130 5 7.005 3.7 7.5 50 100
6 9.006 4.4 9 55 109 6 7.006 4.4 9 75 80
7 9.007 5.1 10.5 75 94 7 7.007 5.1 10.5 100 70
9 9.009 6.6 13.5 125 72 9 7.009 6.6 13.5 160 56
12 9.012 8.8 18 220 55 12 7.012 8.8 18 288 42
14 9.014 10.2 21 300 47 14 7.014 10.2 21 400 35
18 9.018 13.1 27 500 36 18 7.018 13.2 27 650 27.7
21 9.021 15.3 31.5 700 30 21 7.021 15.4 31.5 900 23.4
24 9.024 17.5 36 900 27 24 7.024 17.5 36 1150 21
28 9.028 20.5 42 1200 23 28 7.028 20.5 42 1600 17.5
36 9.036 26.3 54 2000 18 36 7.036 26.3 54 2600 13.8
48 9.048 35 72 3500 14 48 7.048 35 72 4800 10
60 9.060 43.8 90 5500 11 60 7.060 43.8 90 7200 8.4
90 9.090 65.7 135 12500 7.2 90 7.090 65.7 135 16200 5.6
110 9.110 80.3 165 18000 6.2 110 7.110 80.3 165 23500 4.7
125 9.125 91.2 188 23500 5.3 125 7.125 91.2 188 32000 3.9
* Umin = 0.8 UN for 40.61
AC coil data (types 40.31/51/52/61) AC/DC coil data - bistable (types 40.31/51/52/61)
Nominal Coil Operating range Resistance Rated coil Nominal Coil Operating range Resistance Rated coil DC: Release
voltage code consumption voltage code consumption resistance**
UN Umin Umax R I at UN (50 Hz) UN Umin Umax R I at UN RDC
V V V Ω mA V V V Ω mA Ω
6 8.006 4.8 6.6 21 168 5 6.005 4 5.5 23 215 37
12 8.012 9.6 13.2 80 90 6 6.006 4.8 6.6 33 165 62
24 8.024 19.2 26.4 320 45 12 6.012 9.6 13.2 130 83 220
48 8.048 38.4 52.8 1350 21 24 6.024 19.2 26.4 520 40 910
60 8.060 48 66 2100 16.8 48 6.048 38.4 52.8 2100 21 3,600
110 8.110 88 121 6900 9.4 110 6.110 88 121 11000 10 16,500
120 8.120 96 132 9000 8.4
** RDC = Resistance in DC, RAC = 1.3 x RDC 1 W
230 8.230 184 253 28000 5
240 8.240 192 264 31500 4.1
VIII-2019, www.findernet.com
10
40 SERIES 40
PCB/Plug-in relays 8 - 10 - 12 - 16 A SERIES
Contact specification
R 40 - DC coil operating range v ambient temperature R 40 - DC coil operating range v ambient temperature
Standard coil Sensitive coil, types 40.31/51/52/61/62
A
40.61
40.31/51/52/62
R 40 - DC coil operating range v ambient temperature R 40 - AC coil operating range v ambient temperature
Sensitive coil, type 40.11
On momentary closure of the SET switch the relay is magnetised through On momentary closure of the SET switch the relay is magnetised and the
the diode and the relay contacts transfer to the set position and remain in relay contacts transfer to the set position and remain in this position.
this position. On momentary closure of the RESET switch the relay is demagnetised
On momentary closure of the RESET switch the relay is demagnetised through limiting resistor (RDC) and the contacts return to the reset position.
VIII-2019, www.findernet.com
through limiting resistor (RAC) and the contacts return to the reset position.
Notes: T he minimum SET or RESET impulse time is 20 ms. The maximum time can be continuous. In practice, always ensure that the SET and RESET
contacts cannot be operated simultaneously.
11
40 40 SERIES
SERIES PCB/Plug-in relays 8 - 10 - 12 - 16 A
Outline drawings
Types 40.31/51/52/61/62 (page 3 and 5) Types 40.31/51/52/61 (page 4) Type 40.11 (page 5)
VIII-2019, www.findernet.com
12
95 SERIES 40
Socket overview for 40 series relays SERIES
13
40 95 SERIES
SERIES Socket and accessories for 40 series relays
11 COM
Total socket current (A)
14 NO
12 NC
A2 A1 COIL
95.P3
097.58
097.52
VIII-2019, www.findernet.com
14
95 SERIES 40
Socket and accessories for 40 series relays SERIES
A
097.42
097.00
99.02 coil indication and EMC suppression modules for 95.P3 and 95.P5 sockets
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
99.02 LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
LED + Varistor (6…24)V DC/AC 99.02.0.024.98
LED + Varistor (28…60)V DC/AC 99.02.0.060.98
DC Modules with LED + Varistor (110…240)V DC/AC 99.02.0.230.98
non-standard polarity RC circuit (6…24)V DC/AC 99.02.0.024.09
(+A2) on request. RC circuit (28…60)V DC/AC 99.02.0.060.09
RC circuit (110…240)V DC/AC 99.02.0.230.09
Residual current by-pass (110…240)V AC 99.02.8.230.07
VIII-2019, www.findernet.com
15
40 95 SERIES
SERIES Socket and accessories for 40 series relays
Screw terminal (Box clamp) socket panel or 35 mm rail mount 95.03 (blue) 95.03.0 (black) 95.05 (blue) 95.05.0 (black)
For relay type 40.31 40.51, 40.52, 40.61, 40.62
Accessories
A Metal retaining clip 095.71
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 095.01 095.01.0 095.01 095.01.0
95.05
Approvals 8-way jumper link 095.18 095.18.0 095.18 095.18.0
(according to type): Marker tag holder (for tags 060.48 type) 097.00
Identification tag 095.00.4
Modules (see table below) 99.02
Timer modules (see table below) 86.30
ertain relay/socket
C Sheet of marker tags for plastic retaining and release clip
095.01 and for marker tag holder 097.00, 48 tags, 6 x 12 mm,
combinations
for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V*
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV
Protection category IP 20
095.01 Ambient temperature °C –40…+70 (see diagram L95)
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 95.03 and 95.05 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
060.48 * For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
L 95 - Total socket current v ambient temperature
Total socket current (A)
11 COM
14 NO
12 NC
A2 A1 COIL
PEAN
8-way jumper link for 95.03 and 95.05 sockets 095.18 (blue) 095.18.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.18
16
95 SERIES 40
Socket and accessories for 40 series relays SERIES
Screwless terminal socket panel or 35 mm rail mount 95.55 (blue) 95.55.0 (black)
For relay type 40.51, 40.52, 40.61, 40.62
Accessories
Metal retaining clip 095.71 A
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 095.91.3
Modules (see table below) 99.02
95.55 Timer modules (see table below) 86.30
Approvals Sheet of marker tags for plastic retaining and release clip
(according to type): 095.91.3, 48 tags, 6 x 12 mm, for CEMBRE thermal transfer
printers 060.48
Technical data
Rated values 10 A - 250 V*
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV
Protection category IP 20
Ambient temperature °C –25…+70 (see diagram L95)
Wire strip length mm 8
Max. wire size for 95.55 socket solid wire stranded wire
095.91.3
mm2 2 x (0.5…1.5) 2 x (0.5…1.5)
AWG 2 x (21…18) 2 x (21…18)
* For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
060.48
99.02 coil indication and EMC suppression modules for 95.55 socket
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
99.02 LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
(according to type):
LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
LED + Varistor (6…24)V DC/AC 99.02.0.024.98
VIII-2019, www.findernet.com
Screw terminal (Box clamp) socket panel or 35 mm rail mount 95.83.3 (blue) 95.83.30 (black) 95.85.3 (blue) 95.85.30 (black)
For relay type 40.31 40.51, 40.52, 40.61, 40.62
Accessories
A Metal retaining clip 095.71
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 095.91.3 095.91.30 095.91.3 095.91.30
95.85.3 8-way jumper link 095.08 095.08.0 095.08 095.08.0
Approvals Identification tag 095.00.4
(according to type): Modules (see table below) 99.80
Marker tag holder 097.00
Sheet of marker tags for plastic retaining and release clip
095.91.3, 48 tags, 6 x 12 mm, for CEMBRE thermal transfert
printer 060.48
Technical data
Rated values 10 A - 250 V*
095.91.3
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV 2 kV
Protection category IP 20
Ambient temperature °C –40…+70 (see diagram L95)
Screw torque Nm 0.5
Wire strip length mm 7
Max. wire size for 95.83.3 and 95.85.3 sockets solid wire stranded wire
060.48 mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
* For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
L 95 - Total socket current v ambient temperature
Total socket current (A)
95.83.3 95.85.3
PEAN
8-way jumper link for 95.83.3 and 95.85.3 sockets 095.08 (blue) 095.08.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.08
99.80 coil indication and EMC suppression modules for 95.83.3 and 95.85.3 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.80.3.000.00
LED(6…24)V DC/AC 99.80.0.024.59
LED(28…60)V DC/AC 99.80.0.060.59
LED(110…240)V DC/AC 99.80.0.230.59
99.80 LED + Diode (+A1, standard polarity) (6…24)V DC 99.80.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.80.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.80.9.220.99
LED + Varistor (6…24)V DC/AC 99.80.0.024.98
LED + Varistor (28…60)V DC/AC 99.80.0.060.98
* Modules in Black LED + Varistor (110…240)V DC/AC 99.80.0.230.98
housing are available
VIII-2019, www.findernet.com
18
95 SERIES 40
Socket and accessories for 40 series relays SERIES
Screw (Box clamp) terminal socket panel or 35 mm rail mount 95.93.3 (blue) 95.93.30 (black) 95.95.3 (blue) 95.95.30 (black)
For relay type 40.31 40.51, 40.52, 40.61, 40.62
Accessories
Metal retaining clip 095.71 A
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 095.91.3 095.91.30 095.91.3 095.91.30
8-way jumper link 095.08 095.08.0 095.08 095.08.0
95.95.3 Identification tag 095.00.4
Approvals Modules (see table below) 99.80
(according to type): Sheet of marker tags for plastic retaining and release clip
095.91.3 and for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V*
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV
095.91.3 Protection category IP 20
Ambient temperature °C –40…+70 (see diagram L95)
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 95.93.3 and 95.95.3 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
060.48
* For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
L 95 - Total socket current v ambient temperature
Total socket current (A)
95.93.3 95.95.3
PEAN
8-way jumper link for 95.93.3 and 95.95.3 sockets 095.08 (blue) 095.08.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.08
99.80 coil indication and EMC suppression modules for 95.93.3 and 95.95.3 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.80.3.000.00
LED(6…24)V DC/AC 99.80.0.024.59
LED(28…60)V DC/AC 99.80.0.060.59
LED(110…240)V DC/AC 99.80.0.230.59
99.80 LED + Diode (+A1, standard polarity) (6…24)V DC 99.80.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.80.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.80.9.220.99
LED + Varistor (6…24)V DC/AC 99.80.0.024.98
LED + Varistor (28…60)V DC/AC 99.80.0.060.98
* Modules in Black LED + Varistor (110…240)V DC/AC 99.80.0.230.98
housing are available
RC circuit (6…24)V DC/AC 99.80.0.024.09
VIII-2019, www.findernet.com
on request.
Green LED is standard. RC circuit (28…60)V DC/AC 99.80.0.060.09
Red LED available on RC circuit (110…240)V DC/AC 99.80.0.230.09
request. Residual current by-pass (110…240)V AC 99.80.8.230.07
19
40 95 SERIES
SERIES Socket and accessories for 40 series relays
Screw terminal (Box clamp) socket panel or 35 mm rail mount 95.63 95.65
For relay type 40.31 40.51, 40.52, 40.61, 40.62
Accessories
A Metal retaining clip 095.71
8-way jumper link 095.08 095.08
95.63
Approvals Modules (see table below) 99.01 —
(according to type): Technical data
Rated values 10 A - 250 V*
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV 2 kV
Protection category IP 20
Ambient temperature °C –40…+70 (see diagram L95)
Screw torque Nm 0.5
Wire strip length mm 7
Max. wire size for 95.63 and 95.65 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
95.65
Approvals AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
(according to type): * For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
95.63 95.65
PEAN
8-way jumper link for 95.63 and 95.65 sockets 095.08 (blue)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.08
99.01 coil indication and EMC suppression modules for type 95.63 socket
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.01.3.000.00
Diode (+A2, non-standard polarity) (6…220)V DC 99.01.2.000.00
LED(6…24)V DC/AC 99.01.0.024.59
LED(28…60)V DC/AC 99.01.0.060.59
99.01
LED(110…240)V DC/AC 99.01.0.230.59
Approvals
LED + Diode (+A1, standard polarity) (6…24)V DC 99.01.9.024.99
(according to type):
LED + Diode (+A1, standard polarity) (28…60)V DC 99.01.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.01.9.220.99
LED + Diode (+A2, non-standard polarity) (6…24)V DC 99.01.9.024.79
* Modules in Black
LED + Diode (+A2, non-standard polarity) (28…60)V DC 99.01.9.060.79
housing are available
LED + Diode (+A2, non-standard polarity) (110…220)V DC 99.01.9.220.79
on request.
LED + Varistor (6…24)V DC/AC 99.01.0.024.98
Green LED is standard.
LED + Varistor (28…60)V DC/AC 99.01.0.060.98
Red LED available on
VIII-2019, www.findernet.com
20
95 SERIES 40
Socket and accessories for 40 series relays SERIES
PCB socket 95.13.2 (blue) 95.13.20 (black) 95.15.2 (blue) 95.15.20 (black)
For relay type 40.31 40.51, 40.52, 40.61, 40.62
Accessories
95.13.2 Metal retaining clip (supplied with socket - A
packaging code SMA) 095.51
Plastic retaining clip 095.52
Technical data
Rated values 12 A - 250 V 10 A - 250 V*
Dielectric strength between coil and contacts (1.2/50 μs) 6 kV
95.15.2 Protection category IP 20
Approvals Ambient temperature °C –40…+70
(according to type): * For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
With the relay 40.51 the change-over contact will be 21-12-14.
40.31 40.51
13
7.5 12 14 22 24
3.5
A1 12 11 14
30
11 21
20
3.5
A2 22 21 24
A1 A2
1.5
40.52
95.13.2 5 5 95.15.2
95.13. 2
=
Copper side view Copper side view
12 .4
7.5
1.5
=
3 20 6
29
40.61
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 5 . P 5 S P A
A Standard packaging
Medical and
dentistry
Industrial robots
Building
automation
Control
systems
Timers and
lighting
controls
Electronic
circuit boards
Vending
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
41 SERIES 41
Low profile PCB relays 8 - 12 - 16 A SERIES
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range AC/DC °C –40…+70/–40… +85 –40…+70/–40… +85 –40…+70/–40… +85
Environmental protection RT II RT II RT II
Approvals (according to type)
3
41 41 SERIES
SERIES Bistable low profile PCB relays 8 - 16 A
For outline drawing see page 9 Copper side view Copper side view
Contact specification
Contact configuration 2 CO (DPDT) 1 CO (SPDT)
Rated current/
Maximum peak current (IN/Imax)A 8/15 16/30
Rated voltage/
Maximum switching voltage (UN/Umax)V AC 250/400 250/400
Rated load AC1 VA 2000 4000
Rated load AC15 (230 V AC)VA 350 750
Single phase motor rating (230 V AC)kW 0.37 0.55
Breaking capacity DC1: 30/110/220 VA 8/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 500 (5/100) 500 (5/100)
Standard contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN) V DC 5 - 12 - 24 5 - 12 - 24
Rated power (PN)W 0.65 0.65
Operating range DC (0.7…1.1)UN (0.7…1.1)UN
Min. impulse duration ms 20 20
Max. impulse duration s 30 30
Technical data
Mechanical life DC cycles 5 · 106 5 · 106
Electrical life at rated load AC1 cycles 30 · 103 30 · 103
Operate/release time ms 10/5 10/10
Insulation between coil
and contacts (1.2/50 μs) kV 6 (10 mm) 6 (10 mm)
XI-2018, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+85 –40…+85
Environmental protection RT II RT II
Approvals (according to type)
4
41 SERIES 41
Low profile PCB relays (SSR) 3 - 5 A SERIES
For outline drawing see page 9 Copper side view Copper side view
Output circuit
Contact configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms) A 5/40 3/40
Rated voltage/
Maximum blocking voltage V (24/35)DC (240/—)AC
Switching voltage range V (1.5…24)DC (12…275)AC
Repetitive peak off-state voltage Vpk — 600
Minimum switching current mA 1 50
Max. “OFF-state” leakage current mA 0.01 1
Max. “ON-state” voltage drop V 0.3 1.1
Input circuit
Nominal voltage V DC 12 24 12 24
Operating range V DC 8…17 14…32 8…17 14…32
Control current mA 5.5 9 8.8 9
Release voltage V DC 4 9 4 9
Impedance Ω 1550 2600 1030 2600
Technical data
Operate/release time ms 0.05/0.25 10/10
Dielectric strength
between input/output V AC 2500 2500
Ambient temperature range °C –20…+60 –20…+60
Environmental protection RT III RT III
Approvals (according to type)
XI-2018, www.findernet.com
5
41 41 SERIES
SERIES Low profile PCB relays
Ordering information
Electromechanical relay (EMR)
Example: 41 series low-profile PCB relay, 2 CO (DPDT), 24 V DC coil.
A
A B C D
4 1 . 5 2 . 9 . 0 2 4 . 0 0 1 0
Series A: Contact material D: Special versions
0 = Standard AgNi 0 = Flux proof (RT II)
Type 4 = AgSnO2 1 = Wash tight (RT III)
3 = PCB - 3.5 mm pinning 5=A gNi + Au 6 = Bistable version (RT II)
5 = PCB - 5.0 mm pinning
6 = PCB - 5.0 mm pinning B: Contact circuit C: Options
0=C O (nPDT) 0 = Production line 0
No. of poles 3=N O (nPST) 1 = Production line 1
1 = 1 pole for
41.31, 12 A
41.61, 16 A
2 = 2 pole for
41.52, 8 A
Coil version
6 = DC bistable, 2 coils
8 = AC
9 = DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
4 1 . 8 1 . 7 . 0 2 4 . 9 0 2 4
Series Output circuit
9024 = 5 A - 24 V DC
Type 8240 = 3 A - 240 V AC
8 = SSR type
Output
1 = 1 NO (SPST-NO)
Input circuit
See coil specifications
XI-2018, www.findernet.com
6
41 SERIES 41
Low profile PCB relays SERIES
Electromechanical relay
Technical data
Insulation according to EN 61810-1
A
1 pole 1 pole bistable 2 pole 2 pole bistable
Nominal voltage of supply system V AC 230/400 230/400 230/400 230/400
Rated insulation voltage V AC 250 400 250 250 400 250
Pollution degree 3 2 2 3 2 2
Insulation between coil and contact set
Reinforced Reinforced Reinforced Reinforced
Type of insulation
(8 mm) (10 mm) (8 mm) (10 mm)
Overvoltage category III III III III
Rated impulse voltage kV (1.2/50 μs) 6 6 6 6
Dielectric strength V AC 4000 4000 4000 4000
Insulation between adjacent contacts
Type of insulation — — Basic Basic
Overvoltage category — — III III
Rated impulse voltage kV (1.2/50 μs) — — 4 4
Dielectric strength V AC — — 2000 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 4/6 (monostable) - 2/10 (bistable)
Vibration resistance (5…55)Hz: NO/NC g 15/2 (monostable) - 5/3 (bistable)
Shock resistance g 16 (monostable) - 10 (bistable)
Power lost to the environment without contact current W 0.4 (monostable)
with rated current W 1.7 (41.31) 1.2 (41.52) 1.8 (41.61)
Recommended distance
between relays mounted on PCB mm ≥ 5
XI-2018, www.findernet.com
7
41 41 SERIES
SERIES Low profile PCB relays
Contact specification
F 41 - Electrical life (AC) v contact current (monostable) F 41 - Electrical life (AC) v contact current (monostable)
Types 41.31/61 Type 41.52
A
Resistive load - cosφ = 1
Resistive load - cosφ = 1 Inductive load - cosφ = 0.4
Inductive load - cosφ = 0.4
Cycles
Cycles
limit for 41.31
F 41 - Electrical life (AC) v contact current (bistable) H 41- Maximum DC1 breaking capacity
1 pole
2 pole
single contact
DC voltage (V)
V V V V Ω mW
5 6.005 3.5 3.5 5.5 38 650
12 6.012 8.4 8.4 13.2 220 650
24 6.024 16.8 16.8 26.4 885 650
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
8
41 SERIES 41
Low profile PCB relays SERIES
Input specification
Input data - DC types
Nominal Input Operating range Release Impedance Control
voltage code voltage current
UN Umin Umax I at UN
V V V V Ω mA
12 7.012 8 17 4 1550 5.5
24 7.024 14 32 9 2600 9
Output specification
L 41 - Output current v ambient temperature L 41 - Output current v ambient temperature
SSR - 5 A DC output types SSR - 3 A AC output types
Output current
Output current
Outline drawings
Types 41.31/52/61 Types 41.52.6.xxx/41.61.6.xxx Types 41.81-9024/41.81-8240
XI-2018, www.findernet.com
9
41 93 SERIES
SERIES Sockets and accessories for 41 series relays
10
93 SERIES 41
Sockets and accessories for 41 series relays SERIES
Accessories
PEAN
8-way jumper link for 93.02 and 93.52 sockets 093.08 (blue) 093.08.0 (black) 093.08.1 (red)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
093.08
Approvals
(according to type):
060.48
11
41 93 SERIES
SERIES Sockets and accessories for 41 series relays
13
7.5
3.5
30
20
3.5
95.13.2 95.15.2
95.13.
Copper side2view Copper side view
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 5 . 1 3 . 2 S L A
A Standard packaging
Medical and
dentistry
Alarm systems
Air conditioners
Burners,
boilers and
furnaces
Electric and
electronic toys
and games
Electronic
circuit boards
Vending
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
43 SERIES 43
Low profile PCB relays 10 - 16 A SERIES
For outline drawing see page 5 Copper side view Copper side view Copper side view
Contact specification
Contact configuration 1 CO (SPDT) 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current/Maximum peak current A 10/15 10/15 16/25
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 2500 2500 4000
Rated load AC15 (230 V AC) VA 500 500 750
Single phase motor rating (230 V AC) kW — — —
Breaking capacity DC1: 30/110/220 V A 10/0.3/0.12 10/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) — — —
V DC 3 - 6 - 9 - 12 - 18 - 24 - 36 - 48 3 - 6 - 9 - 12 - 18 - 24 - 36 - 48 12 - 24 - 48
Rated power AC/DC VA (50 Hz)/W —/0.25 —/0.25 —/0.4
Operating range AC — — —
DC (0.7…1.5)UN (0.7…1.5)UN (0.7…1.2)UN
Holding voltage AC/DC —/0.4 UN —/0.4 UN —/0.4 UN
Must drop-out voltage AC/DC —/0.05 UN —/0.05 UN —/0.05 UN
Technical data
Mechanical life AC/DC cycles —/10 · 106 —/10 · 106 —/10 · 106
Electrical life at rated load AC1 cycles 100 · 103 100 · 103 50 · 103
Operate/release time ms 6/4 6/2 6/2
Insulation between coil
and contacts (1.2/50 µs) kV 6 (10 mm) 6 (10 mm) 6 (10 mm)
IX-2018, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+85 –40…+85 –40…+85
Environmental protection RT II RT II RT II
Approvals (according to type)
3
43 43 SERIES
SERIES Low profile PCB relays 10 - 16 A
Ordering information
Example: 43 series low-profile PCB relay, 1 CO (SPDT), 24 V DC coil.
A A B C D
4 3 . 4 1 . 7 . 0 2 4 . 2 0 0 . 0
Series A: Contact material D: Special versions
0 = AgNi 0 = Flux proof (RT II)
Type 2 = AgCdO 1 = Wash tight (RT III)
4 = PCB - 3.2 mm pinning 4 = AgSnO2
(CO/SPDT, 10 A) 5=A gNi + Au C: Options
PCB - 5 mm pinning 0 = None
(NO/SPST-NO, 10 A) B: Contact circuit
6 = PCB - 5 mm pinning 0=C O (SPDT) - (for 43.41 only)
(NO/SPST-NO, 16 A) 3=N O (SPST)
No. of poles
1 = 1 pole
Coil version
7 = Sensitive DC (only for 43.41)
Selecting features and options: only combinations in the same row are possible.
9 = DC (only for 43.61)
Preferred selections for best availability are shown in bold.
Coil voltage
Type Coil version A B C D
See coil specifications
43.41 sensitive DC 0-2-4-5 0-3 0 0-1
43.61 DC 0-2-4 3 0 0
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of insulation Reinforced (10 mm)
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 3/6
Vibration resistance (5…55)Hz: NO/NC g 15/3
Shock resistance g 15
Power lost to the environment without contact current W 0.25 (43.41) 0.4 (43.61)
with rated currentW 1.3 (43.41) 2 (43.61)
Recommended distance between relays mounted on PCB mm ≥ 5
IX-2018, www.findernet.com
4
43 SERIES 43
Low profile PCB relays 10 - 16 A SERIES
Contact specification
F 43 - Electrical life (AC) v contact current H 43 - Maximum DC1 breaking capacity
DC voltage (V)
Coil specifications
DC coil data - 0.25 W sensitive (type 43.41) R 43 - DC coil operating range v ambient temperature
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
3 7.003 2.2 4.5 36 83.5
6 7.006 4.2 9 150 40
9 7.009 6.5 13.5 324 27.7
12 7.012 8.4 18 580 20.7
18 7.018 13 27 1300 13.8
24 7.024 16.8 36 2200 10.9
36 7.036 25.2 54 5200 6.9
48 7.048 33.6 72 9200 5.2
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
DC coil data - 0.4 W standard (type 43.61)
Outline drawings
Type 43.41 Types 43.41-0300/43.61-0300
IX-2018, www.findernet.com
5
43 95 SERIES
SERIES Sockets and accessories for 43 series relays
PCB socket (for changeover contacts only) 95.23 (blue) 95.23.0 (black)
For relay type 43.41 43.41
Accessories
A 95.23 Metal retaining clip
Approvals (supplied with socket - packaging code SNA) 095.43
(according to type): Technical data
Rated values 10 A - 250 V
Insulation 6 kV (1.2/50 µs) between coil and contacts
Protection category IP 20
Ambient temperature °C –40…+70
43.41
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 5 . 2 3 S N A
A Standard packaging
Burners, boilers
and furnaces
Film projectors
Infrared and
microwave
ovens
Jacuzzis and
hot tubs
Electronic
circuit boards
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
45 SERIES 45
Miniature PCB relays 10 - 16 A SERIES
45.31…x310 45.31…0610
(1 NO/SPST-NO) (1 NO/SPST-NO)
Dielectric strength
between open contacts V AC 2500 3000
Ambient temperature range °C –40…+105 –40…+105
Environmental protection RT II RT II
Approvals (according to type)
3
45 45 SERIES
SERIES Miniature PCB relays 16 A
45.71…0310
(1 NO)/(SPST-NO)
45.91…0310
(1 NO/SPST-NO)
45.71…0410
(1 NC)/(SPST-NC)
Dielectric strength
between open contacts V AC 1000 2500
Ambient temperature range °C –40…+125 –40…+125
Environmental protection RT II RT II
Approvals (according to type)
4
45 SERIES 45
Miniature PCB relays 10 - 16 A SERIES
Ordering information
Example: 4
5 series for PCB relay + Faston 250, 1 NO (SPST-NO), 12 V DC coil.
A B C D
A
4 5 . 7 1 . 7 . 0 1 2 . 0 3 1 0
Series A: Contact material D: Special versions
0 = S tandard AgCdO 0 = Flux proof (RT II)
Type for 45.71, 1 = Wash tight (RT III) 45.71
3 = PCB mount, ≥ 3 mm or ≥ 3.6 mm Standard AgNi and 45.91 only
contact gap for 45.31 and 45.91
7 = PCB + Faston 250 mount 1 = AgNi C: Options
9 = PCB + Faston 250 mount, ≥ 3 mm 2 = AgCdO 1 = None
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Technical data
Insulation according to EN 61810-1
45.71 45.31 / 45.91
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltageV AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm) Reinforced (8 mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 6
Dielectric strength V AC 4000 4000
Insulation between open contacts
Type of disconnection Micro-disconnection Full-disconnection
Overvoltage category — III
Rated impulse voltage kV (1.2/50 µs) — 4
Dielectric strength V AC/kV (1.2/50 µs) 1000/1.5 2500/4
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data 45.71 45.31 / 45.91
Bounce time: NO/NC ms 3/3 2/—
Vibration resistance (10…150)Hz: NO/NC g 20/10 20/—
XII-2018, www.findernet.com
Shock resistance g 20
Power lost to the environment without contact current W 0.4
with rated current W 1.8
Recommended distance between relays mounted on PCB mm ≥ 5
5
45 45 SERIES
SERIES Miniature PCB relays 10 - 16 A
Contact specification
F 45 - Electrical life (AC) v contact current F 45 - Electrical life (AC) v contact current
Type 45.71 Type 45.31/45.91
A
Resistive load - cosφ = 1
Cycles
H 45 - Maximum DC1 breaking capacity
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100 · 103 cycles (45.71) and
≥ 30 · 103 cycles (45.31, 45.91) can be expected.
DC breaking current (A)
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC voltage (V)
Coil specifications
DC coil data - 0.36 W sensitive DC coil data - 0.55 W standard
Nominal Coil Operating range Resistance Rated coil Nominal Coil Operating range Resistance Rated coil
voltage code consumption voltage code consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN
V V V Ω mA V V V Ω mA
6 7.006 4.2 7.2 100 60 6 9.006 4.2 7.2 72 83
12 7.012 8.4 14.4 400 30 12 9.012 8.4 14.4 300 40
24 7.024 16.8 28.8 1600 15 24 9.024 16.8 28.8 1150 21
48 7.048 33.6 57.6 6400 7.5 48 9.048 33.6 57.6 4400 11
60 7.060 42 72 10000 6 60 9.060 42 72 7200 8.3
6
45 SERIES 45
Miniature PCB relays 10 - 16 A SERIES
Outline drawings
Type 45.31 Types 45.71/91
A
XII-2018, www.findernet.com
Miniature Industrial
relay 8 - 16 A
Automation for
blinds, grilles
and shutters
Shipyards
Road / tunnel
lighting
Hoists and
cranes
Bottling plant
Control panels
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)
3
46 46 SERIES
SERIES Miniature industrial relays 8 to16 A
Ordering information
Example: 46 series Miniature industrial relay, 1 CO, 24 V DC coil, lockable test button and mechanical indicator.
A A B C D
4 6 . 6 1 . 9 . 0 2 4 . 0 0 4 0
Series A: Contact material D: Special versions
0 = AgNi 0 = S tandard
Type 4 = AgSnO2 (46.61 only)
5 = Spade/blade solder terminal 5 = AgNi + Au C: Options
(2.5 x 0.5)mm 2 = M echanical indicator
6 = Spade/blade terminal B: Contact circuit 4 = L ockable test button +
Faston 187 (4.8 x 0.5)mm 0 = CO (nPDT) mechanical indicator
54 = L ockable test button + LED (AC) +
No. of poles mechanical indicator
1 = 1 pole, 16 A 74 = L ockable test button + double LED
2 = 2 poles, 8 A (DC non-polarized) + mechanical
indicator
Coil version
9 = DC
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Descriptions: Options
C: Option 54 C: Option 74
LED (AC) LED (DC, non-polarized)
EAN
OP
2
EUR
T
N
T E
EUR
P A
Lockable test button and mechanical flag indicator (0040, 0054, 0074)
OP
EAN
(in addition to the above function), when the test button is pushed and rotated, the
contacts are latched in the operating state, and remain so until the test button is rotated
back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
4
46 SERIES 46
Miniature industrial relays 8 to16 A SERIES
Technical data
Insulation according to EN 61810-1
1 pole 2 pole A
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of Insulation Reinforced (8 mm) Reinforced (8 mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 6 6
Dielectric strength V AC 4000 4000
Insulation between adjacent contacts
Type of insulation — Basic
Overvoltage category — III
Rated impulse voltage kV (1.2/50 μs) — 4
Dielectric strength V AC — 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data 46.61 46.52
Bounce time: NO/NC ms 2/6 1/4
Vibration resistance (10…150)Hz: NO/NC g 20/12 20/15
Shock resistance g 20 20
Power lost to the environment without contact current W 0.6 0.6
with rated current W 1.6 2
Recommended distance between relays mounted on PCB mm ≥ 5
Contact specification
F 46 - Electrical life (AC) v contact current F 46 - E
lectrical life (AC) v contact current
Type 46.52 Type 46.61
Cycles
DC voltage (V)
5
46 46 SERIES
SERIES Miniature industrial relays 8 to16 A
Coil specifications
DC coil data AC coil data
A Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN
V V V Ω mA V V V Ω mA
12 9.012 8.8 13.2 300 40 12 8.012 9.6 13.2 80 90
24 9.024 17.5 26.4 1200 20 24 8.024 19.2 26.4 320 45
48 9.048 35 52.8 4800 10 48 8.048 38.4 52.8 1350 21
110 9.110 80 121 23500 4.7 110 8.110 88 121 6900 9.4
125 9.125 91.2 138 32000 3.9 120 8.120 96 132 9000 8.4
230 8.230 184 253 28000 5
240 8.240 192 264 31500 4.1
R 46 - DC coil operating range v ambient temperature R 46 - AC coil operating range v ambient temperature
1 1
2 2
Outline drawings
Type 46.52 Type 46.61
29 12.4
32.8
20
X-2018, www.findernet.com
6
97 SERIES 46
Sockets and accessories for 46 series relays SERIES
Accessories
Flange mount adaptor for relays types 46.52 and 46.61 046.05
36.6
3.6 2 A
046.05
38
14.4 46 18.1
35 mm rail adaptor for relays types 46.52 and 46.61 046.07
42.4
14.4 39.8
046.07
46.9
34.8
35.4
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types 46.52 and 46.61 (48 tags),
6 x 12 mm 060.48
060.48
X-2018, www.findernet.com
7
46 97 SERIES
SERIES Sockets and accessories for 46 series relays
Push-in terminal socket panel or 35 mm rail (EN 60715) mount 97.P1 97.P2
For relay type 46.61 46.52
Accessories
A Plastic retaining and release clip
(supplied with socket - packaging code SPA) 097.01
Metal retaining clip 097.71
97.P2
Identification tag 095.00.4
Approvals 8-way jumper link 097.58
(according to type): 2-way jumper link 097.52
2-way jumper link 097.42
Marker tag holder 097.00
Modules (see table below) 99.02
Timer modules (see table below) 86.30
Sheet of marker tags for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers 060.48
Technical data
097.01 Rated values 10 A-250 V AC 8 A-250 V AC
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
Ambient temperature °C –40…+70
Wire strip length mm 8
Min. wire size for 97.P1 and 97.P2 socket solid wire stranded wire
mm2 0.5 0.5
060.48 AWG 21 21
Max. wire size for 97.P1 and 97.P2 socket solid wire stranded wire
mm2 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 2 x 16 / 1 x 14 2 x 16 / 1 x 14
97.P1 97.P2
097.58
097.52
X-2018, www.findernet.com
8
97 SERIES 46
Sockets and accessories for 46 series relays SERIES
A
097.42
097.00
99.02 coil indication and EMC suppression modules for 97.P1 and 97.P2 sockets
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
99.02 LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
LED + Varistor (6…24)V DC/AC 99.02.0.024.98
LED + Varistor (28…60)V DC/AC 99.02.0.060.98
DC Modules with LED + Varistor (110…240)V DC/AC 99.02.0.230.98
non-standard polarity RC circuit (6…24)V DC/AC 99.02.0.024.09
(+A2) on request. RC circuit (28…60)V DC/AC 99.02.0.060.09
RC circuit (110…240)V DC/AC 99.02.0.230.09
Residual current by-pass (110…240)V AC 99.02.8.230.07
X-2018, www.findernet.com
9
46 97 SERIES
SERIES Sockets and accessories for 46 series relays
Screw terminal socket panel or 35 mm rail (EN 60715) mount 97.01 97.01.0 97.02 97.02.0
(blue) (black) (blue) (black)
For relay type 46.61 46.52
A Accessories
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 097.01
97.01 Metal retaining clip 097.71
Marker tag holder 097.00
Approvals
Identification tag 095.00.4
(according to type):
8-way jumper link 095.18 (blue) 095.18.0 (black)
Modules (see table below) 99.02
Timer modules (see table below) 86.30
Sheet of marker tags for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 16 A-250 V AC 8 A-250 V AC
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
097.01
Protection category IP 20
Ambient temperature °C –40…+70 (see diagram L97)
Screw torque Nm 0.8
Wire strip length mm 8
Max. wire size for 97.01 and 97.02 socket solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
060.48 AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
L 97 - Rated current v ambient temperature
(for 46.61 relay/97.01 socket combination)
Rated current (A)
EAN 8-way jumper link for 97.01 and 97.02 sockets 095.18 (blue) 095.18.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
095.18
10
97 SERIES 46
Sockets and accessories for 46 series relays SERIES
Screwless terminal socket panel or 35 mm rail (EN 60715) 97.51 97.51.0 97.52 97.52.0
mount (blue) (black) (blue) (black)
For relay type 46.61 46.52
Accessories A
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 097.01
97.51
Metal retaining clip 097.71
Approvals Modules (see table below) 99.02
(according to type):
Timer modules (see table below) 86.30
Technical data
Rated values 10 A - 250 V AC 8 A - 250 V AC
Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
Ambient temperature °C –25…+70
097.01 Wire strip length mm 8
Max. wire size for 97.51 and 97.52 sockets solid wire stranded wire
mm2 2 x (0.5…1.5) 2 x (0.5…1.5)
AWG 2 x (21…18) 2 x (21…18)
11
46 97 SERIES
SERIES Sockets and accessories for 46 series relays
97.12
Rated current (A)
Approvals
(according to type):
97.11 97.12
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 7 . P 1 S P A
A Standard packaging
X-2018, www.findernet.com
Automation for
blinds, grilles
and shutters
Control and
management of
electric power
Shipyards
Road / tunnel
lighting
Hoists and
cranes
Circuit breakers
and switches
Control panels
Type 55.12
-- 2 CO 10 A A
Type 55.13
-- 3 CO 10 A
Type 55.14
-- 4 CO 7 A
• AC & DC coils
• Cadmium Free contacts
• Contact material options
• RT III (wash tight) option available • 2 CO 10 A • 3 CO 10 A • 4 CO 7 A
• PCB mount • PCB mount • PCB mount
For outline drawing see page 6 Copper side view Copper side view Copper side view
Contact specification
Contact configuration 2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)
Rated current/Maximum peak current A 10/20 10/20 7/15
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/250
Rated load AC1 VA 2500 2500 1750
Rated load AC15 (230 V AC)VA 500 500 350
Single phase motor rating (230 V AC)kW 0.37 0.37 0.125
Breaking capacity DC1: 30/110/220 VA 10/0.5/0.25 10/0.5/0.25 7/0.5/0.25
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240
V DC 6 - 12 - 24 - 48 - 60 - 110 -125 - 220
Rated power AC/DC VA (50 Hz)/W 1.5/1 1.5/1 1.5/1
Operating range AC (0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
DC (0.8…1.1)UN (0.8…1.1)UN (0.8…1.1)UN
Holding voltage AC/DC 0.8 UN / 0.5 UN 0.8 UN / 0.5 UN 0.8 UN / 0.5 UN
Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN
Technical data
Mechanical life AC/DC cycles 20 · 106 / 50 · 106 20 · 106 / 50 · 106 20 · 106 / 50 · 106
Electrical life at rated load AC1 cycles 200 · 103 200 · 103 150 · 103
Operate/release time ms 10/5 9/5 9/5
Insulation between coil
and contacts (1.2/50 μs) kV 4 4 4
I-2019, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+85 –40…+85 –40…+85
Environmental protection RT I RT I RT I
Approvals (according to type)
3
55 55 SERIES
SERIES General purpose relays 7 to 10 A
Type 55.32
A -- 2 CO 10 A
Type 55.33
-- 3 CO 10 A
Type 55.34
-- 4 CO 7 A
• AC & DC coils
• Lockable test button and mechanical flag
indicator as standard on 2 & 4 pole types
• Integral LED and coil suppression options • 2 CO 10 A • 3 CO 10 A • 4 CO 7 A
• 94 series sockets for PCB or 35 mm rail • Plug-in 94 series sockets • Plug-in 94 series sockets • Plug-in 94 series sockets
mounting (EN 60715) with Screw, Screwless or
Push-in terminals
• Coil Indication and EMC suppression modules
99 series and Timer module 86.30 options
• Optional alternative mounting adaptors
• UL Listing (certain relay/socket combinations)
• Cadmium Free contacts
• Contact material options
• European Patent
4
55 SERIES 55
General purpose relays 7 to 10 A SERIES
Ordering information
Example: 55 series plug-in relay, 4 CO, 12 V DC coil, lockable test button and mechanical indicator.
A B C D A
5 5 . 3 4 . 9 . 0 1 2 . 0 0 4 0
Series A: Contact material D: Special versions
0 = Standard AgNi 0 = Standard
Type 5 = AgNi + Au 1 = Wash tight (RT III)
1 = PCB for 55.12, 55.13 and 55.14 only
3 = Plug-in B: Contact circuit
0 = CO (nPDT) C: Options
No. of poles 0 = None
2 = 2 pole, 10 A 1 = Lockable test button
3 = 3 pole, 10 A 2 = Mechanical indicator
4 = 4 pole, 7 A 3 = LED (AC)
4 = Lockable test button +
Coil version mechanical indicator
8 = AC (50/60 Hz) 5 = Lockable test button + LED (AC)
9 = DC 54 = Lockable test button + LED (AC) +
mechanical indicator
Coil voltage 6* = Double LED (DC non-polarized)
See coil specifications 7* = Lockable test button + double
LED (DC non-polarized)
74* = Lockable test button + double
Selecting features and options: only combinations in the same row are possible. LED (DC non-polarized) +
Preferred selections for best availability are shown in bold. mechanical indicator
8* = LED + diode (DC, polarity positive
Type Coil version A B C D to pin A1/13)
55.32/34 AC - DC 0-5 0 0 0 9* = Lockable test button + LED +
AC 0-5 0 2-3-4-5 0 diode (DC, polarity positive to pin
AC 0-5 0 54 / A1/13)
94* = Lockable test button + LED +
DC 0-5 0 2-4-6-7-8-9 0
diode (DC, polarity positive to pin
DC 0-5 0 74 - 94 / A1/13) + mechanical indicator
55.33 AC - DC 0-5 0 0 0 * Options not available for 220 V DC
AC 0-5 0 1-3-5 0 versions.
DC 0-5 0 1-6-7-8-9 0
55.12/13/14 AC - DC 0-5 0 0 0-1
T
N
T E
EUR
P A
Lockable test button and mechanical flag indicator
3
OP
EAN
(0010, 0040, 0050, 0054, 0070, 0074, 0090, 0094)
1
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when
the test button is pushed, the contacts operate. When the test button is released the contacts
return to their former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition
I-2019, www.findernet.com
2 to the above function), when the test button is pushed and rotated, the contacts are latched in
the operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
5
55 55 SERIES
SERIES General purpose relays 7 to 10 A
Technical data
Insulation according to EN 61810-1 2 pole - 3 pole 4 pole
Nominal voltage of supply system V AC 230/400 230
A Rated insulation voltage V AC 400 250
Pollution degree 2 2
Insulation between coil and contact set
Type of Insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 4
Dielectric strength V AC 2000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III II
Rated impulse voltage kV (1.2/50 μs) 4 2.5
Dielectric strength V AC 2000 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 1/4 (2 pole), 1/6 (3 pole), 2/4 (4 pole)
Vibration resistance (5…55)Hz: NO/NC g 15/15
Shock resistance g 16
Power lost to the environment without contact current W 1
with rated current W 3 (2 pole) 4 (3 pole) 3 (4 pole)
Recommended distance between relays mounted on PCB mm ≥ 5
Contact specification
F 55 - Electrical life (AC) v contact current F 55 - Electrical life (AC) v contact current
2 and 3 pole relays 4 pole relays
contacts in series
Note: the release time of the load will be increased.
I-2019, www.findernet.com
DC voltage (V)
6
55 SERIES 55
General purpose relays 7 to 10 A SERIES
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil A
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN
V V V Ω mA V V V Ω mA
6 9.006 4.8 6.6 40 150 6 8.006 4.8 6.6 12 200
12 9.012 9.6 13.2 140 86 12 8.012 9.6 13.2 50 97
24 9.024 19.2 26.4 600 40 24 8.024 19.2 26.4 190 53
48 9.048 38.4 52.8 2400 20 48 8.048 38.4 52.8 770 25
60 9.060 48 66 4000 15 60 8.060 48 66 1200 21
110 9.110 88 121 12500 8.8 110 8.110 88 121 3940 12.5
125 9.125 100 138 17300 7.2 120 8.120 96 132 4700 12
220 9.220 176 242 54000 4 230 8.230 184 253 17000 6
240 8.240 192 264 19100 5.3
R 55 - DC coil operating range v ambient temperature R 55 - AC coil operating range v ambient temperature
1
1
2 2
Outline drawings
Types 55.12/13/14 Types 55.32/33/34
I-2019, www.findernet.com
7
55 55 SERIES
SERIES General purpose relays 7 to 10 A
Accessories
Top flange mount adaptor for 55.32, 55.33, 55.34 056.25
I-2019, www.findernet.com
8
94 SERIES 55
Socket overview for 55 series relays SERIES
94.P3 94.P4
EAN 6-way jumper link for 94.P3 and 94.P4 sockets 094.56 (blue)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.56
094.52.1
I-2019, www.findernet.com
10
94 SERIES 55
Sockets and accessories for 55 series relays SERIES
A
097.52
097.00
99.02 coil indication and EMC suppression modules for 94.P3 and 94.P4 sockets
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
99.02 LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
LED + Varistor (6…24)V DC/AC 99.02.0.024.98
LED + Varistor (28…60)V DC/AC 99.02.0.060.98
DC Modules with LED + Varistor (110…240)V DC/AC 99.02.0.230.98
non-standard polarity RC circuit (6…24)V DC/AC 99.02.0.024.09
(+A2) on request. RC circuit (28…60)V DC/AC 99.02.0.060.09
RC circuit (110…240)V DC/AC 99.02.0.230.09
Residual current by-pass (110…240)V AC 99.02.8.230.07
I-2019, www.findernet.com
11
55 94 SERIES
SERIES Sockets and accessories for 55 series relays
Screw terminal (Box clamp) socket panel or 35 mm 94.02 94.02.0 94.03 94.03.0 94.04 94.04.0
(EN 60715) rail mount Blue Black Blue Black Blue Black
For relay type 55.32 55.33 55.32, 55.34
A Accessories
Metal retaining clip 094.71
Plastic retaining and release clip
94.04 (supplied with socket - packaging code SPA) 094.91.3 094.91.30 094.91.3 094.91.30 094.91.3 094.91.30
Approvals 6-way jumper link 094.06 094.06.0 094.06 094.06.0 094.06 094.06.0
(according to type): Identification tag 094.00.4
Marker tag holder 097.00
Modules (see table below) 99.02
Timer modules (see table below) 86.30
Certain relay/socket Sheet of marker tags for plastic retaining and release clip
combinations 094.91.3 and for marker tag holder 097.00 , 48 tags, 6 x 12 mm
for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
094.91.3 Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 94.02/03/04 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
060.48 AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
Top
terminals
94.04 Bottom
terminals
EAN 6-way jumper link for 94.02, 94.03 and 94.04 sockets 094.06 (blue) 094.06.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.06
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.0.024.0000
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.120.0000
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.240.0000
99.02 coil indication and EMC suppression modules for 94.02, 94.03 and 94.04 sockets
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
99.02 LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
Approvals LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
LED + Varistor (6…24)V DC/AC 99.02.0.024.98
LED + Varistor (28…60)V DC/AC 99.02.0.060.98
I-2019, www.findernet.com
12
94 SERIES 55
Sockets and accessories for 55 series relays SERIES
Top
terminals
060.48
Sockets +
jumper link
Bottom
terminals
N T
EU
T E
EUR
P A
OP
EAN
094.56
13
55 94 SERIES
SERIES Sockets and accessories for 55 series relays
Top terminals
Bottom terminals
94.84.2
EAN
6-way jumper link for 94.84.2 socket 094.06 (blue) 094.06.0 (black)
OP
R
T E
EUR
P A
OP
EAN
094.06
99.80 coil indication and EMC suppression modules for 94.84.2 socket
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.80.3.000.00
LED(6…24)V DC/AC 99.80.0.024.59
LED(28…60)V DC/AC 99.80.0.060.59
99.80 LED(110…240)V DC/AC 99.80.0.230.59
Approvals LED + Diode (+A1, standard polarity) (6…24)V DC 99.80.9.024.99
(according to type): LED + Diode (+A1, standard polarity) (28…60)V DC 99.80.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.80.9.220.99
LED + Varistor (6…24)V DC/AC 99.80.0.024.98
* Modules in Black LED + Varistor (28…60)V DC/AC 99.80.0.060.98
housing are available on LED + Varistor (110…240)V DC/AC 99.80.0.230.98
request.
RC circuit (6…24)V DC/AC 99.80.0.024.09
Green LED is standard.
RC circuit (28…60)V DC/AC 99.80.0.060.09
Red LED available on
I-2019, www.findernet.com
14
94 SERIES 55
Sockets and accessories for 55 series relays SERIES
Screw terminal (Box clamp) socket panel or 35 mm 94.92.3 94.92.30 94.94.3 94.94.30
rail mount (blue) (black) (blue) (black)
For relay type 55.32 55.32, 55.34
Accessories A
Metal retaining clip 094.71
Plastic retaining and release clip 094.91.3 094.91.30 094.91.3 094.91.30
94.94.3 6-way jumper link 094.06 094.06.0 094.06 094.06.0
Approvals Identification tag 094.80.3
(according to type): Modules (see table below) 99.80
Sheet of marker tags for retaining and release clip 094.91.3,
plastic, 48 tags, 6 x 12 mm for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
094.91.3 Ambient temperature °C –25…+70
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 94.92.3 and 94.94.3 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
060.48
Top terminals
Bottom terminals
94.94.3
EAN
6-way jumper link for 94.92.3 and 94.94.3 sockets 094.06 (blue) 094.06.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.06
99.80 coil indication and EMC suppression modules for 94.92.3 and 94.94.3 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.80.3.000.00
LED(6…24)V DC/AC 99.80.0.024.59
LED(28…60)V DC/AC 99.80.0.060.59
99.80 LED(110…240)V DC/AC 99.80.0.230.59
Approvals LED + Diode (+A1, standard polarity) (6…24)V DC 99.80.9.024.99
(according to type): LED + Diode (+A1, standard polarity) (28…60)V DC 99.80.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.80.9.220.99
LED + Varistor (6…24)V DC/AC 99.80.0.024.98
* Modules in Black LED + Varistor (28…60)V DC/AC 99.80.0.060.98
housing are available on LED + Varistor (110…240)V DC/AC 99.80.0.230.98
request.
RC circuit (6…24)V DC/AC 99.80.0.024.09
Green LED is standard.
RC circuit (28…60)V DC/AC 99.80.0.060.09
I-2019, www.findernet.com
15
55 94 SERIES
SERIES Sockets and accessories for 55 series relays
Screw terminal (Plate clamp) socket panel or 35 mm 94.72 94.72.0 94.73 94.73.0 94.74 94.74.0
(EN 60715) rail mount Blue Black Blue Black Blue Black
For relay type 55.32 55.33 55.32, 55.34
A Accessories
Metal retaining clip (supplied with socket - packaging code SMA) 094.71
94.74 Modules (see table below) 99.01
Approvals Screw terminal (Plate clamp) socket: panel or 35 mm rail mount 94.82 (blue) 94.82.0 (black)
(according to type): For relay type 55.32 55.32
Accessories
Metal retaining clip (supplied with socket - packaging code SMA) 094.71
Modules (see table below) 99.01
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.5
94.82
Approvals Wire strip length mm 8 (94.72/73/74) 9 (94.82)
(according to type): Max. wire size for 94.72/73/74 and 94.82 sockets solid wire stranded wire
mm2 1 x 2.5 / 2 x 1.5 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16 1 x 14 / 2 x 16
Top
terminals
Bottom
terminals
94.82
99.01 coil indication and EMC suppression modules for 94.72, 94.73, 94.74 and 94.82 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.01.3.000.00
Diode (+A2, non standard polarity) (6…220)V DC 99.01.3.000.00
LED(6…24)V DC/AC 99.01.0.024.59
LED(28…60)V DC/AC 99.01.0.060.59
99.01 LED(110…240)V DC/AC 99.01.0.230.59
Approvals LED + Diode (+A1, standard polarity) (6…24)V DC 99.01.9.024.99
(according to type): LED + Diode (+A1, standard polarity) (28…60)V DC 99.01.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.01.9.220.99
LED + Diode (+A2, non standard polarity) (6…24)V DC 99.01.9.024.99
LED + Diode (+A2, non standard polarity) (28…60)V DC 99.01.9.060.99
* Modules in Black LED + Diode (+A2, non standard polarity) (110…220)V DC 99.01.9.220.99
housing are available on LED + Varistor (6…24)V DC/AC 99.01.0.024.98
request. LED + Varistor (28…60)V DC/AC 99.01.0.060.98
I-2019, www.findernet.com
16
94 SERIES 55
Sockets and accessories for 55 series relays SERIES
Panel mount solder socket 1 mm thick panel 94.22 94.22.0 94.23 94.23.0 94.24 94.24.0
Blue Black Blue Black Blue Black
For relay type 55.32 55.33 55.32, 55.34
94.22 Accessories
Approvals Metal retaining clip
(according to type): (supplied with socket - packaging code SMA) 094.51
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Ambient temperature °C –40…+70
I-2019, www.findernet.com
17
55 94 SERIES
SERIES Sockets and accessories for 55 series relays
Panel mount socket M3 screw fixing - solder connections 94.32 94.32.0 94.33 94.33.0 94.34 94.34.0
Blue Black Blue Black Blue Black
For relay type 55.32 55.33 55.32, 55.34
A 94.34 Accessories
Approvals Metal retaining clip
(according to type): (supplied with socket - packaging code SMA) 094.51
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Ambient temperature °C –40…+70
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 4 . P 4 S P A
A Standard packaging
Miniature power
relays 12 A
Industrial
furnaces and
ovens
Control and
management of
electric power
Industrial
motors
Circuit breakers
and switches
Panels for
electrical
distribution
Control panels
Carousel
warehouses
Vending
machines
56 SERIES 56
Miniature power relays 12 A SERIES
Dielectric strength
between open contacts V AC 1000 2000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
3
56 56 SERIES
SERIES Miniature power relays 12 A
Dielectric strength
between open contacts V AC 1000 2000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
4
56 SERIES 56
Miniature power relays 12 A SERIES
Ordering information
Example: 56 series plug-in relay, 2 CO (DPDT), 12 V DC coil, lockable test button and mechanical indicator.
A B C D A
5 6 . 3 2 . 9 . 0 1 2 . 0 0 4 0
Series A: Contact material D: Special versions
0 = Standard AgNi 0 = Standard
Type 2 = AgCdO 6 = Rear flange mount (4 pole only)
3 = Plug-in 4 = AgSnO2 8 = Rear 35 mm rail mount (4 pole
4 = PCB only)
B: Contact circuit For other mounting options see page 9
No. of poles 0 = CO (nPDT)
2 = 2 pole, 12 A 3 = NO (nPST), ≥ 1.5 mm C: Options
4 = 4 pole, 12 A contact gap 0 = None
2 = Mechanical indicator
Coil version 3* = LED (AC)
8 = AC (50/60 Hz) 4 = Lockable test button +
9 = DC mechanical indicator
5* = Lockable test button + LED (AC)
Coil voltage 54* = Lockable test button + LED (AC) +
See coil specifications mechanical indicator
6* = Double LED (DC non-polarized)
7* = Lockable test button + double
Selecting features and options: only combinations in the same row are possible. LED (DC non-polarized)
Preferred selections for best availability are shown in bold. 74* = Lockable test button + double
LED (DC non-polarized) +
Type Coil version A B C D mechanical indicator
AC 0-2-4 0 0-2-3-4-5 0 8* = LED + diode (DC, polarity positive
AC 0-2-4 0 54 / to pin 7) for 56.32 only
9* = Lockable test button + LED +
56.32 AC 0-2-4 3 0-3-5 0 diode (DC, polarity positive to pin
DC 0-2-4 0 0-2-4-6-7-8-9 0 7) for 56.32 only
94* = Lockable test button + LED +
DC 0-2-4 0 74 - 94 /
diode (DC, polarity positive to
AC 0-2-4 0 0-2-3-4-5 0-6-8 pin 7) + mechanical indicator for
AC 0-2-4 0 54 / 56.32 only
56.34 *O ptions not available for 220 V DC and
DC 0-2-4 0 0-2-4-6-7 0-6-8 400 V AC versions.
DC 0-2-4 0 74 /
DC 0-2-4 0 0 0
56.42
AC 0-2-4 0-3 0 0
56.44 AC - DC 0-2-4 0 0 0
T
N
(56.32 only) T E
EUR
P A O
PEAN
Lockable test button and mechanical flag indicator (0040, 0050, 0054, 0070, 0074, 0090,
3 0094)
1
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly above the test button) remains intact. In this case,
when the test button is pushed, the contacts operate. When the test button is released the
contacts return to their former state.
V-2019, www.findernet.com
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in
addition to the above function), when the test button is pushed and rotated, the contacts are
2 latched in the operating state, and remain so until the test button is rotated back to its former
position.
In both cases ensure that the test button actuation is swift and decisive.
5
56 56 SERIES
SERIES Miniature power relays 12 A
Technical data * Only in applications where over voltage category II is permitted. In applications of over voltage category III: Micro-disconnection.
Insulation according to EN 61810-1 2 CO - 4 CO 2 NO
Nominal voltage of supply system V AC 230/400 230/400
A Rated insulation voltage V AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of Insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 4
Dielectric strength V AC 2500 2500
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 4
Dielectric strength V AC 2500 2500
Insulation between open contacts
Type of disconnection Micro-disconnection Full-disconnection*
Overvoltage category — II
Rated impulse voltage kV (1.2/50 μs) — 2.5
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 2000/3
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 1/4 (2 CO) , 1/7 (4 CO) 3/— (normally open)
Vibration resistance (5…55)Hz: NO/NC g 17/14
Shock resistance g 20/14
Power lost to the environment without contact current W 1 (56.32, 56.42) 1.3 (56.34, 56.44)
with rated current W 3.8 (56.32, 56.42) 6.9 (56.34, 56.44)
Recommended distance between relays mounted on PCB mm ≥ 5
Contact specification
F 56 - Electrical life (AC) v contact current
2 - 4 pole relays
V-2019, www.findernet.com
Coil specifications
DC coil data, 2 pole relay AC coil data, 2 pole relay
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil A
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin* Umax R I at UN (50 Hz)
V V V Ω mA V V V Ω mA
6 9.006 4.8 6.6 40 150 6 8.006 4.8 6.6 12 200
12 9.012 9.6 13.2 140 86 12 8.012 9.6 13.2 50 97
24 9.024 19.2 26.4 600 40 24 8.024 19.2 26.4 190 53
48 9.048 38.4 52.8 2400 20 48 8.048 38.4 52.8 770 25
60 9.060 48 66 4000 15 60 8.060 48 66 1200 21
110 9.110 88 121 12500 8.8 110 8.110 88 121 3940 12.5
125 9.125 100 138 17300 7.2 120 8.120 96 132 4700 12
220 9.220 176 242 54000 4 230 8.230 184 253 17000 6
240 8.240 192 264 19100 5.3
* Umin = 0.85 UN for normally open version.
R 56 - DC coil operating range v ambient temperature R 56 - AC coil operating range v ambient temperature
2 and 4 pole relay 2 pole relay
1
1
normally open version
2
2
changeover version 2
changeover version 2
V-2019, www.findernet.com
7
56 56 SERIES
SERIES Miniature power relays 12 A
Outline drawings
Types 56.32/32-0300 Type 56.34
V-2019, www.findernet.com
8
56 SERIES 56
Miniature power relays 12 A SERIES
Accessories
Top flange mount adaptor for 56.32 056.25
Sheet of marker tags for relay type 56.34, plastic, 48 tags, 6 x 12 mm, for
CEMBRE thermal transfer printers 060.48
V-2019, www.findernet.com
060.48
9
56 96 SERIES
SERIES Sockets and accessories for 56 series relays
96.02
96.02 96.04 96.04
PEAN
O 6-way jumper link for 96.02 socket 094.06 (blue) 094.06.0 (black)
EUR
T
N
T E Rated values 10 A - 250 V
EUR
P A O
PEAN
094.06
96.72 96.74
99.01 coil indication and EMC suppression modules for types 96.72 and 96.74 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.01.3.000.00
Diode (+A2, non-standard polarity) (6…220)V DC 99.01.2.000.00
LED (6…24)V DC/AC 99.01.0.024.59
99.01 LED (28…60)V DC/AC 99.01.0.060.59
LED (110…240)V DC/AC 99.01.0.230.59
Approvals
LED + Diode (+A1, standard polarity) (6…24)V DC 99.01.9.024.99
(according to type):
LED + Diode (+A1, standard polarity) (28…60)V DC 99.01.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.01.9.220.99
LED + Diode (+A2, non-standard polarity) (6…24)V DC 99.01.9.024.79
* Modules in Black LED + Diode (+A2, non-standard polarity) (28…60)V DC 99.01.9.060.79
housing are available on LED + Diode (+A2, non-standard polarity) (110…220)V DC 99.01.9.220.79
request. LED + Varistor (6…24)V DC/AC 99.01.0.024.98
Green LED is standard. LED + Varistor (28…60)V DC/AC 99.01.0.060.98
Red LED available on LED + Varistor (110…240)V DC/AC 99.01.0.230.98
request. RC circuit (6…24)V DC/AC 99.01.0.024.09
RC circuit (28…60)V DC/AC 99.01.0.060.09
RC circuit (110…240)V DC/AC 99.01.0.230.09
Residual current by-pass (110…240)V AC 99.01.8.230.07
V-2019, www.findernet.com
11
56 96 SERIES
SERIES Sockets and accessories for 56 series relays
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 6 . 7 4 S M A
A Standard packaging
Shipyards
Road / tunnel
lighting
Burners, boilers
and furnaces
Wood-processing
machines
Control panels
Control systems
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
60 SERIES 60
General purpose relays 6 - 10 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
3
60 60 SERIES
SERIES General purpose relays 6 - 10 A
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
4
60 SERIES 60
General purpose relays 6 - 10 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type) Z
5
60 60 SERIES
SERIES General purpose relays 6 - 10 A
Ordering information
Example: 60 series plug-in relay, 3 CO (3PDT), 12 V DC coil, test button and mechanical indicator.
A A B C D
6 0 . 1 3 . 9 . 0 1 2 . 0 0 4 0
Series A: Contact material D: Special versions
Type 0 = Standard 0 = Standard
1 = 8/11 pin plug-in 5 = AgNi + Au C: Options
6 = Faston 187 (4.8 x 0.8 mm) B: Contact circuit 0 = None
with flange mount 0 = CO (nPDT) 2 = Mechanical indicator
No. of poles 2 = Bifurcated contacts 3 = LED (AC)
2 = 2 pole 60.12/13 - 6 A only 4 = Lockable test button +
3 = 3 pole mechanical indicator
5* = Lockable test button + LED (AC)
Coil version
54* = Lockable test button + LED (AC) +
4 = Current sensing (60.12/13 only)
mechanical indicator
8 = AC (50/60 Hz)
6* = LED + diode (DC, polarity positive
9 = DC
to pin 2)
Coil voltage 7* = Lockable test button + LED + diode
See coil specifications (DC, polarity positive to pin 2)
74* = Lockable test button + LED +
diode (DC, polarity positive to pin
2) + mechanical indicator
* Options not available for 220 V DC and
400 V AC versions.
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
60.12/13 AC 0 0 0-2-3-4-5 0
AC 0 0 54 /
AC 5 0-2 0-2-3-4-5 0
AC 5 0-2 54 /
DC 0 0 0-2-4-6-7 0
DC 0 0 74 /
DC 5 0-2 0-2-4-6-7 0
DC 5 0-2 74 /
current sensing 0 0 4 0
60.62/63 AC-DC 0-5 0 0 0
C: Option 3, 5, 54 C: Option 6, 7, 74
LED (AC) LED + diode (DC, polarity
EAN
positive to pin 2) OP
R
N T
EU
T E
EUR
P A
Lockable test button and mechanical flag indicator (0040, 0050, 0054, 0070, 0074) EAN
OP
the above function), when the test button is pushed and rotated, the contacts are latched in the
operating state, and remain so until the test button is rotated back to its former position.
2 In both cases ensure that the test button actuation is swift and decisive.
6
60 SERIES 60
General purpose relays 6 - 10 A SERIES
Technical data
Insulation according to EN 61810-1 2 pole 3 pole
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 400 250 400 A
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 3.6
Dielectric strength V AC 2000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 3.6
Dielectric strength V AC 2000 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 1/4
Vibration resistance (5…55)Hz: NO/NC g 22/22
Shock resistance g 20
Power lost to the environment without contact current W 1.3 1.3
with rated current W 2.7 (60.12, 60.62) 3.4 (60.13, 60.63)
Contact specification
F 60 - Electrical life (AC) v contact current H 60 - Maximum DC1 breaking capacity
contacts in series
DC breaking current (A)
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
7
60 60 SERIES
SERIES General purpose relays 6 - 10 A
Coil specifications
R 60 - DC coil operating range v ambient temperature R 60 - AC coil operating range v ambient temperature
Outline drawings
Type 60.12/60.12 - 52xx Type 60.13/60.13 - 52xx Type 60.62 Type 60.63
I-2018,www.findernet.com
8
90 SERIES 60
Socket overview for 60 series relays SERIES
Accessories
Module Socket Relay Description Mounting Accessories
99.02 90.02
90.03
60.12
60.13
Screw terminal (Box clamp) socket
Double A1 terminal
Panel or 35 mm rail
(EN 60715) mount
-C oil indication and EMC
suppression modules
A
- J umper link
- Timer modules
-M etal retaining clip
90.03
See page 10
90.21
See page 11
90.83.3
See page 12
90.23
See page 12
90.26
See page 13
Sheet of marker tags (CEMBRE Thermal transfer printers) for relay types 60.12 and 60.13,
060.48
plastic, 48 tags, 6 x 12 mm
I-2018,www.findernet.com
060.48
9
60 90 SERIES
SERIES Sockets and accessories for 60 series relays
6-way jumper link for 90.02 and 90.03 sockets 090.06 (blue) 090.06.0 (black)
PEAN
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A
PEAN
O Approvals
(according to type):
090.06
99.02 coil indication and EMC suppression modules for 90.02 and 90.03 sockets
Diode (+A1, standard polarity) (6…220)V DC 99.02.3.000.00
86.30
LED (6…24)V DC/AC 99.02.0.024.59
LED (28…60)V DC/AC 99.02.0.060.59
LED (110…240)V DC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity) (6…24)V DC 99.02.9.024.99
LED + Diode (+A1, standard polarity) (28…60)V DC 99.02.9.060.99
99.02 LED + Diode (+A1, standard polarity) (110…220)V DC 99.02.9.220.99
Approvals LED + Varistor (6…24)V DC/AC 99.02.0.024.98
(according to type): LED + Varistor (28…60)V DC/AC 99.02.0.060.98
I-2018,www.findernet.com
10
90 SERIES 60
Sockets and accessories for 60 series relays SERIES
90.20 90.21
99.01 coil indication and EMC suppression modules for 90.20 and 90.21 sockets
Blue*
Diode (+A1, standard polarity) (6…220)V DC 99.01.3.000.00
Diode (+A2, non-standard polarity) (6…220)V DC 99.01.2.000.00
LED (6…24)V DC/AC 99.01.0.024.59
99.01
LED (28…60)V DC/AC 99.01.0.060.59
Approvals
LED (110…240)V DC/AC 99.01.0.230.59
(according to type):
LED + Diode (+A1, standard polarity) (6…24)V DC 99.01.9.024.99
LED + Diode (+A1, standard polarity) (28…60)V DC 99.01.9.060.99
LED + Diode (+A1, standard polarity) (110…220)V DC 99.01.9.220.99
* Modules in Black
LED + Diode (+A2, non-standard polarity) (6…24)V DC 99.01.9.024.79
housing are available on
LED + Diode (+A2, non-standard polarity) (28…60)V DC 99.01.9.060.79
request.
LED + Diode (+A2, non-standard polarity) (110…220)V DC 99.01.9.220.79
Green LED is standard. LED + Varistor (6…24)V DC/AC 99.01.0.024.98
Red LED available on
LED + Varistor (28…60)V DC/AC 99.01.0.060.98
request.
LED + Varistor (110…240)V DC/AC 99.01.0.230.98
RC circuit (6…24)V DC/AC 99.01.0.024.09
RC circuit (28…60)V DC/AC 99.01.0.060.09
RC circuit (110…240)V DC/AC 99.01.0.230.09
Residual current by-pass (110…240)V AC 99.01.8.230.07
I-2018,www.findernet.com
11
60 90 SERIES
SERIES Sockets and accessories for 60 series relays
90.82.3 90.83.3
90.22 90.23
I-2018,www.findernet.com
12
90 SERIES 60
Sockets and accessories for 60 series relays SERIES
90.26 90.27
Flange mount solder socket mount with M3 screw 90.12 (black) 90.13 (black)
For relay type 60.12 60.13
Technical data
90.12
Rated values 10 A - 250 V
Approvals
Dielectric strength 2 kV AC
(according to type):
Ambient temperature °C –40…+70
90.12 90.13
I-2018,www.findernet.com
13
60 90 SERIES
SERIES Sockets and accessories for 60 series relays
90.14 90.15
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 0 . 2 1 S M A
A Standard packaging
Power relays 16 A
Road / tunnel
lighting
Industrial
furnaces and
ovens
Burners,
boilers and
furnaces
Control and
management
of electric
power
Punches,
cleaners,
planers and
sanders
Control panels
Circuit breakers
and switches
Industrial
motors
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
62 SERIES 62
Power relays 16 A SERIES
Dielectric strength
between open contacts V AC 1500 3000
Ambient temperature range °C –40…+70 –40…+50
Environmental protection RT I RT I
Approvals (according to type)
3
62 62 SERIES
SERIES Power relays 16 A
Dielectric strength
between open contacts V AC 1500 3000
Ambient temperature range °C –40…+70 –40…+50
Environmental protection RT I RT I
Approvals (according to type)
4
62 SERIES 62
Power relays 16 A SERIES
Dielectric strength
between open contacts V AC 1500 3000
Ambient temperature range °C –40…+70 –40…+50
Environmental protection RT I RT I
5
62 62 SERIES
SERIES Power relays 16 A
Dielectric strength
between open contacts V AC 3000 2000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
6
62 SERIES 62
Power relays 16 A SERIES
Ordering information
Example: 62 series power relay + Faston 250 (6.3 x 0.8 mm), rear flange mount, 2 NO (DPST-NO), 12 V DC coil.
A B C D
6 2 . 8 2 . 9 . 0 1 2 . 0 3 0 0 A
T
E N
Lockable test button and mechanical flag indicator (0040, 0050, 0054, 0070, 0074) P A T
EUR
O
PEAN
The dual-purpose Finder test button can be used in two ways:
1 3 Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when
the test button is pushed, the contacts operate. When the test button is released the contacts return
to their former state.
X-2018, www.findernet.com
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition
to the above function), when the test button is pushed and rotated, the contacts are latched in
the operating state, and remain so until the test button is rotated back to its former position.
2 In both cases ensure that the test button actuation is swift and decisive.
7
62 62 SERIES
SERIES Power relays 16 A
Technical data
Insulation according to EN 61810-1
A 2 CO - 3 CO 2 NO - 3 NO 1 NO* 2 NO*
Nominal voltage of supply system V AC 230/400 230/400 230/400 230/400
Rated insulation voltage V AC 400 400 400 400
Pollution degree 3 3 3 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced Reinforced Reinforced
Overvoltage category III III III III
Rated impulse voltage kV (1.2/50 µs) 6 6 6 6
Dielectric strength V AC 4000 4000 4000 4000
Insulation between adjacent contacts
Type of insulation Basic Basic — Basic
Overvoltage category III III — III
Rated impulse voltage kV (1.2/50 µs) 4 4 — 4
Dielectric strength V AC 2500 2500 — 2500
Insulation between open contacts
Type of disconnection Micro-disconnection Full-disconnection Full-disconnection Full-disconnection**
Overvoltage category — III III II
Rated impulse voltage kV (1.2/50 µs) — 4 4 2.5
Dielectric strength V AC/kV (1.2/50 µs) 1500/2 3000/4 3000/4 2000/2.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 1/5 3/— 3/— 3/—
(changeover) (normally open) (normally open) (normally open)
Vibration resistance (10…150)Hz: NO/NC g 20/8
Shock resistance g 15
Power lost to the environment 2 pole (CO) 3 pole (CO) 2 pole (NO) 3 pole (NO) 1 pole (NO)* 2 pole (NO)*
without contact current W 1.3 1.3 3 3 1.3 1.3
with rated current W 3.3 4.3 5 6 3 3.3
Recommended distance between relays mounted on PCB mm ≥ 5 —
8
62 SERIES 62
Power relays 16 A SERIES
Contact specification
F 62 - Electrical life (AC) v contact current
• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time of the load will be increased.
50 50
DC breeaking current (A)
DC1 DC1
DC breaking current (A)
10 10
DC13
1 L/R = 40 ms 1 DC13
L/R = 40 ms
0.1 0.1
20 60 100 140 180 220 260 20 60 100 140 180 220 260
(V) (V)
Voltage DC (V) Voltage DC (V)
• When switching a resistive load (DC1), or a DC13 load with a diode in parallel to the load, having voltage and current values under the DC1 curve, an
electrical life of ≥ 100 · 103 can be expected. Note: the release time for the load will be increased.
• When switching a DC13 load without a diode in parallel to the load, the DC13 curve applies and an electrical life of ≥ 80 · 103 can be expected.
X-2018, www.findernet.com
9
62 62 SERIES
SERIES Power relays 16 A
Coil specifications
DC version data AC version data
A Nominal
voltage
Coil
code
Operating range
Rated coil
Resistance consumption
Nominal
voltage
Coil
code
Operating range
Rated coil
Resistance consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN (50Hz)
V V V Ω mA V V V Ω mA
6 9.006 4.8 6.6 28 214 6 8.006 4.8 6.6 4.6 367
12 9.012 9.6 13.2 110 109 12 8.012 9.6 13.2 19 183
24 9.024 19.2 26.4 445 54 24 8.024 19.2 26.4 74 90
48 9.048 38.4 52.8 1770 27 48 8.048 38.4 52.8 290 47
60 9.060 48 66 2760 21.7 60 8.060 48 66 450 37
110 9.110 88 121 9420 11.7 110 8.110 88 121 1600 20
125 9.125 100 138 12000 10.4 120 8.120 96 132 1940 18.6
220 9.220 176 242 37300 5.8 230 8.230 184 253 7250 10.5
240 8.240 192 264 8500 9.2
400 8.400 320 440 19800 6
10
62 SERIES 62
Power relays 16 A SERIES
Coil specifications
R 62 - DC coil operating range v ambient temperature R 62 - AC coil operating range v ambient temperature
Changeover contacts Changeover contacts
A
R 62 - DC coil operating range v ambient temperature R 62 - AC coil operating range v ambient temperature
Normally open contacts Normally open contacts
11
62 62 SERIES
SERIES Power relays 16 A
Outline drawings
Type 62.22 Type 62.23 Type 62.2x Type 62.2x-0300
62.22-0300 62.23-0300
A
Type 62.31-4800
Type 62.32-4800
X-2018, www.findernet.com
12
62 SERIES 62
Power relays 16 A SERIES
Accessories
Mounting adaptor for types 62.3x and 62.8x.xxxx.xxx9 (M4) 062.10
A
062.10
062.60
062.05
Top 35 mm rail (EN 60715) mount for types 62.3x and 62.8x.xxxx.xxx9 062.07
062.07
Rear 35 mm rail (EN 60715) mount for types 62.3x and 62.8x.xxxx.xxx9 062.08
062.08
Sheet of marker tags (CEMBRE Thermal transfer printers) for 62 series relays,
plastic, 48 tags, 6 x 12 mm 060.48
060.48
13
62 92 SERIES
SERIES Sockets and accessories for 62 series relays
86.30
99.02 coil indication and EMC suppression modules for 92.03 socket
Diode (+A1, standard polarity) (6...220)V DC 99.02.3.000.00
LED(6...24)V DC/AC 99.02.0.024.59
LED (28...60)V DC/AC 99.02.0.060.59
LED (110...240)V DC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity) (6...24)V DC 99.02.9.024.99
99.02
Approvals LED + Diode (+A1, standard polarity) (28...60)V DC 99.02.9.060.99
(according to type): LED + Diode (+A1, standard polarity) (110...220)V DC 99.02.9.220.99
LED + Varistor (6...24)V DC/AC 99.02.0.024.98
LED + Varistor (28...60)V DC/AC 99.02.0.060.98
X-2018, www.findernet.com
14
92 SERIES 62
Sockets and accessories for 62 series relays SERIES
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
9 2 . 0 3 S M A
A Standard packaging
Power relays 20 - 30 A
Infrared and
microwave
ovens
Industrial washing
machines
Burners,
boilers and
furnaces
Jacuzzis and
hot tubs
Power
generators
Back-up
generators
Industrial
motors
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
65 SERIES 65
Power relays 20 - 30 A SERIES
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+75 –40…+75
Environmental protection RT I RT I
Approvals (according to type)
3
65 65 SERIES
SERIES Power relays 20 - 30 A
Type 65.31-0300
A - Flange mount and Faston 250 connections
Type 65.61-0300
- PCB mount
Dielectric strength
between open contacts V AC 2500 2500
Ambient temperature range °C –40…+75 –40…+75
Environmental protection RT I RT I
Approvals (according to type)
4
65 SERIES 65
Power relays 20 - 30 A SERIES
Ordering information
Example: 65 series power relay, PCB with bifurcated terminals, 1 NO + 1 NC (SPST-NO + SPST-NC) contact, 12 V DC coil.
A B C D A
6 5 . 6 1 . 9 . 0 1 2 . 0 0 0 0
Series A: Contact material D: Special versions
0 = Standard AgCdO 0 = Standard
Type 4 = AgSnO2 9 = Type 65.31 without rear flange
3 = Faston 250 (6.3 x 0.8 mm) mount
with rear flange mount B: Contact circuit
6 = PCB with bifurcated terminals 0 = 1 NO + 1 NC C: Options
(SPST-NO + SPST-NC) 0 = None
No. of poles 3 = NO (≥ 3 mm contact gap)
1 = 1 NO + 1 NC (SPST-NO + SPST-NC)
Coil version
8 = AC (50/60 Hz)
9 = DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Technical data
Insulation according to EN 61810-1
1 NO + 1 NC 1 NO
Nominal voltage supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 4
Dielectric strength V AC 2500 2500
Insulation between open contacts
Type of disconnection Micro-disconnection Full-disconnection
Overvoltage category — III
Rated impulse voltage kV (1.2/50 μs) — 4
Dielectric strength V AC/kV (1.2/50 μs) 1500/2 2500/4
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV (1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 5/6 (1 NO + 1 NC) 7/— (1 NO)
Vibration resistance (10…150)Hz: NO/NC g 20/13
II-2018,www.findernet.com
Shock resistance g 20
Power lost to the environment without contact current W 1.3
with rated current W 2.1 (65.31, 65.61) 3.1 (65.31/.61.0300)
Recommended distance between relays mounted on PCB mm ≥ 5
5
65 65 SERIES
SERIES Power relays 20 - 30 A
Contact specification
F 65 - Electrical life (AC) v contact current H 65 - Maximum DC1 breaking capacity
DC voltage (V)
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN (50 Hz)
V V V Ω mA V V V Ω mA
6 9.006 5.1 6.6 28 214 6 8.006 4.8 6.6 4.6 367
12 9.012 10.2 13.2 110 109 12 8.012 9.6 13.2 19 183
24 9.024 20.4 26.4 445 54 24 8.024 19.2 26.4 74 90
48 9.048 40.8 52.8 1770 27.1 48 8.048 38.4 52.8 290 47
60 9.060 51 66 2760 21.7 60 8.060 48 66 450 37
110 9.110 93.5 121 9420 11.7 110 8.110 88 121 1600 20
125 9.125 106 138 12000 10.4 120 8.120 96 132 1940 18.6
220 9.220 187 242 37300 5.8 230 8.230 184 253 7250 10.5
240 8.240 192 264 8500 9.2
400 8.400 320 440 19800 6
R 65 - DC coil operating range v ambient temperature R 65 - AC coil operating range v ambient temperature
II-2018,www.findernet.com
6
65 SERIES 65
Power relays 20 - 30 A SERIES
Outline drawings
Type 65.31 Type 65.61 Type 65.31- 0300 Type 65.61- 0300
Accessories
Top flange mount for types 65.31.xxxx.xxx9 065.05
065.05
065.07
065.08
II-2018,www.findernet.com
Power relays 30 A
Power
generators
Industrial washing
machines
Burners,
boilers and
furnaces
Industrial
furnaces and
ovens
Air conditioners
Back-up
generators
Industrial
motors
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
66 SERIES 66
Power relays 30 A SERIES
Type 66.22
- PCB connections & mount A
Type 66.82
- Faston 250 connections and Flange mount
Contact specification
Contact configuration 2 CO (DPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 30/50 (NO) - 10/20 (NC) 30/50 (NO) - 10/20 (NC)
Rated voltage/
Maximum switching voltage V AC 250/440 250/440
Rated load AC1 VA 7500 (NO) - 2500 (NC) 7500 (NO) - 2500 (NC)
Rated load AC15 (230 V AC) VA 1200 (NO) 1200 (NO)
Single phase motor rating (230 V AC) kW 1.5 (NO) 1.5 (NO)
Breaking capacity DC1: 30/110/220 V A 25/0.7/0.3 (NO) 25/0.7/0.3 (NO)
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgCdO AgCdO
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 6 - 12 - 24 - 110/115 - 120/125 - 230 - 240
V DC 6 - 9 - 12 - 24 - 110 - 125
Rated power AC/DC VA (50 Hz)/W 3.6/1.7 3.6/1.7
Operating range AC (0.8…1.1)UN (0.8…1.1)UN
DC (0.8…1.1)UN (0.8…1.1)UN
Holding voltage AC/DC 0.8 UN / 0.5 UN 0.8 UN / 0.5 UN
Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN
Technical data
Mechanical life AC/DC cycles 10 · 106 10 · 106
Electrical life at rated load AC1 cycles 100 · 103 100 · 103
Operate/release time ms 8/15 8/15
Insulation between coil
and contacts (1.2/50 µs) kV 6 (8 mm) 6 (8 mm)
II-2019,www.findernet.com
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)
3
66 66 SERIES
SERIES Power relays 30 A
Type 66.22-x30x
A - PCB mount
Type 66.82-x30x
- Faston 250 connections and Flange mount
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)
4
66 SERIES 66
Power relays 30 A SERIES
Type 66.22-x60x
- PCB mount A
Type 66.22-x60xS
- PCB mount, 5 mm gap between PCB and
relay base
Type 66.82-x60x
- Faston 250 connections and Flange mount
• PCB mount - bifurcated • PCB mount - bifurcated • Flange mount
• ≥ 1.5 mm contact gap (according to terminals terminals • Faston 250 connections
VDE 0126-1-1 for solar inverter applications)
• 5 mm gap between PCB and
• Reinforced insulation between coil and relay base
contacts according to EN 60335-1;
8 mm creepage and clearance distances
• Wash tight version (RT III) available
• DC coils
• Cadmium Free option available
• ATEX compliant (EX nC) option available
Dielectric strength
between open contacts V AC 2500 2500 2500
Ambient temperature range °C –40…+70 –40…+70 –40…+70
Environmental protection RT II RT II RT II
Approvals (according to type)
5
66 66 SERIES
SERIES Power relays 30 A
Ordering information
Example: 66 series relay, Faston 250 (6.3x0.8 mm) with top flange mount, 2 CO (DPDT) 30 A contacts, 24 V DC coil.
A B C D
A
6 6 . 8 2 . 9 . 0 2 4 . 0 0 0 0
Series A: Contact material S=P
CB version with
Type 0 = Standard AgCdO 5 mm gap
2 = PCB 1 = AgNi between PCB and
8 = Faston 250 (6.3 x 0.8 mm) B: Contact circuit relay base
with top flange mount 0 = CO (nPDT) (only 66.22)
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 400
Pollution degree 3
Insulation between coil and contact set
Type of insulation Reinforced (8 mm)
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
Type of insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength V AC 2500
Insulation between open contacts 2 CO 2 NO, ≥ 1.5 mm (x60x version)
Type of disconnection Micro-disconnection Full-disconnection*
Overvoltage category — II
Rated impulse voltage kV (1.2/50 µs) — 2.5
Dielectric strength V AC/kV (1.2/50 µs) 1500/2 2500/2.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms 7/10
Vibration resistance (10…150)Hz: NO/NC g 20/19
II-2019,www.findernet.com
Shock resistance g 20
Power lost to the environment without contact current W 2.3
with rated current W 5
Recommended distance between relays mounted on PCB mm ≥ 10
* Only in applications where over voltage category II is permitted. In applications of over voltage category III: Micro-disconnection.
6
66 SERIES 66
Power relays 30 A SERIES
Contact specification
F 66 - Electrical life (AC) v contact current F 66 - Electrical life (AC) v contact current
250 V (normally open contact) 440 V (normally open contact)
A
Resistive load - 250 V AC cosϕ = 1 Resistive load - 440 V AC cosϕ = 1
Inductive load - 250 V AC cosϕ = 0.4 Inductive load - 440 V AC cosϕ = 0.4
Cycles
Cycles
DC voltage (V) DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
DC coil data AC coil data
Nominal Coil Operating range Resistance Rated coil Nominal Coil Operating range Resistance Rated coil
voltage code Consumption voltage code Consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN (50 Hz)
V V V Ω mA V V V Ω mA
6 9.006 4.8 6.6 21 283 6 8.006 4.8 6.6 3 600
9 9.009 7.2 9.9 45 200 12 8.012 9.6 13.2 11 300
12 9.012 9.6 13.2 85 141 24 8.024 19.2 26.4 50 150
24 9.024 19.2 26.4 340 70.5 110/115 8.110 88 126 930 32.6
110 9.110 88 121 7000 15.7 120/125 8.120 96 137 1050 30
125 9.125 100 138 9200 13.6 230 8.230 184 253 4000 15.7
240 8.240 192 264 5500 15
R 66 - DC coil operating range v ambient temperature R 66 - AC coil operating range v ambient temperature
II-2019,www.findernet.com
A
Specific marking of explosion protection
II
Component for surface plant (different from mines)
3
Category 3: normal level of protection
G
Explosive atmosphere due to presence of combustible gas vapour or mist
Ex nC
Sealed device (type of protection for category 3G)
GAS
IIC
Gas group
Gc
Equipment Protection Level
–40 °C ≤ Ta ≤ +70 °C
Ambient temperature
EUT 14 ATEX 0150 U
EUT: laboratory which issues the CE type certificate
14: year of issue of certificate
0150: number of CE type certificate
U: ATEX component
Electrical characteristics
Characteristics of terminals
Rated current/Maximum peak current A 25/50 (NO) - 10/20 (NC)
Rated voltage/Maximum switching voltage V AC 250/400
Rated load AC1 VA 6250 (NO) - 2500 (NC)
Rated load AC15 VA 1200 (NO)
Capacity for single phase motor (230 V AC) kW 1.5 (NO)
Breaking capacity DC1: 30/110/220 V A 25/0.7/0.3 (NO)
Characteristics of coil
Rated voltage (UN) V AC (50/60 Hz) 6 - 12 - 24 - 110/115 - 120/125 - 230 - 240
V DC 6 - 12 - 24 - 110 - 125
Rated Power AC/DC VA (50 Hz)/W 3.6/1.7
Operating range AC/DC (0.8…1.1)UN
General characteristics
Ambient temperature °C –40…+70
Wiring
The cross-section of conductors connected to the terminals, must be at least 4 mm2 for the Type 66.82.
Layout pcb
The minimum cross-section of the tracks of the printed circuit board must be 0.58 mm2, while the width must be at least 4 mm for Types “66.22” and
“66.22….S”.
II-2019,www.findernet.com
8
66 SERIES 66
Power relays 30 A SERIES
Outline drawings
Type 66.22 Type 66.82
Type 66.22-0600S
Accessories
Top 35 mm rail (EN 60715) mount for types 66.82.xxxx.0x00 066.07
066.07
II-2019,www.findernet.com
Power
generators
Back-up
generators
Pump
control
Disabled lift
Inverter
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
67 SERIES 67
High Power relay 50 A SERIES
Type 67.22-x300
- 2 NO A
Type 67.23-x300
- 3 NO
For outline drawing see page 8 Copper side view Copper side view
Contact specification
Contact configuration 2 NO (DPST-NO) 3 NO (3PST-NO)
Contact gap mm ≥ 3 ≥ 3
Rated current/
Maximum peak current (for 5 ms) A 50/150 50/150
Rated voltage/
Maximum switching voltage V AC 400/690 400/690
Rated load AC1/AC7a (per pole) VA 20000 20000
Rated load AC15 (per pole @ 230 V AC) VA 2300 2300
Single-phase motor rating (230 V AC) kW 2.2 2.2
Three-phase motor rating (480 V AC) kW — 11
Breaking capacity DC1: 24/110/220 V A 50/4/1 50/4/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN)V DC 5 - 6 - 8 - 12 - 24 - 48 - 60 - 110
Rated power W 1.7 1.7
Operating range (–40…+70)°C DC (0.90 …1.1)UN (0.90 …1.1)UN
Energy-saving mode (–40…+85)°C
Operating range for 1 s (0.95…2.5)UN (0.95…2.5)UN
Holding voltage range DC (0.32…0.65)UN (0.32…0.65)UN
Minimum holding power W 0.17 0.17
Must drop-out voltage DC 0.05 UN 0.05 UN
Technical data
Mechanical life cycles 1 · 106 1 · 106
Electrical life at rated load AC7a cycles 30 · 103 30 · 103
II-2018, www.findernet.com
3
67 67 SERIES
SERIES High Power relay 50 A
Type 67.22-x500
A - 2 NO
Type 67.23-x500
- 3 NO
GWFI 850 °C)
• Cadmium free contact materials:
-- AgNi version (for applications where lower
For outline drawing see page 8 Copper side view Copper side view
Contact specification
Contact configuration 2 NO (DPST-NO) 3 NO (3PST-NO)
Contact gap mm ≥ 5.2 ≥ 5.2
Rated current/
Maximum peak current (for 5 ms) A 50/150 50/150
Rated voltage/
Maximum switching voltage V AC 400/690 400/690
Rated load AC1/AC7a (per pole) VA 20000 20000
Rated load AC15 (per pole @ 230 V AC) VA 2300 2300
Single-phase motor rating (230 V AC) kW 2.2 2.2
Three-phase motor rating (480 V AC) kW — 11
Breaking capacity DC1: 24/110/220 A 50/7/2 50/7/2
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN)V DC 5 - 6 - 8 - 12 - 24 - 48 - 60 - 110
Rated power W 2.7 2.7
Operating range (–40…+60)°C DC (0.90 …1.1)UN (0.90 …1.1)UN
Energy-saving mode (–40…+85)°C
Operating range for 1 s (0.95…2.5)UN (0.95…2.5)UN
Holding voltage range DC (0.25…0.5)UN (0.25…0.5)UN
Minimum holding power W 0.17 0.17
Must drop-out voltage DC 0.05 UN 0.05 UN
Technical data
Mechanical life cycles 1 · 106 1 · 106
Electrical life at rated load AC7a cycles 30 · 10 3
30 · 103
II-2018, www.findernet.com
4
67 SERIES 67
High Power relay 50 A SERIES
Ordering information
Example: 67 series solar relay, single PCB terminals, 2 pole NO, ≥ 3 mm contact gap.
A B C D A
6 7 . 2 3 . 9 . 0 1 2 . 4 3 0 0
Series A: Contact material S = Version suggested
1 = AgNi for 100 A switching,
Type
4 = Standard AgSnO2 provided the
2 = Single PCB terminals, 1.5 mm gap
3 contacts are
between PCB and relay base B: Contact circuit
connected in parallel
No. of poles 3 = NO, ≥ 3 mm contact gap
(only 67.23…430xS)
2 = 2 pole 5 = NO, ≥ 5.2 mm contact gap
3 = 3 pole D: Special versions
Coil version 0 = Standard
9 = DC 1 = Wash tight (RT III)
Coil voltage C: Options
See coil specifications 0 = None
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 400/690 3-phase 400 1-phase 230/400
Rated insulation voltage V AC 630 400 400
Pollution degree 3
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
Type of Insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50)µs 6
Dielectric strength V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection* Full-disconnection
Overvoltage category — III
Rated impulse voltage kV (1.2/50)µs — 4
Dielectric strength V AC 2500 (67.xx-x300)/3000 (67.xx-x500)
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO ms 2
Vibration resistance (10…150)Hz: NO g 15
Shock resistance g 35
Power lost to the environment without contact current W 1.7 (67.xx-x300)/2.7 (67.xx-x500)
with rated current W 8.5 (67.xx-x300)/9.5 (67.xx-x500)
Recommended distance between relays mounted on PCB mm ≥ 20
Short circuit protection
II-2018, www.findernet.com
5
67 67 SERIES
SERIES High Power relay 50 A
Contact specification
F 67 - Electrical life v contact current (AC1/AC7a load)
A
Cycles
H 67 - Maximum DC breaking capacity (67.xx-x300) H 67 - Maximum DC breaking capacity (67.xx-x500)
DC voltage (V) DC voltage (V)
When switching a resistive (DC1) or inductive (DC13) load having voltage When switching a resistive (DC1) or inductive (DC13) load having voltage
and current values under the corresponding curve, an electrical life of and current values under the corresponding curve, an electrical life of
> 30000 cycles can be expected. > 30000 cycles can be expected.
6
67 SERIES 67
High Power relay 50 A SERIES
Coil specifications
DC coil data, 67.xx-x300
Nominal Coil code Operating range Holding Resistance Rated coil
voltage (@ 70 °C max) voltage consumption A
I at UN
UN Umin Umax Uh R IN
V V V V Ω mA
5 9.005 4.5 5.5 1.6 14.7 340
6 9.006 5.4 6.6 1.9 21.5 279
8 9.008 7.2 8.8 2.6 37.6 213
12 9.012 10.8 13.2 3.8 85 141
24 9.024 21.6 26.4 7.7 340 71
48 9.048 43.2 52.8 15.4 1355 35
60 9.060 54 66 19.2 2120 28
110 9.110 99 121 35.2 7120 15
DC coil data, 67.xx-x500
Nominal Coil code Operating range Holding Resistance Rated coil
voltage (@ 60 °C max) voltage consumption
I at UN
UN Umin Umax Uh R IN
V V V V Ω mA
5 9.005 4.5 5.5 1.25 9.3 538
6 9.006 5.4 6.6 1.5 13.5 444
8 9.008 7.2 8.8 2 23.7 338
12 9.012 10.8 13.2 3 53.5 224
24 9.024 21.6 26.4 6 213 113
48 9.048 43.2 52.8 12 855 56
60 9.060 54 66 15 1335 45
110 9.110 99 121 27.5 4500 24
R 67 - Operating range v ambient temperature, 67.xx-x300 R 67 - Operating range v ambient temperature, 67.xx-x500
with standard (continuous) coil energization (–40…+70)°C with standard (continuous) coil energization (–40…+60)°C
7
67 67 SERIES
SERIES High Power relay 50 A
Outline drawings
Type 67.22 Type 67.23
II-2018, www.findernet.com
Bistable relay 8 A
Power
Plants
Panels for
electrical
distribution
Control
panels
Automatic
warehouses
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
RB SERIES RB
Bistable relay 8 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+55 –40…+55
Protection category IP 20 IP 20
Approvals relay (according to type)
3
RB RB SERIES
SERIES Bistable relay 8 A
Ordering information
Example: RB series, bistable relay, 4 CO, 125 V DC coil, 35 mm rail (EN 60715) mount.
A
R B . 1 4 . 9 . 1 2 5 . 0 0 0 0
Series Options
0000 = Modular version 35 mm rail (EN 60715)
Type
1 = Modular version
No. of poles
4 = 4 CO
Coil version
9 = DC
Example: RB series, bistable relay, 2 CO, 125 V DC coil, 11 pin socket type 90.21 mount.
R B . 2 2 . 9 . 1 2 5 . 9 0 2 1
Series Options
9021 = Version plug-in 90.21 socket
Type 0000 = Version relay only
2 = 11 pin socket type 90.21 mount
No. of poles
2 = 2 CO
Coil version
9 = DC
4
RB SERIES RB
Bistable relay 8 A SERIES
Technical data
Insulation according to EN 61810-1
2 CO 4 CO A
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 250
Pollution degree 2 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm) Reinforced (8 mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 6
Dielectric strength V AC 2000 3000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 4 4
Dielectric strength V AC 2000 2500
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: SET (NO) / RESET (NC) ms 3/6
Vibration resistance (5…55)Hz: NO/NC g 3/6
Shock resistance g 15
Max cable lenght for push-button connection m 100
Terminals Screw terminal
Solid and stranded cable
Max. wire size mm2 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
V V V mA W
RB - 2 contacts in series 24 9.024 19.2 26.4 290 7
48 9.048 38.4 52.8 150 7
110…125 9.125 88 137.5 60 7
1 contact 220…250 9.250 176 275 30 7
V V V mA W
24 9.024 19.2 26.4 170 4
110…125 9.125 88 137.5 35 4
220…250 9.250 176 275 18 4
5
RB RB SERIES
SERIES Bistable relay 8 A
Wiring diagrams
Type RB.14 Type RB.14 Type RB.14
Functions
XI-2018, www.findernet.com
6
RB SERIES RB
Bistable relay 8 A SERIES
Outline drawing
Type RB.14 Type RB.22
Screw terminal Screw terminal
A
TERMINALS IDENTIFICATION
SOCKETS 90.21 AND 90.49
RB.22.9.125.0000
4 3 5 7
8A 250V
2 6
125VDC
SET RESET
1 11
0V
A2 31 21 11 A1 RESET
10
10 11 6 1 2
0V RESET COM2 SET COM1
MADE IN BRAZIL
RB.22.9.125.0000
79
4
SET
1
WIRING DIAGRAM
3
0V
10
RESET
11
81
SOCKETS 90.21 AND 90.49
TERMINALS IDENTIFICATION
10
A2
34 32 24 22 14 12
0V RESETCOM2 SET COM1
9 8 7 5 3 4
A1
2
25.5
67 38
RB.22.9.125.9021
XI-2018, www.findernet.com
Power
Plants
Panels for
electrical
distribution
Control
panels
Control and
management
of electric
power
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
RR SERIES RR
Fast relay module 8 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+55 –40…+55
Protection category IP 20 IP 20
Approvals relay (according to type)
3
RR RR SERIES
SERIES Fast relay module 8 A
Ordering information
Example: RR series, fast relay module, 4 CO, 125 V DC coil, 35 mm rail (EN 60715) mount.
A
R R . 1 4 . 9 . 1 2 5 . 0 0 0 0
Series Options
0000 = Modular version 35 mm rail (EN 60715)
Type
1 = Modular version
No. of poles
4 = 4 CO
Coil version
9 = DC
Example: RR series, fast relay module, 3 NO + 1 CO, 125 V DC coil, 11 pin socket type 90.21 mount.
R R . 2 4 . 9 . 1 2 5 . 9 0 2 1
Series Options
9021 = Relay + 90.21 sockets
Type 0000 = Only Relay
2 = Plug-in version
No. of poles
4 = 3 NO + 1 CO
Coil version
9 = DC
4
RR SERIES RR
Fast relay module 8 A SERIES
Technical data
Insulation according to EN 61810-1 RR.14 RR.24
4 CO 3 NO + 1 CO A
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 250
Pollution degree 2 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm) Reinforced (8 mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50 μs) 6 4
Dielectric strength V AC 3500 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category II II
Rated impulse voltage kV (1.2/50 μs) 2.5 2.5
Dielectric strength V AC 2000 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 μs) 1000/1.5 1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 1.3/5.1
Vibration resistance (5…55)Hz: NO/NC g 15/3
Shock resistance g 13
Terminals Screw terminal
Solid and stranded cable
2
Max. wire size mm 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
XI-2018,www.findernet.com
5
RR RR SERIES
SERIES Fast relay module 8 A
Contact specification
RR - Electrical life (AC) v contact current RR - Maximum DC1 breaking capacity
A
10
6
6
RR SERIES RR
Fast relay module 8 A SERIES
Outline drawing
Type RR.14 Type RR.24
Screw terminal Screw terminal
A
XI-2018,www.findernet.com
Control panels
Carousel
warehouses
Escalators
Road / tunnel
lighting
99.02
RC module
99.02.0.024.09
RC circuit modules are used for AC and DC coils. The reverse voltage peaks of the
99.02.0.060.09
coil are limited by the RC module to approximately 2.5 times the nominal voltage
99.02.0.230.09
of the supply. The relay release time increases insignificantly.
Bottling plant
Packaging
machines
Control panels
Traffic light
controls
Vending
machines
Programmable
controllers
Labelling
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
38 SERIES 38
Relay interface modules 0.1 - 2 - 3 - 5 - 6 - 8 - 16 A SERIES
Page 1 Page 2
6.2 mm wide 38.21 38.21…9024-8240
• Timed Interface module
• 4 functions & 4 time scales 0.1 s…6 h
• EMR - AC/DC (12 or 24 V) supply versions
• SSR - AC/DC (24 V) supply
• Screw terminals
Page 3 Page 3
14 mm wide 38.01/38.52/38.11/38.62 38.31/38.41
• 2 pole 8 A or 1 pole 16 A
• EMR - DC or AC/DC coil versions
• SSR - DC input versions
• Screw and Screwless terminal options
XI-2018, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range (UN ≤ 60 V/> 60 V)°C –40…+70/–40…+55 —/–40…+55
Protection category IP 20 IP 20
Approvals relay (according to type)
1
38 38 SERIES
SERIES Relay interface modules - Single output SSR
2
38 SERIES 38
Timed interface modules - EMR & SSR SERIES
3
38 38 SERIES
SERIES Relay interface modules - 1 Pole 16 A and 2 Pole 8 A EMR
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range (UN ≤ 60 V/> 60 V)°C –40…+70/–40…+55 –40…+70/–40…+55
Protection category IP 20 IP 20
Approvals relay (according to type)
4
38 SERIES 38
Relay interface modules - Single output SSR SERIES
5
38 38 SERIES
SERIES Relay interface modules - Ordering information
Ordering information
Electromechanical relay - 1 or 2 Pole
Example: 38 series screw terminal relay interface module, 1 CO (SPDT), sensitive 12 V DC coil.
A B C D
3 8 . 5 1 . 7 . 0 1 2 . 0 0 5 0
B Series D: Special versions
0 = Standard
Type
0 = Electromechanical 16 A relay, C: Options
with screw terminal 5 = Standard DC
1 = Electromechanical 16 A relay, 6 = Standard AC or AC/DC
with screwless terminal
B: Contact circuit
2 = Timer multifunction (AI, DI, GI, SW),
0 = CO (nPDT)
with screw terminal
5 = Electromechanical relay, A: Contact material
with screw terminal 0 = AgNi Standard
6 = Electromechanical relay, 4 = AgSnO2
with screwless terminal 5 = AgNi + Au
No. of poles
1 = 1 pole, 6 or 16 A
2 = 2 pole, 8 A
Coil version
0 = AC (50/60 Hz)/DC
3 = L eakage current suppression for
(110…125)V AC/DC - (230…240)V AC
7 = Sensitive DC, (6, 12, 24, 48, 60)V only
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
XI-2018, www.findernet.com
6
38 SERIES 38
Relay interface modules - Ordering information SERIES
Ordering information
Solid state relay - Single output - 6.2 & 14 mm wide
Example: 38 series screw terminal SSR relay interface module, 6.2 mm wide, 6 A output, 24 V DC input.
3 8 . 8 1 . 7 . 0 2 4 . 9 0 2 4
Series Output version B
Type 9024 = 6 A - 24 V DC (38.21, 38.81 & 38.91)
21 = Timer SSR 6.2 mm wide, 9024 = 5 A - 24 V DC (38.31 & 38.41)
with screw terminal 7048 = 0.1 A - 48 V DC (38.81 & 38.91)
31 = SSR 14 mm wide, 8240 = 2 A - 240 V AC (38.21, 38.81 & 38.91)
with screw terminal 8240 = 3 A - 240 V AC (38.31 & 38.41)
41 = SSR 14 mm wide,
with screwless terminal
81 = SSR 6.2 mm wide,
with screw terminal
91 = SSR 6.2 mm wide,
with screwless terminal
Input version
0 = AC/DC
3 = Leakage current suppression for
(110…125)V AC/DC and (230…240)V AC SSR only
7 = DC, (6, 24, 60)V SSR only
Input voltage
See input specifications
Selecting features and options: only combinations in the same row are possible.
7
38 38 SERIES
SERIES Relay interface modules - Technical data
DC voltage (V)
F 38 - Electrical life (AC) v contact current, 1 Pole 16 A and 2 Pole 8 A H 38 - Maximum DC1 breaking capacity, 1 Pole 16 A and 2 Pole 8 A
2 contacts in series
Cycles
DC voltage (V)
XI-2018, www.findernet.com
: 2 Pole 8 A • When switching a resistive load (DC1) having voltage and current
: 1 Pole 16 A values under the curve, an electrical life of ≥ 60 · 103 (1 Pole) or
≥ 80 · 103 (2 Pole) can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
8
38 SERIES 38
Relay interface modules - Technical data SERIES
3
XI-2018, www.findernet.com
9
38 38 SERIES
SERIES Relay interface modules - Technical data
Input specifications - Solid State Relays type 38.81 and 38.91 - 6.2 mm wide
Input data DC Input data AC/DC
Nominal Supply Operating range Release Rated coil Power Nominal Supply Operating range Release Rated coil Power
voltage code voltage consumption consumption voltage code voltage consumption consumption
UN Umin Umax U I at UN P UN Umin Umax U I at UN P
V V V V mA W V V V V mA VA/W
6 7.006 5 7.2 2.4 7 0.2 110…125 0.125 88 138 22 5.5* 0.7/0.7
24 7.024 16.8 30 10 10.5 0.3 220…240 0.240 184 264 44 3.5* 1/0.9
60 7.060 35.6 72 20 6.5 0.4 (*) Rated coil consumption and power consumption values relate to
UN = 125 and 240 V.
Input data - Leakage current suppression types
Nominal Supply Operating range Release Rated coil Power The 38 Series interface modules (supply version 3) have built-in
voltage code voltage consumption consumption leakage current suppression to address industry concerns of the
contacts not dropping-out when there is residual current in the circuit;
UN Umin Umax U I at UN P at UN
at (110…125)V AC and (230…240)V AC.
V V V V mA W
110…125 AC/DC 3.125 94 138 44 8(*) 1/1(*)
This problem can occur, for example, when connecting the interface
230…240 AC 3.240 184 264 72 6.5(*) 1.6/0.6(*) modules to PLC‚s with triac outputs or when connecting via relatively
(*) Rated coil consumption and power consumption values relate to long cables.
UN = 125 and 240 V.
Input specification - Solid State Relay types 38.31 and 38.41 - 14 mm wide
Input data DC Input data AC/DC
Nominal Supply Operating range Release Rated coil Power Nominal Supply Operating range Release Rated coil Power
voltage code voltage consumption consumption voltage code voltage consumption consumption
UN Umin Umax U I at UN P UN Umin Umax U I at UN P
V V V V mA W V V V V mA W
12 7.012 9.6 18 5 9 0.2 24 0.024 16.8 30 9 16.5 0.3
24 7.024 16.8 30 5 12 0.3
XI-2018, www.findernet.com
10
38 SERIES 38
Timed interface modules SERIES
Max recommended switching frequency (Cycles/Hour, with 50% Duty-cycle) at ambient temperature 50°C, single mounting (only 38.81/91/21)
Load 38.x1.x.xxx.9024 38.x1.x.xxx.8240 38.x1.x.xxx.7048
24 V 6 A DC1 180 000 — —
24 V 3 A DC L/R = 10 ms 5000 — —
24 V 2 A DC L/R = 40 ms 3600 — —
24 V 1 A DC L/R = 40 ms 6500 — —
24 V 0.8 A DC L/R = 40 ms 9000 — —
24 V 1.5 A DC L/R = 80 ms 3250 — —
230 V 2 A AC1 — 60 000 —
230 V 1.25 A AC15 — 3600 —
48 V 0.1 A DC1 — — 60 000
XI-2018, www.findernet.com
11
38 38 SERIES
SERIES Timed interface modules
Times scales
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
Functions
LED Supply voltage NO contact/output
OFF Open
ON Closed
(DI) Interval.
1 2 3 4
12
38 SERIES 38
Relay interface modules - Dimensional data SERIES
Outline drawings
Types 3
8.21 Types 3
8.01
38.51 / 38.51.3 38.31
38.81 / 38.81.3 38.52
Screw terminal Screw terminal
Types 3
8.61 / 38.61.3 Types 3
8.11
38.91 / 38.91.3 38.41
Screwless terminal 38.62
Screwless terminal
XI-2018, www.findernet.com
13
38 93 SERIES
SERIES Sockets and accessories for 38 series
14
93 SERIES 38
Sockets and accessories for 38 series SERIES
93.21
Approvals
(according to type):
15
38 93 SERIES
SERIES Sockets and accessories for 38 series
Accessories
PEAN
O 20-way jumper link for 38.21/51/61/81/91 093.20 (blue) 093.20.0 (black) 093.20.1 (red)
EUR
T
N
T E EUR Rated values 36 A - 250 V
P A O
PEAN
093.20
B Approvals
(according to type):
PEAN
O 8-way jumper link for 38.01/11/31/41/52/62 093.08 (blue) 093.08.0 (black) 093.08.1 (red)
EUR
T
N
T E Rated values 10 A - 250 V
EUR
P A O
PEAN
093.08
Approvals
(according to type):
093.48
Sheet of marker tags (CEMBRE Thermal transfer printers) for 38.01/11/31/41/52/62 types
(48 tags), 6 x 12 mm 060.48
060.48
XI-2018, www.findernet.com
MasterINTERFACE -
Relay interface modules
0.1 - 2 - 6 A
Packaging
machines
Bottling plant
Traffic light
controls
Carousel
warehouses
Control panels
Labelling
machines
MasterBASIC MasterPLUS
39.11 - 39.10 - 39.01 - 39.00 39.31 - 39.30 - 39.31.3 - 39.30.3 - 39.61 - 39.60 - 39.61.3 - 39.60.3
• For general interface use in any type of system • This special version provides extra protection for the output circuit thanks to the replaceable fuse
and application. module.
• Can be used for input interface applications • For general interface use in any type of system and application.
between auxiliary contacts, sensors etc. and • Can be used for input interface applications between auxiliary contacts, sensors etc. and
controllers, PLC's or motors. Or for output controllers, PLC's or motors. Or for output interface between PLC’s controllers and relays, solenoids
interface between PLC's controllers and relays, etc.
B solenoids etc.
8012823356709 8012823356709
Fuse module
093.63
093.63.0.024
093.63.8.230
Fuse module
093.63
093.63.0.024
093.63.8.230
IV-2019, www.findernet.com
4
39 SERIES 39
Typical applications SERIES
Fuse module
093.63
093.63.0.024
093.63.8.230
5
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Dielectric strength
between open contacts V AC 1000
Ambient temperature range °C –40…+70
Protection category IP 20
Approvals relay (according to type)
6
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
7
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 (+55 for 220 V DC) –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
8
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
• 0.1, 2 or 6 A solid state relay • 0.1, 2 or 6 A solid state relay
• 24 - 125 V AC/DC, 6 to 220 V DC and 230 V AC, • Leakage current suppression version,
24…240 V AC/DC supply 125 V AC DC and 230 V AC supply
• Screw terminal and push-in terminal • Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.30/39.30.3 39.60/39.60.3
Screw terminal Push-in terminal
9
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Dielectric strength
between open contacts V AC 1000
Ambient temperature range °C –40…+70
Protection category IP 20
Approvals relay (according to type)
10
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
11
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Dielectric strength
between open contacts V AC 1000
Ambient temperature range °C –40…+70
Protection category IP 20
Approvals relay (according to type)
12
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
13
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
14
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
15
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
39.11 39.01
Screw terminal Push-in terminal
Dielectric strength
between open contacts V AC 1000
Ambient temperature range °C –40…+70
Protection category IP 20
Approvals relay (according to type)
16
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
3 9 . 1 1 . 0 . 0 2 4 . 0 0 7 3
Series A: Contact material C - D: Option
0 = AgNi Standard 73 = ATEX B
Type 5 = AgNi + Au Complaiant (Ex nA nC)
0 = Push-in terminals
35 mm rail (EN 60715) mount B: Contact circuit
1 = Screw terminals 0 = CO (nPDT)
35 mm rail (EN 60715) mount
No. of poles
1 = 1 CO, 6 A
Coil version
0 = AC/DC
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
17
39 39 SERIES
SERIES Relay interface modules - Ordering information
Ordering information
Example: MasterPLUS 39 series screw terminal interface module, electromechanical relay output, 1 CO (SPDT), 24 V AC/DC coil.
A B C D
3 9 . 3 1 . 0 . 0 2 4 . 0 0 6 0
Series D: Special Version, EMR
B Type 0 = Standard
1 = MasterBASIC, screw terminal C: Options, EMR
0 = MasterBASIC, push-in terminal 6 = Standard
3 = MasterPLUS, screw terminal,
B: Contact circuit, EMR
fuse-protectable output
0 = CO (except 39.21/51, 1 NO)
6 = MasterPLUS, push-in terminal,
fuse-protectable output A: Contact material, EMR
4 = MasterINPUT, screw terminal 0 = AgNi Standard
7 = MasterINPUT, push-in terminal 4 = AgSnO2
2 = MasterOUTPUT, screw terminal 5 = AgNi + Au
5 = MasterOUTPUT, push-in terminal ABCD: Output version, SSR
8 = MasterTIMER multifunction, 7048 = 0.1 A - 48 V DC
screw terminal, 8240 = 2 A - 230 V AC
fuse-protectable output
9024 = 6 A - 24 V DC
9 = MasterTIMER multifunction,
push-in terminal,
fuse-protectable output
No. of poles
1 = 1 CO (only EMR, except 39.21/51, 1 NO)
0 = 1 NO (only SSR)
Coil version, EMR / Input version, SSR
0 = AC (50/60 Hz)/DC
3 = Leakage current suppression AC (50/60 Hz)
7 = DC sensitive
8 = AC (50/60 Hz)
Coil voltage, EMR/Input voltage, SSR
See page 20
EMR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
0.006 - 0.012
39.11/01 0-4-5 0 6 0
0.024 - 0.125 - 8.230
0.006 - 0.012
0.024 - 0.060
39.31/61 0.125 - 0.240 - 8.230 0-4-5 0 6 0
7.125 - 7.220
3.125 - 3.230
0.006 - 0.012
39.41/71 0.024 - 0.125 0-4-5 0 6 0
8.230
0.006 - 0.012
39.21/51 0.024 - 0.125 0-4-5 0 6 0
8.230
39.81/91 0.012 - 0.024 0 0 6 0
SSR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Input version Output version, ABCD
7.006 - 7.012
39.10/00 7048 - 8240 - 9024
7.024 - 0.125 - 8.230
7.006 - 7.012
7.024 - 7.060
7.125 - 7.220
39.30/60 7048 - 8240 - 9024
0.024 - 0.125 - 0.240
8.230
3.125 - 3.230
7.006 - 7.012
IV-2019, www.findernet.com
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
B
Rated impulse voltage kV (1.2/50)μs 6
Dielectric strength V AC 4000
Insulation between open contacts (EMR)
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50)μs 1000/1.5
Other data
Bounce time (EMR): NO/NC ms 1/6
Vibration resistance (EMR,10…55 Hz): NO/NC g 10/15
without contact current W 0.2 (24 V) - 0.4 (230 V)
Power lost to the environment
with rated current W 0.6 (24 V) - 0.9 (230 V)
Terminals
Screw terminal Push-in terminal
Wire strip length mm 10 8
Screw torque Nm 0.5 —
Solid and stranded cable Solid and stranded cable
Min. wire size mm2 1 x 0.5 1 x 0.5
AWG 1 x 21 1 x 21
Max. wire size mm2 1 x 2.5 1 x 2.5
AWG 1 x 14 1 x 14
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
IV-2019, www.findernet.com
19
39 39 SERIES
SERIES Relay interface modules - Technical data
20
39 SERIES 39
Relay interface modules - Technical data SERIES
21
39 39 SERIES
SERIES Timed interface modules
Max recommended switching frequency (Cycles/Hour, with 50% Duty-cycle) at ambient temperature 50°C, single mounting
Load 39.xx.x.xxx.9024 39.xx.x.xxx.8240 39.xx.x.xxx.7048
24 V 6 A DC1 180 000 — —
24 V 3 A DC L/R = 10 ms 5000 — —
24 V 2 A DC L/R = 40 ms 3600 — —
24 V 1 A DC L/R = 40 ms 6500 — —
24 V 0.8 A DC L/R = 40 ms 9000 — —
24 V 1.5 A DC L/R = 80 ms 3250 — —
230 V 2 A AC1 — 60 000 —
230 V 1.25 A AC15 — 3600 —
48 V 0.1 A DC1 — — 60 000
IV-2019, www.findernet.com
22
39 SERIES 39
Timed interface modules SERIES
Timer specifications
EMC specifications
Type of test Reference standard
contact discharge EN 61000-4-2 4 kV
Electrostatic discharge
air discharge EN 61000-4-2 8 kV
(80 ÷ 1000 MHz) EN 61000-4-3 10 V/m
Radio-frequency electromagnetic field
(1400 ÷ 2700 MHz) EN 61000-4-3 10 V/m
on Supply terminals EN 61000-4-4 4 kV
B
Fast transients (burst) (5-50 ns, 5 and 100 kHz)
on control signal terminals EN 61000-4-4 4 kV
Surges (1.2/50 μs) on supply and control common mode EN 61000-4-5 2 kV
signal terminals differential mode EN 61000-4-5 0.8 kV
Radio-frequency common mode on Supply terminals EN 61000-4-6 10 V
(0.15 ÷ 80 MHz) on control signal terminals EN 61000-4-6 3 V
Radiated and conducted emission EN 55022 class B
Other data
Bounce time (EMR): NO/NC ms 1/6
Vibration resistance (EMR,10...55 Hz): NO/NC g 10/15
without contact current W 0.3
Power lost to the environment
with rated current W 0.8
Terminals
Screw terminal Push-in terminal
Wire strip length mm 10 8
Screw torque Nm 0.5 —
Solid and stranded cable Solid and stranded cable
Min. wire size mm 2
1 x 0.5 1 x 0.5
AWG 1 x 21 1 x 21
Max. wire size mm2 1 x 2.5 1 x 2.5
AWG 1 x 14 1 x 14
Times scales
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
(0.1…3)s (3…60)s (1…20)min (0.3…6)h
OFF Open
ON Open
ON Closed
23
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
(DI) Interval
B Apply power to timer. Output contacts transfer
immediately. After the preset time has elapsed, contacts
1 2 3 4 5
reset.
*
(CE) On- and off-delay with control signal
Power is permenently applied to the timer. Closing the
Signal Switch (S) initiates the preset delay, after which
* With DC supply, 1 2 3 4 5
time the output contacts transfer. Opening the Signal
positive polarity has
switch initiates the same preset delay, after which time
to be conneted to B1,
the output contacts reset.
terminal (according to
EN 60204-1).
(DE) Interval with control signal on
Power is permenently applied to the timer. On momentary
or maintained closure of Signal Switch (S), the output
1 2 3 4 5
contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 24 V AC
IV-2019, www.findernet.com
B1 - A2 = 12 V DC
24
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
Types 3
9.40 Types 3
9.80
39.41 39.81
Screw terminal Screw terminal
IV-2019, www.findernet.com
25
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Main features
Push-in terminals
The push-in terminals permit the quick connection of solid wires or ferrules by their simple insertion into the terminal (A).
It is possible to open the terminal to extract the wire by first pushing down on the push-button using a screwdriver (C).
For stranded cable it is necessary first to open the terminal using the push button, both for the extraction (C) and insertion (B).
It is possible at any time to check the connection via the test aperture, using a 2 mm diameter test probe (D).
A B C D
IV-2019, www.findernet.com
26
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
Solid State Relay (1 Pole 0.1, 2 or 6 A) & Screw Socket Combinations
Interface Module Code Input voltage Relay Socket
MasterBASIC
39.10.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.61.7.024
39.10.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.61.7.024
39.10.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.61.7.024
39.10.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.61.0.125
39.10.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.61.8.230
MasterPLUS
39.30.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.63.7.024
39.30.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.63.7.024
39.30.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.63.7.024
39.30.7.060.xxxx 60 V DC 34.81.7.060.xxxx 93.63.7.060
39.30.7.125.xxxx (110…125)V DC 34.81.7.060.xxxx 93.63.7.125
39.30.7.220.xxxx 220 V DC 34.81.7.060.xxxx 93.63.7.220
39.30.0.024.xxxx 24 V AC/DC 34.81.7.024.xxxx 93.63.0.024
39.30.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.63.0.125
39.30.0.240.xxxx (24…240)V AC/DC 34.81.7.024.xxxx 93.63.0.240
39.30.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.63.8.230
39.30.3.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.63.3.125
39.30.3.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.63.3.230
MasterINPUT
39.40.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.64.7.024
39.40.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.64.7.024
39.40.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.64.7.024
39.40.0.024.xxxx 24 V AC/DC 34.81.7.024.xxxx 93.64.0.024
39.40.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.64.0.125
39.40.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.64.8.230
MasterOUTPUT
39.20.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.62.7.024
IV-2019, www.findernet.com
Solid State Relay (1 Pole 0.1, 2 or 6 A) & Push-in Socket Combinations
Interface Module Code Input voltage Relay Socket
MasterBASIC
39.00.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.60.7.024
39.00.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.60.7.024
39.00.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.60.7.024
39.00.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.60.0.125
39.00.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.60.8.230
MasterPLUS
39.60.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.66.7.024
39.60.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.66.7.024
39.60.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.66.7.024
39.60.7.060.xxxx 60 V DC 34.81.7.060.xxxx 93.66.7.060
39.60.7.125.xxxx (110…125)V DC 34.81.7.060.xxxx 93.66.7.125
39.60.7.220.xxxx 220 V DC 34.81.7.060.xxxx 93.66.7.220
39.60.0.024.xxxx 24 V AC/DC 34.81.7.024.xxxx 93.66.0.024
39.60.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.66.0.125
39.60.0.240.xxxx (24…240)V AC/DC 34.81.7.024.xxxx 93.66.0.240
39.60.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.66.8.230
39.60.3.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.66.3.125
39.60.3.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.66.3.230
MasterINPUT
39.70.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.67.7.024
39.70.7.012.xxxx 12 V DC 34.81.7.012.xxxx 93.67.7.024
39.70.7.024.xxxx 24 V DC 34.81.7.024.xxxx 93.67.7.024
39.70.0.024.xxxx 24 V AC/DC 34.81.7.024.xxxx 93.67.0.024
39.70.0.125.xxxx (110…125)V AC/DC 34.81.7.060.xxxx 93.67.0.125
39.70.8.230.xxxx (230…240)V AC 34.81.7.060.xxxx 93.67.8.230
MasterOUTPUT
39.50.7.006.xxxx 6 V DC 34.81.7.005.xxxx 93.65.7.024
IV-2019, www.findernet.com
29
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Accessories
Output fuse module for 39.31/30/81/80/61/60/91/90 types 093.63 093.63.0.024 093.63.8.230
- For 5 x 20 mm fuses up to 6 A, 250 V
- Type 093.63 - Easy visibility of the fuse condition through the window
- Type 093.63.0.024 - (6…24)V AC/DC with LED fuse status indicator
- Type 093.63.8.230 - (110…240)V AC with LED fuse status indicator
- Quick connection to socket
093.63
B Approvals
Notes
Safety: Because the output circuit can be reinstated (point 3 below), even with the fuse removed, it is important not to
(according to type):
consider the removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse certified
according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output interface to a PLC
no such restrictions apply, and the fuse module can be usefully employed.
Type 093.63 Type 093.63.0.24 / 093.63.8.230
093.63.0.024
093.63.8.230
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open, as
this will generally be the “safe option”.
This state is indicated by the peg/indicator.
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse), or
alternatively, return the peg/indicator to position 0 by gently applying pressure in the direction of the arrow.
IV-2019, www.findernet.com
30
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
Accessories
16-way jumper link 093.16 (blue) 093.16.0 (black) 093.16.1 (red)
Rated values 36 A - 250 V
093.16 Possibility of multiple connection, side by side
093.16.0
B
093.16.1
Approvals
(according to type):
093.60
2. Leaving the ribs in place provides 6.2 mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
093.48
IV-2019, www.findernet.com
Sheet of marker tags (CEMBRE Thermal transfer printers) ,48 tags, 6 x 12 mm 060.48
060.48
31
39 39 SERIES
SERIES Timed interface modules
Accessories
Terminal doubler (for Push-in sockets only) 093.62
Total load 6 A - 300 V
Solid and stranded cable
Max. wire size mm 2
2 x 1.5
AWG 2 x 16
B
MasterADAPTER 093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to 8 MasterINTERFACE modules to PLC outputs
via a 14-Pole ribbon cable, plus simple 2-wire power supply connection ATEX Version.
Technical data
Rated current (per signal path) A 1
Minimum required supply power W 3
Nominal voltage (UN)V DC 24
093.68.14.1 Operating range (0.8…1.1)UN
Approvals
Control logic Positive switching (to A1)
(according to type):
Power supply status indication Green LED
Ambient temperature range °C –40…+70
Terminals for 24 V control logic
Type of connector 14 pole, according to IEC 60603-13
ATEX version II 3G Ex nA IIC Gc
Terminals for 24 V power supply
Wire strip length mm 9.5
Screw torque Nm 0.5
Max. wire size
solid wire mm2 1 x 4 / 2 x 1.5
AWG 1 x 12 / 2 x 16
Connected MasterADAPTER stranded wire mm2 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
Wiring diagram
IV-2019, www.findernet.com
Control panels
Carousel
warehouses
Medical and
dentistry
Shipyards
Elevators and
lifts
Building
automation
Type 48.12
Ideal for safety applications
- 2 CO 8 A
- Screw terminals
- Relay with forcibly guided contacts according
to EN 61810-3 Type B (previously EN 50205)
Type 48.32 B
Ideal for energy applications
- 2 CO 8 A
• 2 CO 8 A • 2 CO 8 A
- Breaking capacity DC inductive (L/R=40 ms)
• Screw terminals • Screw terminals
- 110 V = 0.5 A
- 220 V = 0.2 A
- Screw terminals
• DC coils
• Identification label
• UL Listing (certain relay / socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.12/32
Screw terminal
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
48 48 SERIES
SERIES Relay interface modules 10 A
Type 48.P3
-- 1 CO 10 A
-- Push-in terminals
Type 48.31
B -- 1 CO 10 A
-- Screw terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 1 CO 10 A • 1 CO 10 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P3 48.31
Push-in terminal Screw terminal
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
4
48 SERIES 48
Relay interface modules 8 A SERIES
Type 48.P5
-- 2 CO 8 A
-- Push-in terminals
Type 48.52
-- 2 CO 8 A
-- Screw terminals
B
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 2 CO 8 A • 2 CO 8 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P5 48.52
Push-in terminal Screw terminal
48.52 / 72 48.52 / 72
For outline drawing see page 11
Contact specification
Contact configuration 2 CO (DPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 8/15 8/15
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 2000 2000
Rated load AC15 (230 V AC) VA 400 400
Single phase motor rating (230 V AC) kW 0.3 0.3
Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12 8/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
V DC 12 - 24 - 125 12 - 24 - 125
Rated power AC/sens. DC VA (50 Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)UN (0.8…1.1)UN
sens. DC (0.73…1.5)UN (0.73…1.5)UN
Holding voltage AC/DC 0.8 UN / 0.4 UN 0.8 UN / 0.4 UN
Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN
Technical data
Mechanical life cycles 10 · 106 10 · 106
Electrical life at rated load AC1 cycles 100 · 103 100 · 103
Operate/release time ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
Insulation between coil
and contacts (1.2/50 µs) kV 6 (8 mm) 6 (8 mm)
VII-2019, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
5
48 48 SERIES
SERIES Relay interface modules 16 A
Type 48.P6
-- 1 CO 16 A
-- Push-in terminals
Type 48.61
B -- 1 CO 16 A
-- Screw terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 1 CO 16 A • 1 CO 16 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material available
48.P6 48.61
Push-in terminal Screw terminal
48.61 / 81 48.61 / 81
* For currents > 10 A, contact terminals * For currents > 10 A, contact terminals
must be connected in parallel must be connected in parallel
For outline drawing see page 11 (21 with 11, 24 with 14, 22 with 12). (21 with 11, 24 with 14, 22 with 12).
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 16*/30 16*/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 4000 4000
Rated load AC15 (230 V AC) VA 750 750
Single phase motor rating (230 V AC) kW 0.55 0.55
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 500 (10/5) 500 (10/5)
Standard contact material AgCdO AgCdO
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
V DC 12 - 24 - 125 12 - 24 - 125
Rated power AC/sens. DC VA (50 Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)UN (0.8…1.1)UN
sens. DC (0.8…1.5)UN (0.8…1.5)UN
Holding voltage AC/DC 0.8 UN / 0.4 UN 0.8 UN / 0.4 UN
Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN
Technical data
Mechanical life cycles 10 · 106 10 · 106
Electrical life at rated load AC1 cycles 100 · 10 3
100 · 103
Operate/release time ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
Insulation between coil
and contacts (1.2/50 µs) kV 6 (8 mm) 6 (8 mm)
VII-2019, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
6
48 SERIES 48
Relay interface modules 10 A SERIES
Type 48.P8
-- 2 CO 10 A
-- Push-in terminals
Type 48.62
-- 2 CO 10 A
-- Screw terminals
B
• DC sensitive coils
• Supply status indication and EMC coil • 2 CO 10 A • 2 CO 10 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P8 48.62
Push-in terminal Screw terminal
48.62 / 82 48.62 / 82
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
7
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Ordering information
Example: 48 series, 35 mm rail (EN 60715) mount, Push-in terminal relay interface module, 2 CO 8 A contacts, 24 V sensitive DC coil, green LED + diode,
99.02 coil indication.
A B C D
4 8 . P 5 . 7 . 0 2 4 . 0 0 5 0
B Series A: Contact material D: Special versions
0 = Standard AgNi for 0 = Standard
Type 48.P3/P5/P8/31/52/62 7 = Standard (for 48.12 only)
Screw terminal AgCdO, Standard
1 = 35 mm rail (EN 60715) mount, for 48.P6/61 C: Options
forcibly guided contacts relay 4 = AgSnO2, for 48.P6/P8/ 0 = Standard (for 48.12 only)
3 = 35 mm rail (EN 60715) mount 61/62 only 5 = Standard for DC:
5 = 35 mm rail (EN 60715) mount 5 = AgNi + Au, for 48.12 and green LED + diode (polarity +A1)
6 = 35 mm rail (EN 60715) mount 48.P3/P5/31/52 only 6 = Standard for AC and 48.32:
Push-in terminal Standard for 48.32 green LED + Varistor
P = 35 mm rail (EN 60715) mount
B: Contact circuit
Type 0 = CO (nPDT)
Screw terminal
1 = for 48.31, 1 pole, 10 A
48.61, 1 pole, 16 A
2 = for 48.12/48.32 (DC only), 48.52, 2 poles, 8 A
48.62 (DC only), 2 poles, 10 A
Push-in terminal Selecting features and options: only combinations in the same row are possible.
3 = for 48.P3, 1 pole, 10 A Preferred selections for best availability are shown in bold.
5 = for 48.P5, 2 pole, 8 A
6 = for 48.P6, 1 pole, 16 A Type Coil version A B C D
8 = for 48.P8 (DC only), 2 pole, 10 A 48.12 DC 5 0 0 7
Coil version 48.32 DC 5 0 6 0
7 = Sensitive DC 48.P3/P5/31/52 AC 0-5 0 6 0
8 = AC (50/60 Hz) 48.P3/P5/31/52 Sensitive DC 0-5 0 5 0
9 = DC (for 48.12 only)
48.P6/61 AC 0-4 0 6 0
Coil voltage 48.P6/61 Sensitive DC 0-4 0 5 0
See coil specifications
48.P8/62 Sensitive DC 0-4 0 5 0
Technical data
Insulation 48.12/31/32/61/P3/P6 48.52/P5 48.12/31/61/62/P3/P6/P8
Insulation according to EN 61810-1 insulation rated voltage V 250 250 400
rated impulse withstand voltage kV 4 4 4
pollution degree 3 2 2
overvoltage category III III III
Insulation between coil and contacts (1.2/50 µs) kV 6 (8 mm)
Dielectric strength between open contacts V AC 1000; 1500 (48.12/32)
Dielectric strength between adjacent contacts V AC 2000 (48.P5/52); 2500 (48.P8/62) 3000 (48.12/32)
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/5; 2/10 (48.12/32)
Vibration resistance (10…200)Hz: NO/NC g 20/5 (for 1 pole) 15/3; 20/6 (48.12/32) for 2 pole
Power lost to the environment without contact current W 0.7
with rated current W 1.2 (48.12/31/32/P3) 2 (48.52/P5/61/62/P6/P8)
Wire strip length mm 8
Screw torque (only for 48.12/31/32/52/61/81) Nm 0.5
Min. wire size Screw terminal Push-in terminal
solid cable stranded cable solid cable stranded cable
mm2 0.5 0.5 0.5 0.5
VII-2019, www.findernet.com
AWG 21 21 21 21
Max. wire size Screw terminal Push-in terminal
solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x 16 / 1 x 14 2 x 16 / 1 x 14
8
48 SERIES 48
Relay interface modules 8 - 10 - 16 A SERIES
Contact specification
F 48 - Electrical life (AC) v contact current F 48 - Electrical life (AC) v contact current
Types 48.P3/P6/31/61 Types 48.P8/62
Cycles
Inductive load AC15
8 12
F 48 - Electrical life (AC) v contact current F 48 - Electrical life (AC) v contact current
Types 48.P5/52 Type 48.12/32
Cycles
H 48 - Maximum DC1 breaking capacity H 48 - Maximum DC1 breaking capacity
Types 48.P3/P5/P6/31/52/61 Types 48.P8/62
2 contacts in series
2 contacts in series
single contact
single contact
9
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Coil specifications
* Umin = 0.8 UN for 48.61, 48.62, 48.P6, 48.P8 120 8.120 96 132 11.8
230 8.230 184 253 7.0
DC coil data, (0.7 W standard) - Type 48.12/48.32, (48.32 available only 24 V DC)
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
12 9.012 9 14.4 205 58.5
24 9.024 18 28.8 820 29.3
R 48 - DC coil operating range v ambient temperature R 48 - AC coil operating range v ambient temperature
48.P3/P5/31/52
48.P6/P8/61/62 1
48.P6/P8/61/62
2 2
48.P3/P5/31/52
10
48 SERIES 48
Relay interface modules 8 - 10 - 16 A SERIES
Outline
drawings
64.5
15.8 25.9 17.5 17.5
21.6
78.6
35.4
25.5
32
Types 4
8.31 48.32 / 48.52 / 48.61 / 48.62 Type 48.12
Screw terminal Screw terminal
11
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Accessories
8-way jumper link for type 48.P3/P5/P6/P8 097.58
Rated values 10 A - 250 V
097.58
B
2-way jumper link for type 48.P3/P5/P6/P8 097.52
Rated values 10 A - 250 V
097.52
097.42
097.00
PEAN
8-way jumper link for screw terminal version 095.18 (blue) 095.18.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.18
060.48
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
4 8 . P 5 . 7 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
Relay interface
modules 8 - 10 - 16 A
Escalators
Road / tunnel
lighting
Hoists and
cranes
Carousel
warehouses
Control panels
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C ≤ 12 A: –40…+70/>12 A: –40…+50 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
4
4C SERIES 4C
Relay interface modules 8 to 16 A SERIES
Ordering information
Example: 4C series, 35 mm rail (EN 60715) mount, Push-in terminal relay interface module, 1 CO 10 A contacts, 24 V DC coil, green LED + diode.
A B C D
4 C . P 1 . 9 . 0 2 4 . 0 0 5 0
Series A: Contact material
0 = AgNi
D: Special versions
0 = Standard
B
Type 4 = AgSnO2
0 = 35 mm rail (EN 60715) mount 5 = AgNi + Au C: Options
screw terminal socket 5 = Standard for DC:
P = 35 mm rail (EN 60715) mount B: Contact circuit green LED + diode (polarity +A1)
Push-in terminal socket 0 = CO (nPDT) 6 = Standard for AC:
green LED + Varistor
No. of poles
1 = 1 pole, 10/16 A
2 = 2 pole, 8 A
Coil version
8 = AC (50/60 Hz) Selecting features and options: only combinations in the same row are possible.
9 = DC Preferred selections for best availability are shown in bold.
Technical data
Insulation
Insulation according to EN 61810-1 insulation rated voltage V 250 440
rated impulse withstand voltage kV 4 4
pollution degree 3 2
overvoltage category III III
Insulation between coil and contacts (1.2/50 μs) kV 6 (8 mm)
Dielectric strength between open contacts V AC 1000
Dielectric strength between adjacent contacts V AC 2000
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/6 (4C.01/P1) 1/4 (4C.02/P2)
Vibration resistance (10…150)Hz: NO/NC g 20/12
Power lost to the environment without contact current W 0.6
with rated current W 1.6 (4C.01/P1) 2 (4C.02/P2)
Terminals 4C.01/4C.02 4C.P1/4C.P2
Wire strip length mm 8 8
Screw torque Nm 0.8 —
Min. wire size solid cable stranded cable solid cable stranded cable
mm 2
0.5 0.5 0.5 0.5
AWG 21 21 21 21
XII-2018, www.findernet.com
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x 16 / 1 x 14 2 x 16 / 1 x 14
5
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Contact specification
F 4C - Electrical life (AC) v contact current F 4C - Electrical life (AC) v contact current
Types 4C.02/P2 Types 4C.01/P1
Cycles
limit for 4C.P1
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN
V V V Ω mA V V V Ω mA
12 9.012 8.8 13.2 300 40 12 8.012 9.6 13.2 80 90
24 9.024 17.5 26.4 1200 20 24 8.024 19.2 26.4 320 45
125 9.125 91.2 138 32000 3.9 110 8.110 88 121 6900 9.4
120 8.120 96 132 9000 8.4
230 8.230 184 253 28000 5
R 4C - DC coil operating range v ambient temperature R 4C - AC coil operating range v ambient temperature
XII-2018, www.findernet.com
6
4C SERIES 4C
Relay interface modules 8 to 16 A SERIES
Outline drawings B
Accessories
8-way jumper link for type 4C.P1 and 4C.P2 097.58
Rated values 10 A - 250 V
097.58
097.52
097.42
XII-2018, www.findernet.com
7
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Accessories
Marker tag holder for type 4C.P1/P2/01/02 097.00
097.00
PEAN
8-way jumper link for 4C.01 and 4C.02 095.18 (blue)
O
T
N
T E
EUR
P A O
PEAN
095.18
060.48
Packaging codes
How to code and identify retaining clip and packaging options for relay interface module.
Example:
4 C . P 1 . 9 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
XII-2018, www.findernet.com
Relay interface
modules 6 - 7 - 10 A
Control panels
Packaging
machines
Shipyards
Textile
machines
Carousel
warehouses
Wood-processing
machines
58 SERIES 58
Relay interface modules 7 - 10 A SERIES
Type 58.P3
-- 3 CO 10 A
-- Push-in terminals
Type 58.P4
-- 4 CO 7 A
-- Push-in terminals
B
• AC coils or DC coils
• Supply status indication and EMC coil • 3 CO 10 A • 4 CO 7 A
suppression module as standard
• Push-in terminals • Push-in terminals
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
58.P3 / 58.P4
Push-in terminals
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
58 58 SERIES
SERIES Relay interface modules 7 - 10 A
Type 58.32
-- 2 CO 10 A
-- Screw terminals
Type 58.33
B -- 3 CO 10 A
-- Screw terminals
Type 58.34
-- 4 CO 7 A
• 2 CO 10 A • 3 CO 10 A • 4 CO 7 A
-- Screw terminals
• Screw terminals • Screw terminals • Screw terminals
• AC coils or DC coils
• Supply status indication and EMC coil
suppression module as standard
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
58.32 / 58.33 / 58.34
Screw terminals
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+70 –40…+70 –40…+70
Protection category IP 20 IP 20 IP 20
Approvals relay (according to type)
4
58 SERIES 58
Relay interface modules 6 - 10 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
5
58 58 SERIES
SERIES Relay interface modules 6 - 7 - 10 A
Ordering information
Example: 58 series, 35 mm rail (EN 60715) mounting, Push-in terminals interface module, 4 CO, 24 V DC coil, green LED + diode.
A B C D
5 8 . P 4 . 9 . 0 2 4 . 0 0 5 0
No. of poles
2 = 2 pole, 10 A
3 = 3 pole, 10 A
4 = 4 pole, 7 A
Selecting features and options: only combinations in the same row are possible.
Coil version
Preferred selections for best availability are shown in bold.
8 = AC (50/60 Hz)
9 = DC
Type Coil version A B C D
Coil voltage 58.P3/P4/32/33/34 AC 0-5 0 6 0
See coil specifications 58.P3/P4/32/33/34 DC 0-5 0 5 0
A B C D
5 8 . 3 4 . 8 . 1 2 0 . 0 0 4 9
Series A: Contact material D: Special versions
0 = AgNi Standard 8 = ATEX compliant (Ex nA nC)
Type 2 = AgCdO without mechanical indicator
3 = Screw terminals 5 = AgNi + Au 9 = ATEX compliant (Ex nA nC)
35 mm rail (EN 60715) mount with mechanical indicator
B: Contact circuit
No. of poles 0 = CO (nPDT) C: Options
2 = 2 pole, 10 A 4 = Module 99 LED (AC/DC)
4 = 4 pole, 6 A 5 = Module 99
LED + Diode (DC)
Coil version
8 = AC (50/60 Hz)
9 = DC
Coil voltage
See coil specifications
VII-2019, www.findernet.com
6
58 SERIES 58
Relay interface modules 6 - 7 - 10 A SERIES
Technical data
Insulation
Insulation according to EN 61810-1 insulation rated voltage V 400 (2-3 pole) 250 (4 pole)
rated impulse withstand voltage kV 3.6 (2-3 pole) 2.5 (4 pole)
pollution degree 2 2
overvoltage category III II
Insulation between coil and contacts (1.2/50 μs) kV 3.6
Dielectric strength between open contacts V AC 1000 B
Dielectric strength between adjacent contacts V AC 2000 (58.32,58.33, 58.P3) 1550 (58.34, 58.P4)
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4
Other data
Bounce time: NO/NC ms
1/3
Vibration resistance (10…55)Hz: NO/NC g
6/6
Power lost to the environment without contact current W
1
with rated current W
3 (58.32, 58.34, 58.P4) 4 (58.P3, 58.33)
58.32/33/34 (screw terminals) 58.P3/P4 (Push-in terminals)
Wire strip length mm 8 8
Screw torque Nm 0.5 —
Min. wire size solid cable stranded cable solid cable stranded cable
mm2 0.5 0.5 0.5 0.5
AWG 21 21 21 21
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x 16 / 1 x 14 2 x 16 / 1 x 14
Ambient temperature
EPT 15 ATEX 0195 U
EPT: laboratory which issues the CE type certificate
15: year of issue of certificate
0195: number of CE type certificate
U: ATEX component
7
58 58 SERIES
SERIES Relay interface modules 7 - 10 A
Contact specification
F 58 - Electrical life (AC) v contact current F 58 - Electrical life (AC) v contact current
2 & 3 pole relays 4 pole relay
Cycles
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
DC voltage (V)
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage absorption voltage absorption
UN Umin Umax R I at UN UN Umin Umax R I at UN (50 Hz)
V V V Ω mA V V V Ω mA
12 9.012 9.6 13.2 140 86 12 8.012 9.6 13.2 50 97
24 9.024 19.2 26.4 600 40 24 8.024 19.2 26.4 190 53
48 9.048 38.4 52.8 2400 20 48 8.048 38.4 52.8 770 25
125 9.125 100 138 17300 7.2 110 8.110 88 121 4000 12.5
120 8.120 96 132 4700 12
230 8.230 184 253 17000 6
R 58 - DC coil operating range v ambient temperature R 58 - AC coil operating range v ambient temperature
1
1
2 2
VII-2019, www.findernet.com
8
58 SERIES 58
Relay interface modules 7 - 10 A SERIES
Outline drawings B
9
58 58 SERIES
SERIES Relay interface modules 7 - 10 A
Accessories
2-way jumper link for type 58.P3 and 58.P4 094.52.1
Rated values 10 A - 250 V
094.52.1
B
097.52
Marker tag holder for type 58.P3, 58.P4, 58.32, 58.33 and 58.34 097.00
097.00
PEAN
6-way jumper link for type 58.32, 58.33, 58.34 094.06 (blue) 094.06.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
094.06
PEAN
6-way jumper link for type 58.P3 and 58.P4 094.56 (blue)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
094.56
060.48
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
5 8 . P 4 . 9 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
Panels for
electrical
distribution
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Wiring diagram
DC (0.8…1.1)UN
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
3
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Wiring diagram
DC (0.8…1.1)UN
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
4
19 SERIES 19
Relay actuators & Status indicating modules SERIES
5
19 19 SERIES
SERIES Relay actuators & Status indicating modules
6
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Ordering information
Example: 19 series Auto/Off/On override module, 1 CO (SPDT) 10 A contact, 24 V AC/DC supply.
1 9 . 2 1 . 0 . 0 2 4 . 0 0 0 0
Series Contact circuit
Type
0 = Standard B
21 = Auto/Off/On output module, 11.2 mm 3 = NO (19.6K)
50 = Analogue override module (0…10)V
91 = Power relay module Contact material
6K = KNX actuator, 6 poles 16 A 0 = Standard for 19.21, 19.50
4 = Standard for 19.91, 19.6K
Supply version
0 = AC (50/60 Hz)/DC
9 = DC
Supply voltage
012 = 12 V
024 = 24 V Codes / Module width
030 = KNX Bus 19.21.0.024.0000/11.2 mm
19.50.0.024.0000/17.5 mm
19.91.9.012.4000/17.5 mm
19.91.9.024.4000/17.5 mm
19.6K.9.030.4300/70 mm
Technical data
Insulation 19.21 19.50 19.91
Dielectric strength (V AC) between supply and contacts 3000 — 4000
between open contacts 1000 — 1000
between supply and feedback output 2000 1500 —
EMC specifications
Type of test Reference standard 19.21/91 19.50
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 30 V/m
Fast transients (burst) (5-50 ns, 5 kHz) EN 61000-4-4 4 kV
Voltage pulses (1.2/50 µs) common mode EN 61000-4-5 2 kV 1 kV
on supply terminals differential mode EN 61000-4-5 1 kV 0.5 kV
Terminals 19.21/6K 19.50/91
Screw torque Nm 0.5 0.8
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 1.5 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 16 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Wire strip length mm 7 9
VII-2019, www.findernet.com
7
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Type 19.50
In selector position A (Automatic) the (0…10)V controller variable is transferred via Yin - A2 and Yout to the end process.
In selector position H (Hand) the (0…10)V value set by the regulator is transferred via Yout to the end process.
Type 19.6K
VII-2019, www.findernet.com
8
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Outline drawings
Type 19.21 Type 19.50
Screw terminal Screw terminal
9
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Accessories
Sheet of marker tags (CEMBRE Thermal transfer printers) for 19.21/50/91/6K types
(48 tags), 6 x 12 mm 060.48
060.48
B
Identification tag, for 19.50 types, plastic, 1 tag, 17 x 25.5 mm 019.01
019.01
Adaptor for panel mounting, for 19.21/50/91 types, plastic, 17.5 mm wide 020.01
020.01
VII-2019, www.findernet.com
10
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Application notes
Intervention Modules
The demand for security apparatus, heating, air conditioning or
efficient energy use in offices, hotels, and private homes or in
industrial space is growing constantly, leading to the installation of
increasingly complex electronic systems. But what happens if these
systems malfunction and a qualified service technician will only be
available in a few hours, or even days?
B
With the use of carefully installed intervention modules, a trained
caretaker or security guard can be in a position to recognize
interruptions in service, and by manual intervention perform the
necessary override actions to maintain system operation until a repair
can be effected.
guided contacts 8 A
Escalators
Medical and
dentistry
Hospitals
Carousel
warehouses
Elevators and
lifts
Disabled lift
Wood-
processing
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
*A
ccording to EN 61810-3 only 1 NO and 1 NC
(11-14 and 21-22 or 11-12 and 21-24) shall be
used as forcibly guided contacts.
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)
3
50 50 SERIES
SERIES Forcibly guided contacts relay 8 A
3 NO + 1 NC
Ø1.3
7.6
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT III RT III
Approvals (according to type)
4
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
Ordering information
Example: 50 series forcibly guided contacts, 2 CO (DPDT) 8 A contacts, 24 V DC coil.
A B C D
5 0 . 1 2 . 9 . 0 2 4 . 5 0 0 0
Series A: Contact material D: Special versions
1 = AgNi (50.12) 0 = Flux proof (RT II)
Type 4 = AgSnO2 (50.14) 0 = Wash tight (RT III), 50.14, 50.16
1 = PCB 5 = AgNi + Au (50.12) C: Options
5 = AgSnO2 + Au (50.16) 0 = CO
No. of poles
2 = 2 pole 8 A B: Contact circuit
1 = 1 NC
2 = 2 NC
C
4 = 4 pole 8 A 0 = CO (DPDT) 3 = 3 NC
6 = 6 pole 8 A 2 = 2 NO
3 = 3 NO
Coil version 4 = 4 NO
9 = DC 5 = 5 NO
Coil voltage
See coil specifications
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm)
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
Type of insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength (50.12, 50.16) V AC 3000
Dielectric strength (50.14) V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1500/2.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/10
Vibration resistance (10…200)Hz: NO/NC g 20/6
Shock resistance NO/NC g 20/5
Power lost to the environment without contact current W 0.7
with rated current W 1.2
Recommended distance between relays mounted on PCB mm ≥ 5
VII-2019, www.findernet.com
5
50 50 SERIES
SERIES Forcibly guided contacts relay 8 A
Contact specification
F 50 - Electrical life (AC) v contact current (type 50.12) H 50 - Maximum DC1 breaking capacity (type 50.12)
C
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
R 50 - DC coil operating range v ambient temperature
DC coil data (type 50.12) Standard coil (type 50.12)
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
5 9.005 3.8 6 35 143
6 9.006 4.5 7.2 50 120
12 9.012 9 14.4 205 58.5
24 9.024 18 28.8 820 29.3
48 9.048 36 57.6 3280 14.4
60 9.060 45 72 5140 11.7
110 9.110 82.5 131 17250 6.4
125 9.125 93.7 150 22300 5.6
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
DC coil data (type 50.14/16)
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
12 9.012 9 14.4 180 66.6
VII-2019, www.findernet.com
6
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
Contact specification
F 50 - Electrical life (AC) v contact current (type 50.14) H 50 - Maximum DC1 breaking capacity (type 50.14)
2 4 6 8
C
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
F 50 - Electrical life (AC) v contact current (type 50.16) H 50 - Maximum DC1 breaking capacity (type 50.16)
2 4 6 8
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Outline drawings
Types 50.12…1000/50.12…5000 Type 50.14 Type 50.16
VII-2019, www.findernet.com
forcibly guided
contacts 6 - 10 A
Chemical and
petrolchemical
Wood-
processing
machines
Carousel
warehouses
Escalators
Elevators
and lifts
Process
Industry
Automatic
car-washes
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7S SERIES 7S
Modular relays with forcibly guided contacts 6 A SERIES
3
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 10 A
4
7S SERIES 7S
Modular relays with forcibly guided contacts 6 A SERIES
5
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Ordering information
Example: 7S series Modular relay with forcibly guided contacts, 6 contact (4 NO + 2 NC) 6 A, supply voltage 24 V DC.
7 S . 1 6 . 9 . 0 2 4 . 5 4 2 0
Series Special versions
Type 0 = Standard
1 = 22.5 mm wide, screwless terminals 1 = NO auxliary contact
2 = 17.5 mm wide, screw terminals NO and NC contatcs
3 = 22.5 mm wide, screw terminals 11 = 1 NO + 1 NC
4 = 22.5 mm wide, screwless terminals 21 = 2 NO + 1 NC
C 6 = 22.5 mm wide, screw terminals 22 = 2 NO + 2 NC
Output 31 = 3 NO + 1 NC
2 = 2 contacts 42 = 4 NO + 2 NC
3 = 3 contacts Contact material
4 = 4 contacts 0 = AgNi +Au (7S.23) only
6 = 6 contacts 0 = AgSnO2 & AgNi + Au
Supply version (7S.43/63) only
8 = AC (50 /60 Hz) 4 = AgSnO2 (7S.14/34) only
9 = DC 5 = AgNi +Au (7S.12/32) only
Supply voltage 5 = AgSnO2 + Au (7S.16/36) only
See page 10
Codes, Preferred selections for best availability are shown in bold.
7S.12.9.012.5110 7S.14.9.012.4220 7S.16.9.012.5420
7S.12.9.024.5110 7S.14.9.012.4310 7S.16.9.024.5420
7S.12.8.120.5110 7S.14.9.024.4220 7S.16.9.110.5420
7S.12.8.230.5110 7S.14.9.024.4310 7S.16.8.120.5420
7S.14.9.110.4220 7S.16.8.230.5420
7S.32.9.012.5110 7S.14.9.110.4310
7S.32.9.024.5110 7S.14.8.120.4220 7S.36.9.012.5420
7S.32.8.120.5110 7S.14.8.120.4310 7S.36.9.024.5420
7S.32.8.230.5110 7S.14.8.230.4220 7S.36.9.110.5420
7S.14.8.230.4310 7S.36.8.120.5420
7S.43.9.012.0211 7S.36.8.230.5420
7S.43.9.024.0211 7S.34.9.012.4220
7S.43.9.048.0211 7S.34.9.012.4310 7S.23.9.012.0210
7S.43.9.110.0211 7S.34.9.024.4220 7S.23.9.024.0210
7S.34.9.024.4310 7S.23.9.048.0210
7S.63.9.012.0211 7S.34.9.110.4220 7S.23.9.110.0210
7S.63.9.024.0211 7S.34.9.110.4310
7S.63.9.048.0211 7S.34.8.120.4220
7S.63.9.110.0211 7S.34.8.120.4310
7S.34.8.230.4220
7S.34.8.230.4310
VII-2019, www.findernet.com
6
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250
Pollution degree 2
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
C
Type of Insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1500/2.5
7
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Contact specifications
Contact diagrams
7S.12/7S.32 7S.14/34....4220 7S.14....4310 7S.16/36....5420 7S.23
12 34
11 33
11 12
43
C
54 33 34
7S.43/7S.63
23 47
23 47
24 48
24 48
11 33 23
33 23
11 47 48
47 48
12
12 34 24
24
F 7S12 - Electrical life (AC) v contact current - 7S.12 H 7S12* - Maximum DC breaking capacity - 7S.12
Resistive load
Corrente DC (A)
Tensione DC (V)
F 7S14 - Electrical life (AC) v contact current - 7S.14/34 H 7S14* - Maximum DC breaking capacity - 7S.14/34
VII-2019, www.findernet.com
2 4 6 8
Tensione DC (V)
* When switching a load having voltage and current values under the
curve, an electrical life of ≥ 100 · 103 can be expected.
8
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Contact specifications
F 7S16 - Electrical life (AC) v contact current - 7S.16/36 H 7S16* - Maximum DC breaking capacity - 7S.16/36
C
2 4 6 8
DC voltage (V)
F 7S23 - Electrical life (AC) v contact current - 7S.23 H 7S23* - Maximum DC breaking capacity - 7S.23
DC voltage (V)
F 7S43 - Electrical life (AC) v contact current - 7S.43/63 H 7S43* - Maximum DC breaking capacity - 7S.43/63
DC breaking current (A)
Resistive load
Resistive load - cosϕ = 1
Inductive load - AC15 Inductive load - DC13
Cycles
2 4 6 8
DC voltage (V)
* When switching a load having voltage and current values under the
curve, an electrical life of ≥ 100 · 103 can be expected.
VII-2019, www.findernet.com
9
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Coil specifications
DC coil data - type 7S.12/32 AC coil data - type 7S.12/32
Nominal Coil Operating range Rated input Rated Nominal Coil Operating range Rated input Rated
voltage code current power voltage code current power
at UN at UN at UN at UN
UN Umin Umax IN UN Umin Umax IN
V V V mA W V V V mA VA/W
12 9.012 9.6 14.4 55 0.7 110…125 8.120 93 138 9.8 1.2/1.1
24 9.024 16.8 30 38.2 0.9 230…240 8.230 195 264 11.8 2.8/1.2
DC coil data - type 7S.14/34 / 7S.16/36 AC coil data - type 7S.14/34 / 7S.16/36
Nominal Coil Operating range Rated input Rated Nominal Coil Operating range Rated input Rated
C voltage code current power voltage code current power
at UN at UN at UN at UN
UN Umin Umax IN UN Umin Umax IN
V V V mA W V V V mA VA/W
12 9.012 9.6 14.4 64.7 0.8 110…125 8.120 93 138 10.2 1.3/1.1
24 9.024 16.8 30 42.2 1 230…240 8.230 195 264 11.8 2.9/1.2
110 9.110 77 138 11.6 1.4
R 7S - DC coil operating range v ambient temperature - R 7S - AC coil operating range v ambient temperature -
7S.12/32 / 7S.23 / 7S.14/34 / 7S.16/36 7S.12/32 / 7S.14/34 / 7S.16/36
10
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Safety PLC
feedback
output
feedback
Type 7S.43
Safety PLC L
feedback
output
K1
K2
K3
K4
23 47
48
K2 K3
feedback
3
K1 K4
4
VII-2019, www.findernet.com
11
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Outline drawings
Types 7S.12/14/16/43 Type 7S.23
Screwless terminal Screw terminal
22.5 4.3 96
33.8
59.5
78.8
86.2
30.5
Accessories
Sheet of marker tags, plastic, 48 tags, 6 x 12 mm, for CEMBRE thermal transfer printers 060.48
VII-2019, www.findernet.com
060.48
Drying kilns
Heating and
cooling
Lighting control
in corridors (for
hotels, offices
and hospitals)
Bottling plant
Labelling
machines
Packaging
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
77 SERIES 77
Modular Solid State Relays 5 A SERIES
Simplified Simplified
For outline drawing see page 16 circuit diagram circuit diagram
Output specification
Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current IN/Max. peak current* (10 ms) A 5/300* 5/300*
Rated voltage V AC (50/60 Hz) 230 230
Switching voltage range V AC (50/60 Hz) 48…265 48…265
Repetitive peak off-state voltage Vpk 800 800
Rated load AC7a (cos ϕ = 0.8) A 5 5
Rated load AC15 A 5 3
Single phase motor rating (230 V AC) kW — 0.1
Nominal lamp rating:
230 V incandescent/halogen W 1000 800
fluorescent tubes with
electronic ballast W 1000 800
fluorescent tubes with
electromechanical ballast W 1000 800
CFL W 800 400
230 V LED W 800 400
LV halogen or LED with
electronic ballast W 800 400
LV halogen or LED with
electromechanical ballast W 1000 800
Minimum switching current @ 230 V mA 100 100
Typical “OFF-state” leakage current @ 230 V mA 0.5 3.5
Max “ON-state” voltage drop
@ 25 °C and 5 A/100 mA V 0.85/1.5 0.85/1.5
Power loss @ 5 A W 4 4
Input specification
Nominal voltage (UN) V AC (50/60 Hz) 24 230 24 230
V DC 12…24 — 12…24 —
Rated power VA (50 Hz)/W 0.6/0.5 3.6/0.3 0.6/0.5 3.6/0.3
Operating range V AC (50/60 Hz) 16…32 90…265 16…32 90…265
V DC 9.8…32 — 9.8…32 —
Must drop-out voltage V AC (50/60 Hz)/DC 2.4 24 2.4 24
Technical data
Electrical life cycles 10 · 106 10 · 106
Operate/release time ms 20/12 9/8
VII-2018, www.findernet.com
3
77 77 SERIES
SERIES Modular Solid State Relays 7 - 15 A
Simplified Simplified
For outline drawing see page 16 circuit diagram circuit diagram
Output specification
Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current IN/Max. peak current (10 ms) A 15/160 7/60
Rated voltage V DC 24 125
Switching voltage range V DC 16…32 43…140
Rated load DC13 A 5 2.5
DC motor rating kW 0.2 —
Minimum switching current mA 100 50
Typical “OFF-state” leakage current mA 3 6
Max “ON-state” voltage drop
@ 25 °C and INV 0.06 0.2
Power loss @ INW 1 1.5
Input specification
Nominal voltage (UN) V DC 6…24 6…24
Rated power W 0.5 0.5
Operating range V DC 4…36 4…36
Must drop-out voltage V DC 3 3
Technical data
Electrical life cycles 10 · 106 10 · 106
Operate/release time ms 0.05/2 0.05/2
Insulation between input
and output (1.2/50 µs) kV 4 4
Ambient temperature °C –20…+70* –20…+70*
Protection category IP 20 IP 20
Approvals (according to type)
VII-2018, www.findernet.com
4
77 SERIES 77
Modular Solid State Relays 15 A SERIES
5
77 77 SERIES
SERIES Modular Solid State Relays 30 A
6
77 SERIES 77
Modular Solid State Relays 30 A SERIES
7
77 77 SERIES
SERIES Hockey puck Solid State Relays 25 - 40 - 50 A
8
77 SERIES 77
Hockey puck Solid State Relays 25 - 40 - 50 A SERIES
9
77 77 SERIES
SERIES Solid State Relays
Ordering information
Example: 77 series modular SSR, 1 output 30 A AC, input voltage 230 V AC, relay style terminals arrangement, zero-crossing switch-on.
A B C D
7 7 . 3 1 . 8 . 2 3 0 . 8 0 5 0
Series D: Switch-on mode
Type/rated current 0 = Zero-crossing
0 = 5/7/15 A output (77.01) 1 = Random
1 = 15 A output (77.11) C: Terminals arrangement
2 = 25 A output (77.25) 5 = “Relay style” (input and
3 = 30 A output (77.31) output on opposite sides)
4 = 40 A output (77.45) 7 = “Contactor style” (input and
5 = 50 A output (77.55) output on adjacent sides)
No. of poles/mounting AB: Output circuit
1 = 1 pole, modular housing (rated voltage)
(plastic or heat sink/plastic), DIN rail mounting 80 = 230 V AC (77.01), 400 V AC (77.31)
5 = 1 pole, heat-sink or directly panel mounting 82 = 230 V AC (77.11, 77.x5)
(“hockey puck”) 86 = 600 V AC (77.x5)
D Input version 9024 = 24 V DC
0 = DC/AC (50/60 Hz) 9125 = 110…125 V DC
8 = AC (50/60 Hz)
9 = DC
Supply voltage
See “input specification”
Codes/Module width
77.01.8.230.8050/17.5 mm 5 A 77.11.8.230.8250/22.5 mm 15 A 77.31.8.230.8050/22.5 mm 30 A 77.25.8.230.8250/hockey puck 25 A
77.01.0.024.8050/17.5 mm 5 A 77.11.9.024.8250/22.5 mm 15 A 77.31.9.024.8050/22.5 mm 30 A 77.25.9.024.8250/hockey puck 25 A
77.01.8.230.8051/17.5 mm 5 A 77.11.8.230.8251/22.5 mm 15 A 77.31.8.230.8051/22.5 mm 30 A 77.25.8.230.8650/hockey puck 25 A
77.01.0.024.8051/17.5 mm 5 A 77.11.9.024.8251/22.5 mm 15 A 77.31.9.024.8051/22.5 mm 30 A 77.25.9.024.8650/hockey puck 25 A
77.01.9.024.9125/17.5 mm 7 A 77.31.8.230.8070/22.5 mm 30 A 77.45.8.230.8250/hockey puck 40 A
77.01.9.024.9024/17.5 mm 15 A 77.31.9.024.8070/22.5 mm 30 A 77.45.9.024.8250/hockey puck 40 A
77.31.8.230.8071/22.5 mm 30 A 77.45.8.230.8650/hockey puck 40 A
77.31.9.024.8071/22.5 mm 30 A 77.45.9.024.8650/hockey puck 40 A
77.55.8.230.8250/hockey puck 50 A
77.55.9.024.8250/hockey puck 50 A
77.55.8.230.8650/hockey puck 50 A
77.55.9.024.8650/hockey puck 50 A
Technical data
77.01.8xxx 77.01.9xxx 77.11 77.31 72.25/45/55
Dielectric Impulse Dielectric Impulse Dielectric Impulse Dielectric Impulse Dielectric Impulse
strength (1.2/50 µs) strength (1.2/50 µs) strength (1.2/50 µs) strength (1.2/50 µs) strength (1.2/50 µs)
Between input and output 2500 V AC 5 kV 3000 V AC 4 kV 3000 V AC 6 kV 3000 V AC 6 kV 4000 V AC 5.6 kV
Between input and ground (heat-sink) — — — — 3000 V AC 6 kV 3000 V AC 6 kV 4000 V AC 5.6 kV
Between output and ground (heat-sink) — — — — 2500 V AC 4 kV 4000 V AC 6 kV 4000 V AC 5.6 kV
EMC specifications Reference 77.01.x.xxx 77.01.9.xxx 77.11 77.31 77.25/45/55
standard
24 V AC/DC 230 V AC 24 V DC 24 V DC 230 V AC 24 V DC 230 V AC 24 V DC - 230 V AC
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV 4 kV 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV 8 kV 8 kV 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 30 V/m — 20 V/m 30 V/m —
Fast transients on supply terminals
(burst 5/50 ns, 5 and 100 kHz) EN 61000-4-4 1 kV 4 kV 2 kV 1 kV 3 kV 1 kV 3 kV 2 kV
Voltage pulses on supply common mode EN 61000-4-5 2 kV 4 kV 1 kV 3 kV 3 kV 3 kV 3 kV 2 kV
terminals (surge 1.2/50 µs) differential mode EN 61000-4-5 1 kV 4 kV 0.5 kV 0.5 kV 1.5 kV 0.5 kV 1.5 kV 1 kV
Radio-frequency common
mode voltage (0.15…230 MHz) on supply terminals EN 61000-4-6 — 10 V 10 V 10 V —
Terminals 77.01.x.xxx 77.01.9.xxx 77.11 77.31 77.25/45/55
Input Output
Screw torque Nm 0.8 0.8 0.8 0.8 0.5 1.2
Max. wire size solid stranded solid stranded solid stranded solid stranded solid and stranded
cable cable cable cable cable cable cable cable cable
mm2 1 x 6 / 1 x 4 / 1 x 6 / 1 x 4 / 1 x 6 / 1 x 6 / 1 x 6 / 1 x 6 / 1 (with 4 (with
2 x 4 2 x 2.5 2 x 4 2 x 2.5 2 x 4 2 x 4 2 x 4 2 x 4 ferrule) ferrule)
10 (with
fork tip)
AWG 1 x 10/ 1 x 12/ 1 x 10/ 1 x 12/ 1 x 10/ 1 x 10/ 1 x 10/ 1 x 10/ 18 (with 12 (with
2 x 12 2 x 14 2 x 12 2 x 14 2 x 12 2 x 12 2 x 12 2 x 12 ferrule) ferrule)
8 (with
VII-2018, www.findernet.com
fork tip)
Wire strip length mm 9 9 9 9 10 10
Other data
Power lost to the environment without output current W 0.5 0.5 0.9 0.9 0.6
with rated current W 4.0 4.0 14 16 40/64/80
10
77 SERIES 77
Solid State Relays SERIES
77.x5.x.xxx.8250
Nominal Input Operating range Must Input
voltage code AC DC drop-out current
voltage
UN Umin Umax Umin Umax (AC/DC) IN at UN
V V V V V V mA
24 9.024 — — 3 32 1 22
230 8.230 90 280 — — 10 20
77.x5.x.xxx.8650
Nominal Input Operating range Must Input
voltage code AC DC drop-out current
voltage
UN Umin Umax Umin Umax (AC/DC) IN at UN
V V V V V V mA
24 9.024 — — 4 32 1 25
230 8.230 90 280 — — 10 10
VII-2018, www.findernet.com
11
77 77 SERIES
SERIES Solid State Relays
Output specification
L77-1 Output RMS current v ambient temperature L77-2 Output RMS current v ambient temperature
77.01.0.024.805x @ 32 V DC 77.01.8.230.805x @ 265 V AC
5 A 5 A
8
15 A 7 A
L77-6 Output RMS current v ambient temperature L77-4 Output RMS current v ambient temperature
77.11.x.xxx.82xx 77.31.x.xxx.80xx
15 A 30 A
12
77 SERIES 77
Solid State Relays SERIES
Output specification
L77-10 Output RMS current v ambient temperature L77-9 Output RMS current v ambient temperature
77.25.x.xxx.8x50 77.45.x.xxx.8x50
60 60
25 A 40 A
40 40
40
L77-5 Inrush peak current (AC) v inrush time L77-11 Inrush peak current (AC) v inrush time
77.31.x.xxx.80xx 77x5.x.xxx.8x50
VII-2018, www.findernet.com
1 - Cold” conditions (ambient temperature = 23 °C, no output current during the last 15 minutes)
2 - “Hot” conditions (ambient temperature = 50 °C, rated output current)
13
77 77 SERIES
SERIES Solid State Relays
Output specification
Max recommended switching frequency (Cycles/Hour, with 50% Duty-cycle)
Load 77.01.8xxx 77.01.9xxx 77.11 77.31 77.25 77.45 77.55
5 A 230 V (AC1) 5000 — — — — — —
5 A 24 V DC L/R = 20 ms — 3600
1 A (AC15) 10000 — — — — — —
0.5 A (AC15) 20000 — — — — — —
15 A 305 V cos ϕ = 0.8 — — 1800 — — — —
15 A 305 V cos ϕ = 0.5 — — 1200 — — — —
30 A 480 V cos ϕ = 0.8 — — — 1800 — — —
30 A 480 V cos ϕ = 0.5 — — — 1200 — — —
25 A 230 V cos ϕ = 0.7 — — — — 1800 — —
40 A 230 V cos ϕ = 0.7 — — — — — 1800 —
50 A 230 V cos ϕ = 0.7 — — — — — — 1800
Other data
VII-2018, www.findernet.com
14
77 SERIES 77
Solid State Relays SERIES
Wiring diagrams
Single-phase connection Single-phase connection DC Single-phase connection (77.11) Single-phase connection
(77.01.....802x) (77.01.....9x2x) (77.31....805x)
LOAD
Single-phase connection
Single-phase connection (77.x5) Example of three-phase connection (with 3 x 77.01)
(77.31....807x)
15
77 77 SERIES
SERIES Solid State Relays
Outline drawings
Type 77.01 Types 77.11/31
Screw terminal Screw terminal
D
Type 77.01 DC Type 77.x5
Screw terminal Screw terminal (plate clamp)
Accessories
Adaptor for panel mounting, plastic, 17.5 mm wide for 77.01 only 020.01
020.01
022.09
Sheet of marker tags (CEMBRE Thermal transfer printers) for all relays (48 tags), 6 x 12 mm 060.48
VII-2018, www.findernet.com
060.48
16
77 SERIES 77
Solid State Relays SERIES
Accessories
Heat-sink, anodized aluminium, 2 K/W, 65 x 100 mm, for 77.25 only 077.25
- Both the SSR and 35 mm rail clip mount to the heat-sink using M4 screws (supplied with heat-sink)
- Before assembling to the heat-sink, it is necessary to apply a thin and even layer of thermal conductive paste (not supplied)
to the lower metal surface of the SSR
077.25
D
077.25 with 77.25
Heat-sink, anodized aluminium, 0.9 K/W, 111 x 100 mm, for 77.45 and 77.55 077.55
- Both the SSR and 35 mm rail clip mount to the heat-sink using M4 screws (supplied with heat-sink)
- Before assembling to the heat-sink, it is necessary to apply a thin and even layer of thermal conductive paste (not supplied)
to the lower metal surface of the SSR
077.55
Air
conditioners
Wood-
processing
machines
Hoists and
cranes
Escalators
Control panels
for pumps
Forced-air
ventilators
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
70 SERIES 70
Line monitoring relay SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
3
70 70 SERIES
SERIES Line monitoring relay
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
4
70 SERIES 70
Line monitoring relay SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
5
70 70 SERIES
SERIES Line monitoring relay
Ordering information
Example: 70 series, three-phase voltage monitoring relay, 1 output, supply voltage 380…415 V AC.
A B C D
7 0 . 3 1 . 8 . 4 0 0 . 2 . 0 . 2 . 2
Series D: Fault memory option
Type 0 = No fault memory
1 = 1 phase AC line monitoring 2 = Fault memory function selectable
3 = 3 phase AC line monitoring C: Time delay setting
4 = 3 phase + neutral AC line monitoring 0 = Fixed switch-off delay
6 = 3 phase loss and rotation monitoring 2 = Adjustable switch-off delay
No. of poles 3 = Adjustable switch-off
1 = 1 pole delay and asymmetry
2 = 2 pole B: Contact circuit
Supply version 0 = CO
8 = AC (50/60 Hz) A: Detection values
Supply voltage 0 = Non-adjustable detection values
230 = 220…240 V (70.11) 2 = 2 adjustable detection values
400 = 380…415 V (70.31/41/42) Codes
400 = 208…480 V (70.61/62) 70.11.8.230.2022 70.42.8.400.2032
E 70.31.8.400.2022 70.61.8.400.0000
70.41.8.400.2030 70.62.8.400.0000
Selection guide
Type 70.11.8.230.2022 70.31.8.400.2022 70.41.8.400.2030 70.42.8.400.2032 70.61.8.400.0000 70.62.8.400.0000
3-phase /
Supply system type Single phase 3-phase 3-phase + neutral 3-phase 3-phase
3-phase + neutral
Functions
Undervoltage/Overvoltage AC AC — AC — —
Window mode
AC AC AC AC — —
(Undervoltage and Overvoltage)
Phase loss — • • • • •
Phase rotation — • • • • •
Asimmetry — — • • — —
Neutral loss — — • • — —
Overcurrent/Undercurrent — — — — — —
Window mode
— — — — — —
(Undercurrent and Overcurrent)
Thermistor relay (PTC) — — — — — —
Delay Times
Fixed — — — — • •
Adjustable • • • • — —
Supply voltage
24 V AC/DC — — — — — —
230 V AC • — — — — —
400 V AC — • • • • •
Module width
35 mm wide — • • • — —
22.5 mm wide — — — — — •
17.5 mm wide • — — — • —
V-2019, www.findernet.com
Other data
Fault memory • • — • — —
Contact configuration 1 CO 1 CO 1 CO 2 CO 1 CO 2 CO
See selection guide for 71 series functions
6
70 SERIES 70
Line monitoring relay SERIES
Technical data
Insulation 70.11/31/41/42 70.61 70.62
Between supply and contacts dielectric strength V AC 2500 2500 3000
impulse (1.2/50 µs) kV 4 5 5
Between open contacts dielectric strength V AC 1000 1000 1000
impulse (1.2/50 µs) kV 1.5 1.5 1.5
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field 80…1000 MHz EN 61000-4-3 10 V/m
1…2.8 GHz EN 61000-4-3 5 V/m
Fast transients on supply terminals
(burst 5/50 ns, 5 and 100 kHz) EN 61000-4-4 4 kV
Voltage pulses on supply common mode EN 61000-4-5 4 kV
terminals (surge 1.2/50 µs)
differential mode EN 61000-4-5 4 kV
Radiofrequency common mode on supply terminals
voltage (0.15…230 MHz) EN 61000-4-6 10 V
Voltage dips 70% UN EN 61000-4-11 25 cycles
E
Short interruptions EN 61000-4-11 1 cycle
Radiofrequency conducted emissions 0.15…30 MHz CISPR 11 class B
Radiated emissions 30…1000 MHz CISPR 11 class B
Terminals solid cable stranded cable
Max. wire size mm2 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Screw torque Nm 0.8
Wire strip length mm 9
Other data 70.11 70.31/41 70.42/61/62
Power lost to the environment without output current W 0.8 0.9 1
with rated output current W 2 1.2 1.4
V-2019, www.findernet.com
7
70 70 SERIES
SERIES Line monitoring relay
Functions
Output relay On (NO closed) when all OK: positive logic.
H = Hysteresis
Green LED
Green LED
Red LED
Green LED
Red LED
Green LED
Red LED
Green LED
Red LED
V-2019, www.findernet.com
8
70 SERIES 70
Line monitoring relay SERIES
Functions
Output relay On (NO closed) when all OK: positive logic.
Type Phase loss and phase rotation If the sequence (L1, L2, L3) is incorrect at power-on, the output
70.31 relay will not turn-on.
70.41
70.42 If a phase is lost, the output relay turns off immediately.
70.61 When the phase is again active, the output relay turns on
70.62 immediately.
Red LED
Red LED
Type
70.41
Neutral loss and asymmetry If the neutral is lost (and the Neutral control function is set), the
output relay turns off immediately.
E
Asymmetry
70.42 When the neutral is again present, the output relay turns on
immediately
Neutral Loss
Green LED
Yellow LED
Red LED
V-2019, www.findernet.com
9
70 70 SERIES
SERIES Line monitoring relay
UMax: UMin:
(220…270)V (300…400)V
(4…25)% UN
Toff delay:
(0.5…60)sec
70.42
E Functions:
OV, OVm, UV,
UVm, W, Wm
UMax:
(380…480)V
(5…25)% UN
UMin:
(300…400)V
Toff delay:
(0.5…60)sec
V-2019, www.findernet.com
10
70 SERIES 70
Line monitoring relay SERIES
LED indication
Monitoring relay LED Supply system normal Supply system abnormal Supply system abnormal
Type (Voltage out of limits, (Reason for switch-off,
switch-off delay RESET necessary when ”with Memory”* is selected)
time T running)
Contact 11 - 14 closed Contact 11 - 14 closed Contact 11-14 open
• Overvoltage OV and OVm
• Phase loss
Phase rotation
70.41.8.400.2030 • Undervoltage UV
Asymmetry
•
Phase loss
Neutral loss
Phase rotation
• Asymmetry
Phase loss
Neutral loss
Phase rotation
Phase rotation
* The function “with Memory” is only available for type 70.11, 70.42 and 70.31.
** It is necessary to switch the supply OFF and then On again (U off U on) or to rotate the function selector first to an adjacent position and then to the
original position.
V-2019, www.findernet.com
11
70 70 SERIES
SERIES Line monitoring relay
Wiring diagrams
L L1 L1
N L2 L2
L3 L3
N
Application example
The output contact switches the coil of the line contactor.
L1
L2
L3
N
V-2019, www.findernet.com
12
70 SERIES 70
Line monitoring relay SERIES
Outline drawings
Type 70.11 Type 70.31
Screw terminal Screw terminal
Type 70.41
Screw terminal
Type 70.42
Screw terminal
E
22.5 4.3 96
33.8
59.5
78.8
86.2
30.6
V-2019, www.findernet.com
13
70 70 SERIES
SERIES Line monitoring relay
Accessories
Adaptor for panel mounting, plastic, 17.5 mm wide for 70.11 and 70.61 020.01
020.01
Adaptor for panel mounting, plastic, 35 mm wide for 70.31, 70.42 and 70.41 011.01
011.01
E Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
70.11, 70.31, 70.41, 70.42 and 70.62 (48 tags), 6 x 12 mm 060.48
060.48
Identification tag, plastic, 1 tag, 17 x 25.5 mm for 70.11, 70.31, 70.42 and 70.41 019.01
019.01
022.09
V-2019, www.findernet.com
Industrial
motors
Industrial
refrigerators
Elevators and
lifts
Textile
machines
Labelling
machines
Carousel
warehouses
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
71 SERIES 71
Monitoring relays 10 A SERIES
programmable programmable
E
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 10/15 10/15
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 2500 2500
Rated load AC15 (230 V AC) VA 500 500
Single phase motor rating (230 V AC) kW 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 10/0.3/0.12 10/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgSnO2 AgSnO2
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 230 230
V DC — —
Rated power AC/DC VA (50 Hz)/W 4/— 4/—
Operating range AC (0.85…1.15)UN (0.85…1.15)UN
DC — —
Technical data
Electrical life at rated load AC1 cycles 100 · 103 100 · 103
Detection levels AC(50/60 Hz)/DC (15…480)V/(15…700)V (0.1…10)A at transducer to 600 A/(0.1…10)A
Switch-off/reaction/Start delay (0.1…12)s/< 0.35 s/< 0.5 s (0.1…12)s/< 0.35 s/(0.1…20)s
Switch-on level of the detecting level % 5…50 5…50
Fault memory - programmable Yes Yes
V-2019,www.findernet.com
3
71 71 SERIES
SERIES Monitoring relays 10 A
4
71 SERIES 71
Monitoring relays 10 A SERIES
Ordering information
Example: Universal voltage monitoring relay with LCD display for AC/DC voltage detection, 1 CO (SPDT) contact rated 10 A 250 V, supply voltage 230 V,
programmable delay time and fault memory.
7 1 . 4 1 . 8 . 2 3 0 . 1 0 2 1
Series Special versions
Type 0 = No fault memory
4 = AC/DC universal- Voltage detection 1 = Fault memory
5 = AC/DC universal- Current detection Options
9 = Thermistor relay (temperature 0 = No delay time
monitoring with PTC thermistor) 2 = Adjustable delay times
No. of poles Contact circuit
1 = 1 CO (SPDT) types 71.41, 51 0 = CO (nPDT)
1 = 1 NO (SPST-NO) type 71.91 3 = NO (nPST-NO)
2 = 2 CO (DPDT) type 71.92
Supply version
0 = AC(50/60 Hz)/DC
8 = AC (50/60 Hz)
Supply voltage
024 = 24 V AC/DC E
230 = 230 V
400 = 400 V
Additional functions
0 = Basic function
1 = Adjustable detection value
Selection guide
Type 71.41.8.230.1021 71.51.8.230.1021 71.91.0.024.0300 71.91.8.230.0300 71.92.0.024.0001 71.92.8.230.0001
Supply system type Single phase Single phase Single phase Single phase Single phase Single phase
Functions
Undervoltage/Overvoltage AC or DC — — — — —
Window mode
AC or DC — — — — —
(Undervoltage and Overvoltage)
Phase loss — — — — — —
Phase rotation — — — — — —
Asimmetry — — — — — —
Neutral loss — — — — — —
Overcurrent/Undercurrent — AC or DC — — — —
Window mode
— AC or DC — — — —
(Undercurrent and Overcurrent)
Thermistor relay (PTC) — — • • • •
Delay Times
Fixed — — • • • •
Adjustable • • — — — —
Supply voltage
24 V AC/DC — — • — • —
230 V AC • • — • — •
400 V AC — — — — — —
Module width
35 mm wide • • — — — —
22.5 mm wide — — • • • •
V-2019,www.findernet.com
17.5 mm wide — — — — — —
Other data
Fault memory • • — — • •
Contact configuration 1 CO 1 CO 1 NO 1 NO 2 CO 2 CO
See selection guide for 70 series functions
5
71 71 SERIES
SERIES Monitoring relays 10 A
Technical data
Insulation
Insulation according to EN 61810-1 insulation rated voltage V 250
rated impulse withstand voltage kV 4
pollution degree 3
over-voltage category III
Dielectric strength (A1, A2, B1, B2), and contact terminals V AC 2500
(11, 12, 14) and terminals (Z1, Z2) kV (1.2/50 µs) 6
Dielectric strength at open contact V AC 1000
EMC specifications
Type of test Reference Standard
Electrostatic discharge contact discharge EN 610004-2 8 kV
air discharge EN 610004-2 8 kV
Radio-frequency electromagnetic field (80…1000)MHz EN 610004-3 3 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on (A1, A2, B1, B2) and (Z1, Z2) EN 610004-4 2 kV
Surges (1.2/50 μs) on (A1, A2, B1, B2) and (Z1, Z2) common mode EN 610004-5 4 kV
differential mode EN 610004-5 4 kV
6
71 SERIES 71
Monitoring relays 10 A SERIES
Outline drawings
Types 71.41/51 Type 71.91
Screw Terminal Screw Terminal
Type 71.92
Screw Terminal
E
V-2019,www.findernet.com
7
71 71 SERIES
SERIES Monitoring relays 10 A
V-2019,www.findernet.com
8
71 SERIES 71
Monitoring relays 10 A SERIES
9
71 71 SERIES
SERIES Monitoring relays 10 A
Functions
Type 71.41.8.230.1021 Switch off
ULo – mode
Programmable
If the monitored value is
less than the lower-limit
and, time T has expired.
UUp – mode
If the monitored value
is higher than the upper
limit, and time T has
expired.
RESET MEMORY
Pressing “SET/RESET”
> 1 sec.
C = output contact
Normally open 11-14
(6-2) closed.
V-2019,www.findernet.com
10
71 SERIES 71
Monitoring relays 10 A SERIES
Functions
Type 71.51.8.230.1021 Switch off
ILo – mode
If the monitored value is
Programmable
less than the lower-limit
and, time T1 has expired.
IUp – mode
If the monitored value
is higher than the upper
limit, and time T1 has
expired.
RESET MEMORY
Pushing “SET/RESET”
> 1 sec.
C = output contact
Normally open 11-14
(6-2) closed.
Type 71.91.x.xxx.0300 Switch off
––Thermistor line break
––Over temperature RPTC
> (2.5…3.6)kΩ
––Thermistor line short
circuit (RPTC≈< 20 Ω)
––Loss of supply
Switch on
Temperature within
limits
RPTC > (1.0…1.5)kΩ on
power-up.
(1…1.5)kΩ on cooling.
C = output contact
* PTC-Break ** PTC-Short circuit
Normally open
11-14 Closed when
temperature within
limits.
V-2019,www.findernet.com
11
71 71 SERIES
SERIES Monitoring relays 10 A
Functions
Type 71.92.x.xxx.0001 Switch off
––Thermistor line break
––Over temperature
RPTC > (2.5…3.6)kΩ,
––Thermistor line short
circuit (RPTC < 20 Ω)
––Loss of supply
Switch on
Temperature within
limits
(20 Ω…2.5 kΩ)
on power-up.
MEMORY OFF
RPTC > (1…1.5)kΩ on
cooling.
Select
MEMORY OFF
If monitored value is
MEMORY ON
E Select
MEMORY ON
* PTC-Break ** PTC-Short circuit
*** RESET MEMORY = Operate the RESET key, or interrupt the supply.
If monitored value is
expected to remain
within limits.
RESET MEMORY
Operate the RESET key,
or interrupt the supply.
C = output contact
Normally open 11-14
(21-24)
Closed when
temperature within
limits.
V-2019,www.findernet.com
Industrial washing
machines
Swimming pools
Control and
management
of water
Bottling plant
Milk processing
plant
Control panels
for pumps
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
72 SERIES 72
Monitoring relays SERIES
Min./Max. limits
72.01/11 F = Filling
Screw terminal
E = Emptying E
Insulation between
supply/contacts/electrode (1.2/50 µs) kV 6 6
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
3
72 72 SERIES
SERIES Monitoring relays
Type 72.42
-- Priority change relay
• 2 independent NO output, 12 A
• 4 functions
• 2 independent control signals, insulated from
supply
• 110…240 V and 24 V AC/DC supply versions
• Modular housing, 35 mm wide
• 35 mm rail (EN 60715) mount
• Cd-free contact material • Multi-function (MI, ME, M2, M1)
72.42
Screw terminal
Dielectric strength
between open contacts V AC 1000
Ambient temperature °C –20…+50
Protection category IP 20
Approvals (according to type)
4
72 SERIES 72
Monitoring relays SERIES
Ordering information
Example: 72 series level control relay, adjustable sensitivity range, (230…240)V AC supply voltage.
7 2 . 0 1 . 8 . 2 4 0 . 0 0 0 0
Series Contact material Option
Type 0 = Standard AgCdO for 0 = Max. 150 kΩ
72.01/72.11, AgNi for 2 = Sensitivity range
0 = Level control relay, sensitivity range
72.42 adjustable
adjustable (5…150)kΩ
5 = AgNi + Au** (5…450)kΩ types
1 = Level control relay, sensitivity fixed 150 kΩ
4 = Priority change relay Supply voltage 72.01.8.024.0002*
024 = 24 V 72.01.8.240.0002*
No. of poles 125 = (110…125)V AC 72.01.8.240.5002**
1 = 1 CO (SPDT) 230 = (110 … 240)V
2 = 2 NO (DPST-NO) 240 = (230…240)V AC
400 = 400 V AC (72.01 only)
Supply version
0 = DC/AC (50/60 Hz)
8 = AC (50/60 Hz)
9 = DC
All versions
72.01.8.024.0000 E
72.01.8.024.0002*
72.01.8.125.0000
72.01.8.240.0000
72.01.8.240.0002*
72.01.8.240.5002**
72.01.8.400.0000
72.01.9.024.0000
72.11.8.024.0000
72.11.8.125.0000
72.11.8.240.0000
72.11.9.024.0000
72.42.0.230.0000
72.42.0.024.0000
5
72 72 SERIES
SERIES Monitoring relays
Technical data
Insulation 72.01/72.11 72.42
Insulation Dielectric strength Impulse (1.2/50 µs)
between supply and contacts 4000 V AC 6 kV 6 kV
between supply and control (for 110…240 V version only) 2500 V AC — 4 kV
between electrodes, Z1-Z2 and supply* 4000 V AC 6 kV —
between contacts and electrodes 4000 V AC 6 kV —
between open contacts 1000 V AC 1.5 kV 1.5 kV
EMC specifications
Type of test Reference standard 72.01/72.11 72.42
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80…1000 MHz) EN 61000-4-3 10 V/m 10 V/m
(1…2.8 GHz) EN 61000-4-3 — 5 V/m
Fast transients on supply terminals EN 61000-4-4 4 kV 4 kV
(burst 5/50 ns, 5 and 100 kHz) on control terminals EN 61000-4-4 — 4 kV
Voltage pulses on supply terminals common mode EN 61000-4-5 4 kV 4 kV
E (surge 1.2/50 µs) differential mode EN 61000-4-5 4 kV 4 kV
Radiofrequency common mode on supply terminals EN 61000-4-6 10 V 10 V (0.15…230 MHz)
voltage (0.15…280 MHz) on control terminals EN 61000-4-6 — 10 V
Voltage dips 70% UN EN 61000-4-11 — 25 cycles
Short interruptions EN 61000-4-11 — 1 cycles
Radiofrequency conducted emissions (0.15…30 MHz) CISPR 11 class B class B
Radiated emissions (30…1000 MHz) CISPR 11 class B class B
Terminals
Screw torque Nm 0.8
Wire strip length mm 9
Max. wire size solid cable stranded cable
mm2 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Other data
Current absorption on Z1 and Z2 (type 72.11) mA < 1
Current absorption on control signal (B1-B2 and B2-B3) - (type 72.42) 5 mA, 5 V
Power lost to the environment 72.01/72.11 72.42
without contact current W 1.5 0.9 (1 relay ON)
with rated current W 3.2 3.0 (2 relays ON)
Max cable length between electrode and relay (types 72.01/72.11) m 200 (max. capacitance of 100 nF/km)
* There is no electrical isolation between electrodes and supply voltage for the 24 V DC types (72.x1.9.024.0000). Therefore, for SELV applications it would
be necessary to use a SELV (non-grounded) power supply. In the case of a PELV (grounded) power supply take care to protect the level control relay
against harmful circulating currents by ensuring that no electrodes are grounded.
However, there is no such problem for the 24 V AC types (72.x1.8.024.0000) which, by virtue of an internal isolating transformer, assure reinforced
isolation between electrodes and supply.
II-2019,www.findernet.com
6
72 SERIES 72
Monitoring relays SERIES
Filling functions
Wiring diagram Examples with 3 electrodes E
Type 72.01 Filling Control – between Min. and
U = 24 V DC Max. levels.
24 V AC 50/60 Hz Under normal operation the liquid
(110…125)V AC 50/60 Hz
(230…240)V AC 50/60 Hz
level can be expected to cycle
between the Minimum and the
Level
Maximum electrodes, B2 and B1
(plus a degree of over and under-
shoot).
Switch On:
• On “power-up”, if the liquid is
below B1 the output relay will
Type 72.11 operate after time T has expired.
• On the liquid level falling below
B2, the output relay will operate
after time T has expired.
F = Filling Switch Off:
• On the liquid level reaching
electrode B1, the output relay
will de-energise after time T has
expired.
• On “power-off”, the output relay
will immediately de-energise.
7
72 72 SERIES
SERIES Monitoring relays
Emptying functions
Wiring diagram Examples with 3 electrodes
Type 72.01 Emptying Control - between Max.
U = 24 V DC and Min. levels.
24 V AC 50/60 Hz
(110…125)V AC 50/60 Hz Under normal operation the liquid
(230…240)V AC 50/60 Hz level can be expected to cycle
between the Maximum and the
Level Minimum electrodes, B1 and B2 (plus
a degree of over and under-shoot).
Switch On:
• On “power-up”, if the liquid level
is above B2 the output relay will
Type 72.11 operate after time T has expired.
• On the liquid level rising to B1, the
output relay will operate after time T
has expired.
Switch On:
• On “power-up”, if the liquid is
above B1 the output relay will
operate after time T has expired.
Type 72.11 • On the liquid level rising to B1, the
output relay will operate after time T
has expired.
––Fuels
––Oil
––Liquids with high-percentage alcohol
––Liquid gas
––Paraffins
––Ethylene glycol
––Paint
8
72 SERIES 72
Monitoring relays SERIES
Wiring diagram
9
72 72 SERIES
SERIES Monitoring relays
MI function example
This shows the 72.42 Priority change relay working in conjunction
with a single 72.01 level controller. Under normal conditions the
liquid level is expected to remain within the range shown as Min
to Max. In this case the function of the 72.42 will be to alternate
the duty between both pumps, to even wear across both pumps.
There is no provision to run both pumps simultaneously.
E
ME function example
This shows the 72.42 Priority change relay working in conjunction
with two 72.01 level controllers. Under normal conditions the
liquid level is expected to remain within the range shown as Min
to Max. In this case the function of the 72.42 will be to alternate
the duty between both pumps, to even wear across both pumps.
Should the liquid level rise above the Alarm level then the function
of the 72.42 will call for the simultaneous operation of both pumps,
by virtue of the signal to terminal B3 from the Alarm/Low level
controller.
Outline drawings
Types 72.01/11 Type 72.42
Screw terminal Screw terminal
II-2019,www.findernet.com
10
72 SERIES 72
Monitoring relays SERIES
• Electrode compatible with food processing applications (according to European Directive 2002/72 and cod. FDA title 21
part 177):
• Electrode for swimming pools with high levels of chlorine, or in salt-water pools with high levels of salinity:
Cable length: 6 m (1.5 mm2) 072.02.06
Technical data
Max. liquid temperature °C +100
072.02.06
Electrode material stainless steel (AISI 316L)
11
72 72 SERIES
SERIES Monitoring relays
Function
Electrode holder with two pole connector, one connected directly to the electrode and the
second connected to the grounded installation thread. Suitable for metal tank with G3/8” linkage.
Electrode not incuded. Order appropriate number of electrodes holders - additional to the relay. 072.51
Technical data
Max liquid temperature °C +100
Max tank pressure bar 12
Cable grip mm Ø ≤ 6
072.51
Electrode material stainless steel (AISI 316L )
II-2019,www.findernet.com
12
72 SERIES 72
Monitoring relays SERIES
Electrode and electrode connector, multiple electrodes may be interconneced to provide required length
Technical data E
Electrode - 475 mm long, M4 thread, stainless steel (AISI 316L) 072.500
072.500 Inter-electrode connector - M4 thread, stainless steel (AISI 316L) 072.501
Illustration of interconnection of electrodes.
072.501
072.503
011.01
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
72.42 (48 tags), 6 x 12 mm 060.48
060.48
019.01
II-2019,www.findernet.com
13
72 72 SERIES
SERIES Monitoring relays
14
72 SERIES 72
Float switch SERIES
Float switch suitable for fluid level regulation 72.A1.0000.xxxx 72.A1.0000.xx02 72.B1.0000.xxxx
• 1 CO
• 10 A (resistive load)
• 8 A (inductive load)
• 2 or 3 watertight chambers resistant to high
pressures
• Cable length 5 m, 10 m, 15 m or 20 m
• Suitable for emptying and filling
• Contact material AgNi
• Float switch with 2 watertight • Float switch with 2 watertight • Float switch with 3 watertight
chambers, for grey water chambers, for fluid foodstuff chambers, for black water
pumping and drainage and potable water systems, drainage plants and
• Counterweight (230 g) with • Suitable for swimming pools pumping stations
cable grip, included with high levels of chlorine, or • Supplied with fixing kit
in salt-water pools with high
levels of salinity
• Counterweight (230 g) with
cable grip, included
• Cable and plastics ACS
certified for alimentary uses
15
72 72 SERIES
SERIES Float switch
Ordering information
Example: 72 Series, float switch, 1 CO.
7 2 . A 1 . 0 0 0 0 . 0 5 0 0
Series Cable
00 = PVC
Type
01 = H07 RN F
A = 2 chamber float switch
02 = ACS Certified
B = 3 chamber float switch
version
No. of pole
Cable length
1 = 1 CO
05 = 5 meters
10 = 10 meters
15 = 15 meters
20 = 20 meters
Counterweight (230 g) for Type 72.A1. Fixes to the cable to allow Screw clamp with cable grommet for Type 72.B1.
adjustment of the overall level and the switching hysteresis. For "strain relief" fixing of the cable.
II-2019,www.findernet.com
16
72 SERIES 72
Float switch SERIES
Applications
Type 72.A1
Emptying function Filling function
Type 72.B1
Emptying function Filling function
17
72 72 SERIES
SERIES Float switch
Outline drawings
Type 72.A1 Type 72.B1
II-2019,www.findernet.com
Control panels
Electrical
energy control
Industrial
robots
Road / tunnel
lighting
3
7E 7E SERIES
SERIES Energy meters
4
7E SERIES 7E
Energy meters SERIES
Type 7E.64.8.230.0001
kWh, kW, V
• Display of active energy consumption (kWh)
• Scroll to view instantaneous voltage (V) and
active power (kW)
• 7 digit backlit LCD display
• Class 1 accuracy according to EN 62053-21
• SO output for remote energy monitoring • Reference current 5 A (40 A Maximum) • Reference current 5 A (40 A Maximum)
according to EN 62053-31. Active energy (kWh) • 1-phase 230 V AC • 1-phase 230 V AC
only • kWh + instantaneous voltage & kW, V • kWh, kVAh or kvarh + instantaneous V, A, PF,
Type 7E.64.8.230.0010 kW, kVA, kvar & Hz
Multifunction MID certified • MID certified
• Display of total or partial (resettable) energy
consumption: kWh, kVAh or kvarh
• Scroll to view the following instantaneous
values: V, A, PF, kW, kVA, kvar, Hz and direction
of power flow
• 7 digit backlit LCD display
• Active power accuracy Class B according to
EN 50470-3 E
• Programmable* SO pulse output for remote
energy monitoring according to EN 62053-31
• Accessories: sealable tamperproof terminal
cover
• Protection category II
• 35 mm rail (EN 60715) mount
+24V +24V
EN 50470-3 (MID) 1 B
Ambient temperature (Within accuracy class) °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP 50/IP 20 IP 50/IP 20
Approvals (according to type)
5
7E 7E SERIES
SERIES Energy meters
6
7E SERIES 7E
Energy meters SERIES
Single-phase 7E.64.8.230.0210
Multifunction, Bi-directional energy meter
MID certified with RS485 Modbus integrated
interface and backlit LCD display
• Display of total or partial (resettable) energy
consumption: kWh, kVAh or kvarh
• Scroll to view the following instantaneous
values: V, A, PF, kW, kVA, kvar, Hz and direction
of power flow
• 7 digit backlit LCD display
• Active power accuracy Class B according to
EN 50470-3 • Reference current 5 A (40 A Maximum)
• RS485 Modbus integrated communications port • RS485 Modbus integrated interface
• Programmable** SO pulse output for remote • 1-phase 230 V 50/60 Hz
energy monitoring according to EN 62053-31 • MID certified
• Accessories: sealable tamperproof terminal
cover
• Protection category II
• 35 mm rail (EN 60715) mount Modbus
+
_
SO
+24V
EN 50470-3 COM
Accuracy class B B
Ambient temperature (Within accuracy class) °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP 50/IP 20 IP 50/IP 20
Approvals (according to type)
8
7E SERIES 7E
Energy meters SERIES
Single-phase 7E.64.8.230.0310
Multifunction energy meter
Bi-directional, MID certified with M-Bus
integrated interface and backlit LCD display
• Display of total or partial (resettable) energy
consumption: kWh, kVAh or kvarh
• Scroll to view the following instantaneous
values: V, A, PF, kW, kVA, kvar, Hz and direction
of power flow
• 7 digit backlit LCD display
• Active power accuracy Class B according to
EN 50470-3 • Reference current 5 A (40 A Maximum)
• M-Bus integrated communications port • M-Bus integrated interface
• Programmable** SO pulse output for remote • 1-phase 230 V 50/60 Hz
energy monitoring according to EN 62053-31 • MID certified
• Accessories: sealable tamperproof terminal
cover
• Protection category II
• 35 mm rail (EN 60715) mount
SO
+ 24V
EN 50470-3
E • Reactive power accuracy Class 2 according to
EN 62053-23
• Protection category II
• Accessories: sealable tamperproof terminal cover
• 35 mm rail (EN 60715) mount
* Minimum CT ratio: 1:1
Maximum CT ratio: 10 000:1
CT secondary programmable: 1 or 5 A
** Default transmission baud rate: 2400 bps
*** SO output can be associate with kWh, kVAh or
kvarh.
Accuracy class B B
Ambient temperature (Within accuracy class) °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP 50/IP 20 IP 50/IP 20
Approvals (according to type)
10
7E SERIES 7E
Energy meters SERIES
Accuracy class B B
Ambient temperature (Within accuracy class) °C –25…+55 –25…+55
Protective class II II
Protection category: Housing/terminals IP 50/IP 20 IP 50/IP 20
Approvals (according to type)
11
7E 7E SERIES
SERIES Energy meters
Ordering information
Example: Energy meter 32 A/230 V AC, with PTB certified, with MID certification, Class B accuracy, for 35mm rail (EN 60715) mounting. Available with
Tamper-proof lead sealed cover as accessory.
7 E . 1 3 . 8 . 2 3 0 . 0 0 1 0
Series Option
Function 0 = SO +/- pulse output
1 = 1-phase Special version
3 = 3-phase 0 = Standard
Current 1 = MID compliant versions
2 = 25 A Option
3 = 32 A 0 = Standard
6 = 65 A 2 = Standard (7E.12)
Supply version 2 = Dual tariff (7E.36)
8 = AC 50 Hz Supply voltage
230 = 230 V AC 50 Hz
400 = 3 x 230/400 V AC 50 Hz
All versions/width 7E.36.8.400.0010/70 mm
7E.12.8.230.0002/35 mm 7E.36.8.400.0012/70 mm
7E.13.8.230.0010/17.5 mm
7E.16.8.230.0010/35 mm
E Technical data
Insulation EN 62053-21 7E.12, 7E.13, 7E.16 7E.36
Insulation rated voltage V 250 250
Overvoltage category IV IV
Insulation between active parts and SO+/SO– terminals kV (1.2/50 μs) 6 6
between adjacent phases kV (1.2/50 μs) — 6
Insulation between supply and SO+/SO– V AC 4000 4000
between adjacent phases V AC — 4000
Protection class II II
EMC Specification Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 8 kV
air discharge EN 61000-4-2 15 kV
Radio-Frequency Electromagnetic Field (80…1000)MHz EN 61000-4-3 10 V/m
Fast Transients (Burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 Class 4 (4 kV)
on SO+/SO– terminals EN 61000-4-4 Class 4 (2 kV)
Surge (1.2/50 μs) on Supply terminals EN 61000-4-5 Class 4 (4 kV)
on SO+/SO– terminals EN 61000-4-5 Class 3 (1 kV)
Radio-Frequency Common Mode (0.15…80)MHz on Supply terminals EN 61000-4-6 10 V
Radiated and Conducted Emission EN 55022 Class B
Other data
Pollution degree 2
Vibration resistance (10…60)Hz mm 0.075
(60…150)Hz g 1
Vibration resistance of the internal mechanical counter (10…500)Hz g 2
Shock resistance g/18 ms 30
Shock resistance of the internal mechanical counter g/18 ms 350
Power lost to the environment 7E.12, 7E.13 7E.16 7E.36
without current W 0.4 0.4 1.5
with maximum current W 1 2 6
Supply terminals 7E.12, 7E.13 7E.16, 7E.36
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1…6 0.75…4 1.5…16 1.5…16
AWG 18…10 18…12 16…6 16…6
Screw torque for Imax Nm 0.8…1.2 1.5…2
Screw Pozidriv No.1, Flat No.1, 2
SO+/SO– terminals Max. wire size solid cable stranded cable solid cable stranded cable
mm2 2.5 1.5 2.5 1.5
V-2018, www.findernet.com
AWG 14 16 14 16
Screw torque for Imax Nm 0.5 0.8
Screw Pozidriv No.0, Flat No.1 Pozidriv No.0, Flat No.2
12
7E SERIES 7E
Energy meters SERIES
7 E . 8 6 . 8 . 4 0 0 . 0 1 1 2
Series Special version Special version
Function 0 =Standard 0 =Single tariff
6 = 1-phase, backlit display 1 = kWh only (0001)
Option 2 = Dual tariff
7 = 3-phase, backlit display, direct connection
0 = SO pulse output 3 = Panel mounting
8 = 3-phase, backlit display, 1 = Infra-red comms. port Version
for current transformer operation + two SO pulse outputs 0 =Standard
Current 2 = RS485 Modbus integrated interface 1 = Conforms to MID directive
+ SO pulse output
4 = 40 A
3 = M-Bus integrated interface + Table 1
6 = 6 A (up to 50 000 A, using 7E.86 and CT) SO pulse output
8 = 80 A Imp/kWh* CT ratio
4 = Ethernet integrated interface plus SO
1000 1…4
Supply version pulse output
200 5…24
8 = AC 50/60 Hz Supply voltage 40 25…124
230 = 230 V AC 50/60 Hz 8 125…624
400 = 3 x 230/415 V AC 50/60 Hz 1 625…3124
0.1 3125…10 000
*Imp/kWh, Imp/kvarh, Imp/kVAh
Available versions
Infra-red comms. port for use with E
communication modules Modbus M-Bus E thernet SO only
7E.78.8.400.0112 7E.64.8.230.0210 7E.64.8.230.0310 7E.78.8.400.0410 7E.64.8.230.0001
7E.86.8.400.0112 7E.78.8.400.0212 7E.78.8.400.0312 7E.86.8.400.0410 7E.64.8.230.0010
7E.86.8.400.0212 7E.86.8.400.0312
Technical data
Insulation 7E.64.8.230.0xxx 7E.78.8.400.0xxx 7E.86.8.400.0xxx
Insulation rated voltage V 250 250 250
Insulation between active parts and SO+/SO– terminals kV (1.2/50 μs) 6
between supply and Modbus, M-Bus terminal kV (1.2/50 μs) 6
between adjacent phases kV(1.2/50 µs) n/a
Insulation between active parts and SO+/SO– terminals V AC 4000
between supply and Modbus, M-Bus terminal V AC 4000
between adjacent phases V AC n/a
Protection class II
EMC Specification according to 61000-4-(2/3/4) 7E.64.8.230.0xxx 7E.78.8.400.0xxx 7E.86.8.400.0xxx
Electrostatic discharge contact discharge 8 kV
air discharge 15 kV
Radio frequency Electromagnetic field (80…2000)MHz 30 V/m
Fast Transients (burst) (5-50 ns, 5 kHz) on Supply terminals 4 kV
on SO+/SO– terminals 2 kV
Modbus, M-Bus terminal 2 kV
Surge (1.2/50 μs) on Supply terminals 4 kV
on SO+/SO– terminals 1 kV
Modbus, M-Bus terminal 1 kV
Other data 7E.64.8.230.0xxx 7E.78.8.400.0xxx 7E.86.8.400.0xxx
Pollution degree 2
Vibration resistance EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Shock resistance EN 60068-2-27 EN 60068-2-27 EN 60068-2-27
Power lost to the environment Max value per phase 0.5W/1.5 VA 1W/7.5VA 1W/7.5VA
CT burden — — 0.04 VA/per phase
Supply terminals 7E.64.8.230.0xxx 7E.78.8.400.0xxx 7E.86.8.400.0xxx
Max. wire size solid stranded solid stranded solid stranded
cable cable cable cable cable cable
mm2 max 6 1.5…6 max 35 1.5…35 max 6 1.5…6
AWG — — — — — —
Screw torque for Imax Nm 1.5 1.5 2 2 1.5 1.5
V-2018, www.findernet.com
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
E
Phase L2↑ L2↓ inverted Phase L1↑ L1↓ and L3↑ L3↓
or loss 3s 3s 3s 3s 3s inverted or loss 3s 3s 3s 3s 3s
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
Phase L3↑ L3↓ inverted Phase L2↑L2↓ and L3↑L3↓
or loss 3s 3s 3s 3s 3s inverted or loss 3s 3s 3s 3s 3s
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
Phase L1↑L1↓ and L2↑L2↓
and L3↑L3↓ inverted or 3s 3s 3s 3s 3s
loss
↑
↑
↑
↑
↑
↑
↑
↑
↑
↑
SO+/SO– Open collector output wiring diagram Type 7E.12, 7E.13, 7E.16, 7E.36
The pulsating open collector output available at terminals SO+ and SO– can be interfaced with the input of a computer, plc or other energy
management equipment to allow the remote monitoring of energy consumed.
+
24 V DC
–
14
7E SERIES 7E
Energy meters SERIES
Outline drawings
Type 7E.12.8.230.0002/7E.16.8.230.0010 Type 7E.13.8.230.0010
15
7E 7E SERIES
SERIES Energy meters
Outline drawing
Type 7E.64.8.230.0210 Type 7E.64.8.230.0310
16
7E SERIES 7E
Energy meters SERIES
Accessories
Terminal cover for type 7E.13 07E.13
For the tamper-proof lead seal use two terminal covers
07E.13
Terminal cover for type 7E.12, 7E.16 and 7E.36 07E.16
7E.12, 7E.16 - For the tamper-proof lead seal use two terminal covers
7E.36 - For the tamper-proof lead seal use four terminal covers
07E.16
Panels for
electrical
distribution
Control panels
Surge
protection
Road / tunnel
lighting
Elevators and
lifts
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
SPD Type 1+2 Surge arrester range high 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025
discharge capability with no following current -
single/three phase systems
• Surge arresters, suitable for low-voltage applications,
to protect equipment against overvoltage by direct
lightning strike, induced overvoltage and switching
overvoltage
• To be installed at the boundary of LPZ 0 - LPZ 1 zones
or higher
• Versions with combination of varistor and high-
performance spark gap (GDT) ensures:
--high discarge current
--high insulation resistance that eliminates leakage current
--no following current • SPD Type 1 • SPD Type 1+2 • SPD Type 1+2
• Very low residual voltage • Spark gap module for N-PE • Combination of varistor and • Combination of varistor and
• Replaceable modules application in three phase encapsulated spark gap (for encapsulated spark gap (for
• Upside down mounting possible (thanks to dual system, 3+1 configuration single or three phase systems) single phase systems)
terminal markings and new restraint system for the • Remote contact signalling of • Visual fault and remote • Visual fault and remote contact
replaceable module that permits its inversion) GDT presence contact fault signalling fault signalling varistor/GDT
• Visual fault signalling: Healty/Replace • Upside down mounting possible varistor/GDT status status, N-PE GDT presence
• Double screw terminal • Replaceable modules • Upside down mounting possible • Upside down mounting possible
• Remote status signalling contact: • Replaceable modules • Replaceable modules
Healty/Replace/Presence. Connector 07P.01 included
• According to EN 61 643-11
• 35 mm rail EN 60715 mounting, 36 mm each pole 7P.01.8.260.1025
3
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
SPD Type 1+2 Surge arrester range - three 7P.03.8.260.1025 7P.04.8.260.1025 7P.05.8.260.1025
phase high discharge capability with no
following current - system (230/400 V)
• Surge arresters, suitable for low-voltage
applications, to protect equipment against
overvoltage by direct lightning strike, induced
overvoltage and switching overvoltage
• To be installed at the boundary of LPZ 0 - LPZ 1
zones or higher
• Combined high energy varistor block and
high-performance spark gap (GDT) ensures:
--high discarge current
--high insulation resistance that eliminates leakage • SPD Type 1+2 • SPD Type 1+2 • SPD Type 1+2
current • 3 x combined varistor and • 3 x combined varistor and • 4 x combined varistor and
--no following current encapsulated spark gap encapsulated spark gap + 1 encapsulated spark gap
• Very low residual voltage
• Replaceable modules • Visual fault and remote encapsulated spark gap • Visual fault and remote
• Upside down mounting possible (thanks to dual contact fault signalling • Visual fault and remote contact contact fault signalling
terminal markings and new restraint system for
the replaceable module that permits its inversion) varistor/GDT status fault signalling varistor/GDT varistor/GDT status
• Visual fault signalling: Healty/Replace • Upside down mounting position status, N-PE GDT presence • Upside down mounting position
• Double screw terminal • Replaceable modules • Upside down mounting position • Replaceable modules
• Remote status signalling contact:
Healty/Replace/Presence. Connector 07P.01 included • Replaceable modules
• According to EN 61 643-11
• 35 mm rail EN 60715 mounting, 36 mm each pole
7P.03.8.260.1025 SPD Type 1+2 for three phase
TN-C system without Neutral
(PEN conductor). Varistor +
GDT protection L1, L2, L3-PEN
7P.04.8.260.1025 SPD Type 1+2 for three
E phase TT and TN-S system
with Neutral. Varistor + GDT
protection L1, L2, L3-N + spark
gap protection N-PE
7P.05.8.260.1025 SPD Type 1+2 for three phase
TN-S system with Neutral.
Varistor + GDT protection
L1, L2, L3-N + varistor + GDT
protection N-PE
4
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
SPD Type 1+2 Surge arrester range with high 7P.12.8.275.1012 7P.13.8.275.1012
performance “Low Up” - Single phase/three
phase system
• Surge arrester suitable for 230/400 V system
applications to prevent overvoltage effects
caused by direct or indirect lightning strikes
• To be installed at the boundary of LPZ 0 and
LPZ 1 zones
• Very Low Up level to protect senstive equipment
• Visual indication of varistor status -
Healthy/Replace
• Contact for remote signalling of varistor status.
Connector 07P.01 included
• Replaceable spark gap and modules
• Complies with EN 61 643-11 • SPD Type 1+2 • SPD Type 1+2
• 17.5 mm rail EN 60715 mounting for each • Replaceble spark gap and varistor modules • Replaceable varistor modules
module (for single phase systems) (for three phase systems)
7P.12.8.275.1012 SPD Type 1+2 for single phase • Visual and remote signalling of varistor status • Visual and remote signalling of varistor status
TT and TN-S system with
Neutral.
• Varistor protection L-N + spark gap protection
N-PE for single phase systems
• Replaceble spark gap and varistor modules
7P.13.8.275.1012 SPD Type 1+2 for three phase
TN-C system without Neutral
(PEN conductor).
• Varistor protection L1, L2, L3-PEN for three
phase systems E
• Replaceable varistor modules
7P.12 / 7P.13
Screw terminals
Wire size (07P.01) solid cable stranded cable solid cable stranded cable
mm2 1.5 1.5 — 1.5 1.5
AWG 16 16 — 16 16
Approvals (according to type)
5
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
SPD Type 1+2 Surge arrester range with high 7P.14.8.275.1012 7P.15.8.275.1012
performance “Low Up” - three phase system
• Surge arrester suitable for 230/400 V system
applications to prevent overvoltage effects
caused by direct or indirect lightning strikes
• To be installed at the boundary of LPZ 0 and
LPZ 1 zones
• Very Low Up level to protect senstive equipment
• Visual indication of varistor status -
Healthy/Replace
• Contact for remote signalling of varistor status.
Connector 07P.01 included
• Replaceable varistor modules • SPD Type 1+2 • SPD Type 1+2
• Complies with EN 61 643-11 • Replaceable varistor module • Replaceable varistor module
• 17.5 mm rail EN 60715 mounting for each module • Visual and remote signalling of varistor status • Visual and remote signalling of varistor status
7P.14.8.275.1012 SPD Type 1+2 for three phase
TT and TN-S system with
Neutral.
• Varistor protection L1, L2, L3-N + spark gap
protection N-PE
• Replaceable varistor modules
• Non replaceable high discharge current spark gap
7P.15.8.275.1012 SPD Type 1+2 for three phase
TN-S system with Neutral.
E • Varistor protection L1, L2, L3,N-PE
• Replaceable varistor modules
7P.14 / 7P.15
Screw terminals
6
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
SPD Type 2 Surge arrester range for single/ 7P.21.8.xxx.x0xx 7P.22.8.275.x020 7P.27.8.275.x020
three phase AC systems and for DC systems
• Surge arrester suitable for AC and DC systems
to protect equipment against induced
overvoltage or switching transients
• To be installed at the boundary of LPZ 1 - LPZ 2
zones or higher
• Visual indication of varistor status -
Healthy/Replace
• Contact for remote signalling of varistor status.
Connector (07P.01) included (depending on the
version)
• Replaceable varistor and spark gap modules
• Complies with EN 61643-11:2012
• 17.5 mm rail EN 60715 mounting for each module
7P.21.8.075.1015 SPD Type 2, unipolar • SPD Type 2 (1 varistor) • SPD Type 2 (1 varistor + 1 • SPD Type 2 (2 varistors)
protection suitable for DC • Replaceable varistor module spark-gap) • Replaceable varistor modules
applications or low voltage AC • Visual and optional remote • Combination of replaceable • Visual and optional remote
single phase systems
• Varistor protection +/– or L/N (GND); –/+ or GND (L/N) connector for signalling of the varistor and encapsulated connector for signalling of the
• Replaceable module varistor status spark gap modules varistor status
7P.21.8.130.1015 SPD Type 2, unipolar • Visual and optional remote
protection suitable for DC connector for signalling of the
application or low voltage AC
single phase systems varistor status
• Varistor protection +/– or L/N (GND); –/+ or GND (L/N)
• Replaceable module
7P.21.8.275.x020 SPD Type 2, unipolar
protection suitable to realize
single phase or three phase
systems (230/400 V)
• Varistor protection L/N(GND)-GND/(L/N) E
• Replaceable module
7P.21.8.440.x020 SPD Type 2, unipolar
protection suitable for three
phase systems (400 V AC)
• Varistor protection L/N(GND)-GND/(L/N)
• Replaceable module
7P.22.8.275.x020 SPD Type 2 for single phase TT
and TN-S system with Neutral
• Varistor protection L-N + spark gap protection N-PE
• Replaceable varistor and spark gap modules
7P.27.8.275.x020 SPD Type 2 for single phase TN
system with Neutral
• Varistor protection L, N-PEx * 7P.20.8.075.0015
• Replaceable varistor modules ** 7P.20.8.130.0015
*** 7P.20.8.275.0020
For outline drawing see page 20 **** 7P.20.8.440.0020
SPD specification 075.1015 130.1015 275.1020 440.1020 L-N N-PE L, N-PE
Nominal voltage (UN) V AC/DC 60/60 110/125 230/— 400/— 230/— — 230/—
Maximum continous operating voltage (UC) V AC/DC 75/100 130/170 275/350 440/585 275/— 255/— 275/—
Nominal discharge current (8/20 μs) (In) kA 15 15 20 20 20 20 20
Maximum discharge current (8/20 μs) (Imax) kA 40 40 40 40 40 40 40
Voltage protection level at 5 kA (UP5) kV 0.3 0.45 0.9 1.5 0.9 — 0.9
Voltage protection level at In(Up) kV 0.4 0.6 1.2 1.9 1.2 1.5 1.2
IPEuA < 350 < 350 < 200 < 350 < 4 < 400
TOV 120 min L-NV AC 115 225 440 — 440 — 440
TOV 5 s L-N V AC 90 175 335 580 335 — 335
TOV 200 ms N-PE V AC — — — — — 1200 —
Response time (ta) ns 25 25 100 25
Short-circuit proof at maximum
overcurrent protection - ISSCRkArms 50 25 50 — 50
Maximum overcurrent protection
(fuse rating gL/gG) A 160 125 160 — 160
Replacement module code * ** *** **** 7P.20.8.275.0020 7P.20.1.000.0020 7P.20.8.275.0020
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable
mm2 1 x 1…1 x 35 1 x 1…1 x 25
AWG 1 x 17…1 x 2 1 x 17…1 x 4
Wire strip length mm 12
Screw torque Nm 3
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current A AC/DC 0.5/0.1 0.5/0.1
I-2019, www.findernet.com
7
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
SPD Type 2 Surge arrester range - three phase 7P.23.8.275.x020 7P.24.8.275.x020 7P.25.8.275.x020
systems
• Surge arrester suitable for 230/400 V system
applications to protect equipments against
induced overvoltage or switching transients
• To be installed at the boundary of LPZ 1 - LPZ 2
zones or higher
• Visual indication of varistor status -
Healthy/Replace
• Contact for remote signalling of varistor status.
Connector (07P.01) included (depending on the
version)
• Replaceable varistor and spark gap modules
• Complies with EN 61643-11:2012 • SPD Type 2 (3 varistors) • SPD Type 2 • SPD Type 2 (4 varistors)
• 35 mm rail (EN 60715) mounting • Replaceable varistor module, (3 varistors + 1 spark-gap) • Replaceable varistor module,
7P.23.8.275.x020 SPD Type 2 for three phase
3 pole • Combination of replaceable 4 pole
TN-C system without Neutral
• Visual and remote signalling varistor and encapsulated • Visual and optional remote
of varistor status spark gap modules connector for signalling of the
(PEN conductor). • Visual and optional remote varistor status
• Varistor protection L1, L2, L3-PEN connector for signalling of the
• Replaceable varistor module 7P.23.8.275.1020 varistor status
7P.24.8.275.x020 SPD Type 2 for three phase TT
and TN-S system with Neutral.
• Varistor protection L1, L2, L3 + spark gap
protection N-PE
• Replaceable varistor and spark gap modules
E 7P.25.8.275.x020 SPD Type 2 for three phase
TN-S system with Neutral.
• Varistor protection L1, L2, L3, N-PE
• Replaceable varistor module
7P.23.8 / 7P.24 / 7P.25
Screw terminals
8
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
9
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
10
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
7P.23.9 / 7P.26
Screw terminals
11
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
SPD Type 1+2 and Type 2 Surge arrester range 7P.26.9.000.x015 7P.23.9.000.x015 7P.03.9.000.1012
for Photovoltaic applications
• Surge arrester for protection of DC side (1020 V)
of systems in photovoltaic applications
• Protects equipment against overvoltage
caused by direct lightning strike (Type 1+2
only) and induced overvoltages (Type 1+2 and
Type 2)
7P.26.9.000.x015, UCPV = 1020 V DC (Type 2)
7P.23.9.000.x015, UCPV = 1020 V DC (Type 2)
7P.03.9.000.1012, UCPV = 1000 V DC (Type 1+2)
• Visual indication of varistor status - • SPD Type 2 (2 varistors + 1 • SPD Type 2 (3 varistors) for • SPD Type 1+2 (3 varistors)
Healthy/Replace spark-gap) for 1020 V DC 1020 V DC photovoltaic for 1000 V DC photovoltaic
• Contact for remote signalling of varistor status. photovoltaic systems systems systems
Connector (07P.01) included (depending on the • Combination of replaceable • Replaceable varistor modules • Replaceable varistor modules
verision) varistor and encapsulated • Visual and optional remote • Visual and remote signalling
• Replaceable modules spark gap modules connector for signalling of the of varistor status
• Complies with prEN 50539-11:2012 • Visual and optional remote varistor status
• 35 mm rail (EN 60715) mounting connector for signalling of the
varistor status
7P.23.9 / 7P.26 / 7P.03
Screw terminals
12
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
13
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
G
P
outlets and 35 mm rail mounting P A T E N T
P
G
E
NDIN
14
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
SH SH SH SH
Wire size solid cable stranded cable solid cable stranded cable
2
mm 4 2.5 4 2.5
AWG 12 14 12 14
Approvals (according to type)
15
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
16
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
Ordering information
Example: 7P series, surge protection device, Type 2, single phase (UC = 275 V), 1 varistor + 1 encapsulated spark gap, with remote status signalling
contact, In = 20 kA
7 P . 2 2 . 8 . 2 7 5 . 1 0 2 0
Series Nominal discharge current
Type 100 = 1
00 kA (Iimp Type 1) only for 7P.09,
N-PE GDT for 7P.04
0 = Combined type 1 + 2 arresters
050 = 5
0 kA (Iimp Type 1 N-PE GDT for 7P.02)
high discharge capability
025 = 2 5 kA (Iimp Type 1+2)
1 = Type 1+2 high performance “Low Up”
surge arresters 020 = 2
0 kA (In Type 2)
2 = Type 2 surge arresters 015 = 1
5 kA (In Type 2)
3 = Type 3 surge arresters 012 = 1
2.5 kA (Iimp Type 1+2)
4 = Type 2 surge arrester without 003 = 3
kA
(In @ Uoc only for 7P.36 and 7P.37)
leakage current
6 = Data line SPD 005 = 5 kA (In @ Uoc for 7P.31, 7P.32 and 7P.62)
485 = R S485 Modbus protocol
Circuit (Data line SPD)
1 = Single phase (1 varistor) 600 = E thernet Cat 6 (Data line SPD)
2 = Single phase (1 varistor + 1 spark-gap), protected
poles (data line SPD)
2 = Protected poles (Data line SPD)
Remote status signalling contact E
0 = Without remote status signalling
3 = Three-phase (3 varistors)
contact (only some Type 2 SPD and
4 = Three-phase (3 varistors + 1 spark-gap)
Data line)
5 = Three-phase (4 varistors)
6 = 2 varistors + 1 spark-gap 1=B uilt-in remote status signalling
6 = 1 varistors + 1 spark-gap(7P.36) contact
7 = Single phase (2 varistors) Type 2 (7P.27) 2=A coustic fault signalling
7 = Single phase (1 varistor + 1 spark gap) Type 3,
DIN rail mounting (7P.37)
8 = Protected poles (Data line SPD)
9 = N-PE spark-gap for three phase system
0 = Spare module
Supply version
1 = N+PE connection
(only for single spark gap replaceable module and 7P.09)
8 = AC (50/60 Hz)
9 = DC (PV application and Data line SPD)
17
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
Replaceable modules
Replacement varistor and modules 7P.00.8.260.0025 7P.00.9.500.0012 7P.00.1.000.0050 7P.00.1.000.0100
Varistor + GDT Varistor + GDT Spark-Gap Spark-Gap
Maximum operating voltage (UC/UCPV ) V AC/DC 260/— —/500 255/— 255/—
Lightning Impulse current (10/350 μs) (Iimp) kA 25 12.5 50 100
Nominal discharge current (8/20 μs) (In) kA 30 30 50 100
Maximum discharge current (8/20 μs) (Imax) kA 60 60 100 100
Voltage protection level (Up) kV 1.5 1.8 1.5 1.5
Leakage current (@ 253 V AC) & Ipe current uA <4 <4 <4 <4
Response time (ta) ns 100 25 100 100
Maximum overcurrent protection 250 A gL/gG — — —
18
7P SERIES 7P
Surge Protection Devices (SPD) - Dimensional data SERIES
Outline drawings
Type 7P.09 Type 7P.01
Screw terminal Screw terminal
Type 7P.02
Screw terminal
PE
PE
Type 7P.03
Screw terminal
Type 7P.04
Screw terminal
I-2019, www.findernet.com
19
7P 7P SERIES
SERIES Surge Protection Devices (SPD) - Dimensional data
Outline drawings
Type 7P.05
Screw terminal
20
7P SERIES 7P
Surge Protection Devices (SPD) - Dimensional data SERIES
Outline drawings
Types 7P.23.8 / 7P.43 Types 7P.24 / 7P.44
Screw terminal Screw terminal
45
21
7P 7P SERIES
SERIES Surge Protection Devices (SPD) - Dimensional data
Outline drawings
Type 7P.68.9.060.0600
Types 7P.62.9.036.0005/7P.62.9.009.0485
Screw terminal
Type Types
7P.36.8.275.2003 7P.31.8.275.0005/7P.32.8.275.0005
39 13
44
180
22
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
TT-THREE PHASE SYSTEM - SPD UP-STREAM OF RCD Wiring diagrams “V-shape” (fuse max = 125 A)
I-2019, www.findernet.com
23
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
N/L
7P.36.8.275.2003
24
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
TN-S THREE PHASE SYSTEM - SPD DOWN-STREAM TN-C THREE PHASE SYSTEM - SPD UP-STREAM
OF OVERCURRENT PROTECTION OF OVERCURRENT PROTECTION
I-2019, www.findernet.com
25
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
Load
PLC, L Input N
PE Bus system, PE
Load Remote monitoring PE
Load
17.5 mm
12-24V DC
E L1 Output N1
Load
Function
Visual local LED signalling and remote signalling of varistor status
I-2019, www.findernet.com
26
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
E
Zone II: SPD spaced, at least from one side, from components that generate heat during their operation (17.5 mm gap)
Zone III: SPD spaced, on both side, from components that generate heat during their operation (20 mm gap)
Zone IV: SPD installed individually in free air (without significant influence from nearby components)
I-2019, www.findernet.com
27
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
I-2019, www.findernet.com
28
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
Surge voltage protectors (such as Finder’s Surge Protection Devices, SPD) Component Symbol Leakage Energy Response Voltage/Current
are intended to be installed in electrical systems, to protect people and current dissipated time characteristic
machines from surge voltages that can occur on the electrical supply line
and which would otherwise have disastrous consequences. These surge 0 High Fast
Ideal
voltages can be atmospheric (lightning) or can originate on the electrical
system due to, for example: the opening and closing of large loads, short
circuits, or the switching of large power factor correction capacitors. The
SPD can be described as a switch that is in parallel with the electrical
system’s supply line - which it is protecting. At the nominal network Spark gap 0 High Medium
voltage (e.g. 230 V) the SPD appears as an open switch, having a very
high impedance (almost infinite). But, under an overvoltage condition its
impedance rapidly falls to near 0 Ω. This effectively applies a short circuit
across the supply lines and immediately “drains” the overvoltage to earth.
In this way the supply line is protected wherever an SPD is installed. When Varistor Very Low Medium Fast
the overvoltage has passed, the SPD impedance rises rapidly and resumes
the state of an open switch again.
Figure 2: S PD component characteristics.
Installation (Overvoltage) categories
Choosing the SPD requires matching the Rated Impulse Voltage of the
SPD with that of the equipment to be protected. This in turn relates to the
Installation category (Overvoltage category). Installation categories are
described within IEC 60664-1, which for a 230/400 V installation prescribes
as follows: E
- I nstallation category I: 1.5 kV for “particularly sensitive” equipment (e.g.
electronic devices like PC or TV set);
- I nstallation category II: 2.5 kV for “user” equipment subject to “normal”
impulse voltages (e.g. household electrical appliances, mobile items);
- I nstallation category III: 4 kV for equipment that are part of a fixed
installation (e.g. switchboards, switches)
- Installation category IV: 6 kV for equipment installed at or near the
origin of main incoming supply mains (e.g. energy meters).
Lightning Protection Zones and installation considerations
International standards refer to the various Lightning Protection Zones by
the letters LPZ followed by an appropriate number.
LPZ 0A: An external area, where a direct lightning strike is possible
and where there is total exposure to the electromagnetic field
induced by the lightning.
LPZ 0B: An external area, but below a lightning conductor providing
direct lightening strike protection. There remains total exposure
to the electromagnetic field.
Figure 1: Ideal operation of an SPD LPZ 1: Area within a building – therefore protected from direct lightning
strike. The electromagnetic field will be attenuated, depending
SPD technologies on the degree of shielding. This zone has to be protected by SPD
Finder surge voltage protectors use either varistors or spark gaps. type 1 device(s) at its boundary with the LPZ 0A or 0B zone.
LPZ 2: An area, typically a room, where the lightning current has been
Varistor: This can be considered as a variable resistance that at nominal limited by preceding surge protectors. This zone has to be protected
voltage has a very high ohmic value. But the resistance rapidly falls to near by SPD type 2 device(s) at its boundary with the LPZ 1 zone.
zero as the voltage surges. In this way the varistor applies a near short LPZ 3: An area within a room where the lightning current has been
circuit which clamps the surge voltage. The varistor is however subject limited by preceding surge protectors (typically the wiring after a
to progressive degradation due to the small leakage current that occurs socket or an area within a metal enclosure).
at the nominal voltage, and with the number of interventions. With every This zone has to be protected by SPD type 3 device(s) at its boundary
overvoltage that occurs the leakage current rises and accelerates the end with the LPZ 2 zone. On the following picture (Figure 3, representation
is not binding) it is shown that the transition from a protection zone to
of life for the device - which is ultimately indicated by the change from
the next is through the installtion of SPD. SPD Type 1 must be connected
green to red in the signal-window. upstream the system, at the point of delivery connection. As an alternative
it is possible to use SPD Type 1+2. The grounding conductor must have a
Spark gap: This comprises two electrodes separated by air, or a gas.
minimum section of 6 mm2 for SPD Type 1, of 4 mm2 for SPD Type 2, and
When a surge voltage occurs an electrical arc bridges the gap and a surge 1.5 mm2 for SPD Type 3 (If the building has an LPS, reference should be
current flows to limit the surge voltage to a low and constant level. The made to CEI 81-10/4 for the correct dimension of the cable).
arc extinguishes only when the surge current falls below about 10 ampere.
LPZ
LPZ 0
The gas guarantees a constant level of breakdown voltage since the arc is
struck in a protected environment; not exposed to pressure or humidity
INSTALLATION CATEGORIES
(RATED IMPULSE VOLTAGE)
LPZ 1
variations or impurities as would happen if it had occurred in air. There is
SPD type 1
IV
however, a delay before the device arcs and the surge current is diverted, LPZ 2
SPD type 2
(6 kV)
and this is dependent on the magnitude of the original voltage surge and III
SPD type 3
I-2019, www.findernet.com
(4 kV) II LPZ 3
on its rate of rise. Therefore, the voltage protection level can vary, although (2.5 kV)
I
it is guaranteed to be less than Up. e.g. household (1.5 kV)
e.g. energy meters e.g. switchboards, electrical appliances, e.g. electronic devices
switches mobile items like PC or TV set
29
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
Rated vaules and marking of SPD Type 1 Uoc: test voltage. This is the peak value of the no load voltage of the
combined test-generator; this has a waveform of 1.2/50 μs (figure 7) and
SPD Type 1 must be connected upstream the system, at the point of
can supply at the same time current with waveform 8/20 μs (figure 6).
delivery of power energy. SPD protects building and people from the risk
of direct lightning (fire and death) and are characterized by:
30
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
Short-circuit protection for the SPD is provided by the overcurrent V-shape connection
protective devices (fuses type gL/gG) recomended. Using a V-shaped connection eliminates transferring downstream the
inductive voltage generated by the surge current in the connecting wire
If the overcurrent protective devices F1 (which are part of the installation)
to the SPD. This increases the protection to the system and equipment
have a rating smaller than or equal to the maximum recommended rating
downstream. A limitation of this connection is that the nominal current for
for the overcurrent protective devices for the SPD, then F2 (back up fuse),
the downstream system is limited to 125 A, which is the maximum current
can be omitted.
permitted through the double SPD terminals.
7P.0X:
125 A
If F1 <= 250 A, F2 can be omitted
125 A
7P.1X, 7P.2X:
Coordination of SPD
Optimal protection from surges requires cascaded coordinated SPDs.
Coordination has the purpose of splitting the energy associated with
voltage across the SPDs and it is achieved by introducing an impedance
between the SPDs, or alternatively, by connecting them using wires having E
the minimum length indicated in the figures below, in order to use the
cable's own impedance.
For systems where the rated current is greater than 125 A, it is necessary to
connect the SPD in parallel with the equipment (E/I).
Connecting cable
Depending on the type of connection, serial (V-shape) or parallel (T-shape),
ensure that both the maximum cable lengths and minimum cross section
of the connecting wires are respected in accordance with the information
below (IEC 60634-5-534):
The section of the connecting wires (copper) must not be less than:
SPD Type 1: 16 mm2 if it is subject to discharge a significant lightning
current, 6 mm2 otherwise
SPD Type 2: 6 mm2
SPD Type 3: 1.5 mm2
I-2019, www.findernet.com
31
7P 7P SERIES
SERIES Surge Protection Devices (SPD)
32
7P SERIES 7P
Surge Protection Devices (SPD) SERIES
A A
78
SЕRIES
Building
automation
Elevators and
lifts
Automation for
blinds, grilles
and shutters
Panels for
electrical
distribution
Pump Control
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
78 SERIES 78
Switch mode power supplies SERIES
3
78 78 SERIES
SERIES Switch mode power supplies
4
78 SERIES 78
Switch mode power supplies SERIES
36 W, 60 W and 50 W High efficiency, low profile 78.36 78.60 78.50
Modular DC Power Supplies for electrical
cabinets
Type 78.36
--Output 24 V DC, 36 W
--Input fuse: Easily replaceable plus spare
--70 mm (4-module) wide x 61 mm deep
Type 78.60
--Output 24 V DC, 60 W
Type 78.50
--Output 12 V DC, 50 W
• High efficiency (up to 91%)
• Low (< 0.4 W) stand-by power consumption • 24 V DC, 36 W output • 24 V DC, 60 W output • 12 V DC, 50 W output
• Thermal protection: internal, with Vout • Output adjustable between • Output adjustable between
shutdown - power OFF to reset 24-28 V 12-14 V
• Short circuit protection: Hiccup (auto-recovery) mode • ZVS technology • ZVS technology
• Input fuse: Easily replaceable plus spare
• Overvoltage protection: Varistor Replaceable fuse + spare
• Flyback topology
• ZVS (Zero-voltage-switching), quasi-resonant
mode switching
• Compliant with EN 60950-1 and EN 61204-3
• Parallel working for automatic redundancy -
with OR diodes
• Dual Polarity and Series connection permissible
• Small dimensions: 70 mm (4-modules) wide,
61 mm deep
• 35 mm rail (EN 60715) mount
Screw terminal * (see diagrams P78)
** peak to peak, 100 Hz component, with 100 V AC input
5
78 78 SERIES
SERIES Switch mode power supplies
6
78 SERIES 78
Switch mode power supplies SERIES
7
78 78 SERIES
SERIES Switch mode power supplies
8
78 SERIES 78
KNX Switch mode power supplies SERIES
9
78 78 SERIES
SERIES Switch mode power supplies
Ordering information
Example: 78 series switch mode power supply, 36 W - 24 V DC output, supply voltage 110…240 V AC, replaceable fuse.
A B C D
7 8 . 3 6 . 1 . 2 3 0 . 2 4 0 1
Series D:
0 = Standard
Power 1 = Replaceable fuse
12 = 12 W output 3 = Replaceable fuse +
25 = 25 W output output voltage regulator
36 = 36 W output 4 = Fuse + regulator + positive
50/51 = 50 W output logic contact
60/61 = 60 W output 5 = Fuse + regulator +
1B = 110 W output
pre-alarm contact
1D = 130 W output
2E = 240 W output C:
2K = KNX 640 mA 0 = Standard
1 = Double stage, with PFC
Voltage conversion (Power Factor Correction)
1 = AC/DC input, DC output AB:
1 = AC input, DC output (78.2K) 12 = 12 V output
Input voltage 24 = 24 V output
230 = 110…240 V AC / 220V DC 30 = 30 V output KNX
230 = 110…240 V AC/DC Codes
230 = 120…240 V AC / 220V DC 78.12.1.230.1200
230 = 230…240 V AC (78.2K) 78.12.1.230.2400
F 78.25.1.230.1200
78.25.1.230.2400
78.36.1.230.2401
78.50.1.230.1203
78.51.1.230.1203
78.60.1.230.2403
78.61.1.230.2403
78.1B.1.230.2403
78.1D.1.230.2414
78.1D.1.230.2415
78.2E.1.230.2414
78.2E.1.230.2415
78.2K.1.230.3000
VII-2019, www.findernet.com
10
78 SERIES 78
Switch mode power supplies SERIES
Technical data
78.12, 78.60, 78.61, 78.1B 78.1D 78.2E
EMC specifications (according to EN 61204-3) Reference standard 78.25, 78.50 78.51
78.36
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV 8 kV 8 kV 8 kV 8 kV
Radiated electromagnetic field 80…1000 MHz EN 61000-4-3 6 V/m 10 V/m 10 V/m 10 V/m 10 V/m 10 V/m
1…2.8 GHz EN 61000-4-3 3 V/m 3 V/m 3 V/m 3 V/m 3 V/m 10 V/m
Fast transients
(burst 5/50 ns, 5 and 100 kHz) on supply terminals EN 61000-4-4 2 kV 3 kV 3 kV 2 kV 3 kV 3 kV
Voltage pulses on supply terminals common mode EN 61000-4-5 2 kV 2 kV 2 kV 2 kV 3 kV 2.5 kV
(surge 1.2/50 µs) differential mode EN 61000-4-5 2 kV 4 kV* 4 kV* 4 kV ** 4 kV** 4 kV**
(78.12),
4 kV*
(78.36)
Radio-frequency common mode
voltage (0.15…230 MHz) on supply terminals EN 61000-4-6 6 V 10 V 10 V 10 V 10 V 10 V
Short interruptions EN 61000-4-11 5 cycles 6 cycles 6 cycles 5 cycles 6 cycles 5 cycles
Radio-frequency conducted emissions 0.15…30 MHz EN 55022 class B class A class B class B class B class B
Radiated emissions 30…1000 MHz EN 55022 class B class A class B class B class A class A
Terminals Max Min…Max
Wire size (Solid cable, stranded cable) mm2 1 x 4 / 2 x 2.5 1 x 0.5…1 x 4
AWG 1 x 12 / 2 x 14 1 x 20…1 x 12
Screw torque Nm 0.8 0.5
F
Wire strip length mm 9 9
Other data
Power lost to the environment with rated output current W 2 (78.12), 2.3 (78.25), 5 (78.36, 78.50/51), 5.4 (78.60/61)
W 9 (78.1B), 13.2 (78.1D), 16.8 (78.2E)
11
78 78 SERIES
SERIES Switch mode power supplies
Output specification
L78-1 Output current v ambient temperature (78.12) P78-1 Output peak current v time (78.12)
L78-2 Output current v ambient temperature (78.25) P78-1 Output peak current v time (78.25)
12
2.1
10
F 1.05 8
12 V
L78-2 Output current v ambient temperature (78.36) P78-2 Output peak current v time (78.36)
VII-2019, www.findernet.com
12
78 SERIES 78
Switch mode power supplies SERIES
Output specification
L78-3 Output current v ambient temperature (78.60) P78-3 Output peak current v time (78.60)
L78-4 Output current v ambient temperature (78.50/51) P78-4 Output peak current v time (78.50/51)
L78-5 Output current v ambient temperature (78.61) P78-5 Output peak current v time (78.61)
VII-2019, www.findernet.com
13
78 78 SERIES
SERIES Switch mode power supplies
Output specification
L78-6 Output current v ambient temperature (78.1B) P78-6 Output peak current v time (78.1B)
230 V AC
115 V AC
L78-7 Output current v ambient temperature (78.1D) P78-7 Output peak current v time (78.1D)
5.4
20
18
F
16
14
12
10
L782E-1 Output current v ambient temperature (78.2E) P782E-1 Output peak current v time (78.2E)
12.5
30
10
25
7.5
5 20
2.5
15
10
VII-2019, www.findernet.com
14
78 SERIES 78
Switch mode power supplies SERIES
Output specification
FB78-5 Output voltage v output current (78.2E)
(V)
30
25
20
15 F
10
Hiccup mode
Overload current
Load current
Current
Time
Under normal conditions, the 78 Series Power Supply supplies the current required by the load.
However, under abnormal conditions such as a short circuit or heavy overload (T0) the output voltage will be rapidly reduced to zero - followed by
the current (T1). After approximately 2 seconds (T1 to T2), the power supply checks for the persistence of the anomaly over the time period T2 to T3
(30 to 100ms - dependent on the type of anomaly). If the anomaly persists, as shown above, the current is again reset to 0 A for a further 2 s (T3 to T4).
This “hiccup” process is repeated until the anomaly is removed (Tn), whereon the power supply then returns to normal working.
78.1B is able to handle this anomaly for 15 s. After this time it enters in protection mode, and a manual reset is necessary by removing and re-applying
the supply voltage
VII-2019, www.findernet.com
15
78 78 SERIES
SERIES Switch mode power supplies
The fold-back mode allows the use of the power supply as a battery charger, in particular 78.51/61 for charging lead acid batteries (both standard and
gel types) rated 7…24 Ah and 78.1D for charging lead batteries rated 17…38 Ah. In any case, it is necessary to verify that the charging characteristics of
the batteries are compliant with the output characteristics of the power supply.
It is suggested to insert a diode in series between the + output and the + input of the battery (if not already installed in the battery unit).
78.51/61/1D
FB78-1 Output voltage v output current (78.51) FB78-2 Output voltage v output current (78.61)
F
14 28
12 24
10 20
8 16
6 12
4 8
2 4
0 0
1 2 3 4 5 0.5 1 1.5 2 2.5
(I) (I)
16
78 SERIES 78
Switch mode power supplies SERIES
13
DC OK
•
ALARM
DC OKDC
DC
ALARMOK
OK
DC OK DC
78.2E.1.230.2414 OK ALARM
DC OK
* OK ALARM
ALARM
DC OK ALARM
DC OK 13
DC OK
ALARM
ALARM
ALARM OK
ALARM
DC
ALARM
DC OK
• ALARM
DC
OFFOK
DC OK
ALARM 13
DCDC
ALARMOKOK DC OK
•
ALARM
Overload ALARM DC OKDC OK
ALARM
78.2E.1.230.2414
DC OK
ALARM
DC OK
** ALARM ALARM
DC OK 13
DC OK ALARM
ALARM
(78.1D only)
DC OK
ALARMDC OK
ALARM
ALARM
• ALARM
DC
OFFOK
DC OK
ALARM
DCDCOK OK DC OK
•
ALARM
78.1D.1.230.2415 ALARM DC OK
DCDC
ALARMOKOK ALARM
78.2E.1.230.2414
*** Short circuit ALARM
78.2E.1.230.2414
DC OK ALARM
DC OK 13
78.2E.1.230.241478.2E.1.230.2414 ALARM
DCALARM
OK
78.2E.1.230.2415
78.2E.1.230.2414
78.2E.1.230.2414 DC OK
ALARM
ALARM
ALARM
DC
DCOK OK
• DC
OFFOK
DC OK
ALARM
78.2E.1.230.2414 ALARM
•
ALARM
78.2E.1.230.2414 DC OK DC OK DC
ALARM
DCDCOK OK
OK ALARM
78.2E.1.230.2414
Thermal limitALARM DCDC
ALARMOK
ALARMOK DC OK
78.2E.1.230.2414
78.2E.1.230.2414
ALARM ALARMDC
ALARM
DC
OK
ALARM
OK
ALARM • DC OK
ALARM
ALARM
ALARM
DC
DC OK OK
•
ALARM
DC OK ALARM
DC OK OFF
DC# OK ALARM
DCDC
DCOK OK
OK
Thermal protection DC OK
DCDC OK
ALARMOK
ALARM
ALARM
ALARMDC
DC
OK
ALARM
ALARMOK
• ALARM
78.2E.1.230.2414 ALARM ALARM
#
Remove the supply voltage, following the intervention of the thermal protection, in order ALARM
ALARM
to
DC OK reset the power supply.
DC OK ALARM
ALARM
DC
DC OKOK
ALARM
78.12, 78.25, 78.36, 78.50, 78.60, 78.51, 78.61,
78.2E.1.230.2414
ALARM78.1B LED table
ALARM
ALARM
Type State DC OK LED
78.12.1.230.xx00 DC OK
78.25.1.230.1200
OK •ALARM
ALARM
78.25.1.230.2400
DC OK
78.36.1.230.2401 Short circuit •
78.50.1.230.1203 ALARM
78.60.1.230.2403
78.51.1.230.1203 Thermal limit • OFF
78.61.1.230.2403
OK •
VII-2019, www.findernet.com
17
78 78 SERIES
SERIES KNX Switch mode power supplies
LED table
Type Area State LED OUT
OUTPUT
OUT
OUT
OUT
Vout Vout OK
OK
Vout OK
• OFF ON ON
OUT
ON
Vout OK • OFF ON
Vout OK ON
Vout OK ON
Vout LOW OFF
CHECK START-UP Vout LOW OUT
OFFOFF
CHECK START UP
CHECK START-UP Vout LOW
< 29V < 29V
Vout LOW
• OFF OUT
OFF
CHECK START-UP
< 29V
CHECK START-UP Vout
< 29V LOW • OFF OFF
Vout
Vout OK
LOW OFF
CHECK START-UP ON
< 29V
Vout
Vout
OK
HIGH
• OFF OFF
ON
< 29V OFF
Vout HIGH
Vout HIGH
> 33V
Vout
> 33V HIGH OFFOFF
> 33V OFF
CHECK START-UP
Vout
> 33V
Vout
Vout HIGH
HIGH
LOW
OK
• OFF OUT
OFF
OFF
> 33V LOW OFF
78.2K.1.230.3000 CHECK START-UP Vout
< 29V OK
78.2K.1.230.3000 > 33V
Vout OK ON
< 29V ON 13
78.2K.1.230.3000 Iout
OK > 0.9A
Vout Vout OK
78.2K.1.230.3000 NORMAL FUNCTION
78.2K.1.230.3000 Iout
Vout
Iout > 0.9A > 0.9AOK • OFF ON ON
DC >
Iout OK0.9A ON
OFF
78.2K.1.230.3000 NORMAL FUNCTION Vout HIGH
Vout>< 0.9A29V ON
OFF
NORMAL FUNCTION Iout Vout
ALARM HIGH
NORMAL FUNCTION Vout < 29V
> >33V ON
NORMAL FUNCTION Vout Iout 0.9A
> 33V< 29V
NORMAL FUNCTION Iout
CHECK START-UP Vout
DC > OK LOW
0.9A
• OFF ON
OFF
F Vout
Vout <Vout
Iout
29V >
< 29V
OK
0.9A • OFF
ON
78.2K.1.230.3000 < 29V
Vout
Vout < OK
29V ON ON
Iout > 0.9A
ALARM
Iout > 0.9A ON
78.2K.1.230.3000 ON
Iout >
> 0.9A
0.9A ON
Iout
Pre-alarm: OUT
DC
Iout >OK0.9A
NORMAL FUNCTION Iout up > 0.9A
Pre-alarm:
to HIGH
60s ON
OFF
Vout
Pre-alarm: ON
NORMAL FUNCTION up
ALARMto 60s
78.2E.1.230.2414 Vout
up <60s
29V ON
Alarm condition: Pre-alarm: > to33V
Pre-alarm:
Vout < OK
29V
TambAlarm condition:
> 45°C @ Inom. Pre-alarm:
up
DC
up to 60s to 60s
OK • OFF ON ON
ON
TambAlarm condition:
> 45°C @ Inom. Iout up >to 60s
Vout 0.9A
OK
Latched OFF
78.2K.1.230.3000 Tamb > 45°C
Alarm @ Inom. Iout
condition: > 0.9A
ALARM
Latched OFF
alarm ON
TambAlarm
Alarm condition: condition:
> 45°C @ Inom. Latched
alarm OFF
Tamb > 45°CTamb
@ Inom.
CHECK > 45°C @ Inom. Iout
START-UP >
DCalarm
Vout 0.9A
OKLOW
Latched
• OFF OFF
OFF
Pre-alarm:
NORMAL FUNCTION Latched • OFF ON
<alarm
up
Latched ALARM
alarm 29V
Pre-alarm:
to 60s OFF OFF
upalarm
Vout to<60s
29V ON
Alarm condition: ON
TambAlarm condition:
> 45°C @ Inom. OFF
Iout > 0.9A
Tamb > 45°C @ Inom. Vout HIGH
Latched OFF
>alarm
33V
Latched OFF
alarm
Pre-alarm:
Vout OK
up to 60s ON
78.2K.1.230.3000
ON
Alarm condition: Iout > 0.9A
Tamb > 45°C
NORMAL @ Inom.
FUNCTION
Latched
Vout < 29V OFF
alarm ON
Iout > 0.9A
Pre-alarm:
up to 60s ON
VII-2019, www.findernet.com
Alarm condition:
Tamb > 45°C @ Inom.
Latched OFF
alarm
18
78 SERIES 78
Switch mode power supplies SERIES
Wiring diagrams for 78.12, 78.25, 78.36, 78.50, 78.51, 78.60 & 78.61
Basic connections Basic connections
L(L1) N(L2)
F
L(L1) N(L2) L(L1) N(L2)
19
78 78 SERIES
SERIES Switch mode power supplies
VII-2019, www.findernet.com
20
78 SERIES 78
Switch mode power supplies SERIES
21
78 78 SERIES
SERIES Switch mode power supplies
Diode(s)
Insulating sheet
Insulating sheet
or
e.g. e.g.
TO-220AC TO-220AB
STPS1545D STPS30L40CT
F
Diode for type 78.1B, 78.1D, 78.2E
e.g.
TO-247AD
MBR 4060PT
VII-2019, www.findernet.com
22
78 SERIES 78
Switch mode power supplies SERIES
Outline drawings
Type 78.12 Type 78.25
Screw terminal Screw terminal
23
78 78 SERIES
SERIES Switch mode power supplies
Outline drawings
Type 78.1D
Screw terminal
F Type 78.2E
Screw terminal
VII-2019, www.findernet.com
24
78 SERIES 78
Switch mode power supplies SERIES
Outline drawings
Type 78.2K
Screw terminal
Accessories
Sheet of marker tags (CEMBRE Thermal transfer printers), (48 tags), 6 x 12 mm 060.48
060.48
019.01
VII-2019, www.findernet.com
Drying kilns
7T
SЕRIES
Industrial
refrigeration
Road / tunnel
lighting
Industrial
furnaces and
ovens
Automatic
car-washes
Panels for
electrical
distribution
Control panels
Forced-air
ventilators
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7T SERIES 7T
Panel Thermo-hygrostat and thermostats SERIES
Panel Thermo-Hygrostat
7T.51 7T.81.0.000.240x 7T.81.0.000.230x
• Small, compact size (17.5 mm wide)
• Electronic control
• 4 functions
• Nominal voltage 110…240 V AC/DC
• Temperature ranges from +10 ° to +60°C
• Humidity range up to 90%
• LED status indication contact ON
• 35 mm rail (EN 60715) mount
Panel thermostat
• Small, compact size (17.5 mm wide)
• Snap action themostatic Bimetal sensor • Thermo-Hygrostatic control • Heating control • Ventilation control
• Wide temperature setting range • Nominal voltage
• Long electrical life 110…240 V AC/DC
• 35 mm rail (EN 60715) mount
3
7T 7T SERIES
SERIES Panel Thermo-hygrostat and thermostats
Ordering information
Example: 7T Series, Thermo-Hygrostat for temperature and humidity control, 110…240 V AC/DC, Multifunction, 35 mm rail (EN 60715) mount.
7 T . 5 1 . 0 . 2 3 0 . 4 3 6 0
Series Control function
Type 60 = Multifunction (only 7T.51)
5 = Thermo-Hygrostatic control 01 = –20…+40 °C (only 7T.81)
8 = Temperature control 03 = 0…+60 °C (only 7T.81)
Technical data
Insulation 7T.51 7T.81
Dielectric strength between open contacts V AC 1000 500
Dielectric strength between supply and contact V AC 2000 —
Other data
Screw torque Nm 0.5 0.5
Max. wire size solid cable stranded cable
G mm 2
1 x 2.5 1 x 1.5
AWG 1 x 12 1 x 16
Functions 7T.51
HT: RH > RHset OR Tamb > Tset
The contact 13-14 closes if the ambient humidity (RH) is > of set humidity
(RHset) OR if the ambient temperature (Tamb) is < of set temperature
(Tset).
4
7T SERIES 7T
Panel Thermo-hygrostat and thermostats SERIES
Functions 7T.51
HL: RH < RHset
The contact 13-14 closes if the ambient humidity (RH) is < of set humidity
(RHset)
RH
13-14
The contact 13-14 closes if the ambient humidity (RH) is > of set humidity
RH (RHset)
13-14
Functions 7T.81
Max
Min
Heating control - Should the panel temperature fall below the (minimum) set temperature the contact will close to call for heat.
The contact will open when this set temperature is exceeded.
Ventilation control - Should the panel temperature exceed the (maximum) set temperature then the contact will close to call for cooling.
The contact will open when the temperature falls below this set temperature.
VII-2019, www.findernet.com
5
7T 7T SERIES
SERIES Panel Thermo-hygrostat and thermostats
Wiring diagrams
7T.51 7T.81…230x
7T.81.0.000.230X
7H/7F
7F SERIES
SERIES
PRODUCTS
PRODUCTS
13 14
7T.81…240x
7T.81.0.000.240X
7H SERIES
PRODUCTS
G
11 12
Outline drawings
Type 7T.51 Type 7T.81
Screw terminal Screw terminal
VII-2019, www.findernet.com
Drying kilns
7F
SЕRIES
Textile machines
Machines
for paper
processing
Machines for
ceramics
Wood-
processing
machines
Panels for
electrical
distribution
Control panels
Forced-air
ventilators
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Protection class I
Protection category according to EN 60529 IP 54
Protection category according to NEMA Type 12
Approvals (according to type)
3
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Note:
By reversing the fan motor, the air direction
G can be changed from “Inlet” Filter Fan mode
to “Exhaust” Filter Fan mode** (except for the
types 7F.50.8.xxx.4370, 7F.50.8.xxx.5500 and
7F.50.8.xxx.5630).
** Supplied in “Inlet” Filter Fan mode (Standard).
4
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Note:
By reversing the fan motor, the air direction
can be changed from “Inlet” Filter Fan mode
to “Exhaust” Filter Fan mode** (except for the G
types 7F.50.8.xxx.4370, 7F.50.8.xxx.5500 and
7F.50.8.xxx.5630).
** Supplied in “Inlet” Filter Fan mode (Standard).
5
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Protection class I
Protection category according to EN 60529 IP54
Protection category according to NEMA Type 12
Approvals (according to type)
6
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Note:
By reversing the fan motor, the air direction
can be changed from “Inlet” Filter Fan mode
to “Exhaust” Filter Fan mode** (except for the G
types 7F.50.8.xxx.4370, 7F.50.8.xxx.5500 and
7F.50.8.xxx.5630).
** Supplied in “Inlet” Filter Fan mode (Standard).
7
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Ordering information
Example: Series 7F, Filter Fan for mounting in sidewalls, nominal voltage 230 V AC, size 1, air volume 24 m3/h.
7 F . 2 0 . 8 . 2 3 0 . 1 0 2 0
Series
Type
20 = Filter Fan - for indoor use
21 = Reverse flow Filter Fan - for indoor use
50 = Filter Fan - for indoor use
70 = EMC Filter Fan - for indoor use
80 = Reverse flow Filter Fan - for indoor use
Supply version
8 = AC (50/60 Hz)
9 = DC
Operating voltage
024 = 24 V DC
120 = 120 V AC
230 = 230 V AC
Enclosure cut-out
1 = Size 1 (92+0.5 x 92+0.5) mm
2 = Size 2 (125+1.0 x 125+1.0) mm
3 = Size 3 (177+1.0 x 177+1.0) mm
4 = Size 4 (224+1.0 x 224+1.0) mm
5 = Size 5 (291+1.0 x 291+1.0) mm
Air volume (free flow)
020 = 24 m3/h
055 = 55 m3/h
100 = 100 m3/h
G 230 = 230 m3/h
370 = 370 m3/h
500 = 500 m3/h
630 = 630 m3/h
Note:
The technical features (air volume, dimensions and electrical parameters) for the Standard Filter Fans (7F.20 and 7F.50), the EMC Filter Fans (7F.70) and
the Reverse flow versions (7F.21 and 7F.80) - are exactly the same.
7F.50.8.120.5630 has no UL approval. Other versions on request.
8
7F SERIES 7F
Exhaust Filter SERIES
9
7F 7F SERIES
SERIES Exhaust Filter
10
7F SERIES 7F
Exhaust Filter SERIES
Ordering information
Example: Series 7F, Exhaust Filter for mounting in sidewalls, size 1.
7 F . 0 2 . 0 . 0 0 0 . 1 0 0 0
Series
Type
02 = Exhaust Filter - for indoor use
05 = Exhaust Filter - for indoor use
07 = EMC Exhaust Filter - for indoor use
Operating voltage
000 = Not applicable for Exhaust Filter
Exhaust Filter - All versions
Enclosure cut-out
Standard-versions EMC - versions
1000 = Size 1 (92+0.5 x 92+0.5) mm
2000 = Size 2 (125+1.0 x 125+1.0) mm 7F.02.0.000.1000 — Exhaust Filter, Size 1
3000 = Size 3 (177+1.0 x 177+1.0) mm 7F.02.0.000.2000 — Exhaust Filter, Size 2
4000 = Size 4 (224+1.0 x 224+1.0) mm 7F.02.0.000.3000 — Exhaust Filter, Size 3
5000 = Size 5 (291+1.0 x 291+1.0) mm
7F.05.0.000.4000 7F.07.0.000.4000 Exhaust Filter, Size 4
7F.05.0.000.5000 7F.07.0.000.5000 Exhaust Filter, Size 5
Components Standard-Filter Fan Standard-Exhaust Filter EMC-Filter Fan EMC-Exhaust Filter Filter mat Size
7F.20.8.xxx.1020 7F.02.0.000.1000 — — 07F.15 1
7F.20.8.xxx.2055 7F.02.0.000.2000 — — 07F.25 2
7F.20.8.xxx.3100 7F.02.0.000.3000 — — 07F.35 3
7F.50.8.xxx.4230 7F.05.0.000.4000 7F.70.8.230.4230 7F.07.0.000.4000 07F.45 4
7F.50.8.xxx.4370 7F.05.0.000.4000 7F.70.8.230.4370 7F.07.0.000.4000 07F.45 4
G
7F.50.8.xxx.5500 7F.05.0.000.5000 7F.70.8.230.5500 7F.07.0.000.5000 07F.55 5
7F.50.8.xxx.5630 7F.05.0.000.5000 7F.70.8.230.5630 7F.07.0.000.5000 07F.55 5
7F.20.9.024.1020 7F.02.0.000.1000 — — 07F.15 1
7F.20.9.024.2055 7F.02.0.000.2000 — — 07F.25 2
7F.20.9.024.3100 7F.02.0.000.3000 — — 07F.35 3
7F.50.9.024.4230 7F.05.0.000.4000 7F.70.9.024.4230 7F.07.0.000.4000 07F.45 4
07F.80
VII-2019, www.findernet.com
11
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Filter
The installation with the only clips is optimized for 1.5 mm thick sheets;
it is also possible with thicknesses from 1 to 2.5 mm.
Fixing with screws (supplied) is recommended.
Tightening torque 0.3 Nm.
Fan
G
Replacement of Filter mat ( Type 7F.20)
VII-2019, www.findernet.com
12
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Drilling template and mounting cut-outs for Filter Fans and Exhaust Filter
G
VII-2019, www.findernet.com
13
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Outline drawings
Type 7F.20.x.xxx.1020 AC version DC version Type 7F.02.0.000.1000
92.5 ±0.5
92.5 ±0.5
90 ±0.1
92 ±0.5
92 ±0.5
120
120
120
120
120 54.4
54.4 99 41
41 99 120 11.1 9
VII-2019, www.findernet.com
14
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Outline drawings
Type 7F.50.x.xxx.4230 Type 7F.05.0.000.4000
15
7F 7F SERIES
SERIES Filter Fan (24…630)m3/h
Fan selection
G 24 m3/h
55 m3/h
100 m3/h
230 m3/h
370 m3/h
500 m3/h
630 m3/h
Example
First, estimate the power dissipated within the cabinet. Then calculate the maximum difference between the internal and external temperature (green
lines) by considering the difference between the maximum permitted internal temperature (as dictated by the temperature rating of the enclosed
components, or specification) and the maximum temperature expected outside the cabinet.
The projection onto the X axis, of the intersection between the power (watts) and the appropriate green line, corresponds to the air flow rate in m3/h
required to meet the maximum internal temperature limit. Extending this line vertically to intersect with the blue horizontal lines, indicates the most
appropriate model of 7F fan to be fitted to the cabinet to provide the requisite air flow.
The example above considers a cabinet with an internal thermal power dissipation of 500 W, and assumes the maximum temperature difference between
the inside and the outside of the cabinet to be 20K. The required air flow can be seen to be a little less than 80 m3/h.
It is suggested that this is increased by 10% to allow for the affects of a dirty filter.
And so, it can be seen that models of the 7F with 100 m3/h flow rate will provide the proper dissipation of heat under these circumstances.
VII-2019, www.findernet.com
16
7F SERIES 7F
Filter Fan (24…630)m3/h SERIES
Application notes
Filter Fan Mounting of the pressure compensation device
The ball-bearing axial fan housing is made of aluminium and the rotor is In sealed cabinets and enclosures the internal pressure can vary due to
made of plastic or metal (depending on the type). changes in temperature. The pressure compensation device (07F.80) will
relieve this internal/external pressure differential whilst maintaining a high
Filter classes level of protection - preventing the ingress of dust and moisture into the
Within EN 779 are specified 9 filter classes, categorised into 4 coarse dust cabinet or the enclosure. The pressure compensation device is approved
filters und 5 fine dust filters. for use in cabinets and enclosures according to DIN EN 62208.
The coarse dust filters G1 - G4 are able to filter particles > 10 μm and the
fine dust filters G5 - G9 are able to filter particles from (1…10)μm. Drill a hole Ø 37+1.0 mm in the housing wall and fix the pressure
compensation device with the accompanying nut. It is important to ensure
Filter classes Example of particle Particle size that the sealing ring is located on the outside. To ensure optimum pressure
Textile fibers, hair, sand, balance, it is recommended to fit 2 pressure compensation device at the
G1 - G4 upper sides of the cabinet or enclosure.
pollen, spores, insects, > 10 μm
(EU1 - EU4)
cement dust
Pollen, spores, cement dust,
G5 - G9
tobacco smoke, oil smoke, (1…10)μm
(EU5 - EU9)
soot
Filter mats
The quality of these filters mats has been independently tested, according
EN 779 and branded after passing the test.
The filter mats are to filter class G3 and have an average filtering degree
of (80…90)%.
Filter material
The filter material consists of a synthetic fiber with progressive construction
which is moisture-resistant to 100% RH and temperature resistant to
+100 °C. G
According to the strict requirements of fire class F1, DIN 53438, these filter
mats are self extinguishing.
(7F.80).
Drying kilns
7H
SЕRIES
Hoists and cranes
Road / tunnel
lighting
Plastic
moulding
machines
Automatic
car-washes
Panels for
electrical
distribution
Control panels
Forced-air
ventilators
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7H SERIES 7H
Panel Heaters 25 - 50 - 100 - 150 W SERIES
3
7H 7H SERIES
SERIES Panel Heaters 25 - 50 - 100 - 150 W
4
7H SERIES 7H
Panel Heaters 250 - 400 W SERIES
5
7H 7H SERIES
SERIES Panel Heaters
Ordering information
Example: 7H series, Panel heaters, heating power 50 W, 110…230 V AC/DC.
7 H . 5 1 . 0 . 2 3 0 . 0 0 5 0
Series
Type
51 = Panel heaters safe touch
Supply version
0 = AC (50/60 Hz)/DC
8 = AC (50/60 Hz) only fan assisted version
Supply voltage
230 = 110…230 V
230 = 230 V only fan assisted version
Heater power
0025 = 25 W
0050 = 50 W
0100 = 100 W
0150 = 150 W
0250 = 250 W
0400 = 400 W
General data
Terminals solid cable stranded cable
Wiring diagrams
Fan assisted version
F = aM 6.3 A
IX-2019, www.findernet.com
6
7H SERIES 7H
Panel Heaters SERIES
Wiring diagrams
NOT Fan assisted versions
AC version DC version
SAFETY NOTE
For reasons of safety and performance , heaters must be mounted in the following way:
1. keep a distance of 100 mm. from components above and below and of 60 mm from side components
2. install vertically (cables below heater) in the bottom part of cabinet
3. do not mount heaters over easily inflammable materials
4. do not operate in corrosive ambient air
WARNING
Do not cover the heater.
The 7H.51 Heater surface is very hot for 15-20 minutes after disconnecting.
G
During working and maintenance, don’t touch it.
Caution: risk of burns.
Outline drawings
Type 7H.51.0025 Type 7H.51.0050
Screw terminal Screw terminal
IX-2019, www.findernet.com
7
7H 7H SERIES
SERIES Panel Heaters
Outline drawings
Type 7H.51.0100 Type 7H.51.0150
Screw terminal Screw terminal
IX-2019, www.findernet.com
Building
automation
80
SЕRIES
Elevators
and lifts
Automation for
blinds, grilles
and shutters
Panels for
electrical
distribution
3
80 80 SERIES
SERIES Modular timers 16 A
4
80 SERIES 80
Modular Solid State timer (SST) 1 A SERIES
5
80 80 SERIES
SERIES Modular timers 6 - 8 A
6
80 SERIES 80
Modular timers 8 A SERIES
80.51.0.240.0000 80.51.0.240.P000
• Multi-voltage (24…240) V AC/DC
Screw terminal Push-in terminal
• Multi-function
AI: On-delay
DI: Interval
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
7
80 80 SERIES
SERIES Modular timers 1 - 6 - 8 - 16 A
Ordering information
Example: 80 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (12…240)V AC/DC.
8 0 . 0 1 . 0 . 2 4 0 . 0 0 0 0
Series Versions
Type 0 = Standard
0 = Multi-function (AI, DI, SW, BE, CE, DE) P = Push-in (only for 80.51)
1 = On-delay (AI) Supply voltage
2 = Interval (DI) 240 = (12…240)V AC/DC (80.01, 80.91)
4 = Off-delay with control signal (BE) 240 = (24…240)V AC/DC
5 = Multi-function (AI, DI, SW, BE, CE, DE) (80.11, 80.21, 80.41, 80.51, 80.71, 80.82)
6 = Power off-delay (True off-delay) (BI) 240 = (24…240)V AC, (24…220)V DC (80.61)
7 = Multi-function with solid state output Supply version
(AI, DI, SW, BE, CE, DE) 0 = AC (50/60 Hz)/DC
8 = Star-delta (SD)
No. of poles
9 = Asymmetrical flasher (LI, LE)
1 = 1 CO (SPDT)
1 = 1 NO (SPST-NO), type 80.71 only
2 = 2 NO (DPST-NO), type 80.82 only
Technical data
Insulation
Dielectric strength 80.01/11/21/41/51/82/91 80.61 80.71
between input and output circuit V AC 4000 2500 2500
between open contacts V AC 1000 1000 —
Insulation (1.2/50 µs) between input and output kV 6 4 4
EMC specifications
Type of test Reference standard 80.01/11/21/41/61/71/91 80.51/82
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV 4 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 4 kV 4 kV
differential mode EN 61000-4-5 4 kV 4 kV
H on start terminal (B1) common mode EN 61000-4-5 4 kV 4 kV
differential mode EN 61000-4-5 4 kV 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) on Supply terminals EN 61000-4-6 10 V 10 V
Radiated and conducted emission EN 55022 class B class A
Other data
Current absorption on signal control (B1) < 1 mA
Power lost to the environment without contact current W 1.4
with rated current W 3.2
Terminals Screw terminals Push-in terminals
Wire strip length mm 10 10
Screw torque Nm 0.8 —
Min. wire size solid cable solid cable
mm2 0.5 0.75
AWG 20 18
Max. wire size solid cable solid cable
mm2 1 x 6 / 2 x 4 1 x 1.5 / 2 x 1.5
AWG 1 x 10 / 2 x 12 1 x 16 / 2 x 16
Min. wire size stranded cable stranded cable
mm2 0.5 0.75
AWG 20 18
Max. wire size stranded cable stranded cable
mm2 1 x 4 / 2 x 2.5 1 x 2.5 / 2 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14 / 2 x 14
V-2019, www.findernet.com
8
80 SERIES 80
Modular timers 1 - 6 - 8 - 16 A SERIES
Outline drawings
Types 80.01/80.51 Type 80.51
Screw terminal Push-in terminal
33.8
89.8
45
86
30.5
Types 80.11/80.21/80.61 Type 80.41
Screw terminal Screw terminal
Type 80.82
Screw terminal
V-2019, www.findernet.com
9
80 80 SERIES
SERIES Modular timers 1 - 6 - 8 - 16 A
Functions
U = Supply voltage NO output Contacts
LED* Supply voltage
contact Open Closed
S = Signal switch
OFF Open 15 - 18 15 - 16
= Output contact
ON Open 15 - 18 15 - 16
Open
ON 15 - 18 15 - 16
(Timing in Progress)
ON Closed 15 - 16 15 - 18
* The LED on type 80.61 is illuminated only when the supply voltage is applied to the timer; during the timing period the LED
is not illuminated.
80.71
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
10
80 SERIES 80
Modular timers 6 - 8 - 16 A SERIES
Functions
Wiring diagram
Without control signal Type (AI) On-delay.
80.11 Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
80.11/21/61
80.61 (BI) Power off-delay (True off-delay).
Apply power to timer (minimum 500 ms). Output contacts
transfer immediately. Removal of power initiates the preset
delay, after which time the output contacts reset.
80.41
Without control signal 80.91 (LI) Asymmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is applied.
The ON (T1) and OFF (T2) times are independently adjustable.
H
80.91
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
11
80 80 SERIES
SERIES Modular timers 1 - 6 - 8 - 16 A
Times scales
Rotary switch position series 80
Accessories
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
80.01/11/21/41/51/61/71 (48 tags), 6 x 12 mm 060.48
060.48
V-2019, www.findernet.com
Control panels
81
SЕRIES
Milk processing
plant
Punches,
cleaners,
planers and
sanders
Shipyards
45
84
88.8
3
81 81 SERIES
SERIES Modular timers 16 A
Ordering information
Example: 81 series, modular timer multi-voltage, 1 CO (SPDT) - 16 A, supply rated at (12…230)V AC/DC.
8 1 . 0 . 1 . 0 . 2 3 0 . 0 0 0 0
Series Supply voltage
230 = (12 … 230)V AC/DC
Type
0 = Multi-function Supply version
(AI, DI, SW, SP, BE, DE, EEb) 0 = AC (50/60 Hz)/DC
No. of poles
1 = 1 CO (SPDT)
Technical data
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV
Surges (1.2/50 μs) on Supply terminals common mode EN 61000-4-5 4 kV
differential mode EN 61000-4-5 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) on Supply terminals EN 61000-4-6 10 V
Radiated and conducted emission EN 55022 class A
Other data
Current absorption on signal control (B1) < 1 mA (S-X) < 1 mA (R-X)
H Voltage potential on the input terminal R - X and S -X Not galvanic separation from the supply voltage on A1 - A2
Power lost to the environment without contact current W 1.3
with rated current W 3.2
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm 2
1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
NOTE: time range and function must be set before energising the timer.
X-2017,www.findernet.com
4
81 SERIES 81
Modular timers 16 A SERIES
Functions
U = Supply voltage LED LED Supply NO output Contacts
S = Signal switch (green) (red) voltage contact Open Closed
R = Reset
OFF Open 15 - 18 15 - 16
= Output contact
ON Open 15 - 18 15 - 16
ON Closed 15 - 16 15 - 18
Wiring diagram
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
** Connection of the
Reset (R-X) is optional
Example:
Control signal; ON pulse function.
Closing the external reset switch terminates the interval
time and resets the timer. To re-start, it is necessary to
open the reset switch, before closing the control signal
contact.
5
81 81 SERIES
SERIES Modular timers 16 A
Accessories
Identification tag, for type 81.01, plastic, 1 tag, 17 x 25.5 mm 019.01
019.01
Sheet of marker tags (CEMBRE Thermal transfer printers) for type 81.01, plastic,
060.48
48 tags, 6 x 12 mm
060.48
X-2017,www.findernet.com
Packaging
machines
Pump control
Industrial
refrigeration
Fountains
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
83 SERIES 83
Modular timers 12 - 16 A SERIES
Wiring diagram
(with control signal)
Wiring
(1) Wiring diagram
Short term (10 min) + 70°C diagram (with control signal
For outline drawing see page 7 (with control signal) and pause signal)
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT) 2 CO (DPDT)
H
Rated current/Maximum peak current A 16/30 12/30 12/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 4000 3000 3000
Rated load AC15 (230 V AC) VA 750 750 750
Single phase motor rating (230 V AC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 12/0.3/0.12 12/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24…240 24…240 24…240
V DC 24…240 24…240 24…240
Rated power AC/DC VA (50 Hz)/W < 1.5/< 2 < 2/< 2 < 2/< 2
Operating range V AC 16.8…265 16.8…265 16.8…265
V DC 16.8…265 16.8…265 16.8…265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5…10)min, (0.05…1)h, (0.5…10)h, (0.05…1)d, (0.5…10)d
Repeatability% ± 1 ± 1 ± 1
Recovery time ms 200 200 200
Minimum control impulse ms 50 50 50
Setting accuracy-full range % ± 5 ± 5 ± 5
V-2019,www.findernet.com
3
83 83 SERIES
SERIES Modular timers 16 A
• 1 Pole
• 22.5 mm wide
• Eight time scales from 0.05 s to 10 days
• High input/output isolation • Multi-voltage • Multi-voltage • Multi-voltage
• Wide supply range (24…240)V AC/DC • Mono-function • Mono-function • Mono-function
• 35 mm rail (EN 60715) mount AI: On-delay DI: Interval BE: Off-delay with control signal
• “Blade + cross” - both flat blade and cross head
screw drivers can be used to adjust the range
and function selectors, the timing trimmer, and
to disengage the rail mounting clip
• Multi-voltage versions with “PWM clever”
technology
• Complies with EN 45545-2:2013 (protection
against fire of materials), EN 61373 (resistance
against random vibrations and shock,
Category 1, Class B), EN 50155 (resistance to
temperature and humidity, T1 class)
(1)
Short term (10 min) + 70°C Wiring diagram Wiring diagram Wiring diagram
H For outline drawing see page 7 (without control signal) (without control signal) (with control signal)
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 16/30 16/30 16/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 4000 4000 4000
Rated load AC15 (230 V AC) VA 750 750 750
Single phase motor rating (230 V AC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24…240 24…240 24…240
V DC 24…240 24…240 24…240
Rated power AC/DC VA (50 Hz)/W < 1.5/< 2 < 1.5/< 2 < 1.5/< 2
Operating range V AC 16.8…265 16.8…265 16.8…265
V DC 16.8…265 16.8…265 16.8…265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5…10)min, (0.05…1)h, (0.5…10)h, (0.05…1)d, (0.5…10)d
Repeatability% ± 1 ± 1 ± 1
Recovery time ms 200 200 200
Minimum control impulse ms — — 50
V-2019,www.findernet.com
4
83 SERIES 83
Modular timers 8 - 16 A SERIES
• 22.5 mm wide
• Time scales: • Multi-voltage • Multi-voltage • Multi-voltage
Type 83.62 - 0.05 s to 3 minutes • Mono-function • Mono-function • Multi-function
Type 83.82/83.91 - 0.05 s to 10 days • 2 pole • 2 pole
• Wide supply range (24…240)V AC / DC • Transfer time can be regulated
• 35 mm rail (EN 60715) mount (0.05…1)s***
• Complies with EN 45545-2:2013 (protection BI: Power off-delay (True off-delay) SD: Star-delta LI:
Asymmetrical flasher
(starting pulse on)
against fire of materials), EN 61373 (resistance LE:
Asymmetrical flasher (starting
against random vibrations and shock, pulse on) with control signal
PI:
Asymmetrical flasher
Category 1, Class B), EN 50155 (resistance to (starting pulse off )
PE:
Asymmetrical flasher (starting
temperature and humidity, T1 class) pulse off ) with control signal
Wiring diagram
(without control signal)
Wiring diagram
(with control signal)
* (0.05…2)s, (1…16)s, (8…70)s, (50…180)s
** (0.05…1)s, (0.5…10)s, (0.05…1)min,
(0.5…10)min, (0.05…1)h, (0.5…10)h,
(0.05…1)d, (0.5…10)d
*** 0.05 s, 0.2 s, 0.3 s, 0.45 s, 0.6 s, 0.75 s,
0.85 s, 1 s
(1)
Short term (10 min) + 70°C Wiring diagram Wiring diagram
For outline drawing see page 7
(without control signal) (without control signal) H
Contact specification
Contact configuration 2 CO (DPDT) 2 NO (DPST-NO) 1 CO (SPDT)
Rated current/Maximum peak current A 8/15 16/30 16/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 2000 4000 4000
Rated load AC15 (230 V AC) VA 400 750 750
Single phase motor rating (230 V AC) kW 0.3 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24…240 24…240 24…240
V DC 24…220 24…240 24…240
Rated power AC/DC VA (50 Hz)/W < 1.5/< 2 < 1.5/< 2 < 1.5/< 2
Operating range V AC 16.8…265 16.8…265 16.8…265
V DC 16.8…242 16.8…265 16.8…265
Technical data
Specified time range * **
Repeatability% ± 1 ± 1 ± 1
Recovery time ms — 200 200
Minimum control impulse ms 500 ms (A1 - A2) — 50
V-2019,www.findernet.com
5
83 83 SERIES
SERIES Modular timers 16 A
Ordering information
Example: 83 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (24…240)V AC/DC.
8 3 . 0 1 . 0 . 2 4 0 . 0 0 0 0
Series Versions
0000 = Standard
Type
0 = Multi-function Supply voltage
(AI, DI, GI, SW, BE, CE, DE, WD) 240 = (24 … 240)V AC/DC
1 = On-delay (AI)
2 = Interval (DI) Supply version
4 = Off-delay with control signal (BE) 0 = AC (50/60 Hz)/DC
5 = Multi-function
(AE, GE, IT, FE, EEa, DEp, BEp, SHp) No. of poles
6 = Power off-delay (True off-delay) (BI) 1 = 1 CO (SPDT)
8 = Star-delta (SD) 2 = 2 CO (DPDT) for 83.02, 83.52 and 83.62
9 = Asymmetrical flasher (LI, LE, PI, PE) 2 = 2 NO (DPST-NO) for 83.82
Technical data
Insulation
Dielectric strength between input and output circuit V AC 4000
between open contacts V AC 1000
Insulation (1.2/50 µs) between input and output kV 6
EMC specifications
Type of test Reference standard 83.01/02/52/11/21/41/82/91 83.62
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
(1000 ÷ 2700 MHz) EN 61000-4-3 3 V/m 3 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 7 kV 6 kV
H on control signal terminal (B1) EN 61000-4-4 7 kV 6 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 6 kV 6 kV
differential mode EN 61000-4-5 6 kV 4 kV
on control signal terminal (B1) common mode EN 61000-4-5 6 kV 6 kV
differential mode EN 61000-4-5 4 kV 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) EN 61000-4-6 10 V 10 V
on Supply terminals (80 ÷ 230 MHz) EN 61000-4-6 10 V 10 V
Radiated and conducted emission EN 55022 class A class A
Other data
Current absorption on control signal (B1) < 1 mA
- max cable length (capacity of ≤ 10 nF/100 m) 150 m
- when applying a control signal to B1, which B1 is isolated from A1 and A2 by an opto-coupler, and can therefore be
is different from the supply voltage at A1/A2 operated at a voltage other than the supply voltage.
If using a control signal of between (24… 48)V DC and a supply voltage
of (24…240)V AC, ensure that the signal - is connected to A2 and the +
is applied to B1, and that L is applied to B1 and N to A2.
External potentiometer for 83.02/52 Use a 10 kΩ / ≥ 0.25 W linear potentiometer. Maximum cable length 10
m. When using an external potentiometer, the timer automatically use
its setting in place of the internal setting.
Consider the voltage potential at the potentiometer to be the same as
the timer supply voltage.
Power lost to the environment without contact current W 1.4
with rated current W 3.2
V-2019,www.findernet.com
6
83 SERIES 83
Modular timers 16 A SERIES
Outline drawings
Type 83.01 Types 83.02/52
Screw terminal Screw terminal
7
83 83 SERIES
SERIES Modular timers 16 A
Accessories
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
83.01/11/21/41/62/82, plastic, 48 tags, 6 x 12 mm 060.48
060.48
087.02.2
Z1 Z2
Functions LED*
Supply NO output Contacts
voltage contact Open Closed
15 - 18 15 - 16
OFF Open
H 25 - 28 25 - 26
15 - 18 15 - 16
ON Open
25 - 28 25 - 26
Open 15 - 18 15 - 16
ON
(Timing in Progress) 25 - 28 25 - 26
15 - 16 15 - 18
ON Closed
25 - 26 25 - 28
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
*
* With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1).
V-2019,www.findernet.com
** ** A voltage other than the supply voltage can be applied to the control signal (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
8
83 SERIES 83
Modular timers 16 A SERIES
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Multi-function Type (AI) On-delay.
without control signal 83.01 Apply power to timer. Output contacts transfer after preset time has
83.02 elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
83.01
83.02 type
Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE)
2 timed contacts
Both output contacts (15-18 and 25-28) Both output contacts (15-18 and 25-28)
follow the timing function follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open stay permanently open
1 timed +
1 instantaneous contact
V-2019,www.findernet.com
The output contact 15-18 follows the timing function The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U) The output contact 21-24 follows the control signal (S)
9
83 83 SERIES
SERIES Modular timers 16 A
Functions
Wiring diagram U = Supply voltage S = Signal switch P = Pause switch = Output contact
Multi-function Type (AE) On-delay with control signal.
with control signal 83.52 Power is permanently applied to the timer.
Closing the Signal Switch (S) initiates the preset delay, after which times the
AE output contacts transfer and remain so until the power is removed.
T
with control signal and pause (BEp) Off-delay with control signal and pause signal.
signal Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. The current state of the output contacts will be maintained. On
opening of the pause switch, timing resumes from the retained value.
(DEp) Interval with control signal on and pause signal.
Power is permanently applied to the timer. On momentary or maintained closure
of Signal Switch (S), the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset. Closure of the pause switch (X1-X2)
will immediately halt the timing process, but the elapsed time will be retained. The
current state of the output contacts will be maintained. On opening of the pause
switch, timing resumes from the retained value.
(SHp) “Shower” function (Off-delay with control signal and pause signal).
H Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. During the pause, the output contacts 15-18 and 25-28 will
be open. On opening of the pause switch, timing resumes from the retained value
and the output contacts will take the previous condition.
83.52 type
Functions with control signal and pause signal
Contact mode selector Function SHp
(example: BEp)
2 timed contacts
Both output contacts (15-18 and 25-28) follow the timing function Both output contacts (15-18 and 25-28) follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] stay permanently open Both output contacts [15-18 and 25(21)-28(24)] stay permanently open
1 timed +
1 instantaneous contact
V-2019,www.findernet.com
The output contact 15-18 follows the timing function The output contact 15-18 follows the timing function. The output
The output contact 21-24 follows the control signal (S) contact 21-24 is always open, unless during the pause, when is closed
10
83 SERIES 83
Modular timers 16 A SERIES
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Mono-function Type (AI) On-delay.
without control signal 83.11 Apply power to timer. Output contacts transfer after preset time has
elapsed. Reset occurs when power is removed.
83.82
with control signal (S) 83.41 (BE) Off-delay with control signal.
Power is permanently applied to the timer.
The output contacts transfer immediately on closure of the control
signal (S). Opening the control signal initiates the preset delay, after
which time the output contacts reset.
83.41
Asymmetrical recycler 83.91 (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
without control signal Apply power to timer. Output contacts transfer immediately and cycle
between ON and OFF for as long as power is applied. The ON and OFF
times are independently adjustable.
83.91 (PE) Asymmetrical flasher (starting pulse off) with control signal -
(Z1-Z2 linked).
Power is permanently applied to the timer.
Closing the control signal (S) initiates delay T1 after which the output
Z1-Z2 open: (LE) function contacts transfer and continue to cycle between OFF and ON, until the
Z1-Z2 linked: (PE) function control signal is opened.
Times scales
Rotary switch position series 83
1s 10 s 1m 10 m 1h 10 h 1d 10 d
Timers and
lighting controls
84
SЕRIES
Automatic
car-washes
Labelling
machines
Punches,
cleaners, planers
and sanders
Industrial
furnaces and
ovens
Discotheques,
swimming pools
and fountains
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
84 SERIES 84
SMARTimer 16 A SERIES
Screw terminal
Wiring diagram
3
84 84 SERIES
SERIES SMARTimer 16 A
Ordering information
Example: 84 series, SMARTimer, 2 CO - 16 A, supply rated at (110…240)V AC/DC.
8 4 . 0 2 . 0 . 2 3 0 . 0 0 0 0
Series Versions
Type 0 = Standard
0 = 2 Channel multi-function SMARTimer Supply voltage
230 = (110…240)V AC/DC (not polarized)
024 = (12…24)V AC/DC (not polarized)
Supply version
0 = AC (50/60 Hz)/DC
No. of poles
2 = 2 CO (DPST)
Technical data
Insulation
Dielectric strength between input and output circuit V AC 4000
between open contacts V AC 1000
between input/output and displayV AC 2000
Insulation (1.2/50 µs) between input and output kV 6
EMC specifications
Type of test Reference standard 84.02.0.230 84.02.0.024
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV 4 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 4 kV 2 kV
differential mode EN 61000-4-5 4 kV 1.5 kV
on start terminal (B1…B4) common mode EN 61000-4-5 4 kV 2 kV
differential mode EN 61000-4-5 3 kV 1 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) on Supply terminals EN 61000-4-6 10 V 10 V
H Radiated and conducted emission EN 55022 class B class B
Other data
Current absorption on control terminals (B1…B4) < 2.4 mA (0.230), < 5.5 mA (0.024)
Power lost to the environment without contact current W 1.6
with rated current W 3.6
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm2 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
I-2019, www.findernet.com
4
84 SERIES 84
SMARTimer 16 A SERIES
Outline drawing
Type 84.02
Screw terminal
“Smart” “Classic”
Android, Google Play and the Google Play logo are trademarks of Google Inc.
5
84 84 SERIES
SERIES SMARTimer 16 A
Functions
Wiring diagram
Type (OFF) Relay OFF.
84.02 The output contact stays permanently open.
18 16 15 28 26 25 (AI) On-delay.
Apply power to timer. Output contact transfers after preset
time has elapsed. Reset occurs when power is removed.
U (DI) Interval.
Apply power to timer. Output contact transfers immediately.
After the preset time has elapsed, contact resets.
H time has elapsed. The timer now cycles between OFF and ON as
long as power is applied. The ratio is 1:1 (time on = time off ).
(AE) On-delay with control signal.
Power is permanently applied to the timer. Closing the Signal
Switch (S) initiates the preset delay, after which the output
contact transfers and remains so until the power is removed.
Switch (S), the output contact transfers and remain so for the
duration of the preset delay, unless the Signal Switch opens
before the preset time has elapsed in which case the output
contact resets immediately.
6
84 SERIES 84
SMARTimer 16 A SERIES
Functions
Wiring diagram
Type (EE) Interval with control signal off.
84.02 Power is permanently applied to the timer. On opening of the
Signal Switch (S) the output contact transfers, and remain so for
the duration of the preset delay, after which it resets.
(WD) Watchdog
(retriggerable interval with control signal on).
Power is permanently applied to the timer. On momentary or
maintained closure of Signal Switch (S), the output contact
transfers, and remain so for the duration of the preset delay,
after which it resets; subsequent closures of Signal Switch
during the delay will extend the time. If the closure of the
Signal Switch (S) is longer than the preset time (T) then the
output contact resets.
(GE) Pulse delayed with control signal on.
Power is permanently applied to the timer. Closing the Signal
Switch (S) initiates T1 delay, after which the output contact H
transfers. Reset occurs after T2 time.
(LC) A
symmetrical flasher (starting pulse on) with maintained
control signal.
Power is permanently applied to the timer. On closure of
Signal Switch (S), the output contact transfers immediately and
cycles between ON and OFF for as long as the control signal is
applied. The ON and OFF times are independently adjustable.
After the Signal Switch (S) is opened, the output contact resets.
signal.
Power is permanently applied to the timer. Closing the Signal
Switch (S) initiates delay T1 after which the output contact
transfers and continues to cycle between OFF and ON, until the
Signal Switch is opened.
7
84 84 SERIES
SERIES SMARTimer 16 A
Functions
Wiring diagram
Type (PC) Asymmetrical flasher (starting pulse off) with maintained
84.02 control signal.
Power is permanently applied to the timer. On closure of
Signal Switch (S), the output contact transfers after time
T1 has elapsed and cycles between OFF and ON for as long
as the control signal is applied. The OFF and ON times are
independently adjustable. After the Signal Switch (S) is opened,
18 16 15 28 26 25
the output contact resets.
(SHp) "Shower"
(off-delay with control signal and pause signal).
Power is permanently applied to the timer. The output contact
transfers immediately on closure of the Signal Switch (S).
H Opening the signal switch initiates the preset delay, after which
the output contact resets. Closure of the Pause Switch (P) will
immediately halt the timing process, but the elapsed time will
be retained. During the pause, the output contact will be open.
On opening of the Pause Switch, timing resumes from the
retained value and the output contact will take the previous
condition.
8
84 SERIES 84
SMARTimer 16 A SERIES
H
I-2019, www.findernet.com
Timers and
lighting controls
85
SЕRIES
Medical and
dentistry
Drying kilns
Elevators
and lifts
Panels for
electrical
distribution
Control panels
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
85 SERIES 85
Miniature plug-in timers 7 - 10 A SERIES
3
85 85 SERIES
SERIES Miniature plug-in timers 7 - 10 A
Ordering information
Example: 85 series timer, 4 CO (4PDT), 24 V AC/DC supply voltage, AI, DI, GI, SW functions.
8 5 . 0 4 . 0 . 0 2 4 . 0 0 0 0
Series Supply voltage
012 = 12 V AC/DC
Type
024 = 24 V AC/DC
0 = Multifunction (AI, DI, GI, SW)*
048 = 48 V AC/DC
* AI = On-delay
125 = (110…125)V AC/DC
DI = Interval
240 = (230…240)V AC
GI = Pulse delayed
SW = Symmetrical flasher Supply version
(starting pulse on) 0 = AC (50/60 Hz)/DC
8 = AC (50/60 Hz) for 240 V only
No. of poles
2 = 2 pole - 10 A
3 = 3 pole - 10 A
4 = 4 pole - 7 A
Technical data
Insulation
Dielectric strength 85.02, 85.03 85.04
between input and output circuit V AC 2000 2000
between open contacts V AC 1000 1000
between adjacent contactsV AC 2000 1550
Insulation (1.2/50 µs) between input and output kV 6 4
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 n.a.
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 15 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV
Surges (1.2/50 µs) on common mode EN 61000-4-5 4 kV
Supply terminals differential mode EN 61000-4-5 2 kV
Outline drawings
Types85.02/04 85.03
Times scales
X-2017, www.findernet.com
NOTE: time scales and functions must be set before energising the timer.
4
85 SERIES 85
Miniature plug-in timers 7 - 10 A SERIES
Functions
U = Supply Supply NO (SPDT-NO) Contacts
LED
voltage voltage output contact Open Closed
= Output
OFF Open x1 - x4 x1 - x2
contact
ON Open x1 - x4 x1 - x2
Open
ON x1 - x4 x1 - x2
(Timing in Progress)
ON Closed x1 - x2 x1 - x4
(AI) On-delay.
Apply power to timer.
Output contacts transfer after preset time has elapsed.
Reset occurs when power is removed.
(DI) Interval.
85.02
Apply power to timer.
Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
85.04
U =
Supply voltage
Signal ON Pulse
S = Signal switch On mometary closure of Signal Switch (S) > 50 ms,
Uc = Supply voltage the output contacts transfer and remain so (with self-
to the timer holding on contact 11-14) for the duration of the preset
delay, after which they reset.
11-14 = Self-holding
contact
= Output contact
X-2017, www.findernet.com
5
85 94 SERIES
SERIES Sockets and accessories for 85 series timers
H 94.P3 94.P4
EAN 6-way jumper link for 94.P3 and 94.P4 sockets 094.56 (blue)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.56
2-way jumper link for 94.P3 and 94.P4 sockets 094.52.1
Rated values 10 A - 250 V
094.52.1
097.52
097.00
6
94 SERIES 85
Sockets and accessories for 85 series timers SERIES
Screw terminal (Box clamp) socket panel or 35 mm 94.02 94.02.0 94.03 94.03.0 94.04 94.04.0
(EN 60715) rail mount Blue Black Blue Black Blue Black
For timer type 85.02 85.03 85.04
Accessories
Metal retaining clip 094.81
6-way jumper link 094.06 094.06.0 094.06 094.06.0 094.06 094.06.0
94.04
Identification tag 094.00.4
Approvals Marker tag holder 097.00
(according to type):
Sheet of marker tags marker tag holder 097.00 , 48 tags,
6 x 12 mm for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
Ambient temperature °C –40…+70
Screw torque Nm 0.5
Wire strip length mm 8
060.48 Max. wire size for 94.02/03/04 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
EAN 6-way jumper link for 94.02, 94.03 and 94.04 sockets 094.06 (blue) 094.06.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
H
EUR
P A
OP
EAN
094.06
X-2017, www.findernet.com
7
85 94 SERIES
SERIES Sockets and accessories for 85 series timers
Top terminals
EAN
6-way jumper link for 94.84.2 socket 094.06 (blue) 094.06.0 (black)
OP
R
T E
EUR
P A
H
OP
EAN
094.06
X-2017, www.findernet.com
8
94 SERIES 85
Sockets and accessories for 85 series timers SERIES
Screw terminal (Box clamp) socket panel or 35 mm 94.92.3 94.92.30 94.94.3 94.94.30
rail mount (blue) (black) (blue) (black)
For timer type 85.02 85.04
Accessories
Metal retaining clip 094.81
6-way jumper link 094.06 094.06.0 094.06 094.06.0
94.94.3 Identification tag 094.80.3
Approvals Technical data
(according to type): Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
Ambient temperature °C –25…+70
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 94.92.3 and 94.94.3 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
Top terminals
Bottom terminals
94.94.3
EAN
6-way jumper link for 94.92.3 and 94.94.3 sockets 094.06 (blue) 094.06.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
H
094.06
X-2017, www.findernet.com
9
85 94 SERIES
SERIES Sockets and accessories for 85 series timers
Screw terminal (Plate clamp) socket 94.72 94.72.0 94.73 94.73.0 94.74 94.74.0
panel or 35 mm rail (EN 60715) mount Blue Black Blue Black Blue Black
For timer type 85.02 85.03 85.02, 85.04
Accessories
94.74
Metal retaining clip (supplied with timer) 094.81
Screw terminal socket 94.82 94.82.0
Approvals
(according to type): panel or 35 mm rail (EN 60715) mount Blue Black
For timer type 85.02 85.02
Accessories
Metal retaining clip (supplied with timer) 094.81
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
Ambient temperature °C –40…+70
94.82 Screw torque Nm 0.5
Approvals Wire strip length mm 8 (94.72, 94.73, 94.74) 9 (94.82)
(according to type): Max. wire size for 94.72, 94.73, 94.74 and 94.82 sockets solid wire stranded wire
mm2 1 x 2.5 / 2 x 1.5 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16 1 x 14 / 2 x 16
94.82
X-2017, www.findernet.com
Machines for
ceramics
Machines
for paper
86
processing SЕRIES
Printing
machines
Packaging
machines
Wood-
processing
machines
Milk processing
plant
Textile machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
86 SERIES 86
Timer modules SERIES
Contact specification*
Contact configuration
Rated current/Maximum peak current A
H
Rated voltage/
Maximum switching voltage V AC
Rated load AC1 VA See 56, 60 and 62 series relays
See 40, 44, 46, 55, 56, 60 and
Note: Do not use with relays
Rated load AC15 (230 V AC) VA 62 series relays
62.3x.x012.x300 and 62.3x.x012.x600
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification*
Nominal voltage (UN) V AC (50/60 Hz) 12…240 12…24 110…125 230…240
V DC 12…240 12…24 — —
Rated power AC/DC W 1.2 0.15
Operating range V AC (50/60 Hz) 10.2…265 9.6…33.6 88…137 184…265
DC 10.2…265 9.6…33.6 — —
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (5…100)s, (0.5…10)min, (5…100)min, (0.5…10)h, (5…100)h
Repeatability% ± 1 ± 1
Recovery time ms ≤ 50 ≤ 50
Minimun control impulse ms 50 —
II-2018,www.findernet.com
3
86 86 SERIES
SERIES Timer modules
Ordering information
Example: 86 series multi-function timer module, (12…240)V AC/DC supply voltage.
8 6 . 0 0 . 0 . 2 4 0 . 0 0 0 0
Series Supply voltage
Type 024 = (12…24)V AC/DC (86.30 only)
0 = Multi-function (AI, DI, SW, BE, CE, DE, EE, FE) 120 = (110…125)V AC (86.30 only)
3 = Bi-function (AI, DI) 240 = (12…240)V AC/DC (86.00 only)
240 = (12…48) V AC/DC
No. of poles
(86.00.0.240.0073 only)
See 40, 44, 46, 55, 56, 60 and 62 series relays
240 = (230…240)V AC (86.30 only)
Poles for chosen relay/socket combination -
according to chart below Supply version
0 = AC (50/60 Hz)/DC
8 = AC (50/60 Hz)
H
Other data Timer ATEX versions
Code available Nominal voltage Operating range Use temperature
86.00.0.240.0073 12-48 V AC/DC 10.2…60 V AC/DC –20…+50°C
86.30.0.024.0073 12-24 V AC/DC 9.6…33.6 V AC/DC –20…+50°C
IIC
Gas group
Gc
Equipment Protection Level
–20 °C ≤ Ta ≤ +50 °C
II-2018,www.findernet.com
Ambient temperature
EPTI 17 ATEX 0264 U
EPTI: laboratory which issues the CE type certificate
17: year of issue of certificate
0264: number of CE type certificate
U: ATEX component
4
86 SERIES 86
Timer modules SERIES
Technical data
EMC specifications
Type of test Reference standard 86.00 86.30
Electrostatic discharge contact discharge EN 61000-4-2 4 kV n.a.
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV 2 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 4 kV 2 kV
differential mode EN 61000-4-5 4 kV 1 kV
Radio-frequency common mode (0.15 ÷ 80 MHz)
on Supply terminals EN 61000-4-6 10 V 10 V
Radiated and conducted emission EN55022 class B class B
Other data 86.00 86.30
Current absorption on signal control (B1) mA 1 —
Power lost to the environment without contact current W 0.1 (12 V) - 1 (230 V) 0.2
with rated current See 56, 60 and 62 series relays See 40, 44, 46, 55, 56, 60, 62 series
relays
Times scales
NOTE: Time scales and functions must be set before energising the timer.
To achieve the minimum time setting of 0.05 seconds it is necessary to use one of the functions with control signal.
When setting very short times it may be necessary to take into account the operate time of the relay used.
Outline drawings
Type 86.00 Type 86.30
H
II-2018,www.findernet.com
5
86 86 SERIES
SERIES Timer modules
Functions
U = Supply voltage LED LED Supply NO output
Type 86.00 Type 86.30 voltage contact
S = Signal switch
OFF Open
= Output contact
ON Open
Open
ON
(Timing in Progress)
ON Closed
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
6
86 SERIES 86
Sockets and accessories SERIES
38 81.1
20.4
77.5
35.5
3.2
34.8
21.6
4
90.02
30.5 26.9
90.03
33.5
90.02
H
6-way jumper link for 90.02 and 90.03 sockets 090.06
O
PEAN Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
090.06
Approvals
(according to type):
II-2018,www.findernet.com
7
86 86 SERIES
SERIES Sockets and accessories
34.3
Rated current (A)
3.2
91.3
35.4
46.3
21.6
II-2018,www.findernet.com
8
86 SERIES 86
Sockets and accessories SERIES
94.P3 94.P4 H
EAN 6-way jumper link for 94.P3 and 94.P4 sockets 094.56 (blue)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.56
2-way jumper link for 94.P3 and 94.P4 sockets 094.52.1
Rated values 10 A - 250 V
094.52.1
097.52
097.00
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.0.024.0000
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.120.0000
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.240.0000
86.30 Approvals (according to type):
9
86 86 SERIES
SERIES Sockets and accessories
Screw terminal (Box clamp) socket panel or 35 mm 94.02 94.02.0 94.03 94.03.0 94.04 94.04.0
(EN 60715) rail mount Blue Black Blue Black Blue Black
For relay type 55.32 55.33 55.32, 55.34
Accessories
Metal retaining clip 094.71
Plastic retaining and release clip
94.04
(supplied with socket - packaging code SPA) 094.91.3 094.91.30 094.91.3 094.91.30 094.91.3 094.91.30
Approvals
6-way jumper link 094.06 094.06.0 094.06 094.06.0 094.06 094.06.0
(according to type):
Identification tag 094.00.4
Marker tag holder 097.00
Timer modules (see table below) 86.30
Certain relay/socket Sheet of marker tags for plastic retaining and release clip
combinations 094.91.3 and for marker tag holder 097.00 , 48 tags, 6 x 12 mm
for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V
Dielectric strength 2 kV AC
Protection category IP 20
094.91.3
Ambient temperature °C –40…+70
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 94.02/03/04 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
060.48 AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
Top
terminals
H 94.04 Bottom
terminals
EAN 6-way jumper link for 94.02, 94.03 and 94.04 sockets 094.06 (blue) 094.06.0 (black)
OP
Rated values 10 A - 250 V
R
N T
EU
T E
EUR
P A
OP
EAN
094.06
10
86 SERIES 86
Sockets and accessories SERIES
11 COM
Total socket current (A)
14 NO
12 NC
A2 A1 COIL
H
95.P3
95.P3 95.P5
95.P5
8-way jumper link for 95.P3 and 95.P5 sockets 097.58
Rated values 10 A - 250 V
097.58
2-way jumper link for 95.P3 and 95.P5 sockets 097.52
Rated values 10 A - 250 V
097.52
097.42
097.00
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.0.024.0000
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.120.0000
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h) 86.30.8.240.0000
86.30 Approvals (according to type):
11
86 86 SERIES
SERIES Sockets and accessories
Screw terminal (Box clamp) socket panel or 35 mm rail mount 95.03 (blue) 95.03.0 (black) 95.05 (blue) 95.05.0 (black)
For relay type 40.31 40.51, 40.52, 40.61
Accessories
Metal retaining clip 095.71
Plastic retaining and release clip
95.05 (supplied with socket - packaging code SPA) 095.01 095.01.0 095.01 095.01.0
Approvals 8-way jumper link 095.18 095.18.0 095.18 095.18.0
(according to type): Marker tag holder (for tags 060.48 type) 097.00
Identification tag 095.00.4
Timer modules (see table below) 86.30
Sheet of marker tags for plastic retaining and release clip
ertain relay/socket
C 095.01 and for marker tag holder 097.00, 48 tags, 6 x 12 mm,
combinations for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 10 A - 250 V*
Dielectric strength 6 kV (1.2/50 µs) between coil and contacts
Protection category IP 20
095.01 Ambient temperature °C –40…+70 (see diagram L95)
Screw torque Nm 0.5
Wire strip length mm 8
Max. wire size for 95.03 and 95.05 sockets solid wire stranded wire
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14
060.48 * For currents > 10 A, contact terminals must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
L 95 - Total socket current v ambient temperature
Total socket current (A)
11 COM
14 NO
12 NC
H
A2 A1 COIL
PEAN
8-way jumper link for 95.03 and 95.05 sockets 095.18 (blue) 095.18.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.18
12
86 SERIES 86
Sockets and accessories SERIES
094.91.3
96.02 96.02 + 56.32 + 094.91.3 + 86.30 96.04 96.04 + 56.34 + 096.71 + 86.00
PEAN
6-way jumper link for 96.02 socket 094.06 (blue) 094.06.0 (black)
O
EUR
N
T
Rated values 10 A - 250 V
T E
EUR
P A O
PEAN
094.06
II-2018,www.findernet.com
13
86 86 SERIES
SERIES Sockets and accessories
Push-in terminal socket panel or 35 mm rail (EN 60715) mount 97.P1 97.P2
For relay type 46.61 46.52
Accessories
Plastic retaining and release clip
(supplied with socket - packaging code SPA) 097.01
Metal retaining clip 097.71
97.P2 Identification tag 095.00.4
8-way jumper link 097.58
Approvals
2-way jumper link 097.52
(according to type):
2-way jumper link 097.42
Marker tag holder 097.00
Timer modules (see table below) 86.30
Sheet of marker tags for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers 060.48
Technical data
Rated values 16 A-250 V AC 8 A-250 V AC
097.01 Dielectric strength 6 kV (1.2/50 μs) between coil and contacts
Protection category IP 20
Ambient temperature °C –40…+70 (see diagram L97)
Wire strip length mm 8
Min. wire size for 97.P1 and 97.P2 socket solid wire stranded wire
mm2 0.5 0.5
060.48 AWG 21 21
Max. wire size for 97.P1 and 97.P2 socket solid wire stranded wire
mm2 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 2 x 18 / 1 x 14 2 x 18 / 1 x 14
L 97 - Rated current v ambient temperature
Rated current (A)
H
97.P1 97.P2
097.58
2-way jumper link for 97.P1 and 97.P2 sockets 097.52
Rated values 10 A - 250 V
097.52
097.42
097.00
II-2018,www.findernet.com
14
86 SERIES 86
Sockets and accessories SERIES
Rated current (A)
PEAN
8-way jumper link for 97.01 and 97.02 sockets 095.18 (blue) 095.18.0 (black)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
095.18
II-2018,www.findernet.com
Drying kilns
88
SЕRIES
Industrial
furnaces and
ovens
Industrial
washing
machines
Wood-
processing
machines
Medical and
dentistry
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
88 SERIES 88
Plug-in timers 8 A SERIES
• Multi-function • Multi-function
• 11 pin • 8 pin, 2 timed contacts or
• Plug-in for use with 90 series sockets 1 timed + 1 instantaneous contact
• Plug-in for use with 90 series sockets
AI: On-delay Al a: On-delay (2 timed contacts)
DI: Interval Al b: On-delay (1 timed + 1 instantaneous contact)
GI: Pulse delayed Dl a: Interval (2 timed contacts)
SP: Symmetrical flasher (starting pulse off ) Dl b: Interval (1 timed + 1 instantaneous contact)
without control signal GI: Pulse delayed
SW: Symmetrical flasher (starting pulse on)
P = Pause
S = Start
For outline drawing see page 5 R = Reset
Contact specification
Contact configuration 2 CO (DPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 8/15 8/15
Rated voltage/ H
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 2000 2000
Rated load AC15 (230 V AC) VA 400 400
Single phase motor rating (230 V AC) kW 0.3 0.3
Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12 8/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24…230 24…230
V DC 24…230 24…230
Rated power AC/DC VA (50 Hz)/W 2.5 (230 V)/1 (24 V) 2.5 (230 V)/1.5 (24 V)
Operating range V AC 20.4…264.5 20.4…264.5
V DC 20.4…264.5 20.4…264.5
Technical data
Specified time range (0.05 s…5 h) - (0.05 s…10 h) - (0.05 s…50 h) - (0.05 s…100 h)
Repeatability % ± 1 ± 1
Recovery time ms 300 200
Minimum control impulse ms 50 —
XI-2018,www.findernet.com
3
88 88 SERIES
SERIES Plug-in timers 8 A
• Mono-function • Mono-function
• 8 pin, 2 timed contacts • 8 pin, 2 timed contacts
• Plug-in for use with 90 series sockets • Plug-in for use with 90 series sockets
PI: Asymmetrical flasher (starting pulse OFF) LI: Asymmetrical flasher (starting pulse ON)
4
88 SERIES 88
Plug-in timers 8 A SERIES
Ordering information
Example: 88 series multi-function timer, 2 CO (DPDT) 8 A contacts, (24…230)V AC (50/60 Hz) and (24…230)V DC supply.
8 8 . 0 2 . 0 . 2 3 0 . 0 0 0 2
Series Special versions
Type 0 = Functions PI (starting pulse OFF) for 88.92
0 = Functions AI, DI, GI, 1 = Functions LI (starting pulse ON) for 88.92
SP, BE, CEa, DE, 11 pin 2 = Standard
1 = Functions Al a, Al b, Supply voltage
Dl a, Dl b, GI, SW, 8 pin 230 = (24…230)V AC/DC for 88.02, 88.12
9 = Functions LI, PI, 8 pin 240 = (12…240)V AC/DC for 88.92
No. of poles Codes
2 = 2 pole 88.02.0.230.0002
Supply version 88.12.0.230.0002
0 = AC (50/60 Hz)/DC 88.92.0.240.0000
88.92.0.240.0001
Technical data
EMC specifications
Type of test Reference standard 88.02/88.12 88.92
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 6 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 2 kV —
Surges (1.2/50 μs) on Supply terminals common mode EN 61000-4-5 2 kV —
differential mode EN 61000-4-5 1 kV —
Radio-frequency common mode (0.15 ÷ 80 MHz) on Supply terminals EN 61000-4-6 3 V —
Other data
Power lost to the environment without contact current W 3.4
with rated current W 4.7
Outline drawings
Types 88.02/12 Type 88.92
H
XI-2018,www.findernet.com
5
88 88 SERIES
SERIES Plug-in timers 8 A
Time scales
Full scale value for types 88.02, 88.12 Types 88.02, 88.12
H s min h 10 h F
D A
B E
0.5 0.5 second 0.5 minute 0.5 hour 5 hour
1 1 second 1 minute 1 hour 10 hour
C G
5 5 second 5 minute 5 hour 50 hour
D H
10 10 second 10 minute 10 hour 100 hour
LED/visual indication
Types 88.02, 88.12 Type 88.92
A Yellow LED: power ON (U) A Red LED: pulse ON (T1)
H B Red LED: timing in progress (C) B Green LED: pulse OFF (T2)
C Unit of time selected C Red timing regulator: T1 time setting
D Time scale selector D Unit of time selector: T1 (ON)
E Function selector E Unit of time selector: T2 (OFF)
F Function selected F Green timing regulator: T2 time setting
G Time scale selected G Time scale selected
H Unit of time selector H Time scale selector XI-2018,www.findernet.com
6
88 SERIES 88
Plug-in timers 8 A SERIES
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
7
88 88 SERIES
SERIES Plug-in timers 8 A
(Al b) O
n-delay
(1 timed contact + 1 instantaneous contact).
Apply power to timer. Output contact (C1) transfers immediately.
Contact (C2) transfers after the preset time has elasped.
Reset occurs when power is removed.
8
88 SERIES 88
Plug-in timers 8 A SERIES
Sockets 8-11 pin backwired with solder terminals 90.12.4 (black) 90.13.4 (black)
For timer type 88.12, 88.92 88.02
Technical data
90.13.4
Rated values 10 A - 250 V
Approvals Dielectric strength 2 kV AC
(according to type):
Ambient temperature °C –40…+70
XI-2018,www.findernet.com
Packaging
machines
93
Traffic light SЕRIES
controls
Bottling plant
Carousel
warehouses
Control panels
Labelling
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
93 SERIES 93
Timed socket for 34 series SERIES
Fuse module
093.63
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
For outline drawing see page 5 EE: Interval with control signal off
Contact specification H
Contact configuration
Rated current/Maximum peak current A
Rated voltage/
Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA See 34.51 and 34.81 relays
Electrical life at rated load in AC1 cycles See 34.51 (EMR) and 34.81 (SSR) relays
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
3
93 93 SERIES
SERIES Timed socket for 34 series
Ordering information
Example: type 93.68 multi-function timer module for 34 series relay, screw terminals, (12…24)V AC/DC supply voltage.
9 3 . 6 8 . 0 . 0 2 4
Series Supply voltage
024 = (12…24)V AC/DC
Type
6 = Multi-function Supply version
(AI, DI, GI, SW, BE, CE, DE, EE) 0 = AC (50/60 Hz)/DC
No. of poles
8 = 1 CO (EMR type 34.51), screw terminals
8 = 1 NO (SSR type 34.81), screw terminals
9 = 1 CO (EMR type 34.51), push-in terminals
9 = 1 NO (SSR type 34.81), push-in terminals
4
93 SERIES 93
Timed socket for 34 series SERIES
Input specifications
Input data AC/DC timer
Nominal Operating range Must drop-out Rated input Rated power at UN
voltage (AC/DC) voltage current at UN
UN Umin Umax Ur DC AC DC AC
V V V V mA mA mA mA
12 9.6 13.2 1.2 15 23 0.2 0.3/0.2
24 19.2 26.4 2.4 11 19 0.25 0.4/0.3
Outline drawing
93.68 93.69
Screw terminals Push-in terminal
H
X-2017, www.findernet.com
5
93 93 SERIES
SERIES Timed socket for 34 series
Times scales
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
(0.1…3)s (3…60)s (1…20)min (0.3…6)h
OFF Open
ON Open
ON Closed
(AI) On-delay
Apply power to timer.
Output contacts transfer after preset time has elapsed.
1 2 3 4 5
Reset occurs when power is removed
(DI) Interval
Apply power to timer.
Output contacts transfer immediately.
1 2 3 4 5 After the preset time has elapsed, contacts reset.
• Possible to control an external load, such as ** A voltage other than the supply voltage can be
X-2017, www.findernet.com
another relay coil or timer, connected to the applied to the command Start (B1), example:
control signal terminal B1. A1 - A2 = 24 V AC
B1 - A2 = 12 V DC
6
93 SERIES 93
Accessories for 34 series relays SERIES
Accessories
Output fuse module 093.63
- For 5 x 20 mm fuses up to 6 A, 250 V
- Easy visibility of the fuse condition through the window
- Quick connection to socket
Notes
Safety: Because the output circuit can be reinstated, even with the fuse removed, it is important not to consider the
093.63
removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
Approvals UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse
(according to type): certified according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output
interface to a PLC no such restrictions apply, and the fuse module can be usefully employed.
093.16.0
093.16.1
Approvals
(according to type):
093.60
2. Leaving the ribs in place provides 6.2 mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
Sheet of marker tags, plastic, 48 tags, 6 x 12 mm, for CEMBRE thermal transfer printers 060.48
X-2017, www.findernet.com
060.48
7
93 93 SERIES
SERIES Timed socket for 34 series
Accessories
Terminal doubler (for socket Push-in only) 093.62
Total load 6 A - 300 V
Solid and stranded cable
093.62
Max. wire size mm 2
2 x 1.5
AWG 2 x 16
MasterADAPTER 093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to MasterINTERFACE modules to PLC outputs via
a 14-Pole ribbon cable, plus simple 2-wire power supply connection.
Technical data
Rated current (per signal path) A 1
Minimum required supply power W 3
Nominal voltage (UN) V DC 24
093.68.14.1
Operating range (0.8…1.1)UN
Approvals
Control logic Positive switching (to A1)
(according to type):
Power supply status indication Green LED
Ambient temperature range °C –40…+70
Terminals for 24 V control logic
Type of connector 14 pole, according to IEC 60603-13
Terminals for 24 V power supply
Wire strip length mm 9.5
Screw torque Nm 0.5
Max. wire size
solid wire mm2 1 x 4 / 2 x 1.5
AWG 1 x 12 / 2 x 16
H stranded wire mm2 1 x 2.5 / 2 x 1.5
Connected AWG 1 x 14 / 2 x 16
MasterADAPTER
X-2017, www.findernet.com
Garden and
night lighting
10
NEON Shop displays SЕRIES
Lighting for
parks
Streetlights
and car park
lighting
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
10 SERIES 10
Light dependent relays 12 - 16 A SERIES
Preset threshold lx 10 10
Delay time: switching ON/OFF s 15/30 15/30
Ambient temperature range °C –30…+70 –30…+70
Protection category IP 54 IP 54
Approvals (according to type)
3
10 10 SERIES
SERIES Light dependent relays 12 - 16 A
Preset threshold lx 10 10 10
Delay time: switching ON/OFF s 15/30 15/30 15/30
Ambient temperature range °C –30…+70 –30…+70 –30…+70
Protection category IP 54 IP 54 IP 54
Approvals (according to type)
4
10 SERIES 10
Light dependent relays 12 - 16 A SERIES
Ordering information
Example: 10 series light dependent relay, 2 NO (DPST-NO) 16 A contact, screw terminal connections, 230 V AC supply.
1 0 . 3 2 . 8 . 2 3 0 . 0 0 0 0
Series Supply voltage
Type 120 = 120 V
32 = Double output - 2 NO 16 A 230 = 230 V
41 = Single output - 1 NO 16 A Supply version
42 = Two independent outputs - 2 NO 16 A 8 = AC (50/60 Hz)
51 = Single output - 1 NO 12 A
61 = Mounting on street light body - 1 NO 16 A
Technical data
Insulation 10.32 / 41 / 42 10.51 10.61
Dielectric strength between open contacts V AC 1000 1000 1000
Conducted disturbance immunity
Surge (1.2/50 μs) on L and N (differential mode) kV 4 4 6
Other data
Cable grip Ø mm (8.9…12) (7.5…9) —
Screw torque Nm 0.8 0.8 —
Max. wire size solid cable stranded cable solid cable stranded cable —
mm2 1 x 6 / 2 x 4 1 x 6 / 2 x 2.5 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5 —
AWG 1 x 10 / 2 x 12 1 x 10 / 2 x 14 1 x 10 / 2 x 12 1 x 12 / 2 x 14 —
Output wires
Material — — Silicone rubber UV resistant
Size mm2 — — 1.5
Length mm — — 500, ends-ferruled
Rated insulation voltage kV — — 0.6/1
Max temperature °C — — 120
I
Functions
10.32 / 10.41 / 10.42 10.51
LED*
Supply voltage NO output contact Supply voltage NO output contact
ON Open ON Closed
Open Open
ON ON
(Timing in Progress) (Timing in Progress)
ON Closed — —
* The LED is located under the terminal cover, close to the Lux adjustment knob. It indicates the contact status and assists in the
test and setting of the correct light threshold level.
X-2017, www.findernet.com
5
10 10 SERIES
SERIES Light dependent relays 12 - 16 A
Wiring diagrams
L L
N N
L L
N N
Internal connection
Internal connection
Type 10.42 Type 10.51
L
F = brown wire
N N = blue wire
18 = white wire
Internal connection
Type 10.61
X-2017, www.findernet.com
6
10 SERIES 10
Light dependent relays 12 - 16 A SERIES
Ambient light level as measured by the light dependent relay’s integral light sensor.
Ambient light + controlled light level as measured by the light dependent relay’s integral light sensor.
Notes
1. It is good practice to try to achieve a correct installation where the light emitted from the lamp(s) does not influence the light level seen by the sensor,
although the “light feedback compensation” principle will help when this is not fully achievable. In this case it should be appreciated that the “light
feedback compensation” principle may delay slightly the time of Switch Off - beyond the ideal.
2. The compensation principle is not effective where the combined effect of the ambient light and the controlled lighting exceeds 120 lux.
3. The 10.32 and 10.41 types are compatible with gas discharge lamps that attain full output within 10 minutes, since the electronic circuit monitors
lamps’ light output over a 10 minutes period to achieve a true assessment of its contribution to the overall lighting level.
I
X-2017, www.findernet.com
7
10 10 SERIES
SERIES Light dependent relays 12 - 16 A
Outline drawings
Type 10.32 Type 10.41
Type 10.61
I
X-2017, www.findernet.com
Garden and
night lighting
11
NEON Shop displays SЕRIES
Lighting for
parks
Streetlights and
car park lighting
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
11 SERIES 11
Light dependent relays 12 - 16 A SERIES
3
11 11 SERIES
SERIES Light dependent relays 12 - 16 A
4
11 SERIES 11
Light dependent relays 12 - 16 A SERIES
Ordering information
Example: 11 series light dependent relay with time switch, 1 CO (SPDT) 16 A contact, 230 V AC supply.
1 1 . 9 1 . 8 . 2 3 0 . 0 0 0 0
Series Options
0000 = Standard
Type
3 = 17.5 mm wide Supply voltage
4 = 35 mm wide 024 = 12…24 V (11.31 only)
9 = 35 mm wide, with time switch 230 = 230 V
230 = 110…230 V (11.31 only)
No. of poles 230 = (110…230)V AC/DC (11.91 only)
1 = 1 pole, 16 A
2 = 2 pole, 12 A Supply version
0 = AC (50/60 Hz)/DC (11.31 only)
8 = AC (50/60 Hz)
8 = AC (50/60 Hz)/DC (11.91 only)
Codes
11.31.0.024.0000
11.31.8.230.0000
11.41.8.230.0000
11.42.8.230.0000
11.91.8.230.0000
19.91.9.012.4000
(power module for 11.91 type)
Technical data
Insulation Dielectric strength Impulse (1.2/50 μs)
between supply and contacts 4000 V AC 6 kV
between supply and light sensor 2000 V AC 4 kV
between open contacts 1000 V AC 1.5 kV
EMC specifications
Type of test Reference standard 11.31 11.41 / 42 / 91
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 10 V/m
Fast transients on supply terminals EN 61000-4-4 3 kV 4 kV
(burst 5/50 ns, 5 and 100 kHz) on light sensor connection EN 61000-4-4 3 kV 4 kV
Voltage pulses on supply terminals common mode EN 61000-4-5 4 kV
I
(surge 1.2/50 μs) differential mode EN 61000-4-5 3 kV 4 kV
Radiofrequency common mode voltage on supply terminals EN 61000-4-6 10 V
(0.15…80 MHz) on light sensor EN 61000-4-6 3 V
Voltage dips 70% UN, 40% UN EN 61000-4-11 10 cycles
Short interruptions EN 61000-4-11 10 cycles
Radio frequency conducted emissions 0.15…30 MHz EN 55014 class B
Radiated emissions 30…1000 MHz EN 55014 class B
Terminals
Screw torque Nm 0.8
Max. wire size solid cable 1 x 6 / 2 x 4 mm2 1 x 10 / 2 x 12 AWG
stranded cable 1 x 4 / 2 x 2.5 mm2 1 x 12 / 2 x 14 AWG
Wire strip length mm 9
Other data
Cable grip of light sensor mm 7.5…9
Maximum cable length relay to light sensor m 50 (2 x 1.5 mm2)
II-2018,www.findernet.com
Preset threshold lx 10
Power lost to the environment 11.31 11.41 11.42 11.91
in stand-by W 0.3 1.3 1.4 0.5
without contact current W 0.9 2.0 2.8 2.1
with rated current W 1.7 2.6 3.8 2.7
5
11 11 SERIES
SERIES Light dependent relays 12 - 16 A
Wiring diagrams
Type 11.31 Type 11.42 LL
L/+
N/– NN
A1 A2 21 24
011.02
14 11 12 B1 B2
6
11 SERIES 11
Light dependent relays 12 - 16 A SERIES
OFF threshold
I
Correct functioning - Incorrect functioning where The innovative principle
provided the light sensor the lamps cycle between On of “light feedback
can be shielded from the and Off, because their effect compensation” avoids the
effects of the controlled is being detected by the annoying and damaging
lighting switching light sensor effects of the lamps
On and Off repeatedly “hunting”
between On and Off, due to
poor installation
Ambient light level as measured by the light dependent relay's light sensor.
Ambient light + controlled light level as measured by the light dependent relay's light sensor.
Notes
1. It is good practice to try to achieve a correct installation where the light emitted from the lamp(s) does not influence the light level seen by the light
sensor, although the “light feedback compensation” principle will help when this is not fully achievable. In this case it should be appreciated that the
“light feedback compensation” principle may delay slightly the time of Switch Off - beyond the ideal.
2. The compensation principle is not effective where the combined effect of the ambient light and the controlled lighting exceeds a maximum value
(200 lux for the 11.91, 160/2000 lux for standard/high range of the 11.41).
II-2018,www.findernet.com
3. The 11.41 and 11.91 types are compatible with gas discharge lamps that attain full output within 10 minutes, since the electronic circuit monitors lamps'
light output over a 10 minute period to achieve a true assessment of its contribution to the overall lighting level.
7
11 11 SERIES
SERIES Light dependent relays 12 - 16 A
Functions 11.91
Power-off mode
If the 230 V AC supply is not connected, the relay enters power-off mode and to ensure the long life of the built-in back-up
battery only the clock is maintained active. The display turns off and no other operation (including light measurement) is
performed.
With a press to the joystick during power-off mode it is possible to “awaken” the device and to enter program or set-up
mode (the“electrical plug” symbol is displayed); after about 1 minute inactivity the power-off mode is resumed.
II-2018,www.findernet.com
Note: with the supply not connected, the program or set-up modes absorb a higher current than the power-off mode, thus
influencing the battery life.
8
11 SERIES 11
Light dependent relays 12 - 16 A SERIES
Auxiliary output
A solid state output at terminals Y1-Y2 is provided (rated 12 V DC, 80 mA/1 W max.): this can be used with the power
module 19.91.9.012.4000 connected by the dedicated 011.19 connector. Or, it is possible to connect a suitable relay
(for example, 38-48-49-4C-58-59 interface module) provided the coil is within the rating, and the wiring does not
exceed 40 cm length. The auxiliary output is driven exclusively by the light sensor of the device, and is consequently
independent of the time switch. With the main contact, this permits a flexible lighting system controlled by the ambient
light, both with and without the influence of the time switch function.
11.31/41/42
NO output contact
LED Supply voltage
11.41/11.42 11.31
ON Open Open
ON Closed Closed
9
11 11 SERIES
SERIES Light dependent relays 12 - 16 A
Outline drawings
11.31 11.42
Screw terminal Screw terminal
11.41 11.91
Screw terminal Screw terminal
I
19.91 (power module for 11.91) 11.91 + 19.91 power module
Screw terminal Screw terminal
II-2018,www.findernet.com
11.91 19.91
10
11 SERIES 11
Light dependent relays 12 - 16 A SERIES
Accessories
Light sensor (supplied with light dependent relay) 011.02
- Ambient temperature range: –40…+70 °C
- Cadmium free
- Non polarized
- Double insulated with respect to light dependent relay supply
011.02 - Not compatible with old 11.01 and 11.71 light dependent relay (to be used with 011.00 photosensor)
* ring adaptor
for Ø 18 mm
(Ø 15 mm without adapter)
I
Adaptor for panel mounting (supplied with light dependent relay), 35 mm wide 011.01
011.01
2-pole connector (for type 11.91 and 19.91 power module) 011.19
For direct connection of 11.91 auxiliary
011.19 output (Y1-Y2) to 19.91 supply (A1-A2)
Sheet of marker tags, for types 11.31, 11.41, 11.42, 19.91, plastic, 48 tags, 6 x 12 mm,
060.48
for CEMBRE thermal transfer printers
II-2018,www.findernet.com
060.48
Identification tag, for types 11.41 and 11.42, plastic, 1 tag, 17 x 25.5 mm 019.01
019.01
Please see general technical information 11
Time switches 16 A
Heating and
cooling
Streetlights
and car park
lighting
School bells
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
12 SERIES 12
Time switches 16 A SERIES
Type 12.01
--Daily
--1 CO 16 A
--35.8 mm wide
--35 mm rail mount
Type 12.11
--Daily
--1 NO 16 A
--17.5 mm wide • Mechanical daily time switch • Mechanical daily time switch • Mechanical daily or weekly
--35 mm rail mount • 1 CO 16 A • 1 NO 16 A • 1 CO 16 A
• 35 mm rail (EN 60715) mount • 35 mm rail (EN 60715) mount • Front panel mounting
Type 12.31-0000
--Daily
--1 CO 16 A
--72 x 72 mm
--Front panel mount
Type 12.31-0007
--Weekly
--1 CO 16 A
--72 x 72 mm
--Front panel mount
• Minimum time interval setting:
1 h (12.31-0007)
30 min (12.01)
15 min (12.11 - 12.31-0000)
3
12 12 SERIES
SERIES Time/Astro-Switch 16 A
EAN
OP
Type 12.51 12.51 12.81
R
N T
EU
Digital (analogue-style) time switch, T E
EUR
P A
daily/weekly programming EAN
OP
Accuracy s/day 1 1
–20…+50 (see page 9, –20…+50 (see page 9,
Ambient temperature range °C
diagram L12) diagram L12)
Protection category IP 20 IP 20
Approvals (according to type)
4
12 SERIES 12
Time switches 16 A SERIES
Accuracy s/day 1 1
–20…+50 (see page 9, –20…+50 (see page 9,
Ambient temperature range °C
diagram L12) diagram L12)
Protection category IP 20 IP 20
Approvals (according to type)
5
12 12 SERIES
SERIES Time/Astro-Switch 16 A
Accuracy s/day 1 1
–20…+50 (see page 9, –20…+50 (see page 9,
Ambient temperature range °C
diagram L12) diagram L12)
Protection category IP 20 IP 20
Approvals (according to type)
6
12 SERIES 12
Time switches 16 A SERIES
Ordering information
Example: 12 series digital (analogue style) time switch, 1 CO 16 A contact, (110…230)V AC/DC supply
1 2 . 5 1 . 8 . 2 3 0 . 0 0 0 0
Series Option Option
0 = With power back-up 0 = Standard
Type 1 = Without power back-up 0 = Daily only for 12.31
0 = Daily, 35.8 mm wide (type 12.11) 7 = Weekly only for 12.31
1 = Daily, 17.5 mm wide
3 = Daily or Weekly, 72 x 72 mm Supply voltage Special version
5 = Digital (analogue style), 024 = 24 V AC/DC (type 12.71) 0 = Standard
NFC programming, 35 mm wide 024 = 12…24 V AC/DC
6 = Weekly, NFC programming, (types 12.61, 12.A2)
35 mm wide 120 = 120 V AC
7 = Weekly, 17.5 mm wide 230 = 230 V AC
8 = Astro-switch, NFC programming, 230 = (110…230)V AC/DC
35 mm wide (types 12.51, 12.61, 12.62,
A = Weekly “Astro”, NFC programming, 12.81, 12.A1, 12.A2)
35 mm wide
Supply version
0 = AC (50/60 Hz)/DC
No. of poles
(types 12.61.0.024, 12.A2.0.024, 12.71.0.024)
1 = 1 CO (SPDT), 16 A
8 = AC (50/60 Hz)
1 = 1 NO (SPST), 16 A
8 = AC (50/60 Hz)/DC
2 = 2 CO (DPDT), 16 A
(types 12.51, 12.81, 12.61, 12.62, 12.A1, 12.A2)
Codes
12.01.8.230.0000
12.11.8.230.0000
12.11.8.230.1000
12.31.8.230.0000
12.31.8.230.0007
12.51.8.230.0000
12.71.0.024.0000
12.71.8.230.0000
12.81.8.230.0000
12.61.0.024.0000
12.61.8.230.0000
12.62.8.230.0000
12.A1.8.230.0000
I 12.A2.0.024.0000
12.A2.8.230.0000 XI-2017, www.findernet.com
8
12 SERIES 12
Time switches 16 A SERIES
Technical data
Insulation 12.51, 12.61, 12.62, 12.81, 12.01, 12.11, 12.31, 12.71
12.A1, 12.A2
Dielectric strength between supply and contacts V AC 4000 4000
Dielectric strength between open contacts V AC 1000 1000
Rated impulse voltage (between supply and contacts) kV/(1.2/50)μs 6 6
Rated impulse voltage (between open contacts) kV/(1.2/50)μs 1.5 1.5
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 6 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst 5/50 ns, 5 and 100 kHz) EN 61000-4-4 4 kV 4 kV
Voltage pulses on supply common mode EN 61000-4-5 4 kV 2 kV
terminals (surge 1.2/50 μs) differential mode EN 61000-4-5 4 kV 2 kV
Radiofrequency common mode voltage (0.15…80 MHz) EN 61000-4-6 10 V 10 V
Voltage dips 70% UN , 40% UN EN 61000-4-11 10 cycles 10 cycles
Short interruptions EN 61000-4-11 10 cycles 10 cycles
Radio frequency conducted emissions 0.15…30 MHz EN 55014 class B class B
Radiated emissions 30…1000 MHz EN 55014 class B class B
Terminals
Screw torque Nm 0.8 1.2
Max. wire size mm2 AWG mm2 AWG
solid cable 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 x 6 / 2 x 4 1 x 10 / 2 x 12
stranded cable 1 x 4 / 2 x 2.5 1 x 12 / 2 x 14 1 x 6 / 2 x 2.5 1 x 10 / 2 x 14
Wire strip length mm 9
Other data
Power back-up (Battery life) 6 years (12.51, 12.61, 12.62, 12.81, 12.A1, 12.A2, 12.71)
Battery type CR 2032, 3 V, 230 mAh (12.51, 12.61, 12.62, 12.81, 12.A1, 12.A2)
Power back-up 100 h (12.01, 12.11, 12.31 - following 80 h continuous energisation)
12.51, 12.61, 12.62, 12.A2 12.01, 12.11, 12.71
Power lost to the environment
12.81, 12.A1 12.31
in stand-by W 0.2 0.2 — —
I
without contact current W 0.9 0.9 1.5 2
with rated current W 1.5 2.1 2.5 3 (for 1 pole)
1 pole
2 pole
XI-2017, www.findernet.com
9
12 12 SERIES
SERIES Time switches 16 A
Wiring diagrams
L L
N N
L L
N N
Type 12.71
I Type 12.31
N
XI-2017, www.findernet.com
Type 12.51
12.81
10
12 SERIES 12
Time switches 16 A SERIES
Wiring diagrams
L/+ L/+
N/– N/–
Type 12.61
12.A1
Type 12.62
12.A2
I
XI-2017, www.findernet.com
11
12 12 SERIES
SERIES Time switches 16 A
Two programming modes for type 12.51, 12.61, 12.62, 12.81, 12.A1, 12.A2
“Smart” “Classic”
Android, Google Play and the Google Play logo are trademarks of Google Inc.
1 ccording to the clock off-time , and then turns back on at the clock on-time
(for the remainder of the ASTRO time period). Application example: company car park
lighting, on by AstroON at sunset, off end of the evening shift at 23:00 .
2
On again at the beginning of the morning shift at 5:00 and off automatically by
AstroOFF*.
3 * Depending on the time of year (summer specifically) it may be that the override ON time
will fall after the AstroOFF time. In this case, the output switches off at the AstroOFF time
and the override ON time is ignored.
XI-2017, www.findernet.com
12
12 SERIES 12
Time switches 16 A SERIES
Outline drawings
12.01 12.11
Screw terminal Screw terminal
12.31 12.51/12.81
Screw terminal Screw terminal
I
12.71
Screw terminal
XI-2017, www.findernet.com
13
12 12 SERIES
SERIES Time switches 16 A
Outline drawings
12.61 / 12.A1 12.62 / 12.A2
Screw terminal Screw terminal
Power-save mode
If the 230 V AC supply is not connected, the time switch enters power-save mode: only the clock is
I maintained active whilst the display turns off so as to guarantee a long life for the built-in back-up battery.
With a press to the joystick it is possible to “awake” the device and enter Display mode (with the “plug” symbol
displayed). A further press to will enter the program or set-up mode as explained in the Display mode
section above.
After about 1 minute of inactivity the power-save mode will start again. During program or set-up the current
absorption is higher than in power-save mode, thus influencing the battery life.
In this mode the display back-light is not active. It is activated following a press to the joystick only with the
230 V AC supply connected, but after about 1 minute of inactivity the display back-light will turn off, and to
activate it again it is necessary to press the joystick again.
Note: the output relay only functions if the power supply is connected.
011.01
14
SЕRIES
Staircase
light control
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
14 SERIES 14
Electronic staircase timers16 A SERIES
3
14 14 SERIES
SERIES Electronic staircase timers16 A
4
14 SERIES 14
Electronic staircase timers16 A SERIES
Ordering information
Example: 14 series multi-function timer, 1 NO (SPDT-NO) 16 A contact, supply rated at 230 V AC.
1 4 . 0 1 . 8 . 2 3 0 . 0 0 0 0
Series Supply voltage
120 = 110…125 V AC (14.81 only)
Type 230 = 230 V
0 = 35 mm rail (EN 60715) mount,
8 functions Supply version
7 = 35 mm rail (EN 60715) mount, 8 = AC (50/60 Hz)
3 functions
8 = 35 mm rail (EN 60715) mount,
mono-function, all terminals on
same side
9 = 35 mm rail (EN 60715) mount,
mono-function, 3 terminals
No. of poles
1 = 1 NO 16 A contact
Technical data
Insulation
Dielectric strength between open contacts V AC 1000
Other data
Power lost to the environment
without contact current W 1.2
with rated current W 2
Maximum cable length for push-button connection m 200
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm2 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Note
Using the type 14.91, the lamps are switched on directly by the push-button
Accessories
Adaptor for panel mounting, 17.5 mm wide 020.01
020.01
XII-2018, www.findernet.com
Sheet of marker tags (CEMBRE Thermal transfer printers), plastic, 48 tags, 6 x 12 mm 060.48
060.48
5
14 14 SERIES
SERIES Electronic staircase timers16 A
Wiring diagrams
Type 14.01
14.71
Red LED indication:
Continuous = relay ON
Blinking = relay OFF
L L
N N
L L
N N
Type 14.91 (the push-buttons must be rated for the load current)
N
XII-2018, www.findernet.com
6
14 SERIES 14
Electronic staircase timers16 A SERIES
Wiring diagrams - 14.01 or 14.71 without Staircase maintenance function, triggered by PIR movement detector (18 series).
3 wire connection (with 18.21.8.230.0300 or 18.31.8.230.0300 only) 4 wire connection (with 18.21.8.230.0300 or 18.31.8.230.0300 only)
L L
N N
I
XII-2018, www.findernet.com
7
14 14 SERIES
SERIES Electronic staircase timers16 A
Functions
Type 14.01 Functions selectable with front rotary selector
(BE) Staircase timer
On initial impulse the output contact closes and timing starts for the pre-set duration;
subsequent impulses during the timing period will extend the timing period by the full
pre-set value.
On expiry of the time delay, the output contact opens.
BE
BP
I cleaning activities. The 60 minute timing can be interrupted by a further impulse of ≥ 5 seconds,
and the output contact then opens
Light ON
With this function set - the output contact stays permanently closed.
XII-2018, www.findernet.com
NOTE: The blinking within the Early Warning functions (BP and IP) could cause re-start problems for fluorescent lamps with electromagnetic chokes
(both conventional and compact types); We consequently suggest not to use such lamps with these functions.
8
14 SERIES 14
Electronic staircase timers16 A SERIES
Functions
Type 14.71 Functions selectable with front selector
Light ON
Staircase timer
On initial impulse the output contact closes and timing starts for the pre-set
duration; subsequent impulses during the timing period will extend the timing
period by the full pre-set value.
On expiry of the time delay, the output contact opens.
Staircase maintenance
An impulse of ≥ 5 seconds will close the output contact for 60 minutes, after
which time the contact will open. Ideal for maintenance or cleaning activities.
The 60’ timing can be interrupted by a further impulse of ≥ 5 seconds,
the output contact opens.
Light ON
With this function set - the output contact stays permanently closed.
Type 14.81
Staircase timer
On initial impulse the output contact closes and timing starts for the pre-set
duration; subsequent impulses during the timing period will extend the timing
period by the full pre-set value.
On expiry of the time delay, the output contact opens.
Type 14.91
Signal ON pulse
On initial impulse the output contact closes, and remain so for the duration of
the preset delay. On expiry of the time delay, the output contact opens.
XII-2018, www.findernet.com
9
14 14 SERIES
SERIES Electronic staircase timers16 A
Outline drawings
Type 14.01 Type 14.71
Screw terminal Screw terminal
59.5
33.8
45
84
88.8
30.5
Type 14.81 Type 14.91
Screw terminal Screw terminal
45
84
88.8
I
30.5
XII-2018, www.findernet.com
Kitchen
light control
15
Bedroom SЕRIES
light control
Living room
light control
Lighting control
in corridors
(for hotels, offices
and hospitals)
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
15 SERIES 15
Dimmers SERIES
Select “transformer” (
(3)
) position on the front selector. Preferably, no more than 2 transformers.
(4)
One transformer only.
(5)
Select “CFL” ( ) position on the front selector, and set the appropriate minimum dimming value (dependent on lamp type).
II-2019, www.findernet.com
(6)
Only if lamps or electronic transformers are compatible with leading edge method.
(7)
Only if lamps or electronic transformers are compatible with trailing edge method.
(8)
Specific 60 Hz version available (see ordering information).
(9)
It is not recommended to mount more than one dimmer in the same wall box, unless adequate ventilation is provided or the lamp load is less
than 100 W (15.51) or 50 W (15.91).
(10)
With lamp load > 300 W (> 75 W for CFL or LED lamps), adequate ventilation must be provided - a gap of 9 mm on both side of the dimmer is
suggested. Use the plastic separator type 022.09.
Not compatible with illuminated push-buttons.
4
15 SERIES 15
YESLY Dimmers SERIES
5
15 15 SERIES
SERIES Dimmers
Ordering information
Example: type 15.71, YESLY Bluetooth dimmer, 230 V AC.
1 5 . 7 1 . 8 . 2 3 0 . B 2 0 0
Series Transmission 0 = Standard
protocol 0 = Type 15.71 white
Type B = Bluetooth 4.2 Low 2 = Type 15.71 anthracite gray
1 = Master / slave, 35 mm rail (EN 60715) Energy (BLE) 4 = Only for 15.51 linear dimming
mount, 17.5 mm wide 0 = Standard
AC input frequency
2 = YESLY - round wall box mounting
0 = 50 Hz (15.51)
5 = Panel or wall box mount Supply voltage
50/60 Hz (15.11/71/81/91)
7 = YESLY - wall mounting residential 230 = 230 V
1 = 50/60 Hz (15.10)
switch boxes like AVE, Bticino, Gewiss, 230 = 110…230 V
6 = 60 Hz (15.51)
Simon-Urmet, Vimar (only for 15.10)
8 = 35 mm rail (EN 60715) mount, Output power
17.5 mm wide, for energy saving lamps Supply version 0 = 100 W (15.91)
9 = Wall box mount, for LED lamps 8 = AC 2 = 200 W (15.71)
3 = 300 W (15.21)
No. of poles 4 = 400 W (15.51,15.11)
0 = 0-10 V output (only for 15.10) 5 = 500 W (15.81)
1 = 1 output Available Codes
15.10.8.230.0010 master dimmer, 50/60 Hz
15.11.8.230.0400 slave dimmer, 50/60 Hz
15.21.8.230.B300 YESLY BLE Dimmer - 300 W, White
15.51.8.230.0400 step dimming, 50 Hz
15.51.8.230.0404 linear dimming, 50 Hz
15.51.8.230.0460 step dimming, 60 Hz
15.71.8.230.B200 YESLY BLE Dimmer - 200 W, White
15.71.8.230.B202 YESLY BLE Dimmer - 200 W, Anthracite
15.81.8.230.0500 linear dimming, 50/60 Hz
15.91.8.230.0000 linear dimming, 50/60 Hz
Technical data
EMC specifications
Type of test Reference standard 15.51/15.91 15.10/11/81 15.21/15.71
contact discharge EN 61000-4-2 4 kV 4 kV
Electrostatic discharge
air discharge EN 61000-4-2 8 kV 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 3 V/m 10 V/m 10 V/m
Power lost to the environment without load W 0.5 0.5 0.4 0.7 0.4 0.5 0.4
with rated load W 1.7 2.5 2.5 2.2 2 2.6 1.2
Max cable length for push-button connection m 100 100 100 100 100 100 100
Max cable length for Master and Slaves connection m 100 (keep separate from power cables)
6
15 SERIES 15
Dimmers SERIES
Operating mode with memory: the previous light level is memorized, specific
15.10 for CFL Lamp.
Long control pulse: The light level is progressively raised or lowered in linear way. The
lowest value dependent on the “minimum dimming level” regulator setting (on 15.11).
Short control pulse: Alternately switches between On and Off. When switching On,
the light level reach the full value for a very short time (in order to guarantee the correct
lamp turn-on), then immediately assumes the value set during the previous On state.
• Dimmable compact fluorescent lamps (CFL) It is suggested to initially set the “minimum
• Dimmable LED lamps dimming level” at an intermediate value and
then if necessary, readjust for a level found to be
compatible with the lamp being used.
(Leading Edge)
II-2019, www.findernet.com
• 12/24 V halogen lamps with toroidal or E-core It is suggested to set the “minimum dimming level”
electromagnetic transformer at the lowest value, so that the complete dimming
range is available. But if it is necessary to avoid too
low a level of illumination, a higher value can be set.
(Leading Edge)
7
15 15 SERIES
SERIES Dimmers
15.51…0400 Operating mode 2 (without memory): on switch off, the light level is not memorized.
I
Operating mode setup
Type 15.51 Type 15.91
On 15.51 operating mode 1 or 3 (with memory) is preset, but it is possible to On 15.91 operating mode 4 (without memory) is preset, but it is
change it using the following sequence: possible to change it using the following sequence:
a) remove the supply voltage; a) remove the supply voltage;
b) press the control button; b) press the control button;
c) apply the supply to the relay, keeping the button closed for 3 second; c) apply the supply to the relay, keeping the button closed for 3 second;
d) o n button release, the light will flash twice to indicate the selection of operating d) on button release, the light will flash twice to indicate the selection of
mode 2 or 4, or flash once for operating mode 1 or 3. operating mode 3, or flash once for operating mode 4.
Repeating the above steps will alternately change between operating modes. Repeating the above steps will alternately change between operating
modes.
II-2019, www.findernet.com
8
15 SERIES 15
Dimmers SERIES
Type 15.81
Thermal protection and signaling
LED (15.81 type only) Supply voltage Thermal protection ALARM
The internal thermal protection (active on all dimmer types)
OFF — will detect an unsafe temperature, due to overload or incorrect
installation, and will turn the dimmer output off.
ON — It is possible to turn the dimmer on, by push button, only when
the temperature reduces to a safe level (after 1 to 10 minutes,
ON ALARM depending on installation conditions) and after removing the
cause of the overload.
Functions
Type Linear dimming
Operating mode without memory: at switch-off, the
light level is not memorized.
Light dimming is realized with “phase cutting technology”, which works by “cutting off” part of the mains voltage waveform in order to reduce the RMS
voltage fed to the lamp. When the “cut off” part is at the beginning of each half cycle the dimming method is called Leading Edge. When it is towards
the end of each half cycle, it is called Trailing Edge. These 2 methods are suitable for dimming different lamp types: Trailing Edge is, in general, more
suitable for electronic transformers for low voltage lamps (halogen or LED). Leading Edge is better suited for electromagnetic transformers for LV lamps,
230 V CFL and 230 V LED lamps. Both methods are, however, suitable for dimming 230 V halogen and incandescent lamps.
In consideration of the different lamp types actually available on the market, it is suggested to refer to the technical specification indicated in page 3
and, if given, to the lamp manufacturer’s recommendation.
9
15 15 SERIES
SERIES YESLY Dimmers
Functions
Settable via App.
LED Exponential
3 TE Trailing Edge
LED
4 LE Leading Edge
6 LE Leading Edge
AUTO AUTOMATIC
AUTO: the automatic function verifies with a special algorithm the driving method (Trailing edge or Leading edge) best suited to the applied load. If the
AUTO function is selected, the dimmer carries out a check switching on the load with two working cycles each time the dimmer is powered from the
L & N (even after a blackout). These cycles allow the dimmer to set the right driving method.
Control curve: the Linear or Exponential control curve is useful in achieving the most visually appealing change in light intensity - according to the type
of load being used.
Parameters
Settable via Finder TOOLBOX App.
Minimum light value: Minimum value of load intensity.
Switch time: Switching ON/OFF time.
I Regulation time: Time to reach the highest or lower light value.
Scene time: Reaching the value recalled by a scenario.
Memory: Remembers the brightness value before power off.
Restore after blackout: Restoring the light intensity to the value prior to a loss of power.
II-2019, www.findernet.com
10
15 SERIES 15
Dimmers SERIES
The 0 - 10 V output signal terminals Yout + / Yout of the “Master Dimmer” must be connected to
M
5”(10’)
Dimming speed
(BP:T)
ON/ALLARM
(ϑ PROT.)
Minimum
ON/ALLARM
(ϑ PROT.)
Minimum
ON/ALLARM
(ϑ PROT.)
Minimum
ON/ALLARM
(ϑ PROT.)
Minimum
terminals + Yin / Yin of one or more 15.11.8.230.0400, called the “Slave Dimmers”, which have the
1”(0.5”) 10”(20’)
− + − + − + − +
task of changing the voltage applied to the lamps and therefore their brightness.
15.10.8.230.0010 15.11.8.230.0400 15.11.8.230.0400 15.11.8.230.0400 15.11.8.230.0400
Master Dimmer Slave Dimmer Slave Dimmer Slave Dimmer Slave Dimmer
UN 230V~(50-60Hz) UN 230V~(50-60Hz) UN 230V~(50-60Hz) UN 230V~(50-60Hz) UN 230V~(50-60Hz)
400 W max 400 W max 400 W max 400 W max
14 6A 230V LED 100W max
3W min
LED 100W max
3W min
LED 100W max
3W min
LED 100W max
3W min The result is a flexible system that offers a range of solutions from the minimum configuration of a
Master Dimmer and a Slave Dimmer, up to the maximum configuration of a Master Dimmer and 32
N L N L N L N L N L
Slave Dimmers.
3 14 4 4 4 4 4 4 4 4
Each slave can drive a different lamp type, depending on the appropriate methodology, “Leading
MASTER SLAVE SLAVE SLAVE Edge” or “Trailing Edge”. It can regulate halogen lamps, dimmable LED lamps, dimmable CFL lamps,
electronic transformers, and electromagnetic transformers.
For example, one Master Dimmer can control a Slave Dimmer with LED lamps and at the same time
a second Slave Dimmer with halogen lamps, and a third with electronic transformers.
/
M
1 Supply to Ballast
$OLPHQWDWRUHR%DOODVW
99
M
Dimming speed ON/ALLARM ON/ALLARM
5”(10’) Dimming speed
( PROT.) ( PROT.) 5”(10’)
(BP:T) Minimum Minimum
(BP:T)
/
Master Dimmer
UN 230V~(50-60Hz) UN 230V~(50-60Hz) Master Dimmer
UN 230V~(50-60Hz)
UN 230V~(50-60Hz)
400 W max 400 W max
1 Supply to Ballast
$OLPHQWDWRUHR%DOODVW
14 6A 230V LED 100W max LED 100W max
14 6A 230V
3W min 3W min
99
y
N L N L N L N L
3 14 4 4 4 4 3 14
/
1 Supply to Ballast
$OLPHQWDWRUHR%DOODVW
99
y
L L
N N
MASTER DIMMER TYPE 15.10 AND SLAVE DIMMER TYPE 15.11 MASTER DIMMER + 0 - 10 V ELECTRONIC TRANSFORMER OR BALLAST
It is recommended that the Master controls from one to a maximum of 32 Using only the Master Dimmer it is possible to control electronic transformers
Slave units. or ballasts with a 0 - 10 V / 1 - 10 V input (observing correct polarity).
The push-buttons (including illuminated push-buttons Max. 15) serve as the For 1 - 10 V applications it is suggested to supply the Ballast Live from
ON / OFF (momentary push), or when pressed for a longer time they adjust terminal 14. This will ensure that the supply to the Ballast is cut-off for a
the brightness level. signal < 1 V. I
Each Slave can drive a different load type. Note: Check that the maximum Peak Current of the Ballast does not
exceed the 30 A 230 V AC rating of terminal 14. Use a contactor or power
relay to switch loads exceeding this value.
0-10V 0 -10V
5HJRODWRUH
Control ON/ALLARM
( PROT.)
ON/ALLARM
( PROT.)
9
Minimum Minimum
− + − +
15.11.8.230.0400 15.11.8.230.0400
Slave Dimmer Slave Dimmer
UN 230V~(50-60Hz) UN 230V~(50-60Hz)
400 W max 400 W max
LED 100W max LED 100W max
3W min 3W min
N L N L
4 4 4 4
L
II-2019, www.findernet.com
N
BMS 0 - 10 V OUTPUTS + SLAVE DIMMERS
In the case of Home Automation or Building Automation systems you can use
just the Slave Dimmer Type 15.11 directly controlled by the 0 - 10 V output of
the building management system (BMS), or by 0 - 10 V rotary regulators.
11
15 15 SERIES
SERIES Dimmers
N N
N N
N N
N N
II-2019, www.findernet.com
12
15 SERIES 15
Dimmers SERIES
Outline drawings
Type 15.51 Type 15.91
Screw terminal Screw terminal
Type 15.81
Screw terminal
13
15 15 SERIES
SERIES Dimmers
Accessories
Adaptor for panel mounting for types 15.10, 15.11 and 15.81, plastic, 17.5 mm wide 020.01
020.01
Separator for rail mounting, plastic, 9 mm wide for types 15.10, 15.11 and 15.81 022.09
022.09
Sheet of marker tags for types 15.10, 15.11 and 15.81, plastic, 48 tags, 6 x 12 mm 060.48
060.48
O
PEAN 8-way jumper link for type 15.10 and 15.11 connection, 17.5 mm wide 022.18 (blue)
EUR
T
T E
N
Rated values 10 A - 250 V
EUR
P A O
PEAN
022.18
I
II-2019, www.findernet.com
Hotel room
energy-enabling
units
Lighting control
in corridors (for
hotels, offices
and hospitals)
Offices,
swimming
18
SЕRIES
baths and
schools
Staircase light
control
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
18 SERIES 18
PIR movement detectors 10 A SERIES
3
18 18 SERIES
SERIES PIR movement detectors 10 A
4
18 SERIES 18
PIR movement detectors 10 A SERIES
18.21…0300/18.31…0300
Screw terminal
5
18 18 SERIES
SERIES PIR movement and presence detectors 10 A
6
18 SERIES 18
PIR movement and presence detectors DALI and KNX SERIES
7
18 18 SERIES
SERIES PIR movement detectors 10 A
8
18 SERIES 18
PIR movement detectors 10 A SERIES
9
18 18 SERIES
SERIES PIR movement and presence detectors 10 A
Ordering information
Example: 18 series, PIR movement detector for internal installations, wall mounting, 1 NO 10 A contact, 120…230 V AC supply.
1 8 . 0 1 . 8 . 2 3 0 . 0 0 0 0
Series Program Special version
Type 0 = Standard 31 = High ceilings,
0 = Internal installation - wall mounting B=B luetooth (30 s…35 min)
1 = External installations programming 40 = Push-button
2 = Internal ceiling installation - surface Contact circuit connection
mounting 0 = Voltage output (only 18.51)
3 = Internal ceiling installation - recessed 3 = Volt-free output contact 40 = Push-button
mounting connection, white
Supply voltage
4 = PIR movement detector for corridors color (only 18.91)
024 = 24 V AC/DC for types 18.21/31-0300 only
5 = PIR movement and presence detector 42 = Push-button
030 = KNX Bus
6 = PIR movement detector wall mounting connection, black
230 = 120…230 V for types 18.01, 18.11, 18.21,
9 = PIR movement detector wall mounting color (only 18.91)
18.31
residential switch boxes 230 = 110…230 V for types 18.A1, 18.41, 18.51,
A = External installations IP 55, push-in 18.51.B300, 18.61, 18.5D
terminals 230 = 230 V for type 18.91
Supply version
0 = AC (50/60 Hz)/DC (24 V only)
8 = AC (50/60 Hz)
9 = DC
No. of poles/Output
1 = Single pole switching 1 NO (SPST-NO), 10 A
D = PIR movement and presence detector with
DALI interface
K=P IR movement and presence detector with KNX
interface
Codes
18.01.8.230.0000 18.31.0.024.0300 18.41.8.230.0300
18.11.8.230.0000 18.31.8.230.0000 18.51.8.230.0300
18.21.0.024.0300 18.31.8.230.0300 18.51.8.230.0040
18.21.8.230.0000 18.31.8.230.0031 18.51.8.230.B300
18.21.8.230.0300 18.61.8.230.0300
18.91.8.230.0040
18.91.8.230.0042
18.A1.8.230.0000
18.5D.8.230.0000
18.4K.9.030.0000
18.5K.9.030.0000
J
VII-2019, www.findernet.com
10
18 SERIES 18
PIR movement and presence detectors 10 A SERIES
Technical data
Insulation
Dielectric strength between open contactsV AC 1000 (except for type 18.91 TRIAC output)
Between supply and contact V AC 1500 (types 18.21…0300, 18.31…0300, 18.41, 1851, 18.61)
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80…2000 MHz) EN 61000-4-3 3 V/m
Fast transients (burst 5/50 ns, 5 and 100 kHz) on supply terminals EN 61000-4-4 1 kV
Voltage pulses on supply terminals common mode EN 61000-4-5 4 kV (2 kV for 18.91)
(surge 1.2/50 µs) differential mode EN 61000-4-5 4 kV (2.5 kV for 18.01/11, 1 kV for 18.91)
Radiofrequency common mode
voltage (0.15…230 MHz) on supply terminals EN 61000-4-6 3 V
Voltage dips 70% UN , 40% UN EN 61000-4-11 10 cycles
Short interruptions EN 61000-4-11 10 cycles
Radiofrequency conducted emissions (0.15…30)MHz EN 55014 class B
Radiated emissions (30…1000)MHz EN 55014 class B
18.01, 18.11, 18.21, 18.41, 18.51, 18.51…B300,
Terminals
18.31,18.91 18.61, 18.A1
Type Screw terminal Push-in (see pag. 18)
Screw torque Nm 0.5 —
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5 2.5 2.5
AWG 1 x 10 / 2 x 12 1 x 12 / 2 x 14 14 14
Wire strip length mm 9 9 8 8
Other data
Power lost to the environment without output current W 0.3
with rated output current W 1.4
• Following the initial power-on, and power-on following a power interruption, the detector makes a hardware-software initialisation for approximately
30 seconds. However, the behavior of the output during this 30 seconds will depend on certain circumstances:
--If the detector was in the On state before the power interruption, and if the lighting level is (currently) below the pre-set threshold, then the output
contact will immediately close when the power is re-applied, for the time delay set by the potentiometer (irrespective of whether movement is being
detected).
--If the detector was in the Off state before the power interruption, or if the ambient light is currently over the pre-set threshold, then the detector will
not switch-on until the end of the initialisation phase (assuming movement is then detected).
J
VII-2019, www.findernet.com
11
18 18 SERIES
SERIES PIR movement and presence detectors 10 A
Wiring diagram
Type 18.01/18.11 Type 18.21/18.31/18.31…0031 Type 18.21-0300/18.31-0300
L L L
N N N
2 1 2 1
1 2
N N N
2 2 2
1 3 1 3
1 3
L
N
12
18 SERIES 18
PIR movement and presence detectors 10 A SERIES
Wiring diagram
Type
Type 18.01/18.11 Type 18.01/18.21
18.21/18.31/18.31…0031
L L L
N N N
Finder Toolbox
Android, Google Play and the Google Play logo are trademarks of Google Inc.
Apple is a trademark of Apple Inc. App Store is a service mark of Apple Inc.
J
VII-2019, www.findernet.com
13
18 18 SERIES
SERIES PIR movement and presence detectors 10 A
Functions
Type Functions
18.51…0040
Lux
Movement
Push-button function
A control pulse on the push-button inverts the status of the output relay, until the timing after the last movement detected is elapsed.
Dynamic Light Compensation
By incorporating Finder’s Patented “light feedback compensation” principle, the 18.51…0040 is able to calculate the artificial light contributed by
the lamps controlled by the output relay. In effect, this means the 18.51…0040 is able to continuously monitor the natural ambient light level,
even when the output is On. As a consequence, whenever the natural light level exceeds the threshold setting the output is forced Off.
This can significantly minimises the time the lighting is On, particularly where there is a high level of traffic - and cost savings can be considerable.
This is an advance over other types of movement detectors, which are unable to identify the natural ambient light level when the output is On
and so can only turn Off after the time delay that follows the last detected movement. In busy areas this may mean that the movement detector
is being continuously re-triggered and maintained in the On state, even though the natural light level has long risen above the threshold.
18.5D Comfort - Daylight-linked constant light level
control
Lux
Adjusts to maintain a constant brightness level
considering the detection of movement and the
level of daylight - increasing or decreasing the
power of the artificial light as appropriate.
Movement Suitable for small offices, classrooms or workplaces.
This allows considerable energy saving while
100% maintaining a comfortable level of illumination.
OFF
100%
50%
OFF
Movement
14
18 SERIES 18
PIR movement and presence detectors 10 A SERIES
Sensing area
18.01, 18.11, 18.A1 - Wall mounting 18.01, 18.11 - Ceiling mounting
18.21, 18.31 - Ceiling mounting 18.31…0031 - Internal ceiling installation, 18.31…0031 - High ceilings installations
surface mounting
18.91
Outline drawings
Type Suspended ceiling mounting Recess mounting Surface mounting
18.21
18.31
18.31…0031
18.41
31.6
43.6
18.51
18.5D
18.51…B300
18.4K
18.5K
VII-2019, www.findernet.com
18.61
16
18 SERIES 18
PIR movement and presence detectors 10 A SERIES
Outline drawings
Type 18.01
Type 18.11
Type 18.A1
Type 18.91
VII-2019, www.findernet.com
17
18 18 SERIES
SERIES PIR movement detectors 10 A
A B C
1
1 2 2
The terminals are equipped with a test hole to take a test probe.
J
VII-2019, www.findernet.com
Bathroom
lighting control
Bedroom
light control
Living room
light control
13
SЕRIES
Office lighting
control
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
13 SERIES 13
Quiet electronic step relays 10 - 16 A SERIES
3
13 13 SERIES
SERIES Electronic step/monostable relays 16 A
4
13 SERIES 13
Electronic call & reset relays and monostable relays 8 - 12 A SERIES
13.11 - Call & Reset Relay - Rail mount - 1 Pole 13.11 13.12 13.31
13.12 - Call & Reset Relay - Rail mount - 2 Pole
13.31 - Electromechanical monostable relay
Switch box mount - 1 Pole
• Call relay with reset command suitable for
residential and commercial applications: public
bathroom, hospital, hotel (type 13.11/13.12)
• Can be mounted behind blanking plates, as
widely used in residential wiring systems such
as; BTicino: Axolute, Matix, Living e Magic,
Gewiss: GW24, Vimar: Plana e Idea … (13.31)
• 35 mm rail (EN 60715) or flange mount • 1 CO (SPDT) • 1 CO (SPDT) + 1 NO (SPST-NO) • 1 NO (SPST-NO)
(13.11 and 13.12) • Call relay with reset command • Call relay with reset command • Interposing monostable relay
• Cadmium free contact material (13.31) • 35 mm rail (EN 60715) mount • 35 mm rail (EN 60715) mount • For mounting within
• 17.5 mm wide • 17.5 mm wide residential switch boxes
13.11/12/31
Screw terminals
5
13 13 SERIES
SERIES YESLY Electronic Relays and Actuators
6
13 SERIES 13
Electronic Relays and Actuators SERIES
Ordering information
Example: Multifunction relay with YESLY Bluetooth, 2 contacts 6 A NO (SPST-NO), 230 V AC supply.
A B C D
1 3 . 7 2 . 8 . 2 3 0 . B 0 0 0
0 = Type 13.72 white
2 = Type 13.72 anthracite gray
Series A: Transmission protocol
Type (only for Type 13.22/S2/72)
0 = Step/Monostable, 35 mm rail B = Bluetooth 4.2 Low Energy
(EN 60715) mount, 35 mm wide
1 = Call & Reset relay, 35 mm rail A: Contacts material
(EN 60715) mount, 17.5 mm wide 0 = Standard
2 = YESLY - multifuction relay, 4 = Standard AgSnO2 (only for 13.31)
wall box mounting
3 = Monostable relay, switch box B: Contact circuit
mounting 0 = Standard
6 = Multifunction relay, 35 mm rail 3 = Standard NO (only for 13.31)
(EN 60715) mount, 17.5 mm wide
7 = YESLY - Multifunction relay compatible Codes / Supply voltage
with the most popular Italian wall 13.01.0.012.0000 12 V AC/DC
switch systems: AVE, BTicino, Gewiss, 13.01.0.024.0000 24 V AC/DC
Simon-Urmet, Vimar 13.01.8.125.0000 110…125 V AC
8 = Modular step relay, 35 mm rail 13.01.8.230.0000 230…240 V AC
(EN 60715) mount, 17.5 mm wide 13.11.8.230.0000 230…240 V AC
9 = Step relay and timing step relay, 13.12.0.012.0000 12 V AC/DC
switch box mounting 13.12.0.024.0000 24 V AC/DC
S = YESLY - Shutter/blind/curtain actuator, 13.22.8.230.B000 230 V AC YESLY
wall box mounting 13.S2.8.230.B000 230 V AC YESLY
No. of poles 13.31.8.012.4300 12 V AC
1 = 1 pole 13.31.9.024.4300 24 V DC
2 = 2 poles 6 A NO (SPST-NO) 13.31.8.230.4300 230 V AC
(type 13.72 and 13.22/S2) 13.61.8.230.0000 110…240 V AC
2 = 1 pole CO (SPDT) + 1 NO (SPST-NO) 13.61.0.024.0000 12…24 V AC/DC
Supply version 13.72.8.230.B000 YESLY BLE white
0 = AC (50/60 Hz)/DC 13.72.8.230.B002 YESLY BLE anthracite gray
8 = AC (50/60 Hz) 13.81.8.230.0000 230 V AC
9 = DC 13.91.8.230.0000 230 V AC
Supply voltage
012 = 1 2 V AC/DC (13.01 and 13.12 only)
012 = 1 2 V AC (13.31 only)
024 = 2 4 V AC/DC (13.01 and 13.12 only)
024 = 2 4 V DC (13.31 only)
024 = 1 2…24 V AC/DC (13.61 only)
125 = ( 110…125)V AC (13.01 only)
230 = ( 230…240)V AC (13.01 and 13.11)
230 = 1 10…240 V AC (13.61 only)
230 = 230 V AC (13.31, 13.22, 13.S2, 13.72, 13.81 and 13.91)
Technical data
Insulation 13.01.8 13.01.0 13.11 - 13.12 13.31 - 13.61 13.81 - 13.91
Dielectric strength
between control circuit and supply V AC 4000 — — — —
between control circuit and contacts V AC 4000 4000 — — —
between R-S-A2 and contacts V AC — — 2000 — —
between supply and contacts V AC 4000 4000 — 2000 —
between open contacts V AC 1000 1000 1000 1000 1000
13.22 K
Other data 13.01 13.11 - 13.12 13.31 13.61 13.81 13.91 13.S2
13.72
Power lost to the environment
without contact current W 2.2 — 0.4 1 1.2 0.7 0.5
with rated current W 3.5 1.5 1.6 1.8 2 1.8 1.5
Max cable length for pushbutton connection m 100 100 — 200 200 100 100
Max. no. of illuminated pushbutton (≤1mA) — — — 10* 15 12 5
13.11 - 13.12 - 13.31 - 13.61 -
Terminals 13.01 13.22 - 13.S2
13.72 - 13.81 - 13.91
V-2019, www.findernet.com
Max. wire size solid cable stranded cable solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 4 1 x 6 / 2 x 2.5 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5 2 x 1.5 2 x 1
AWG 1 x 10 / 2 x 12 1 x 10 / 2 x 14 1 x 10 / 2 x 12 1 x 12 / 2 x 14 2 x 16 2 x 16
Screw torque Nm 0.8 0.8
* For 8.230 version.
7
13 13 SERIES
SERIES Electronic Relays and Actuators
13.11
Call and Reset relay
13.12
On momentary closure of the Set switch (S), the output contact
closes. Only a momentary closure of the Reset switch (R) will
open the output contact.
(13.12 only)
13.81
(RI) Step relay
After every impulse, the output contact changes state -
alternately switching from open to closed and vice versa.
13.91
(RI) Step relay
After every impulse, the output contact changes state -
alternately switching from open to closed and vice versa.
IT → RI
K
V-2019, www.findernet.com
8
13 SERIES 13
Electronic Relays and Actuators SERIES
Light ON
With this function set - the output contact stays permanently
closed.
13.61.0.024
(RM) Monostable
On closure of a switch between terminal 3 and Line (or Neutral,
in case of 3-wire connection) the output contact will close,
and remain so, until the switch opens.
Light ON
With this function set - the output contact stays permanently
closed.
V-2019, www.findernet.com
9
13 13 SERIES
SERIES YESLY Electronic Relays and Actuators
(LE) A
symmetric flasher (starting pulse on) with control signal.
Power is permanently applied to the relay.
Closing Signal Switch (S) causes the output contacts to transfer
immediately and cycle between ON (T1) and OFF (T2), until
opened.
(DE) Interval with control signal on.
Power is permanently applied to the relay.
On momentary or maintained closure of Signal Switch (S), the
output contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
(BE) Staircase timer.
On initial impulse the output contact closes and timing starts
for the pre-set duration; subsequent impulses during the
timing period will extend the timing period by the full pre-set
value. On expiry of the time delay, the output contact opens.
10
13 SERIES 13
YESLY Electronic Relays and Actuators SERIES
Sequences Sequences
Type Functions
P1 (SET): press to advance through the sequence 1 2 3 4
13.22
P2 (RESET): press to return to Step 1 02
13.72
03
04
K
05
06
07
08
V-2019, www.findernet.com
11
13 13 SERIES
SERIES Electronic Relays and Actuators
Reset Reset
Set Set
Type 13.31
Connection
K
V-2019, www.findernet.com
12
13 SERIES 13
Electronic Relays and Actuators SERIES
Reset Reset
Set
Type 13.61.8.230 - Examples of multiple 4 wire connection with centralized reset pushbutton
K
V-2019, www.findernet.com
13
13 13 SERIES
SERIES Electronic Relays and Actuators
N N
N N
N N
K
V-2019, www.findernet.com
14
13 SERIES 13
YESLY Electronic Relays and Actuators SERIES
Maximum 5 (≤ 1 mA)
illuminated push buttons
Examples of applications
Function TP - Roller Blinds, Shutters and Curtains
Type 13.72 Type 13.S2
LL LL
N
N
N
N
Ch1-P1: up
Ch1-P1: up
Ch2-P2: down
Ch2-P2: down
LL LL
N
N N
LL LL
V-2019, www.findernet.com
N
N NN
15
13 13 SERIES
SERIES Electronic Relays and Actuators
Outline drawings
Type 13.01 Type 13.11
Screw terminal Screw terminal
33.8
45
84
88.8
30.5
Type 13.12 Types 13.31/13.91
Screw terminal Screw terminal
K
V-2019, www.findernet.com
16
13 SERIES 13
Electronic Relays and Actuators SERIES
Outline drawings
Type 13.72 Type 13.22 / 13.S2
Screw terminal Screw terminal
Accessories
Adaptor for panel mounting, for type 13.01, 35 mm wide 011.01
011.01
Adaptor for panel mounting, for type 13.11, 13.12, 13.61 and 13.81, 17.5 mm wide 020.01
020.01
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types
13.11, 13.12, 13.61 and 13.81 (48 tags), 6 x 12 mm 060.48
060.48
K
V-2019, www.findernet.com
Automation for
blinds, grilles
and shutters
Lighting control
in corridors (for
hotels, offices
and hospitals)
Bedroom
light control
Living room
20
light control SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
20 SERIES 20
Modular step relays 16 A SERIES
1 or 2 Pole 16 A Step relays for direct 35 mm 20.21 20.22, 24, 26, 27, 28 20.23
rail (EN 60715) mounting
• 17.4 mm wide
• Test button with mechanical indicators
• Choice of 7 switching sequences
• AC coils and DC coils
• Identification label
• Possible to connect illuminated push buttons
with the additional part 026.00
• 35 mm rail (EN 60715) mount
• Cadmium free contact material
20.21/22/24/26/27/28/23
Screw terminal • Single phase switch 1 NO • Double phase switch • Double phase switch
(SPST-NO) • 35 mm rail (EN 60715) mount 1NO+1NC (SPST-NO+SPST-NC)
• 35 mm rail (EN 60715) mount • 35 mm rail (EN 60715) mount
3
20 20 SERIES
SERIES Modular step relays 16 A
Ordering information
Example: 20 series relay, 35 mm rail (EN 60715) mount, double phase switch, 2 NO 16 A contacts, coil rated at 12 V DC, AgSnO2 contacts.
2 0 . 2 2 . 9 . 0 1 2 . 4 0 0 0
Series Contact material
0 = AgNi
Type 4 = AgSnO2
2 = 35 mm rail (EN 60715) mount
Coil voltage
No. of poles See coil specifications
1 = Single phase switch 1 NO (SPST-NO)
2 = Double phase switch 2 NO (DPST-NO) Coil version
3 = Double phase switch 1 NC+ 1 NO (SPST-NO+SPST-NC) 8 = AC (50/60 Hz)
4 = 4 sequence double phase switch 2 NO (DPST-NO) 9 = DC
6 = 3 sequence double phase switch 2 NO (DPST-NO)
7 = 3 sequence double phase switch 2 NO (DPST-NO)
8 = 4 sequence double phase switch 2 NO (DPST-NO)
Technical data
Insulation
Dielectric strength
between supply and contacts V AC 3500
between open contacts V AC 2000
between adjacent contacts V AC 2000
Other data
Power lost to the environment
with rated current and coil deenergised W 1.3 (20.21, 20.23, 20.28) 2.6 (20.22, 20.24, 20.26, 20.27)
Screw torque Nm 0.8 0.8
Coil terminals Contact terminals
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 4 / 2 x 2.5 1 x 2.5 / 2 x 2.5 1 x 6 / 2 x 4 1 x 4 / 2 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14 / 2 x 14 1 x 10 / 2 x 12 1 x 12 / 2 x 14
If the coil is operated for a prolonged period of time, adequate ventilation of the relays must be provided - suggested gap of 9 mm between adjacent
relays.
Coil specifications
DC version data
Nominal Coil Operating range Resistance Consumption Number Sequence
Type
voltage code I at UN of steps 1 2 3 4
UN Umin Umax R
20.21 2
V V V Ω mA
12 9.012 10.8 13.2 27 440
20.22 2
24 9.024 21.6 26.4 105 230
48 9.048 43.2 52.8 440 110
K 110 9.110 99 121 2330 47 20.23 2
AC version data
20.24 4
Nominal Coil Operating range Resistance Consumption
voltage code I at UN
20.26 3
UN Umin Umax R (50 Hz)
V V V Ω mA
20.27 3
8 8.008 6.8 8.8 4 800
12 8.012 10.2 13.2 7.5 550
24 8.024 20.4 26.4 27 275 20.28 4
XII-2018, www.findernet.com
4
20 SERIES 20
Modular step relays 16 A SERIES
Wiring diagrams
L L
N N
Outline drawings
Type 20.21 Types 20.22/24/26/27/28
Screw terminal Screw terminal
Type 20.23
Screw terminal
K
XII-2018, www.findernet.com
5
20 20 SERIES
SERIES Modular step relays 16 A
Accessories
Module for use with illuminated push-buttons
020.01
Separator for rail mounting, plastic, 9 mm wide 022.09
022.09
K
XII-2018, www.findernet.com
Lighting control
in corridors (for
hotels, offices
and hospitals)
Bedroom
light control
Living room
light control
26
SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
26 SERIES 26
Step relays 10 A SERIES
1 or 2 Pole electromechanical step relay with 26.01 26.02, 04, 06, 08 26.03
electrically separate coil and contact circuits
• Choice of 6 switching sequences
• Screw terminal connections
• AC coil
• Panel mount
• Cadmium free contact material
26.01/02/04/06/08/03
Screw terminal
Insulation between
coil and contacts (1.2/50 µs) kV 4 4 4
Ambient temperature range °C –40…+40 –40…+40 –40…+40
Protection category IP 20 IP 20 IP 20
Approvals (according to type)
3
26 26 SERIES
SERIES Step relays 10 A
Ordering information
Example: 26 series screw terminal, panel mount relay, double phase switch 2 NO (DPST-NO) 10 A contacts, coil rated 12 V AC.
2 6 . 0 2 . 8 . 0 1 2 . 0 . 0 . 0 . 0
Series Coil voltage
See coil specifications
Type
0 = Screw terminal Coil version
8 = AC (50 Hz)
No. of poles
1 = Single phase switch 1 NO (SPST-NO)
2 = Double phase switch 2 NO (DPST-NO)
3 = Double phase switch 1 NO + 1 NC (SPST-NO + SPST-NC)
4 = 4 sequences double phase switch 2 NO (DPST-NO)
6 = 3 sequences double phase switch 2 NO (DPST-NO)
8 = 4 sequences double phase switch 2 NO (DPST-NO)
Technical data
Insulation
Dielectric strength
between supply and contacts V AC 3500
between open contacts V AC 2000
between adjacent contacts V AC 2000
Other data 26.01, 26.03, 26.08 26.02, 26.04, 26.06
Power lost to the environment
with rated current and coil de-energised W 0.9 1.8
Screw torque Nm 0.8 0.8
Max. wire size solid cable stranded cable solid cable stranded cable
mm 2
1 x 4 / 2 x 2.5 1 x 2.5 / 2 x 2.5 1 x 4 / 2 x 2.5 1 x 2.5 / 2 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14 / 2 x 14 1 x 12 / 2 x 14 1 x 14 / 2 x 14
Coil specifications
AC version data
Nominal Coil Operating range Resistance Consumption Number Sequence
Type
voltage code I at UN of steps 1 2 3 4
UN Umin Umax R (50 Hz)
V V V Ω mA 26.01 2
26.06 3
26.08 4
X-2017, www.findernet.com
4
26 SERIES 26
Step relays 10 A SERIES
Wiring diagrams
L
Accessories
for 12 and 24 V DC control applications
K
X-2017, www.findernet.com
5
26 26 SERIES
SERIES Step relays 10 A
Outline drawings
26.01
Screw terminal 26.02 / 04 / 06 / 08
Screw terminal
26.03
Screw terminal
K
X-2017, www.findernet.com
Lighting control
in corridors (for
hotels, offices
and hospitals)
Bedroom
light control
Living room
light control
27
SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
27 SERIES 27
Step relays 10 A SERIES
3
27 27 SERIES
SERIES Step relays 10 A
Ordering information
Example: 27 series screw terminal, panel mount step relay, single phase switch 1 NO (SPST-NO) 10 A contact, coil rated 230 V AC.
2 7 . 0 . 1 . 8 . 2 3 0 . 0 . 0 . 0 . 0
Series Coil voltage
See coil specifications
Type
0 = Clamp terminal
2 = Clamp terminal, with coil power limiter Coil version
8 = AC (50/60 Hz)
No. of poles
1 = Single phase switch 1 NO (SPST-NO)
5 = 4 sequences double phase switch 2 NO (DPST-NO)
6 = 3 sequences double phase switch 2 NO (DPST-NO)
Technical data
Other data 27.01, 27.21 27.05, 27.06, 27.25, 27.26
Power lost to the environment
with rated current and coil de-energised W 0.9 1.8
Screw torque Nm 0.8 0.8
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 2 x 2.5 1 x 4 / 2 x 2.5 2 x 2.5 1 x 4 / 2 x 2.5
AWG 2 x 14 1 x 12 / 2 x 14 2 x 14 1 x 12 / 2 x 14
Coil specifications
Types 27.01, 27.05, 27.06
Nominal Coil Operating range Resistance Consumption Number Sequence
Type
voltage code (50 Hz) I at UN of steps 1 2 3 4
UN Umin Umax R (50 Hz)
27.01/21 2
V V V Ω mA
110 8.110 88 121 1400 42.0
230 8.230 184 253 6500 17.5 27.05/25 4
Wiring diagram
K
Type 27.01/05/06 Type 27.21/25/26
L L
N N
X-2017, www.findernet.com
4
27 SERIES 27
Step relays 10 A SERIES
Type 027.00
This module is necessary if using up to a maximum of 24 illuminated push-
buttons (1 mA max, 230 V AC) in the switching input circuit.
It must be plugged directly into the relay.
Outline drawings
27.0x / 2x
Screw terminal
K
X-2017, www.findernet.com
Hotel room
energy-enabling
units
Garden and
night lighting
Streetlights and
car park lighting
Bathrooms
lighting
control
Office lighting
control
Pump control
22
SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES
2 NO 1 NO + 1 NC 2 NC
(x3x0) (x5x0) (x4x0)
For outline drawings see page 10
Contact specification
• Contact gap ≥ 3 mm for NO
Contact configuration 2 NO, 3 mm* (or 1 NO + 1 NC or 2 NC) contacts only;
Rated current/Maximum peak current A 25/80 25/120 NC contacts ≥ 1.5 mm
Rated voltage V AC 250/440 250/440
Rated load AC1 / AC-7a (per pole @ 250 V) VA 6250 6250
Rated current AC3 / AC-7b A 10 10
Rated load AC15 (per pole @ 230 V) VA 1800 1800
Single-phase motor rating (230 V AC) kW 1 1
Rated load AC5a (per pole @ 250 V) A 15 15
Rated current AC-7c A — 10
Nominal lamp rating:
230 V incandescent/halogen W 800 2000
fluorescent tubes with
electronic ballast W 300 800
fluorescent tubes with
electromechanical ballast W 200 500
CFL W 100 200
230 V LED W 100 200
LV halogen or LED with
electronic ballast W 100 200
LV halogen or LED with
electromechanical ballast W 300 800
Breaking capacity DC1: 30/110/220 V A 25/5/1 25/5/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
Rated power AC/DC VA (50 Hz)/W 2/2.2 2/2.2
Operating range DC/AC (50/60 Hz) (0.8…1.1)UN (0.8…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.4 UN 0.4 UN
Must drop-out voltage DC/AC (50/60 Hz) 0.1 UN 0.1 UN L
Technical data
Mechanical life AC/DC cycles 2 · 106 2 · 106
Electrical life at rated load AC-7a cycles 70 · 103 30 · 103
Operate/release time ms 30/20 30/20
V-2019, www.findernet.com
3
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A
4 NO 3 NO + 1 NC 2 NO + 2 NC
(x3x0) (x7x0) (x6x0)
For outline drawings see page 10
Contact specification
Contact configuration 4 NO, 3 mm* (or 3NO + 1NC or 2NO + 2NC) * Contact gap ≥ 3 mm for NO
Rated current/Maximum peak current A 25/80 25/120 contacts only;
Rated voltage V AC 250/440 250/440 NC contacts ≥ 1.5 mm
Rated load AC1/AC-7a (per pole @ 250 V) VA 6250 6250
Rated current AC3/AC-7b A 10 10
Rated load AC15 (per pole @ 230 V) VA 1800 1800
Three-phase motor rating (400 - 440 V AC) kW 4 4
Rated load AC5a (per pole @ 250 V) A 15 15
Rated current AC-7c A — 10
Nominal lamp rating:
230 V incandescent/halogen W 800 2000
fluorescent tubes with
electronic ballast W 300 800
fluorescent tubes with
electromechanical ballast W 200 500
CFL W 100 200
230 V LED W 100 200
LV halogen or LED with
electronic ballast W 100 200
LV halogen or LED with
electromechanical ballast W 300 800
Breaking capacity DC1: 30/110/220 V A 25/5/1 25/5/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
Rated power AC/DC VA (50 Hz)/W 2/2.2 2/2.2
Operating range DC/AC (50/60 Hz) (0.8…1.1)UN (0.8…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.4 UN 0.4 UN
L Must drop-out voltage DC/AC (50/60 Hz) 0.1 UN 0.1 UN
Technical data
Mechanical life AC/DC cycles 2 · 106 2 · 106
Electrical life at rated load AC-7a cycles 150 · 10 3
30 · 103
Operate/release time ms 18/40 18/40
V-2019, www.findernet.com
4
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES
4 NO 3 NO + 1 NC 2 NO + 2 NC 3 NO + 1 NC
(4310) (4710) (4610) (4717)
For outline drawings see page 10
Contact specification
Contact configuration 4 NO, (or 3NO + 1NC or 2NO + 2NC) ≥ 3 mm
Rated current/Maximum peak current A 40/176 63/240
Rated voltage V AC 400/440 400/440
Rated load AC1 / AC-7a (per pole @ 400 V) VA 16000 24000
Rated current AC3 / AC-7b (400 V) A 22 30
Rated load AC15 (per pole @ 230 V) VA — —
Three-phase motor rating (400 - 440 V AC) kW 11 15
Rated load AC5a (per pole @ 250 V) A 20 32
Rated current AC-7c A — —
Nominal lamp rating:
230 V incandescent/halogen W 4000 5000
fluorescent tubes with
electronic ballast W 1500 2000
fluorescent tubes with
electromechanical ballast W 1500 2000
CFL W 1000 1500
230 V LED W 1000 1500
LV halogen or LED with
electronic ballast W 1000 1500
LV halogen or LED with
electromechanical ballast W 1500 2000
Breaking capacity DC1: 30/110/220 V A 40/4/1.2 63/4/1.2
Minimum switching load mW (V/mA) 1000 (17/50) 1000 (17/50)
Contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 110…120 (110 V DC) - 230…240 (220 V DC)
Rated power AC/DC VA (50 Hz)/W 6 6
Operating range DC/AC (50/60 Hz) (0.85…1.1)UN (0.85…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.85 UN 0.85 UN
Must drop-out voltage DC/AC (50/60 Hz) 0.2 UN 0.2 UN L
Technical data
Mechanical life AC/DC cycles 3 · 106 3 · 106
Electrical life at rated load AC-7a cycles 100 · 10 3
100 · 103
Operate/release time ms 20/45 20/45
V-2019, www.findernet.com
5
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A
Ordering information
Exemple: 22 series, modular contactor 25 A, 4 NO contacts, coil 230 V AC/DC, AgSnO2 contacts, Auto-On-Off selector + mechanical indicator + LED.
A B C D
2 2 . 3 4 . 0 . 2 3 0 . 4 3 4 0
Series D: Special versions
Type 0 = Standard
3 = 25 A modular contactor range C: Options
4 = 40 A modular contactor range 1 = Mechanical indicator
6 = 63 A modular contactor range 2 = Mechanical indicator + LED
Number of contacts 4 = Auto-On-Off selector + mechanical
2 = 2 pole indicator + LED
4 = 4 pole B: Contact circuit
Coil version 3 = All NO contacts
0 = AC (50/60 Hz)/DC 4 = All NC contacts (22.32 only)
5 = 1 NO + 1 NC
Coil rated voltage 6 = 2 NO + 2 NC
See coil specifications 7 = 3 NO + 1 NC
A: Contact material
1 = AgNi
4 = AgSnO2
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
22.32 AC/DC 1-4 3-4-5 2-4 0
22.34 AC/DC 1-4 3-6-7 2-4 0
22.44 AC/DC 4 3-6-7 1 0
22.64 AC/DC 4 3-6-7 1 0
Options
Auto-On-Off selector + mechanical indicator + LED (xx40 option)
Type 22.32 / 22.34 Options
1 Selector
The three-position manual selector has the following
functions:
1
• ON position - the contacts are latched in the operated
state (NO contacts - closed and NC contacts - open), the
mechanical indicator is visible in its window, the LED is
not illuminated.
3 • AUTO position - the state of contacts, mechanical
2 indicator and LED follow the coil supply voltage.
• OFF position - even if terminals A1 - A2 are supplied
with rated voltage, the coil is not energized, and so
the contacts remain in the non-operated state, the
mechanical indicator is not visible and the LED is not
illuminated.
2 LED
3 Mechanical indicator
L
1
V-2019, www.findernet.com
6
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES
Technical data
Insulation 22.32/22.34 22.44/22.64
Rated insulation voltage V AC 250 440 440
Pollution degree 3* 2 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 4
Dielectric strength V AC 4000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 4
Dielectric strength V AC 2500 2000
Insulation between open contacts NO contact NC contact NO/NC contacts
Contact gap mm 3 1.5 3
Overvoltage category III II III
Rated impulse voltage kV (1.2/50 µs) 4 2.5 4
Dielectric strength V AC/kV (1.2/50 µs) 2500/4 2000/3 2000/3
* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV(1.2/50 µs) 4 2
Short circuit protection 22.32 / 22.34 22.44 22.64
Rated conditional short circuit current kA 3 3 3
Back-up fuse A 32 (gL/gG type) 63 80
Terminals Solid and stranded cable
22.32 / 22.34 22.44 / 22.64
Max. wire size – contact terminals mm2 1 x 6 / 2 x 4 1 x 25 (solid) - 1 x 16 (stranded)
AWG 1 x 10 / 2 x 12 1 x 4 (solid) - 1 x 6 (stranded)
Max. wire size – coil terminals mm2 1 x 4 / 2 x 2.5 1 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14
Min. wire size – contact and coil terminals mm2 1 x 0.2 1 x 1 (coil) - 1 x 1.5 (contacts)
AWG 1 x 24 1 x 18 (coil) - 1 x 16 (contacts)
1.2 (coil terminals) -
Screw torque Nm 0.8
3.5 (contact terminals)
Wire strip length mm 9 10
Other data 22.32 22.34 22.44 22.64
Vibration resistance (10…150)Hz g 4 4 3 3
Shock resistance g 10 10 15 15
Power lost to the environment without contact current W 2 2 6 6
with rated current W 4.8 6.3 17 37
NOTE
22.32/22.34: It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient
temperature > 40 °C, coil operated for a prolonged period of time, all contacts loaded with current > 20 A).
L
22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is + 40 °C; when more than 3 contactors are installed, it is necessary an air
gap of 9 mm.
With 2 adjacent contactors the maximum ambient temperature is + 55 °C; when more than 2 contactors are installed, it is necessary an air
gap of 9 mm.
V-2019, www.findernet.com
7
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A
Contact specification
Ratings and utilization categories according to EN 61095: 2009
Type Utilization category
AC-7a AC-7b AC-7c
Rated current Rated electrical Rated current Rated electrical Rated current Rated electrical
(A) life (Cycles) (A) life (Cycles) (A) life (Cycles)
70 · 103 (NO)
22.32….1xx0 (AgNi contacts) 25 10 30 · 103 — —
30 · 103 (NC)
22.32….4xx0 (AgSnO2 contacts) 25 30 · 103 10 30 · 103 10 30 · 103
150 · 103 (NO)
22.34….1xx0 (AgNi contacts) 25 10 30 · 103 — —
100 · 103 (NC)
22.34….4xx0 (AgSnO2 contacts) 25 30 · 103 10 30 · 103 10 30 · 103
22.44….4xx0 40 100 · 103 22 150 · 103 — —
22.64….4xx0 63 100 · 103 30 150 · 103 — —
Utilization category: AC-7a = Slightly inductive loads (cos ϕ = 0.8)
AC-7b = Motor loads; (cos ϕ = 0.45, Imaking = 6x Ibreaking)
AC-7c = Compensated electric discharge lamps (cos ϕ = 0.9, C = 10 mF/A)
H 22 - Maximum DC1 breaking capacity - Type 22.32/22.34 H 22 - Maximum DC1 breaking capacity - Type 22.44/22.64
DC breaking current (A)
type 22.64
type 22.44
DC voltage (V) DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
AC/DC version data (type 22.32) AC/DC version data (type 22.34)
Nominal Coil Operating range Rated coil Nominal Coil Operating range Rated coil
voltage code consumption voltage code consumption
UN Umin Umax IN at UN (AC) UN Umin Umax IN at UN (AC)
V V V mA V V V mA
12 0.012 9.6 13.2 165 12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83 24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42 48 0.048 38.4 52.8 42
60 0.060 48 66 33 60 0.060 48 66 33
120 (110…125) 0.120 88 138 16.5 120 (110…125) 0.120 88 138 16.5
230 184 (AC) 264 (AC) 230 184 (AC) 264 (AC)
(230…240 AC) 0.230 8.7 (230…240 AC) 0.230 8.7
(220 DC)
176 (DC) 242 (DC) (220 DC)
176 (DC) 242 (DC)
AC/DC version data (type 22.44 / 22.64) R 22 - Coil operating range v ambient temperature
Nominal Coil Operating range Rated coil
voltage code consumption
UN Umin Umax IN at UN (AC)
L V V V mA
12 0.012 10.2 13.2 495
24 0.024 20.4 26.4 250
120
0.120 102 138 50
(110…125)
230
V-2019, www.findernet.com
264 (AC)
(230…240 AC) 0.230 196 26
242 (DC)
(220 DC)
8
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES
Wiring diagrams
Line and neutral switched Line only switched
L
V-2019, www.findernet.com
9
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A
Outline drawings
Type 22.32 Types 22.32 + 022.33/022.35
Screw terminal Screw terminal
L
V-2019, www.findernet.com
10
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES
33
34
11
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A
Accessories
Adaptor for panel mounting (for 22.32 type), plastic, 17.5 mm wide 020.01
020.01
Adaptor for panel mounting (for 22.34 type), plastic, 35 mm wide 011.01
011.01
Sheet of marker tags (CEMBRE Thermal transfer printers) for all relays (48 tags), 6 x 12 mm 060.48
060.48
019.01
022.09
PEAN
8-way jumper link for type 22.32, 17.5 mm wide 022.18 (blue)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A O
PEAN
022.18
PEAN
6-way jumper link for type 22.34, 35 mm wide 022.26 (blue)
O
Rated values 10 A - 250 V
EUR
T
N
T E
EUR
P A
L
O
PEAN
022.26
V-2019, www.findernet.com
Comfort
Energy
savings
Ecological
Flexibility
Heating and
cooling
Building
automation
1T
SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
1T SERIES 1T
Digital thermostats SERIES
Thermostat 1T.91
• Touch display with guided programming
• Stunning design
• Backlit touch keys
• Power supply: 2 1.5 V AA batteries
• 2 selectable temperatures (day/night)
• Summer/Winter switch
• PIN lock padlock function
• Temperature setting range 5-37°C
• Contact rating 5 A 250 V AC
Wiring diagram
Colour Thermostat
White 1T.91.9.003.0000
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0…+50 °C
Temperature setting range +5…+37 °C
Temperature differential 0.2 °C self regulation
Temperature rate of change —
Nighttime set-back YES
Independently set temperature levels 2 (day/night)
Thermostat lock 3 digit PIN
Protection category IP 20
Mounting Wall
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection +5 °C
Energy saving function —
M
X-2018, www.findernet.com
3
1T 1T SERIES
SERIES Digital thermostats
REMOTE
CONTROL
Wiring diagram
Colour
White 1T.51.9.003.0000
Black 1T.51.9.003.2000
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AAA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0 - 50 °C
Temperature setting range +5…+37 °C
Temperature differential 0.1…0.9 °C
Temperature rate of change —
Nighttime set-back YES
Independently set temperature levels 2 (day/night)
Thermostat lock 3 digit PIN
Protection category IP20
Mounting Recess (3 module box)
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection +2…+8 °C
M
X-2018, www.findernet.com
4
1T SERIES 1T
Digital thermostats SERIES
N L
Wiring diagram
Colour
White 1T.31.9.003.0000
Black 1T.31.9.003.2000
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AAA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0…+50 °C
Temperature setting range +5…+37 °C
Temperature differential 0.2 - 0.5 °C
Temperature rate of change —
Nighttime set-back YES
Independently set temperature levels 2 (day/night)
Thermostat lock Push buttons
Protection category IP20
Mounting Surface
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection +2…+8 °C
Energy saving function — M
X-2018, www.findernet.com
5
1T 1T SERIES
SERIES Digital thermostats
Wiring diagram
Colour
White 1T.41.9.003.0000
Black 1T.41.9.003.2000
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AAA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0…+50 °C
Temperature setting range +8…+30 °C (night set-back: Winter +5…+27 °C/Summer +11…+33 °C )
Temperature differential 0.3 °C
Temperature rate of change —
Nighttime set-back YES (0.3 °C)
Independently set temperature levels —
Thermostat lock Mechanical
Protection category IP20
Mounting Surface
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection 5 °C
M Energy saving function —
X-2018, www.findernet.com
6
1T SERIES 1T
Thermostats SERIES
230 V AC
L
N
Wiring diagram
Colour
White 1T.01.0
Technical features
Sensing element Gas bulb
Supply —
Contact configuration 1 CO (SPDT)
Contact rating 16 A/250 V AC
Display range —
Temperature setting range +7…+30 °C
Temperature differential 0.4 - 0.8 °C
Temperature rate of change 1 °C/15 min
Nighttime set-back —
Independently set temperature levels —
Thermostat lock Mechanical
Protection category IP20
Mounting Surface
Display resolution —
Accuracy at +20 °C —
Frost Protection —
Energy saving function — M
X-2018, www.findernet.com
Push buttons —
Supervisory control NO
Back-light display NO
Approvals (according to type)
7
1T 1T SERIES
SERIES Thermostats
230 V AC
L
N
Wiring diagram
Colour
White 1T.01.1
Technical features
Sensing element Gas bulb
Supply —
Contact configuration 1 CO (SPDT)
Contact rating 16 A/250 V AC
Display range —
Temperature setting range +7…+30 °C
Temperature differential 0.4 - 0.8 °C
Temperature rate of change 1 °C/15 min
Nighttime set-back —
Independently set temperature levels —
Thermostat lock Mechanical
Protection category IP20
Mounting Surface
Display resolution —
Accuracy at +20 °C —
Frost Protection —
M Energy saving function —
X-2018, www.findernet.com
Push buttons —
Supervisory control NO
Back-light display NO
Approvals (according to type)
8
1T SERIES 1T
Thermostats SERIES
230 V AC
N
L
Wiring diagram
Colour
White 1T.01.2
Technical features
Sensing element Gas bulb
Supply —
Contact configuration 1 CO (SPDT)
Contact rating 16 A/250 V AC
Display range —
Temperature setting range +7…+30 °C
Temperature differential 0.4 - 0.8 °C
Temperature rate of change 1 °C/15 min
Nighttime set-back —
Independently set temperature levels —
Thermostat lock Mechanical
Protection category IP20
Mounting Surface
Display resolution —
Accuracy at +20 °C —
Frost Protection —
Energy saving function — M
X-2018, www.findernet.com
Push buttons —
Supervisory control NO
Back-light display NO
Approvals (according to type)
Geolocation
Comfort
Energy
savings
Ecological
Flexibility
Heating and
cooling
Building
automation
1C
SЕRIES
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
1C SERIES 1C
Digital chronothermostats SERIES
Wiring diagram
Supervisory control NO
Back-light display YES
Communications Wi-Fi
APP programming YES
Approvals (according to type)
3
1C 1C SERIES
SERIES Digital chronothermostats
Finder Bliss
AVAILABLE ON
Touch keys
Turn on the display using the "Finder" button Adjustment
M
X-2018, www.findernet.com
4
1C SERIES 1C
Digital chronothermostats SERIES
N L
Wiring diagram
5
1C 1C SERIES
SERIES Digital chronothermostats
Finder Clima
Finder Clima
Finder Clima makes it easy to programme the 1C.81 chronothermostat with your smartphone by using NFC (Near Field Communication)
technology. You can assign a name to the different chronothermostats in your house and save the relevant programming on your telephone.
When you place your smartphone against the chronothermostat, the programming is immediately transferred.
With the application, it is possible to programme the temperatures on a weekly basis, change the temperature programming for 24 hours,
suspend the programme when you go on holiday, and regulate the temperature comfort levels.
Finder Clima will guide you step-by-step during the whole procedure!
M
X-2018, www.findernet.com
6
1C SERIES 1C
Digital chronothermostats SERIES
N L
Wiring diagram
Supervisory control NO
Back-light display NO
Communications —
APP programming —
Approvals (according to type)
7
1C 1C SERIES
SERIES Digital chronothermostats
Wiring diagram
Colour Daily Program
White RAL 9010 1C.61.9.003.0101
Metallic Anthracite 1C.61.9.003.2101
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AAA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0…+50 °C
Temperature setting range +5…+37 °C (with sliders: winter +6…+24 °C/summer +18…+30 °C)/–20…+90 °C (with external sensor)
Temperature differential 0.1…0.9 °C
Temperature rate of change —
Nighttime set-back —
Independently set temperature levels Sliders
Thermostat lock Basic or 3 digit PIN
Protection category IP 20
Mounting Surface
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection +2…+8 °C
Weekly/Daily Daily + 7 Daily
Minimum programming interval 1 h or 15 minutes - daily/weekly (weekly: only Auto, Manual and OFF mode)
Energy saving function —
M Push buttons Touch screen
X-2018, www.findernet.com
Supervisory control NO
Back-light display YES
Communications —
APP programming —
Approvals (according to type)
8
1C SERIES 1C
Digital chronothermostats SERIES
Accessories
External temperature sensor 01C.61
Sensing range (–20…+90)°C
Resolution 0.1 °C (–9.9…+90)°C
1 °C (–10…–20)°C
Maximum cable length m 20
01C.61 Degree of protection IP 54
The 01C.61 is used to sense the temperature at a location external to the 1C.61 chronothermostat. The 1C.61 can either;
display the external temperature (and regulate to its internal sensor), or display & regulate to the external sensor temperature.
The 01C.61 sensor communicates with the 1C.61 chronothermostat through a dedicated digital system.
This is the only sensor that can be used.
M
X-2018, www.findernet.com
9
1C 1C SERIES
SERIES Digital chronothermostats
REMOTE
CONTROL
Wiring diagram
Colour Weekly program
White 1C.51.9.003.0007
Black 1C.51.9.003.2007
Technical features
Sensing element NTC
Supply 2 batteries 1.5 V AAA
Contact configuration 1 CO (SPDT)
Contact rating 5 A/250 V AC
Display range 0…+50 °C
Temperature setting range +5…+37 °C
Temperature differential 0.1…0.9 °C
Temperature rate of change —
Nighttime set-back —
Independently set temperature levels 3
Thermostat lock Basic or 3 digit PIN
Protection category IP 20
Mounting Recess (3 module box)
Display resolution 0.1 °C
Accuracy at +20 °C +/–0.5 °C
Frost Protection +2…+8 °C
Weekly/Daily Weekly
Minimum programming interval 1 h
Energy saving function —
M Push buttons Touch sceen
X-2018, www.findernet.com
Supervisory control NO
Back-light display YES
Communications —
APP programming —
Approvals (according to type)
Operate time
Release time XV 2 TABLE 2.3 Certified sockets ratings XI —
Bounce time XV 2 TABLE 3 Motor ratings v relay series XII 1
Ambient temperature XVI 1 TABLE 4 Contact categories XII 2
Ambient temperature range XVI 1 TABLE 5 Contact materials characteristics XII 2
Storage temperature range XVI 1 TABLE 6 Rated impulse voltage XIV 2
Environmental protection XVI 1 TABLE 7 Pollution degree XIV 2
Protection category XVI 1
III
General technical information
Residual current
Reference values and tolerances When AC relay coils are controlled via a proximity switch, or via cables
having length > 10 m, the use of a 99 series “residual current bypass“
Unless expressly indicated otherwise, all technical data is specified under
module is recommended, or alternatively, fit a resistor of 62 kOhm/1 watt
the following environmental conditions:
in parallel with the coil.
- ambient temperature: 23 °C ± 5 K
- pressure: 96 ± 10 kPa Ambient temperature
- humidity: 50 ± 25% The Ambient temperature as specified in the relevant specification and “R”
- altitude: from sea level to 2000 m. Higher altitudes will not affect current chart relates to the immediate environment in which the component is
or temperature ratings, but will require a de-rating of the rated impulse situated, as this may be greater than the ambient temperature in which the
voltage - which must be reduced by 14% at 3000 m, 29% at 4000 m, equipment is located. Refer to page XIV for more detail.
48% at 5000 m
Condensation
Environmental conditions causing condensation or ice formation in the
The following tolerances apply:
relay are not permitted.
- coil resistance, rated consumption and rated power: ± 10%
- frequency: ± 2% Installed orientation
- dimensions indicated in the mechanical drawings: ± 0.1 mm The component’s specification is unaffected (unless expressly stated
otherwise) by its orientation, (provided it is properly retained, eg by a
Regulations for storage and handling of retaining clip in the case of socket mounted relays).
Whether using foam or spray fluxing methods, ensure that flux is applied
sparingly and evenly and does not flood through to the component side
of the PC board.
By following the above precautions, and assuming the use of alcohol or
water based fluxes, it is possible to satisfactorily use relays with protection
category RT II or RT III.
IV
General technical information
Full disconnection
Terminal marking Contact separation for the disconnection of conductors so as to provide
European Standard EN 50005 recommends the following numbering for the equivalent of basic insulation between those parts intended to be
the marking of relay terminals: disconnected. There are requirements for both the dielectric strength and
- .1 for common contact terminals (e.g. 11, 21, 31…) the dimensioning of the contact gap. Several Finder relays comply with
- .2 for NC contact terminals (e.g. 12, 22, 32…) this category of disconnection.
- .4 for NO contact terminals (e.g. 14, 24, 34…) Rated current
- A1 and A2 for coil terminals This coincides with the Limiting continuous current - the highest current
- B1, B2, B3 etc. for Signal inputs that a contact can continuously carry within the prescribed temperature
- Z1 & Z2 for potentiometer or sensor connection limits. It also coincides with the Limiting cycling capacity, i.e. the maximum
current that a contact is capable of making and breaking under specified
conditions. In virtually all cases the Rated current is also the current that,
when associated with the Rated switching voltage, gives rise to the Rated
Pole Contact Example:
load (AC1). (The exception being the 30 series relay).
Number configuration Relay with 4 poles
Number Maximum peak current
The highest value of inrush current (≤ 0.5 seconds) that a contact can
For delayed contacts of timers the numbering will be:
make and cycle (duty cycle ≤ 0.1) without undergoing any permanent
- .5 for common contact terminals (e.g. 15, 25,…)
degradation of its characteristics due to generated heat. It also coincides
- .6 for NC contact terminals (e.g. 16, 26,…)
with the Limiting making capacity.
- .8 for NO contact terminals (e.g. 18, 28,…)
Rated switching voltage
American standards prescribes:
This is the switching voltage that when associated with the Rated current
progressive numbering for terminals (1,2,3,…13,14,…) and sometimes A
gives rise to the Rated load (AC1). The Rated load is used as the reference
and B for coil terminals.
load for electrical life tests.
VI-2018, www.findernet.com
V
General technical information
VI
General technical information
VII
General technical information
VIII
General technical information
(AgCdO contact)
86 E106390 / / / / Yes 2 35 or 50 °C
99 E106390 / / / / Yes 2 or 3 50 °C
7T.81…2301 E337851 10 A – 250 Vac (R) 1 ½ Hp (250 Vac) / Yes 2 –20 / +40 °C
7T.81…2401 (10 FLA)
7T.81…2303 E337851 10 A – 250 Vac (R) 1 ½ Hp (250 Vac) / Yes 2 0 / +60 °C
7T.81…2403 (10 FLA)
IX
General technical information
X
General technical information
distance of 5 mm
97.51 - 97.51.3 15A 300V (40°C) 15A 300V (40 °C) Yes 40 or 70°C 14-24
(2-wires/per pole) 10A 300V (70 °C) stranded and solid
10A 300V (70°C)
97.52 - 97.52.3 10A 300V (40°C) 8A 300V Yes 70°C 14-24
8A 300V (70°C) stranded and solid
97.P1/P2 10A 300V 10A 300V Yes 70°C 14-26
stranded and solid
XI
General technical information
leading to a short-circuit within the relay or contactor. AgSnO2 - Excellent resistance - L amp and capacitive loads
3 - Under certain circumstances it may be preferable to use three single (Silver Tin to welding - Very high Inrush current loads
pole relays to control each phase individually, and so achieve greater Oxide)
separation between the phases. (Any relatively small time difference
between the operation times of the three relays is insignificant
compared to the much slower operation of contactors.)
XII
General technical information
Latching relay
ENERGIZATION VOLTAGE A bistable relay, where the contacts retain their state due to a mechanical
0 non operate min pick-up nominal maximum latching mechanism. Subsequent applications of coil energisation causes
voltage voltage voltage voltage the contacts to “toggle” open and closed.
Remanence relay
A bistable relay, where the contacts retain their operated (or Set) state due
not operating range uncertain operating range to remanent magnetism in the relay iron circuit caused by the application
operating zone of a DC current through the coil. Resetting the contact state is achieved
by passing a smaller DC current through the coil in the opposite direction.
DE-ENERGIZATION VOLTAGE For AC excitation, magnetization takes place via a diode to produce a DC
0 must holding nominal maximum set current, and demagnetising is achieved by applying an AC coil current
drop-out voltage voltage voltage of lower magnitude.
voltage
Insulation
Relay function and Isolation
One of the main functions of a relay is to connect and disconnect different
release uncertain operating range electric circuits, and usually, to maintain a high level of electrical separation
range operating zone between the various circuits. It is therefore necessary to consider the level of
isolation appropriate to the application and the task to be performed - and
to relate this to the relay’s specification. In the case of electromechanical
Non-operate voltage
relays the areas of isolation generally considered are:
The highest value of input voltage at which the relay will not operate (not
specified in the catalogue).
• Isolation between coil and all contacts (the “contact set”).
Catalogue data - "Insulation between coil and contact set".
Minimum Pick-up voltage (Operate voltage) • Isolation between physically adjacent, but electrically separate, contacts of
The lowest value of applied voltage at which the relay will operate. a multi-pole relay. Catalogue data - “Insulation between adjacent contacts”.
• Isolation between the open contacts (applies to the NO contact, and the
Maximum permitted voltage
NC contact when the coil is energised).
The highest applied coil voltage that the relay can continuously withstand,
Catalogue data - “Insulation between open contacts”.
dependent on ambient temperature (see “R” diagrams).
Specifying isolation levels
Holding voltage (Non-release voltage)
There are several ways of specifying or describing the level of isolation
The lowest value of coil voltage at which the relay (which has previously
offered by, or demanded of, a relay. These include:
been energised with a voltage within the operating range) will not drop-
out. Insulation coordination, which focuses on the levels of impulse voltage
likely to be seen on the supply lines of the application equipment
Must drop-out voltage (Must release voltage)
and the cleanliness of the immediate surroundings of the relay in the
The highest value of coil voltage at which the relay (having previously
equipment. And, as a consequence, it demands appropriate levels of
been energised with a voltage within the operating range) will definitely
separation between circuits, in terms of isolating distances and quality of
drop-out. The same “per unit” value can be applied to the nominal coil
insulating material used etc. (see additional information under “Insulation
current value to give an indication of the maximum leakage current that
coordination”).
may be permitted in the coil circuit, before problems with relay release
might be expected. Type of insulation; For both equipment and components such as a relay,
there are several types (or levels) of insulation that might be demanded
Coil Resistance
VI-2018, www.findernet.com
between the various circuits. The appropriate type will depend on the
The nominal value of the coil resistance under the standard prescribed
specific function being performed, the voltage levels involved, and the
condition of 23 °C ambient. Tolerance is ± 10%.
associated safety consequences. The various types of insulation are listed
Rated coil consumption below, and those appropriate to each relay series are stated within the
The nominal value of coil current, when energized at nominal voltage (and relay data; Specifically, within the table under the section entitled Technical
at 50 Hz for AC coils). data, sub-heading; Insulation.
XIII
General technical information
Functional insulation; Insulation between conductive parts, which is Nominal voltage of supply system
necessary only for the proper functioning of the relay. This effectively describes the source of the power supply system, so
Basic insulation; Insulation applied to live parts to provide basic 230/400 V AC indicates that this would be (or is likely to be) a three-phase
protection against electric shock. sub-station transformer with a Neutral connection. Being aware of the source
Supplementary insulation; Independent insulation applied in addition to of the supply system is important since (in conjunction with the Overvoltage
basic insulation, in order to provide protection against electric shock in category) it determines the typical levels of impulse voltage likely to be seen
the event of a failure of basic insulation. on the supply lines, and this has to be taken into account in the designing of
Double insulation; Insulation comprising both basic insulation and the relay. However, it does not necessarily follow that the relay will be rated
supplementary insulation. by the manufacturer for use at the highest voltage of the supply system. It is
Reinforced insulation; A single insulation system applied to live parts, the declared Rated Insulation Voltage that confirms this aspect.
which provides a degree of protection against electric shock equivalent
Rated Insulation Voltage
to double insulation.
This is a notional value of voltage that indicates the relay's insulation
(Usually, the decision as to the appropriate type of insulation will have
as being suitable for handling voltages up to this level. Note that this
already been made by the equipment standard.)
notional Rated Insulation Voltage is selected from a list of preferred values.
Dielectric strength, and high voltage impulse tests; These are either, final For Finder relays, 250 V and 400 V are two such preferred values, and of
inspection or Type tests, which prove the level of isolation in terms of course they will cover respectively, the 230 V L-N and 400 V L-L voltages
the minimum voltage stress that can be withstood, between the various commonly encountered in practice.
specified electrical circuits. As the only method of specifying and checking
TABLE 6 Rated impulse voltage
for adequate isolation, this tends to be the more historical approach.
However, there are still some dielectric strength requirements to be Nominal voltage of the Rated
Rated impulse voltage kV
found within both the Insulation coordination approach and the Level of supply system(1) V insulation
Insulation approach. Three-phase Single-phase voltage Overvoltage category
systems systems V I II III IV
Insulation coordination 120 to 240 125 to 250 0.8 1.5 2.5 4
In accordance with EN 61810‑1 and IEC 60664‑1, the Insulation
230/400 250/400 1.5 2.5 4 6
characteristics offered by a relay can be described by just two characteristic
277/480 320/500 1.5 2.5 4 6
parameters – the Rated Impulse Voltage and the Pollution Degree.
To ensure the correct Insulation Coordination between the relay and the (1) In accordance with IEC 60038.
application, the equipment designer (relay user) should establish the Rated Remark: The descriptions of overvoltage categories below are for
Impulse Voltage appropriate to his application, and the Pollution Degree information. The actual overvoltage category to be considered has to be
for the microenvironment in which the relay is situated. He should then taken from the product standard defining the application of the relay.
match (or coordinate) these two figures with the corresponding values Overvoltage category I Applies to equipment intended for connection
given in the appropriate relay data, under the section entitled Technical to fixed installations of buildings, but where measures have been taken
data, sub-heading; Insulation. (either in the fixed installation or in the equipment) to limit transient
Rated Impulse Voltage; To establish the appropriate Rated Impulse overvoltages to the level indicated.
Voltage refer to the appropriate Equipment Standard which may specify Overvoltage category II Applies to equipment intended for connection to
mandatory values for equipment being designed. Alternatively, using the fixed installations of buildings.
Rated Impulse Voltage table (Table 6) with knowledge of the Nominal Overvoltage category III Applies to equipment in fixed installations, and for
Voltage of the Supply System and knowledge of the Overvoltage Category, cases where a higher degree of availability of the equipment is expected.
determine the appropriate Rated Impulse Voltage. Overvoltage category IV Applies to equipment intended for use at or near
Overvoltage Category; this is described in IEC 60664-1, but is also the origin of the installation, from the main distributor towards the supply
summarised in the footnotes to Rated Impulse Voltage table. Alternatively, mains.
it may be specified in the equipment standard.
Pollution Degree; determine this by considering the immediate TABLE 7 Pollution degree
surroundings of the relay (refer to Pollution Degree table 7). Then check Pollution Immediate surroundings of relay
that the relay specification offers the appropriate (or better) Rated Impulse degree
Voltage and Rated Insulation Voltage, for that Pollution Degree. 1 No pollution or only dry, non-conductive pollution occurs.
The pollution has no influence.
2 Only non-conductive pollution occurs, except that
occasionally a temporary conductivity caused by
condensation is to be expected.
3 Conductive pollution occurs or dry, non-conductive pollution
occurs which becomes conductive due to condensation,
which is to be expected.
Dielectric strength
This can be described in terms of an AC voltage test, or in terms of an
Impulse (1.2/50 µs) voltage test. (The correspondence between the AC test
VI-2018, www.findernet.com
XIV
General technical information
is greatly facilitated. All these values must be considered as “average” values, such that an
individual relay can show times differing by about ± 3 ms from the
stated value. For relays with AC coil such differences can reach 10 ms.
XV
General technical information
contact (if the coil is not energised). (The X-axis is the axis through the plane used in the connection of the common side of multiple coils.
of the relay face containing the relay terminals). The vibration resistance is Attention must be paid to the total current that they can carry, if used
usually higher in the energised state, than in the non-energised state. Data to interconnect contact circuits, and to the stability of their mechanical
for other axes and frequency ranges, on request. The level of vibration is and electrical connection (for example, their use is not recommended in
given in terms of the maximum acceleration of the sinusoidal vibration, "g" applications where continuous vibration is expected).
(where g = 9.81 m/s2). But note: the normal testing procedure according to
XVI
General technical information
vectors.
For level control relays, this is the nominal (AC) electrode current.
Detection level
For monitoring relays, this represents, either fixed or adjustable level(s) of Max. sensitivity
voltage, current or phase asymmetry, which define the acceptable limits of For level control relays: the maximum sensitivity is the maximum resistance
operation. Values outside acceptable limits will cause the output relay NO between the electrodes that will be recognised as indicating the presence
contact to open (after any intentional delay). of liquid. This may be fixed, or adjustable over a range - according to type.
XVII
General technical information
Light dependent relays 2 - GWIT (Glow Wire Ignition Temperature) of 775 °C according to
EN 60695‑2‑13 - This requirement can be verified with a GWT (Glow
Threshold setting
Wire Test according to EN 60695-2-11) at a value of 750 °C with a flame
The ambient light level setting, measured in lux (lx), at which the output
extinction within 2 seconds.
relay switches on (following the elapse of the ON Delay time). This is
adjustable over the range specified in the specification. The following Finder products comply with the above mentioned
The relay will switch off, dependent upon the type of Light dependent requirements:
relay used, at either the same or a higher brightness value (following the - electromechanical relays of series 34, 40, 41, 43, 44, 45, 46, 50, 55, 56,
elapse of the OFF Delay time). 60, 62, 65, 66, 67;
-P CB or DIN Rail sockets in special versions 9x.xx.7
Delay time
Switching ON/OFF For light-dependent relays this is an intentional delay in the Important note: Whilst EN 60335-1 permits the application of an
response of the output relay, following a change of state within the electronic alternative needle flame test (if the flame during test no. 2 burns longer
light sensitive circuit (usually indicated by change of state of an LED). than 2 seconds) this can result in some limitation in the relay's mounting
This is to eliminate the possibility of the output relay unnecessarily position. Finder products however, have no such limitations, since the
responding to a momentary change in ambient light level. materials used do not require the alternative test method to be performed.
Friday), but will only use one memory location. Radiated and conducted emission EN 55011/55014/55022
For mechanical daily time switches, this is the maximum number of
switching points during the day that can be set.
XVIII
General technical information
In panel installations, the most frequent and, particularly, more dangerous It is therefore necessary to consider Finder products as not being
type of electrical disturbances are the following: indestructible under all circumstances. The user should pay attention to
the disturbances in electrical systems and reduce as much as possible
Burst (fast transients)
these disturbances. For example, employ arc suppression circuits on
These are packets of 5/50 ns pulses, having high peak voltage level
the contacts of switches, relays or contactors which otherwise might
but low energy since individual pulses are very short - 5 ns rise time
produce over-voltages when opening electrical circuits (particularly highly
(5 x 10-9 seconds) and 50 ns fall time.
inductive or DC loads). Attention should also be paid to the placement of
They simulate the disturbances that can spread along the cables as a
components and cables in such a way as to limit disturbances and their
consequence of commutation transients from relays, contactors or motors.
propagation.
Usually they are not destructive, but they can affect the correct working of
electronic devices. EMC rules
Require that it is the equipment designer who must ensure that the
emissions from panels or equipment does not exceed the limits stated in
EN 61000-6-3 (generic standard for emission in the domestic environment)
or 61000-6-4 (generic standard for emission in the industrial environment)
or any product specific harmonised EMC standard.
establish the risk reduction that is required from a particular safety upon contact loading. The F-diagrams in the Finder catalogue can be
function; although the methods are quite different the outcomes should regarded as indicating the B10 Value of a Weibull type distribution of
be the same (or very similar) for any given function. electrical life (for a 230 V AC1 load); from which the MCTF can be derived
and used ultimately in calculating the “statistical probability of a dangerous
system failure per hour” for the safety control system.
XX
General technical information
ATEX EU
USA
Underwriters Laboratories UL
Canada
VI-2018, www.findernet.com
XXI