RELEASE 4
CONFIGURATION TOOL
CONTENT & GOAL
• Goal: Basic knowledge of:
• Configuration of an AutroSafe 4 system
with AutroConfig, the AutroSafe 4
Configuration Tool.
AUTROSAFE 4 – SYSTEM CONFIGURATION
• A closer look at AutroConfig;
the configuration tool for
AutroSafe system
AUTROSAFE 4 – CONFIGURATION
HEIS HEIS
Autronica
FARE
Autronica
HEIS HEIS FWRE
Autronica
HEIS HEIS Autronica
HEIS HEIS
Transfer Data to AS
Configuration Tool
Projecting
AUTROSAFE 4 – CONFIGURATION TOOL
Version number vs. Model number
AUTROSAFE 4 – CONFIGURATION TOOL
• Standard Windows looks and feel
• A left hand view tree structure used to
add/delete/connect/ disconnect
elements in the configured data
AUTROSAFE 4 – CONFIGURATION TOOL
• A right hand view used to
enter or change parameters
• Separate ways to look at the
configuration data
• Different access levels
AUTROSAFE 4 – CONFIGURATION TOOL
AUTROSAFE 4 – WHERE TO START
• System topography
• Add network, system components,
modules and loops
• Add points and input/output units
• Functionality
• Define rooms (DZ) and floors (AZ)
for one building (OZ)
• Define relationship between points,
alarm units and DZ, AZ
• Define relationship between DZ and AZ
AUTROSAFE 4 – SYSTEM TOPOGRAPHY
Physical connections:
• System components ↔ AutroNet
• System components ↔ system modules
• System modules ↔ loops units & other units
FARE
FWRE
AUTROSAFE 4 – THE BUILDING AND FUNCTIONALITY
Logical connections:
DZ1 DZ2 DZ3 DZ4
DZ31 • Room (DZ) and points
HEIS HEIS
• Room (DZ) and FPE
DZ32
(i.e. output)
Autronica
Autronica
HEIS HEIS
DZ31
• Floors (AZ) and FAD
HEIS HEIS
Autronica
• Alarm areas (DZ to AZ)
• Buildings and rooms (OZ to DZ)
Autronica
DZ33 DZ32
HEIS HEIS
DZ31
• Operation areas
(Panel to OZ)
AUTROSAFE 4 – DIFFERENT WAYS OF FINDING THE DATA
• System view
• Components, modules, loops and units
• Detection zone view
• Which detectors in which rooms
• Alarm zone views
• Which alarm devices in which floors A u tro n ic a
A u tro n ic a
• Operating zone view
• Which rooms and panels in which buildings
AUTROSAFE 4 – A SMALL INSTALLATION
AUTROSAFE 4 – CONFIGURATION STEP BY STEP
1. Establish a new installation (config no., project no., project name, save)
2. Add system components, modules, loops, AFB and power
3. Add loop units (points, sounders etc.)
4. Add functionality to I/O modules
5. Add buildings (if needed) (OZ)
6. Add rooms to buildings (DZ)
7. Add floors (AZ)
8. Connect panels, FARE & FWRE to buildings (OZ)
9. Connect points to rooms (Points to DZ)
10. Connect FAD to floors (FAD to AZ)
11. Connect rooms to floors (DZ to AZ)
12. Define activation groups (Add/Connect) for outputs (DZ/points to output)
13. Choose language
14. Generate config (data files for import in panels)
AUTROSAFE 4 – GENERATE DATA FILES
• Check that required options for download are
marked in the menu tool => option
AUTROSAFE 4 – GENERATE DATA FILES FOR DOWNLOADING
• Choose “Step 4: Generate” from the download menu
AUTROSAFE 4 – CONFIGURATION
Transfer config-file to
AutroSafe system
FARE
FWRE
AUTROSAFE 4 – EXPORT FROM PANEL