Subject   : Switch Gear & Protection
Factors To Be considered while
         selecting CT
                                             - Shivam Patel
                            Current Transformer (CT)
 Definition
    A current transformer is an instrument transformer, used along with measuring or
     protective devices, in which the secondary current is proportional to the primary
     current (under normal conditions of operation) and differs from it by an angle that is
     approximately zero.
 Functions
    Current transformers perform the following functions:
    Current transformers supply the protective relays with currents of magnitude
     proportional to those of power circuit but sufficiently reduced in magnitude.
    The measuring devices cannot be directly connected to the high magnitude supplies.
     Hence current transformers are used to supply those devices with currents of
     magnitude proportional to those of power.
    A current transformer also isolates the measuring instruments from high voltage
     circuits.
                               Current Transformer (CT)
 Principle
    The basic principle of the current transformer is the same as that of the power transformer. Like the power
     transformer, the current transformer also contains a primary and a secondary winding. Whenever an alternating
     current flows through the primary winding, alternating magnetic flux is produced, which then induces alternating
     current in the secondary winding. I
    n the case of current transformers, the load impedance or “burden” is very small. Therefore the current
     operates under short circuit conditions. Also the current in the secondary winding does not depend on load
     impedance but instead depends on the current flowing in the primary winding.
    The current transformer basically consists of an iron core upon which primary and secondary windings are
     The primary winding of the transformer is connected in series with the load and carries the actual current flowing
     the load, while the secondary winding is connected to a measuring device or a relay. The number of secondary
     turns is proportional to the current flowing through the primary; i.e., the larger the magnitude of current flowing
     through the primary, more the number of secondary turns.
                      Current Transformer (CT)                                           (Principle…..)
 Principle :
     The ratio of primary current to the secondary current is known as the current transformation ratio of the CT. Usually
      current transformation ratio of the CT is high. Normally the secondary ratings are of the order 5 A, 1 A, 0.1 A, whereas
      primary ratings vary from 10 A to 3000 A or more.
     The CT handles much less power. Rated burden can be defined as the product of current and voltage at the secondary
      side of the CT. It is measured in volt ampere (VA).
     The secondary of a current transformer should not be disconnected from its rated burden while current is flowing in
      primary. As the primary current is independent of the secondary current, the entire primary current acts as a
      current when secondary is opened. This results in deep saturation of the core, which cannot return to normal state and
      the CT is no longer usable.
                    Current Transformer (CT) : Types
   Based on the function performed by the current
                                                              Based on the function construction
                    transformer
                                                    • Bar Type. This type consists of a bar of suitable size
                                                      and material forming an integral part of the
• Measuring current transformers. These current       transformer.
  transformers are used along with the measuring
  devices for the measurement of current, energy,   • Wound Type. This type has a primary winding of
                                                      ore than one full turn wound over the core.
  power.
                                                    • Window Type. This type has no primary winding.
                                                      The secondary wind of the CT is placed around the
• Protective current transformers. These current      current flowing conductor. The magnetic electric
  transformers are used along with the protection
                                                      field created by current flowing through the
  equipments such as trip coils, relays, etc.
                                                      conductor induces current in the secondary
                                                      which is used for measurement.
       Current Transformer (CT) : Types
              Based on the function construction
Bar Type                 Wound Type                Window Type.
                  Protective Current Transformer
 Purpose :
    Protection Current Transformers are designed to
     measure the actual currents in power systems and to
     produce proportional currents in their secondary
     windings which are isolated from the main power
     circuit.
    Satisfactory operation of protective relays can
     on accurate representation of currents ranging from
     small leakage currents to very high overcurrent's,
     requiring the protective current transformer to be
     linear, and therefore below magnetic saturation at
     values up to perhaps 30 times full load current .
               Protective Current Transformer
 This wide operating range means that protective current transformers require to be constructed
  with larger cross-sections resulting in heavier cores than equivalent current transformers used for
  measuring duties.
 For space and economy reasons, equipment designers should however avoid over-specifying
  protective current transformers ITL technical staff are always prepared to assist in specifying
  protective CT's but require some or all of the following information;
    •   Protected equipment and type of protection.
    •   Maximum fault level for stability.
    •   Sensitivity required.
    •   Type of relay and likely setting.
    •   Pilot wire resistance, or length of run and pilot wire used.
    •   Primary conductor diameter or busbar dimensions.
    •   System voltage level.
  Factors To Be considered while selecting CT
 Accuracy Class :
     CT Accuracy is defined in terms of departure from the true ratio . It is expressed as
     The accuracy varies with the secondary biurden and also dependent upon the satureation flus density of the
      core .
     For many relays ,an accuracy of +_ 10% TO +_ 15% is acceptable. For example incase o fIDMT overcurrent
      relays , the accuracy is less omportanr , particularly at high current as the time of operation od relay is
      practically constant. On the other hand , with the distance and differential relay a CT accuracy of +_3% to +_ 5%
      is derirable.
     CT errors can be also be expressed in terms of composite error.
  Factors To Be considered while selecting CT
 Knee-point voltage :
     The knee-point voltage of a current transformer is the magnitude of the secondary voltage above which
      the output current ceases to linearly follow the input current within declared accuracy. In testing, if a
      voltage is applied across the secondary terminals the magnetizing current will increase in proportion to
      the applied voltage, until the knee point is reached. T
     he knee point is defined as the voltage at which a 10% increase in applied voltage increases the
      magnetizing current by 50%For voltages greater than the knee point, the magnetizing current increases
      considerably even for small increments in voltage across the secondary terminals.
     The knee-point voltage is less applicable for metering current transformers as their accuracy is generally
      much higher, but constrained within a very small range of the current transformer rating, typically 1.2 to
      1.5 times rated current.
     However, the concept of knee point voltage is very pertinent to protection current transformers, since
      they are necessarily exposed to fault currents of 20 to 30 times rated current
 Factors To Be considered while selecting CT
 Burden:
    The secondary load of a current transformer is termed the "burden" to distinguish it from the primary load.
    The burden in a CT metering circuit is the largely resistive impedance presented to its secondary winding.
     Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA, 20 VA, 30 VA, 45 VA and 60 VA. Burden
     ratings are B-0.1, B-0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 will
     maintain its stated accuracy with up to 0.2 Ω on the secondary circuit.
    These specification diagrams show accuracy parallelograms on a grid incorporating magnitude and phase angle
     error scales at the CT's rated burden.
    Items that contribute to the burden of a current measurement circuit are switch-blocks, meters and
     intermediate conductors. The most common cause of excess burden impedance is the conductor between
     the meter and the CT.
    When substation meters are located far from the meter cabinets, the excessive length of cable creates a large
     resistance. This problem can be reduced by using thicker cables and CTs with lower secondary currents (1A),
     both of which will produce less voltage drop between the CT and its metering devices.
  Factors To Be considered while selecting CT
 Short- Time current rating of the Transformer:
     Short time current is maximum fault current that a CT can withstand for a short duration of time. This
      current can be decided by the following factors.
         1.   The rms value of the fault current for a short period
         2.   The duration for which fault current may perisist.
         3.   Peak asymmetric for which fault current may persist.
         4.   Peak asymmetric value of fault current
         5.   Transient Voltage at the instant of fault occurance and the instant of extension of arc by a circuit beaker.
    o   The First two factor constitue the thermal limit. The more th fault current and greater is the time period
        secified ; larger will be the primary conductor cross-section.
    o   The peak Value o fthe symmetric falult current imposes the mechanical limit. The electrodynamic forces
        produced depends the peak value the number of primary turns ans the configuration of the coil.
  Factors To Be considered while selecting CT
 Accuracy Limit Factor :
     Protective CT are reqired to faithfully transform maximum possible fault currents . This value of the fault
      current can be calculated by assuming a three-phased bolted shor – circuit immediately following a CT
      location .
     Accuracy Limit factor (ALF) is given by :
              ALF = Maximum fault current / Rated Primary current
     A CT is so often sopecifid as 15VA, 5P10 where 15Va denotes burden , 5 denotes composite error and 10
      is the ALF
THANK YOU