Installation Instructions Fan Coils Wahl, Wapl, Waxl: Warning
Installation Instructions Fan Coils Wahl, Wapl, Waxl: Warning
Fan Coils
WAHL, WAPL, WAXL
These instructions must be read and understood completely before attempting installation.
TABLE OF CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ! WARNING
HEATER PACKAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PERSONAL INJURY, AND/OR PROPERTY DAMAGE
POSITION UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 HAZARD
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Failure to carefully read and follow this warning could
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . 7 result in equipment malfunction, property damage,
personal injury and/or death.
REFRIGERANT TUBING . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation or repairs made by unqualified persons could
REFRIGERANT FLOW−CONTROL DEVICE . . . . . . 10 result in equipment malfunction, property damage,
REFRIGERANT METERING DEVICE . . . . . . . . . . . . . 11 personal injury and/or death.
CONDENSATE DRAINS . . . . . . . . . . . . . . . . . . . . . . . . 11 The information contained in this manual is intended for
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test
SEQUENCE OF OPERATIONS . . . . . . . . . . . . . . . . . . 12 instruments.
START−UP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . 13 Installation must conform with local building codes and
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . 13 with the National Electrical Code NFPA70 current
edition.
AIRFLOW PERFORMANCE TABLES . . . . . . . . . . . . . 14
AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . 14
R−410A QUICK REFERENCE GUIDE . . . . . . . . . . . . 17
INTRODUCTION ! WARNING
Models WAHL, WAPL, WAXL are for R−410A refrigerant.
FIRE HAZARD
These units leave the factory compliant with low leak
requirements of less than 2% cabinet leakage rate at 0.5 Failure to maintain proper clearances could result in
personal injury, death, and/or property damage.
inches W.C. and 1.4% cabinet leakage rate at 0.5 inches
W.C. when tested in accordance with ASHRAE 193 When heaters are installed, maintain clearances from
combustible materials as specified on unit rating plate.
standard. Do not use plastic lined or combustible flexible ducting
All models are designed for maximum flexibility and can be within 36 inches of the supply end of the fan coil.
used for upflow, horizontal left or right, and downflow
REQUIRED CLEARANCES − ALL MODELS inches (mm)
applications (accessory kit required for downflow).
No All Sides 0
WAPL models are available for system sizes 1−1/2 through
4 tons (18,000 − 48,000 BTUH) nominal cooling capacity. Heaters From Supply Duct 0
All models use an ECM integral electronically commutated All Sides 0
motor for efficiency and use a piston metering device. From First 3 feet of Supply Duct to
With 1 (25)
WAHL and WAXL models are available for system sizes Combustibles
Heaters
1−1/2 through 5 tons (18,000 − 60,000 BTUH) nominal From Supply Duct to Combustibles after
0
cooling capacity. All models use an ECM integral 3 feet
electronically communtated motor for efficiency and have
a factory installed and appropriately sized hard shut−off HEATER PACKAGES
TXV metering device are for R−410A refrigerant ONLY.
Factory approved, field installed, UL listed heater
All models require a field supplied air filter. Factory packages are available from the equipment supplier. See
approved electric heater packages are available in sizes unit rating plate for a list of factory approved heaters.
5kW through 30kW. See Product Specification literature for Heaters that are not factory approved could cause damage
available accessory kits which would not be covered under the equipment warranty.
LOCATION POSITION UNIT
Select the best position which suits the installation site
conditions. The location should provide adequate structural Unit can stand or lie on floor, or hang from ceiling or wall.
support, space in the front of the unit for service access, Allow space for wiring, piping, and servicing unit.
clearance for return air and supply duct connections, space
for refrigerant piping connections and condensate drain
line connections. If heaters are being installed make sure ! CAUTION
adequate clearance is maintained from supply duct work. PROPERTY DAMAGE HAZARD
See clearances below.
Failure to follow this caution may result in property
NOTE: If the door gasket is damaged or missing, the unit damage
may not meet the ASHRAE 193 standard for cabinet air A field fabricated auxiliary drain pan, with a separate
leakage. Contact your supplier and order kit #1191140. drain is REQUIRED for all installations over a finished
Nuisance sweating may occur if the unit is installed in a high living space or in any area that may be damaged by
humidity environment with low airflow. On these installations a overflow from a restricted main drain pan. In some
wrap of 2″ (51mm) fiberglass insulation with a vapor barrier is localities, local codes require an auxiliary drain pan for
recommended. ANY horizontal installation.
NOTE: Internal filter can be accessed from separate filter A. UPFLOW INSTALLATION
door. If the filter can NOT be easily accessed, a remote filter
is recommended. Refer to ACCA Manual D for remote filter If return air is to be ducted through a floor, set unit on floor
sizing. over opening and use 1/8 to 1/4 inch thick (3 to 6 mm thick)
fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut
opening per dimensions shown in Figure 1. A
field−supplied bottom closure is required.
LOW VOLT
ENTRY
OPTIONS
FRONT SERVICE CLEARANCE
18 − 48 models = 21” (533 mm)
60 model = 24” (610 mm)
A−COIL
UNITS
UPFLOW/DOWNFLOW
SECONDARY DRAIN 1½”
UPFLOW/DOWNFLOW
PRIMARY DRAIN 19” (483mm)
FIELD MODIFIED
A SIDE RETURN
LOCATION FOR
2½” SLOPE COIL
(64mm) UNITS ONLY
UPFLOW/DOWNFLOW
SECONDARY DRAIN
SLOPE COIL UNITS In this application, field conversion of the evaporator coil is
required using accessory Downflow Kit along with an
MODEL A
accessory Base Kit. Set unit on floor over opening and use
WAHL18, WAPL18, WAPL244A, 12” (305mm) 1/8” to 1/4” thick fireproof resilient gasket between duct,
WAHL244B unit, and floor. Refer to installation instructions packaged
WAXL18, WAXL24, WAHL244C, WAHL30, 17” (432mm) with accessory kit. See Product Specification literature for
WAPL30, WAHL36, WAPL36 kit part numbers.
WAXL30 19” (483mm) During the conversion process, removed the plastic cap
covering the vertical drains only and discard.
B. DOWNFLOW INSTALLATION
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the
! CAUTION vertical pan fitting to door joint to retain low air leak
performance of the unit.
PRODUCT OR PROPERTY DAMAGE HAZARD NOTE: Gasket kit number (EBAC01GSK) is also required
Failure to follow this caution may result in product or for all downflow applications to maintain low air leak/low
property damage sweat performance.
The conversion of the fan coil to downflow requires C. MODULAR UNITS
special procedures for the condensate drains on both The WAXL60 fan coil is a two−piece modular unit. This
A−coil and Slope−coil units. The vertical drains have an allows the unit to be disassembled and components moved
overflow hole between the primary and secondary drain
separately to the installation area for reassembly. This
holes. This hole is plugged for all applications except
process accommodates small scuttle holes and limiting
downflow, and must be used for downflow.
entrances to installation sites (refer to Figure 2).
Failure to follow instructions could result in personal
injury or product and property damage.
2 SCREWS
2 SCREWS
REAR CORNER
BRACKET
2 SCREWS
COIL BOX
A−COIL
HORIZONTAL LEFT
FIELD
SUPPLIED
HANGING
STRAPS SECONDARY PRIMARY
DRAIN DRAIN
LOW VOLT
ENTRY
OPTIONS
1¾” (45mm)
FILTER ACCESS
CLEARANCE
POWER PRIMARY
ENTRY DRAIN
OPTIONS
COIL
FACTORY SHIPPED BRACKET
HORIZONTAL LEFT
APPLICATION
COIL
SUPPORT
RAIL
B
C DRAIN PAN
SUPPORT
BRACKET
COIL
BRACKET
HORIZONTAL
DRAIN PAN PRIMARY DRAIN
AIR SEAL HORIZONTAL LEFT
ASSEMBLY SECONDARY DRAIN
HORIZONTAL LEFT
REFRIGERANT
CONNECTIONS
Horizontal Right Conversion of Units With Slope Coils 5. Attach coil to casing flange using coil mounting
screw previously removed.
1. Remove blower and coil access panel and fitting
panel (refer to Figure 5). 6. Align holes with tubing connections and condensate
pan connections, and reinstall access panels and
2. Remove coil mounting screw securing coil assembly
fitting panel. After brazing, make sure liquid and
to right side casing flange.
suction tube grommets are in place to prevent air
3. Remove coil assembly. leaks and cabinet sweating.
4. Lay fan coil unit on its right side and reinstall coil assembly
with condensate pan down (refer to Figure 5).
Figure 5 Conversion for Horizontal Right Applications − Slope Coil
SLOPE COIL
SECONDARY DRAIN
A
REFRIGERANT AIR SEAL
CONNECTIONS ASSEMBLY
HORIZONTAL
RIGHT
APPLICATION
COIL
SUPPORT
RAIL
B
C
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
4” (102mm) MAX
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
(TYPICAL BOTH SIDES)
OR
UNIT AGAINST WALL
1/8” (3mm) INCH THICK ANGLE BLOWER BOX
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
2 SCREWS
2 SCREWS
REAR CORNER
BRACKET
DOWN FLOW
BASE KIT
2 SCREWS
SECURE UNIT TO FLOOR
COIL BOX
ANGLE BRACKET OR PIPE STRAP
4” (102mm) MAX
G GRY G
! WARNING W W2
BLU
W3
ELECTRICAL SHOCK HAZARD
VIO
E
Failure to follow this warning could result in personal
BRN AIR COND.
injury or death. C
Wiring Layout − Heat Pump Unit Fan speed is selected at the motor connector. Units with or
Figure 11 (Cooling and 2−Stage Heat for without electric heaters require a minimum CFM. Refer to
Manufactured Housing) the unit wiring label to ensure that the fan speed selected
THERMOSTAT HEAT PUMP is not lower than the minimum fan speed indicated.
FAN COIL (CONTROL)
R R R
SPEED TAP SELECTION AT MOTOR CONNECTOR
G G Tap 1 Low 90 sec off delay
C C C Tap 2 Medium 90 sec off delay
W2 W2 W2 Tap 3 High 90 sec off delay
W3
E E
Tap 4 Electric Heat † 0 sec off delay
ODTS
L Tap 5 Max ‡ 0 sec off delay
O
O † Electric heat airflow is same CFM as Tap 3, but with 0
Y Y sec off delay.
‡ For high static applications, see Airflow Performance
Tables for max airflow.
Transformer Information
To change motor speeds disconnect the BLUE fan lead
Transformer is factory wired for 230V operation. For 208V
from motor connector terminal #2 (factory default position)
applications, disconnect the black wire from the 230V terminal
and move to desired speed−tap; 1, 2, 3, or 5.
on transformer and connect it to the 208V terminal (refer to
Speed−taps 1, 2, and 3 have a 90 second blower off time
Figure 12).
delay pre−programmed into the motor. Speed tap 4 is used
Figure 12 Transformer Connections for electric heat only (with 0 second blower time delay) and
SECONDARY the WHITE wire should remain on tap 4. Speed−tap 5 is
used for high static applications, but has a 0 second blower
time delay pre−programmed into the motor (see Airflow
Performance Tables for actual CFM for each tap). Also, see
BROWN Figure 13 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap
RED
should be used to reduce possibility of water being blown off
coil.
C
YELLOW
Figure 13 Motor Speed Selection
208
230
BLACK
PRIMARY
C. GROUND CONNECTIONS 1 2 3 4 5
! WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground
could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground
in order to minimize potential for personal injury or death
if an electrical fault should occur. The ground may Speed Taps may be located on motor,
consist of electrical wire or metal conduit when installed or on plug close to motor.
in accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground
wire must be used.
REFRIGERANT TUBING
Refrigerant Tubing Connection and Evacuation
! CAUTION
Use accessory tubing package or field−supplied tubing of PRODUCT DAMAGE HAZARD
refrigerant grade. Suction tube must be insulated. Do not
Failure to follow this caution may result in product or
use damaged, dirty, or contaminated tubing because it may
property damage.
plug refrigerant flow−control device. ALWAYS evacuate the
coil and field−supplied tubing to 500 microns before Wrap a wet cloth around rear of fitting to prevent damage
opening outdoor unit service valves. to piston assembly or TXV and factory−made joints.
Figure 14 Refrigerant Flow−Control Device properly sized condensate traps (refer to Figure 15).
Factory approved condensate traps are available
BRASS DISTRIBUTOR (accessory part number EBAC01CTK).
HEX NUT TEFLON SEAL To connect drain lines, the drain connection knock−outs
TEFLON RING must be removed. Use a knife to start the opening near the
tab and using pliers, pull the tab to remove the knock−out.
Clean the edge of the opening if necessary. After drain
fittings are installed, caulk the seam between the fitting and
PISTON the cover to retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic
FLOW IN condensate pan. Do not over−tighten. Finger−tighten plus
COOLING
1−1/2 turns. Use pipe dope, to ensure proper seal.
BRASS
PISTON
RETAINER
HEX BODY Install traps in the condensate lines as close to the coil as
possible (refer to Figure 17), but avoid blocking filter
access panel.
Install drain lines below the bottom of the drain pan and
pitch the drain lines down from the coil at least 1/4 inch per
STRAINER
foot of run (6mm per 0.3m). Horizontal runs over 15 feet
(5m) long must also have an anti−siphon air vents (stand
pipes), installed ahead of the horizontal runs. Extremely
long horizontal runs may require oversized drain lines to
eliminate air trapping.
REFRIGERANT METERING DEVICE Route primary drain line to the outside or to a floor drain.
WAHL and WAXLmodels have a factory installed hard Check local codes before connecting to a waste (sewer)
shut−off TXV designed only for use with R−410A line.
refrigerant. Use only with outdoor units designed for Route the secondary drain line to a place in compliance with
R−410A. local installation codes where it will be noticed when unit is
TXV is factory set and not field adjustable. operational. Condensate flowing from secondary
(overflow) drain indicates a plugged primary drain − unit
requires service or water damage will occur.
! CAUTION Prime all traps, test for leaks, and insulate in areas where
sweating of the traps and drain lines could potentially cause
PRODUCT DAMAGE HAZARD water damage. Consult local codes for additional
Failure to follow this caution may result in product requirements or precautions.
damage. If a gravity drain cannot be used, install a condensate pump.
This Fan Coil has a hard shut−off TXV metering device. Install the pump as close to the indoor section as possible.
A compressor Hard Start Kit is REQUIRED in all
applications where the matching outdoor unit has a
single−phase reciprocating compressor.
! CAUTION
PRODUCT or PROPERTY DAMAGE HAZARD
SEQUENCE OF OPERATIONS
A. CONTINUOUS FAN
Thermostat closes R to G. G sends signal direct to motor
which completes circuit to indoor blower motor. When G is
de−energized, there is a 90 second off delay before relay
DO NOT USE SHALLOW RUNNING TRAPS! opens (based on speed tap selected).
Wiring Layout of Humidifier to Heat
Figure 18
Figure 17 Condensate Drain Pump
THERMOSTAT FAN COIL HEAT PUMP
(CONTROL)
R RED R
R
GRY
G G
BRN
C C
C
W2 WHT W
WHT 2
BLU
W3
E VIO
FILTER E
ACCESS
PANEL L W2
HUMIDISTAT
G
GRY
G
START−UP PROCEDURE
WHT Refer to outdoor unit Installation Instructions for system
W W2
WHT
start−up instructions and refrigerant charging method
BLU
W3 details.
VIO
E
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified
BRN AIR COND.
C service technician. Consult the servicing dealer for
recommended frequency.
C
Between visits, the only consumer service recommended
Y Y or required is air filter maintenance and condensate drain
operation.
HUMIDISTAT
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable type filters should be replaced.
115V M Reusable type filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Install filters with the
arrows on the side pointing in the direction of air flow.
Condensate Drain
B. COOLING MODE
During the cooling season check at least monthly for free
Thermostat energizes R to G, R to Y, and R to O (heat pump flow of drainage and clean if necessary.
only). G sends signal direct to motor which completes circuit
to indoor blower motor. When G is de−energized, there is a
90 second off delay before fan relay opens (based on speed ! CAUTION
tap selected).
C. HEAT PUMP HEATING MODE PRODUCT DAMAGE HAZARD
Thermostat energizes R to G and R to Y. G sends signal Failure to follow this caution may result in poor unit
direct to motor which completes circuit to indoor blower motor. performance and/or product damage.
When G is de−energized, there is a 90 second off delay Never operate unit without a filter. Factory authorized
before fan relay opens (based on speed tap selected). filter kits must be used when locating the filter inside the
D. HEAT PUMP HEATING WITH AUXILIARY unit. For those applications where access to an internal
ELECTRIC HEAT filter is impractical, a field−supplied filter must be
installed in the return duct system.
Thermostat energizes R to G, R to Y, and R to W. G
completes circuit to indoor blower motor. W completes
circuit to heater element(s). When W is de−energized,
electric heat relay(s) open, turning off heater elements.
When G is de−energized there is a 90 second off delay
before fan relay opens (based on speed tap selected).
• Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
• R−410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
• Manifold sets should be 750 psig high−side and 200 psig low−side with 520 psig low−side retard.
• R−410A, as with other HFC refrigerants, is only compatible with POE oils.
• POE oils may cause damage to certain plastics and roofing materials.
• Do not use liquid line filter−driers with rated working pressures less than 600 psig.
• Wrap all filter−driers and service valves with wet cloth when brazing.
• When system must be opened for service, break vacuum with dry nitrogen and replace all filter−driers.
TRAINING
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses. We
believe in providing high quality learning experiences both online and in the classroom.
Please contact us at mylearning@icpusa.com with questions regarding access to My Learning Center.